MATERIAL DATA SUBMITTAL
GREYHAWK BUSINESS PARK
BLDG. D/E, 3220 GREYHAWK CT.
CARLSBAD, CA.
LIFEGUARD FIRE PROTECTION, INC.
2605 TEMPLE HEIGHTS DRIVE, STE. F
OCEANSIDE, CA 92056
760-806-9997 • 760-806-4813 FAX
tqc:a I Fire & Bui/ding f Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Customer Servi les:
Tel: (414) 570-5000/ ( 00) 558-5236
Fax:(414)570-5010/( 00)877-1295
Series TY-FRB -2.8, 4.2, 5.6, and 8.0 K-facto
Upright, Pendent, and Recessed Pendent Spri klers
Quick Response, Standard Coverage
General
Description
The Series TY-FRB, 2.8, 4.2, 5.6, and
8.0 K-factor, l,Jpright and Pendent
Sprinklers described in this data sheet
are quick response -standard cover-
age, decorative 3 mm glass bulb type
spray sprinklers designed for use in
light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20 (1/2 inch NPT) or Style 30 (3/4
inch NPT) Recessed Escutcheon with
1/4 Inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the fixed pipe
drops to the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate In a fire situation or cause
it to operate prematurely.
Page 1 of 8
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing Is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the •
Series TY-FRB Pendent Sprinklers are
detailed in Technical Data Sheet
TFP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Serles TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Fa/lure to do ao may
Impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY1131 -
TY1231 •
TY2131 •
TY2231 •
TY3131 -
Upright 2.BK, 1/2"NPT
Pendent 2.BK, 1/2"NPT
Upright 4.2K, 1/2"NPT
Pendent 4.2K, 1/2"NPT
Upright 5.6K, 1 /2" NPT
JULY, 2004
I
1
TY3231 •
TY4131 •
TY4231 •
Technic
Data
Approvals
UL and C-UL Listed.
5.6K, 1/2"NPT
8.0K, 3/4"NPT
8.0K, 3/4"NPT
FM, LPCB, and NYC pproved.
(Refer to Table A for mplete approval
Information Including corrosion resis-
tant status.)
Maximum Working ressure
175 psi (12,1 bar)
Discharge COefflcl• t
K = 2.8 GPM/psi112 ( 0,3 LPM/bar112)
K = 4.2 GPM/psi112 ( 0,5 LPM/bar112)
K = 5.6 GPM/psi112 ( 0,6 LPM/bar112l
K = 8.0 GPM/psi112 (1 5,2 LPM/bar1i2)
TFP171
Page 2of8
ESCUTCHEON
PLATE SEATING
SURFACE
2-1/4"
(57,2 mm)
7/16" (11,1 mm)
NOMINAL
MAKE-IN
j
STYLE 10 or 20
RECESSED
ESCUTCHEON ssu*
DEFLECTOR
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
WRENCH
FLATS
-=----y'~ 2-3/16"
(55,6mm)
I
SSP DEFLECTOR*
PENDENT
1 -Frame 2-Button
3-Sealing
Assembly
2-7/8" (73,0 mm) DIA. __j
RECESSED PENDENT
4-Bulb
5 -Compression
Screw
6 -Deflector
7-Bushing
RGURE1
1/2" NPT**
UPRIGHT
* Temperature rating is Indicated on defle
orifice seat on frame.
•• Pipe thread connections per ISO 7/1 ca
special request.
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINI( ERS
2.8 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON
PLATE SEATING
SURFACE
2-3.'16"
(55,6 mm)
7/16" (11,1 mm)
NOMINAL
MAKE-IN
j
STYLE 10 or 20
RECESSED
ESCUTCHEON
WRENCH
FLATS
SSP DEFLECTOR*
PENDENT
2-7/8" (73,0 mm) DIA. __j
RECESSED PENDENT
1 -Frame
2 -Button
3 • Sealing
Assembly
4 -Bulb
5 -Compression
Screw
6 -Deflector
FIGURE2
ssu*
DEFLECTOR
1/2" NPT**
UPRIGHT
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
2-3.'16"
(55,6 mm)
I
• Temperature rating is indicated on defle
orifice seat on frame.
** Pipe thread connections per ISO 7/1 ca
special request.
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRIN/Ci
4.2 K-FACTOR, 112 INCH NPT
Finishes Bulb .............. Glass Operatio
TFP171
Sprinkler: Refer to Table A and B
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physlcal Characteristics
Frame . . . . . . . . . . . . . Bronze
Button . . . . . . . . . Brass/Copper
Sealing Assembly . . . . . . . . . .
Compression Screw . . . . . Bronze
Deflector . . . . . . . Copper/Bronze
Bushing (K=2.8) . . . . . . . Bronze The glass Bulb con ns a fluid which
expands when expo d to heat. When
the rated temperatu is reached, the
fluid expands sufficie tly to shatter the
glass Bulb, allowing the sprinkler to
activate and water to low.
. . . . . Beryllium Nickel w/Teflont
TFP171 Page 3of 8
ESCUTCHEON
PLATE SEATING
SURFACE
7116" (11,1 mm)
NOMINAL
MAKE-IN
STYLE 10 or 20
RECESSED
ESCUTCHEON ssu*
DEFLECTOR
2-3/16"
(55,6mm)
SSP DEFLECTOR*
PENDENT
1 -Frame
2 -Button
3 -Sealing
Assembly
t
WRENCH
FLATS
2·7/8" (73,0 mm) DIA. j
RECESSED PENDENT
4 • Bulb
5 -Compression
Screw
6 -Deflector
FIGURE3
1/2" NPT**
UPRIGHT
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
2-3/16"
(55,6 mm)
i
• Temperature rating is indicated on dell or or adjacent to
orttice seat on frame.
** Pipe thread connections per ISO 7/1 can be provided on
special request.
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) ANO PENDENT (TY3231) SPRIN ERS
5.6 K-FACTOR, 112 INCH NPT
ESCUTCHEON
PLATE SEATING
SURFACE
2-5/16"
(58,7mm)
1/2" (12,7 mm)
NOMINAL
MAKE-IN
_l
STYLE 30 or 40
RECESSED
ESCUTCHEON
WRENCH
FLATS
ssu*
DEFLECTOR
2-1/4"
(57,2mm)
e*
2
3
SSP DEFLECTOR*
PENDENT
2-7/8" (73,0 mm) DIA. J
RECESSED PENDENT
3/4" NPT *
UPRIGHT
4-Bulb 6-Deflector 1 -Frame
2 -Button
3-Sealing
Assembly 5 -Compression
Screw
• Temperature rating is indicated on dell or or adjacent to
orHice seat on frame.
•• Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) ANO PENDENT (TY4231) SPRINK, ERS
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are Intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
8.0 K-FACTOR, 314 INCH NPT
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent Installations.
lnstallat
The Series TY-FRB S rinklers must be
installed In accordan with the follow-
ing instructions:
NO
Do not install any bu! type sprinkler if
the bulb Is cracked or there Is a loss of
liquid from the bulb. ith the sprinkler
Page4of8
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB NATURAL CHROIIIE WHITE-
LIQUID BRASS PLATED POLYESTER
135°F/57°C Orange
PENDENT 1ss°F/68°C Red (TY1231) 1, 2, 3, 5
and 11s°F/79°c Yellow
UPRIGHT 200°F/93°C Green
2.8 (TY1131) 286°F/141°C Blue 1/2"
NPT 135°F/57°C Orange
RECESSED 1ss°F/68°C Red PENDENT
(TY1231)* 11s°F/79°C Yellow
Figure 5 200°F/93°c Green 1, 2, 5
135°F/57°C Orange
RECESSED 155°F/68°C Red PENDENT
(TY1231)** 175'F/79°C Yellow
Figure& 200°F/93'C Green
135'F/57°C Orange
PENDENT 155°F/68°C Red (TY2231)
and 175°F/79"C Yellow
UPRIGHT 200'F/93'C Green
42 (TY2131) 286'F/141'C Blue
1/2" 1, 2
NPT 135'F/57°C Orange
RECESSED 1ss°F/68°c Red PENDENT
(TY2231)" 175'F/79'C Yellow
Figure 7 200°F/93°C Green
135'F/57°C Orange
RECESSED 155'F/68°C Red PENDENT
(TY2231)"" 175°F/79'C Yellow
Figures 200'F/93°C Green
NOTES• 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use In Cenads (C-UL) ss Quick Response
Sprinklers.
3. Approved by Fadory Mutual Research Corporation (FM) as Quick Response Sprin-
klers. •
5. Approved by the City of New York under MEA 354-01-E. .
7. Where Polye$1er Coated Sprinklers are noted to be UL and C-UL Listed, the spnn-
klers are UL and C-UL Listed as Corrosion Res-nt Sprinklers.
• Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPn 3/4" Total Adjustment
Recessed EsaJlcheon, as applicable.
•• Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
Recessed Escutcheon, as applicable.
-• Frame and Delledor only. Listings and approvals apply to color (Special Order).
NIA: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1 /16 inch
(1,6 mm) for the 135°F/57"C to 3132
inch (2,4 mm) for the 286'F/141'C
temperature ratings.
A leak tight 1 /2 inch NPT sprinkler joint
should be obtained with a torque of 7
ID 14 ft.lbs. {9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
112 NPT connections. A leak tight 314
TFP171
inch NPT sprinkler jo, t should be ob-
tained with a tDrque f 10 to 20 ft.lbs.
(13,4 ID 26,8 Nm). A maximum of 30
ft.lbs. (40, 7 Nm) of to~ ue is to be used
to Install sprinklers th 314 NPT con-
nections. Higher /eves of torque may
distort the sprinkler nlet and cause
leakage or impairmen of the sprinkler.
Do not attempt to ma e-up for insuffi-
cient adjustment In he escutcheon
plate by under-or ov ,-tightening the
sprinkler. Readjust th position of the
sprinkler fitting ID sui
The Serles TY-FRB
right Sprinklers mu
accordance with the
tlons.
Step 1. Pendent spri klers are to be
installed in the pend nt position, and
upright sprinklers are o be Installed in
the upright position.
Step 2. With pipe th ad sealant ap-
plied to the pipe thre s, hand tighten
the sprinkler into the prinkler fitting.
Step 3. Tighten the prinkler into the
sprinkler fitting using nly the W-Type
6 Sprinkler Wrench el. Figure 13).
With reference to Fig res 1, 2, 3, and
4, the W-Type 6 Sprin ler Wrench is to
be applied to the s rlnkler wrench
flats.
The Serles TY•FRB ecessed Pen-
dent Sprinklers m t be installed in
accordance with the llowlng Instruc-
tions.
Step A. After installi g the Style 10.
20, 30, or 40 Mountln Plate, as appli-
cable, over the sprin ler threads and
with pipe thread seal nt applied to the
pipe threads, hand ti hten the sprin-
kler Into the sprinkler ltting.
Step B, Tighten the prinkler into the
sprinkler fitting using only the W-1ype
7 Recessed Sprinkl r Wrench (Ref.
Figure 14). With refer nee to Figure 1,
2, 3, and 4, the W-7 Recessed
Sprinkler Wrench is o be applied to
the sprinkler wrench ats.
Step C. After the cei ing has been in-
stalled or the finish t has been ap-
plied, slide on the le 10, 20, 30, or
40 Closure over the Serles TY-FRB
Sprinkler and push e Closure over
the Mounting Plate until Its flange
comes In contact wit the celling.
TFP171 Page 5 of 8
SPRINKLER RNISH (See Note 8)
K TYPE TEMP. BULB NATURAL I CHROME WHITE-LEAD
LIQUID BRASS PLATED POLYESTER COATED
135°F/57'C Orange
PENDENT 155°F/68°C Red {TY3231) 1,2,3,4,5,6, 7 1, 2, 3, 5 and 175°F/79°C Yellow
UPRIGHT 200°F/93°C Green
5.6 (TY3131) 286°F/141 •c Blue 1/2"
NPT 135°F/57'C Orange
RECESSED 155°F/68°C Red PENDENT 1, 2, 4, 5 NIA (TY3231)' 175°F/79°C Yellow
Rgure9 200°F/93°C Green
135°F/57'C Orange
RECESSED 155°F/68°C Red PENDENT 1, 2, 3, 4, 5 1, 2,4, 5 NIA
(TY3231)" 175°F/79°C Yellow
Rgure 10 200°F/93°C Green
135°F/57'C Orange
PENDENT 155°F/68°C Red (TY4231) 1,2,5 and 175°F/79°C Yellow 1,2,3,4,5,6, 7 UPRIGHT 200°F/93°C Green
8.0 (TY4131) 286°F/141 •c Blue 314•
NPT 135°F/57'C Green
RECESSED 155°F/68°C Orange PENDENT 1, 2, 4, 5 NIA
(TY4231)' 175°F/79°C Red
Rgure 11 200°F/93°C Yellow
135°F/57'C Orange
RECESSED 155°F/68°C Red PENDENT 1,2,3,4,5 NIA
(TY4231)" 175°F/79°C Yellow
Rgure12 200°F/93°C Green
NOTES:
1. Usted by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Usted by Underwriters Laboratories, Inc. for use In C&nsda (C-UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Resaardl CQrporatlon (FM) as Quick Response Sprinklers.
4. Approved by the Loss P1'8\18nlion Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; howlll/8
LPCB does not rate Iha lhermal sensitivity of racessed sprinklers.
·, lhe
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved (For detalls contact 1yco Are & Building Products, Enschede, Netherlands, Tel. 31-53-42~x 3• ·53-428-33TT).
7. Approved by the Loss Pr11118ntlon Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
~µL Ustedas 8. Where Polyester coated and Lead coated Sprinklers are noted to be UL and C-UL Usted, Iha sprinklers are UL and •
Corrosion Resistant Sprinklers. Where Lead coated Sprinklers ere noted to be FM Approved, Iha sprinkle111 are FM A >proved as a
Corrosion Resistant Sprinklet11.
• Installed with Style 10 (1/2" NPT) or Style 40 (314" NPT) 314" Total Adjustment Recessed Escutcheon, as appllcable.
-Installed with Style 20 (1/2" NPn or Style 30 (314" NPT) 1/2" Total Adjustment Recessed Escutcheon, as appllcable.
-• Frame and Deflector only. Listings and approvals apply to color (Special Order).
NIA: Not Available
TABLES
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
Page8of8
518±114"
(15.~.4mm)
CLOSURE
2-718" DIA. ;l (73,0mm)
2-114" DIA. -j
(57,2mm) r,
314• 19,1 mm
114" (6,4 mm)
SERIES
TY-FRB
FIGURES
1-5116" 33,3 mm)
13116" (20,6 mm)
112<1/8"
(12,7±3,2 mm)
2-718" DIA. ;l (73,0mm)
2-1/4" DIA. -j
(57,2mm) r,
FIGURE6
TFP171
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED P NDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
WITH TWO-PIECE 112 INCH TOTAL VSTMENT
STYLE 20 RECESSED ESC HEON
2.8 K-FACTOR, 112 INCH NPT 2.8 K-FACTOR, 112 INCH PT
518,,1/4"
(15,~.4mm)
CLOSURE
2-718' DIA. ;l (73,0 mm)
2·1/4' DIA. -j
(57.2 nvn> r I
FIGURE7
314" 19,1 mm
1/4' (6,4 nun)
1-1/4" (31,8mm)
314" (19,1 mm)
1/2t1/8'
(12,7"'3,2 nvn)
CLOSURE
2-718" DIA. ;l (73,0 mm)
2-1/4" DIA. -j
(57,2mm) r I
FIGURES
/2' 12,7mm)
1/4" (6,4 mm)
1-/4• 31,8 mm
• (25,4mm)
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED P NDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
WITH TWO-PIECE 112 INCH TOTAL VSTMENT
STYLE 20 RECESSED ESC HEON
4.2 K-FACTOR, 112 INCH NPT 4.2 K-FACTOR, 112 INCH PT
Care and
Maintenance
The Series TY-FRB Sprinklers must be
maintained and serviced In accord-
ance with the following Instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation In
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fled sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinlder with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers -before, during,
and after installation. Sprinklers dam-aged by dropping, triking, wrench
twlsVsllppage, or the Ike, must be re-
placed. Also, replace ny sprinkler that
has a cracked bulb r that has lost
liquid from Its bulb. Ref. Installation
Section).
Frequent visual lnsp lions are rec-
ommended to be lniti ly performed for
corrosion resistant ated sprinklers,
after the installation has been com-
pleted, to verify the i grity of the cor-
rosion resistant coa ing. Thereafter,
annual inspections per NFPA 25
should suffice; h r, instead of in-
specting from the floo level, a random
sampling of close-u visual inspec-
tions should be mad , so as to better
determine the exact sprinkler condl-
TFP171
518±1/4'
(15,9±6,4 mm)
CLOSURE
2·7/8' DIA. ;l (73,0mm)
2-1/4' DIA. 7 (57,2mm) r I
RGURE9
314' (19,1 mm)
1/4' (6,4 mm)
MOUNTING
PLATE
314' (19,1 mm)
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
518±1/4'
(15,9±6,4 mm)
(73,0 mm) 314" 19,1 mm 2·7/8' DIA. =;l
2-1/4' DIA. --j 1/4' (6,4 mm)
(57,2 mm) _j I
CLOSURE SERIES
TY·FRB
FIGURE 11
1-5/16' 33,3 mm
13116' (20,6 mm)
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 314 INCH NPT
lion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
WRENCH RECESS
(END 'B' USED FOR
3/4' NPT MODELS)
112±1/8'
(12,7±3,2 mm)
CLOSURE
2-7/8' DIA. ;l (73,0mm)
2-1/4' DIA
(57,2mm) ~
Page 7 of 8
/2' 12,7 mm
1/4' (6,4 mm)
1-/4' 31,8 mm
'(25,4mm)
FIGURE10
SERIES TY-FRB RECESSED P.
WITH TWO-PIECE 1/2 INCH TOTAL A VSTMENT
STYLE 20 RECESSED ESCU7i HEON
5.6 K-FACTOR, 112 INCH N T
112±1/8'
(12,7±3,2 mm)
2-7/8' DIA.
(73,0mm)
2-1/4' DIA.
(57,2mm)
RGURE12
/'Z' 12,7 mm)
1/4' (6,4 mm)
MOUNTING
PLATE
SERIES TY-FRB RECESSED PE DENT
WITH TWO-PIECE 112 INCH TOTAL A VSTMENT
STYLE 30 RECESSED ESCU7i EON
8.0 K-FACTOR, 314 INCH H T
The owner is responsible for the in-
spection, testing, and maintenance of their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
F/GURE13
W-TYPE 6 SPRINKLER
WRENCH
It is recommended that automatic
sprinkler systems be Inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Page 8 of 8 TFP171
P/N 57-XXX-X-XXX
I I
I TEMF ERATURE
MODEL/SIN RI\TING
SPRINKLER
330 2.8K UPRIGHT (1/2"NPT) TY1131 135 13! °F/57"C
331 2.8K PENDENT (1/2"NPT) TY1231 1 NATURAL BRASS 155 15! oF/68oC
340 4.2K UPRIGHT (1/2"NPT) TY2131 4 WHITE POLYESTER 175 17! °F/79°C
341 4.2K PENDENT (1/2"NPTI TY2231 3 WHITE (RAL901 O)* 200 20( °F/93°C
370 5.6K UPRIGHT (1/2"NPT) TY3131 9 CHROME PLATED 286 286 F/141°C
371 5.6K PENDENT (1/2"NPT) TY3231 7 LEAD COATED
390 8.0K UPRIGHT (314"NPT) TY4131
391 a.OK PENDENT (314 "NPT) TY4231 • Eastern Hemisphere :ales only.
TABLEC
PARTNUMBERSELECnON
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited ORY, FOR INCIDENTAL, INDIRECT, R-■Hd Escutche4 in:
SPECIAL OR CONSEQUENTIAL Specify: Style (specH •) Recessed Es-
Warranty DAMAGES, INCLUDING BUT NOT cutcheon with (spe, lfy finish), P/N
LIMITED TO LABOR CHARGES, RE· (specify).
GARDLESS OF WHETHER TYCO
Products manufactured by Tyco Fire FIRE PRODUCTS WAS INFORMED 112" (15 mm)
Products are warranted solelr to the ABOUT THE POSSIBILITY OF SUCH Slyle10
original Buyer for ten (1 O years DAMAGES, AND IN NO EVENT Chrome Plated .......... . PIN 56-701-9-010
against defects in material and work• SHALL TYCO FIRE PRODUCTS' LI· White Coaled ........... . PIN 56-701-+010
manship when paid for and properly ABILliY EXCEED AN AMOUNT White RAl.9010• ......... . PIN 56-701-3-010
Brass Plaled ............ . PIN 56-701-2-010 installed and maintained under normal EQUAL TO THE SALES PRICE. use and service. This warranty will ex-Itl.E. EQBE.GQUI.G. Wt1BBAtlD'. lS. 112" (15 mm)
pire ten (10) years from date of ship-Style 20
ment by Tyco Fire Products. No war-MAQE. ltl LlEU. QE A.ta Atm. ALL Chrome Plated .......... . P/N 56-705-9-010
ranty is given for products or DTHE.B Wt1BBAtlDE.S. EXPRESS. QB White Coated ........... . P/N 56-705-4-010
components manufactured by compa-lMPLlE.Q ltlCLUDING W;gBBAtmE.S. Whtte RAl.9010" ......... . P/N 56-705-3-010
nies not affiliated by ownership with QE MEBCl:MtlT4B.lLlD'. AtlQ ElI· Brass Plated ............ . PIN 56-705-2-010
1yco Fire Products or for products and tlE.S.S. EQB A ~BIIC.ULAB l!.UB· 3/4" (20 mm)
components which have been subject eDSE. Style 30
to misuse, Improper Installation, corro-Chrome Plated .......... . PIN 56-705-9-011
sion, or which have not been installed, White CoalBd ........... . PIN 56-705-4-011
maintained, modified or repaired in ac-Ordering White RAl.9010• ......... . PIN 56-705-3-011
cordance with applicable Standards of lltua Plated ............ . PIN 56-705-2-011
the National Fire Protection Associa-Procedure 3/4' (20mm)
lion, and/or the standards of any other Style 40
Authorities Having Jurisdiction. Mate-@Dm-,01111 i.caJ distributor for avail• Chrome Plllled .......... . PIN 56-700-9-010
rials found by Tyco Fire Products to be ab~.lndlcate the White Coaled ........... . PIN 56-700-+010
defective shall be either repaired or lu product White RAl.9010• ......... . PIN 58-700-3-010
replaced, at Tyco Fire Products' sole name. Refer to Brass Plated ............ . PIN 58-700-2-010
the Prtce Ust for option. Tyco Fire Products neither as-complete llstlng • Eastern H• mlsphere aalea only.
sumes, nor authorizes any person to of Part Numbers.
assume for it, any other obligation in Sprinkler Wrench:
connection with the sale of products or Sprinkler Assemblies with NPT Specify: W-Type 6 S1 1rinkler Wrench,
parts of products. Tyco Fire Products Thread Connections: PIN 56·000-6-387.
shall not be responsible for sprinkler Specify: (Specify Model/SIN), Quick Specify: W-Type 7 S >rinkler Wrench, system design errors or inaccurate or Response, (specify K-factor), (specify
Incomplete information supplied by temperature rating), Series TY-FRB PIN 56-850-4-001 .
Buyer or 8uyer's representatives. (specify Pendent or Uprl~ht) Sprinkler
IN NO EVENT SHALL TYCO FIRE with (specify type of finis or coating),
PRODUCTS BE LIABLE, IN CON-PIN (specify from Table C).
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE·
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
tqca I Fire & Building
/ Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Customer Service/Sales:
Tel: (414) 570-5000 / (800) 558-5236
Fax: (414) 570-5010 I (800) 877-1295
Series EL0-231 B -11.2 K-factor
Upright and Pendent Sprinklers
Standard Response, Standard Coverage
General
Description
The 11.2 K-factor, Series EL0-2318,
Standard Response, Standard Cover-
age, Upright and Pendent Sprinklers
(Rel. Figure 1) are automatic sprin-
klers of the frangible bulb type. They
are "standard response -spray sprin-
klers" that produce a hemispherical
water distribution pattern below the de-
flector.
The 11.2 K-factor, EL0-231B Sprin-
klers were subjected to full scale, high-
piled storage, fire tests to qualify their
use in lieu of 5.6 or 8.0 K-factor stand-
ard spray sprinklers for the protection
of high-piled storage.
Higher flow rates can be achieved at
much lower pressures with the 11.2
K-factor, EL0-231 B Sprinklers -
making their use highly advantageous
in high density applications, such as
the protection of high-piled storage.
Wax or lead coatings can be used to
extend the life of the copper alloy com-
ponents used in Series EL0-231 B
sprinklers beyond that which would
otherwise be obtained when exposed
to corrosive atmospheres. Although
wax, lead, and polyester coated sprin-
klers have passed the standard corro-
sion tests of the applicable approval
agencies, the testing is not repre-
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 6
sentative of all possible corrosive at-
mospheres. Consequently, it is recom-
mended that the end user be consulted
with respect to the suitability of these
corrosion resistant coatings for any
given corrosive environment. The ef-
fects of ambient temperature, concen-
tration of chemicals, and gas/chemical
velocity, should be considered, as a
minimum, along with the corrosive na-
ture of the chemical to which the sprin-
klers will be exposed.
An upright intermediate level version
of the Series EL0-231 B Sprinklers for
in-rack applications can be obtained
by utilizing the Series EL0-231 B Up-
right Sprinkler with the WSG-2 Guard
& Shield, and a pendent intermediate
level version of the Series EL0-231 B
Sprinklers can be obtained by utiliz-
ing the Series EL0-231 B Pendent
Sprinkler with the WS-2 Shield. If there
is a possibility of the pendent interme-
diate level version being exposed to
mechanical damage, a G-2 Guard can
be added.
WARNINGS
The 11.2 K-factor, Series ELO-2318
Upright and Pendent Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or manufac-
turer should be contacted with any
questions.
Installation of Series ELO-2318 Pen-
dent Sprinklers in recessed escutch-
eons will void all sprinkler warranties,
as well as possibly void the sprinkler's
Approvals and/or Listings.
JANUARY, 2005
,. :---·-----:: :---...:_::......--:.
: .::.:::.=.,~~: :·
; --:::-=---:--~-~----:
~
•·-~..,,.
TFP342
Page 2 of 6 TFP342
SPRINKLER FINISH
TYPE TEMPERATURE BULB NATURAL CHROME LEAD WAX WAX
LIQUID BRASS PLATED COATED COATED OVER LEAD
UPRIGHT 155'F/68'C Red 3
(TY5151 200'F/93'C Green & 1, 2, 3, 4
TY5851) 286'F/141 'C Blue 3 3<•)
155'F/68'C Red 3
PENDENT 200'F/93'C Green (TY5251 1, 2, 3, 4
286'F/141'C Blue 3 3(•)
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL Listed).
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL Listed).
3. Approved by Factory Mutual Research Corporation (FM Approved).
4. Approved by the City of New York under MEA 291-04-E.
(a). FM Approved for a maximum ceiling temperature of 150'F/66'C.
TABLE A
LABORATORY LISTINGS AND APPROVALS
FOR 11.2 K-FACTOR SERIES EL0-2318 UPRIGHT AND PENDENT SPRINKLERS
(Refer to the Design Criteria Section)
Model/Sprinkler
Identification
Numbers
TY5151 -Upright 11.2K, 3/4"NPT
TY5251 -Pendent 11.2K, 3/4"NPT
TY5851 -Upright 11.2K, 1/2"NPT
TY5151 is a redesignation for C5151.
TY5251 is a redesignation for C5251,
G 1871, and S2531 .
TY5851 is a redesignation for C5851.
Technical
Data
Approvals
UL and C-UL Listed. FM and NYC Ap-
proved. (Reier to Table A for complete
approval information including corro-
sion resistant status. The approvals
apply to the service conditions indi-
cated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12, 1 bar)
Discharge Coefficient
K = 11.2 GPM/psil/2
(161,4 LPM/bar1i2)
Temperature Ratings
Reier to Table A
Finishes
Refer to Table A
Physical Characteristics
Frame . . . . . . . . . . . . . Bronze
Cap .............. Bronze
Sealing Assembly . . . . . . . . . . .
...... Beryllium Nickel w/Tellont
Bulb (5 mm dia.) . . . . . . . Glass
Compression Screw . . . . . Bronze
Deflector . . . . . . . . . . . . Bronze
t Registered trademark of DuPont.
Design Criteria
UL and C-UL Listing
Requirements
The 11.2 K-factor, Model ELO-231 B
(TY5151, TY5251 & TY5851) Sprin-
klers are to be installed in accordance
with NFPA 13 standard sprinkler posi-
tion and area/density flow calculation
requirements for light, ordinary, or ex-
tra hazard occupancies with a mini-
mum residual (flowing) pressure of 7
psi (0,5 bar) in wet or dry pipe sprinkler
systems, or they are to be installed in
accordance with NFPA 13 standard
sprinkler position and area/density
flow calculation requirements for high
piled storage occupancies (solid piled,
palletized, rack storage, bin box, and
shelf storage including but not limited
to Class I-IV and Group A plastics) with
a minimum residual (flowing) pressure
of 10 psi (0,7 bar) for wet or dry pipe
systems.
The following example is typical of the
type of arrangement permitted by
NFPA 13. For all combinations of
lesser and greater building heights,
lesser and greater storage heights,
storage arrangements, commodity
classifications, and lesser or greater
required design densities, refer to
NFPA 13 for specifics.
Example: NFPA 13 provides ceiling
only protection (i.e., no in-rack sprin-
klers) criteria using open frame (i.e. no
solid shelves) single, double, multiple-
row, or portable rack storage (without
TFP342
* Temperature rating is indicated on deflector.
** Pipe thread connections per ISO 7/1 can be provided on
special request.
2-13/16"
(71,4 mm)
TYP.
7/16" (11,1 mm)
NOMINAL MAKE-IN
UPRIGHT
TV5851
2•**
PT
l112· (12,7 mm)
NOMINAL MAKE-IN
UPRIGHT
TY5151
1/2' (12,7 mm)
~MINAL MAKE-IN
THREAD
RELIEF
FIGURE 1
PENDENT
TV5251
11.2 K-FACTOR SERIES EL0-231B
3/4"**
NPT
CROSS
SECTION
Page 3 of 6
Components:
1 -Frame
2 • Seal
Assembly
3 • Cap
4 • Bulb
5 -Compression
Screw
6 • Deflector *
UPRIGHT-314" NPT (TY5151), UPRIGHT-1/2" NPT {TY5851), AND PENDENT-314" NPT (TY5251) SPRINKLERS
the need for in-rack sprinkler protec-
tion) of cartoned or uncartoned unex-
panded Group A or B plastics, or, car-
toned expanded Group A or B plastics,
with:
• a storage height of up to 20 feet (6, 1
m);
• a maximum ceiling height of 27 feet
(8,2 m);
• a minimum deflector to top of stor-
age clearance of 18 inches (457
mm);
• a minimum design density of 0.60
gpmlft2 (24,4 mm/min);
• a minimum residual (flowing) pres-
sure of 10 psi (0, 7 bar);
• a minimum design area of 2000 tie
(186 m2) for wet systems or 2600 ft2
(242 m2) for dry pipe systems
FM Approval
Requirements
The 11.2 K-factor, Model ELO-231 B
(TY5151, TY5251 & TY5851) Sprin-
klers are to be installed in accordance
with the applicable "control mode den-
sity/area" guidelines provided by Fac-
tory Mutual. (FM guidelines may differ
from UL and C-UL Listing criteria.)
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Installation
The Series ELO-231 B Sprinklers must
be installed in accordance with the fol-
lowing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 155°F/68°C to 3/32
inch (2,4 mm) for the 286°F/141°C
temperature ratings.
A leak tight 3/4 inch NPT sprinkler joint
should be obtained with a torque of 10
to 20 ft.lbs. (13,4 to 26,8 Nm). A maxi-
mum of 30 ft.lbs. (40, 7 Nm) of torque
is to be used to install sprinklers with
314 NPT connections. A leak tight 1/2
inch NPT sprinkler joint should be ob-
tained with a torque of 7 to 14 ft.lbs.
(9,5 to 19,0 Nm). A maximum of 21 ft.
lbs. (28,5 Nm) of torque may be used
to install sprinklers with 1/2 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
FIGURE2
W-TYPE 3 SPRINKLER
WRENCH
cient adjustment in the escutcheon
plate by under-or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series EL0-231 B Upright and
Pendent Sprinklers must be installed
in accordance with the following in-
structions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
3 Sprinkler Wrench (Rel. Figure 2),
except that an 8 or 10 inch adjustable
Crescent wrench is to be used for wax
coated sprinklers. With reference to
Page 4 of 6
Figure 1, the W-Type 3 Sprinkler
Wrench or the adjustable Crescent
wrench, as applicable is to be applied
to the wrench flats.
When installing wax coated sprinklers
with the adjustable Crescent wrench,
additional care needs to be exercised
to prevent damage to the wax coating
on the sprinkler wrench flats or frame
arms and, consequently, exposure of
bare metal to the corrosive environ-
ment. The jaws of the wrench should
be opened sufficiently wide to pass
over the wrench flats without damag-
ing the wax coating. Before wrench
tightening the sprinkler, the jaws of the
wrench are to be adjusted to just con-
tact the sprinkler wrench flats. After
wrench tightening the sprinkler, loosen
the wrench jaws before removing the
wrench.
After installation, the sprinkler wrench
flats and frame arms must be in-
spected and the wax coating re-
touched (repaired) whenever the coat-
ing has been damaged and bare metal
is exposed. The wax coating on the
wrench flats can be retouched by gen-
tly applying a heated 1 /8 inch diameter
steel rod to the areas of wax that have
been damaged, to smooth it back over
areas where bare metal is exposed.
NOTES
Only retouching of the wax coating ap-
plied to the wrench flats and frame
arms is permitted, and the retouching
is to be performed only at the time of
the initial sprinkler installation.
The steel rod should be heated only to
the point at which it can begin to melt
the wax, and appropriate precautions
need to be taken, when handling the
heated rod, in order to prevent the
installer from being burned.
If attempts to retouch the wax coating
with complete coverage are unsuc-
cessful, additional wax can be ordered
in the form of a wax stick (the end of
which is color coded). Only the co"ect
color coded wax is to be used, and
retouching of wrench flats and frame
arms is only permitted at the time of
initial sprinkler installation. With the
steel rod heated as previously de-
scribed, touch the rod to the area re-
quiring additional wax with the rod an-
gled downward, and then touch the
wax stick to the rod approximately
one-half inch away from the area re-
quiring retouching. The wax will melt
and run down onto the sprinkler.
Care and
Maintenance
Series ELO-231 B Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
control valve for maintenance work on
the fire protection system that it con-
trols, permission to shut down the af-
fected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers -before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb (ref. Installation
Section Note).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant sprinklers, after the
installation has been completed, to
verify the long term potential integrity
of the sprinkler coatings. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
TFP342
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
code.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for It, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL,. INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU Of ANY AND ALL
OTHER WARRANTIES EXPRESS QR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FIT-NESS FOR A PARTICULAR PUB-
.PD.SE.
TFP342
Ordering
Procedure
A Part Number (P/N) is not specified
when ordering sprinklers with thread
connections per ISO 7 /1.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies
with NPT Thread Connection:
Specify: (specify SIN), 11.2 K-factor,
(specify temperature rating), Series
ELO-231 B Standard Response (spec-
ify Pendent or Upright) Sprinkler with
(specify finish), P/N (specify from Ta-
ble B).
Sprinkler Wrench:
Specify: W-Type 3 Sprinkler Wrench,
P/N 56-895-1-001.
Wax Sticks:
(for retouching wrench damaged
wax coating)
Specify: (Specify color) color coded
Wax Stick for retouching (specify tem-
perature rating) temperature rated Se-
ries ELO-231 B Sprinklers, P/N (spec-
ify).
Red for 155°F.
Blue for 200°F and
286°F ..
NOTES
P/N 56-065-1-155
P/N 56-065-1-286
Each wax stick is suitable for retouch-
ing up to twenty-five sprinklers.
The wax used for 286°F sprinklers is
the same as for 200°F sprinklers, and,
therefore, the 286°F sprinkler is limited
to the same maximum ceiling tempera-
ture as the 200°F sprinkler (i.e.,
150°F).
510
512
501
Page 5 of 6
P/N 50-XXX-X-XXX
I
SPRINKLER
TEMPERATURE
TYPE
UPRIGHT
3/4" NPT
(TY5151)
PENDENT
3/4" NPT
(TY5251)
UPRIGHT
1/2" NPT
(TY5851)
1
9
6
7
8
NATURAL BRASS
CHROME PLATED
WAX COATED
LEAD COATED
WAX OVER LEAD
TABLES
155
200
286
PRODUCT SYMBOL NUMBER SELECTION
11.2 K-FACTOR SERIES EL0-231B
RATING
155°F/68°C
200°F/93°C
286°F/141°C
STANDARD RESPONSE UPRIGHT AND PENDENT SPRINKLERS
Page 6 of 6 TFP342
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
tqca I Fire & Building
/ Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
A
Gain
Customer Service/Sales:
Tel: (414) 570-5000 / (800) 558-5236
Fax: (414) 570-5010 / (800) 877-1295
Series TY-B -2.8, 5.6, and B.O K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Standard Response, Standard Coverage
General
Description
The Series TY-B, 2.8, 5.6, and 8.0
K-factor, Upright and Pendent Sprin-
klers described in this data sheet are
standard response -standard cover-
age, decorative 5 mm glass bulb type
spray sprinklers designed for use in
light, ordinary, or extra hazard, com-
mercial occupancies such as banks,
hotels, shopping malls, factories, refin-
eries, chemical plants, etc.
The recessed version of the Series
TY-B Pendent Sprinkler, where appli-
cable, Is intended for use in areas with
a finished ceiling. It uses a two-piece
Style 10 (1/2 inch NPT) orStyle40 (3/4
inch NPT) Recessed Escutcheon. The
Recessed Escutcheon provides 1/2
inch (12,7 mm) of recessed adjust-
ment or up to 3/4 inch (19,1 mm) of
total adjustment from the flush pen-
dent position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the fixed pipe
drops to the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate In a fire situation or cause
it to operate prematurely.
Page 1 of 8
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level version of the
Serles TY-B Pendent Sprinkler can be
obtained by utilizing the Series TY-B
Pendent Sprinkler in combination with
the Model S2 Shield.
WARNINGS
The Series TY-8 Sprinklers described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the
standards of any other authorities hav-
ing Jurisdiction. Failure to do so may
Impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY1151 -
TY1251 •
TY3151 -
TY3251 •
TY4151 -
TY4251 -
TY4851 -
TY4951 -
Upright 2.aK, 1/2"NPT
Pendent 2.aK, 1/2"NPT
Upright 5.6K, 1/2"NPT
Pendent 5.6K, 1/2"NPT
Upright a.OK, 3/4"NPT
Pendent a.OK, 3/4"NPT
Upright a.OK, 1/2"NPT
Pendent a.OK, 1/2"NPT
JULY, 2004
~~
. ,.,
rA,
I .• ,
~~
TFP151
Page 2 of a
ESCUTCHEON
PLATE SEATING
SURFACE
2-1/4'
(57,2 mm)
7/16' (11,1 mm)
NOMINAL
MAKE-IN
t
ssp*
DEFLECTOR
ssu*
DEFLECTOR
6
5
-+-----4
1"7---2
3
TFP151
PENDENT UPRIGHT
CROSS
SECTION
1-Frame
2 -Button
3-Sealing
Assembty
4 • Bulb
5 -Compression
Screw
6 -Deflector
7-Bushing
FIGURE 1
* Temperature rating is indicated on deflector or adjacent to
orttice seat on frame.
** Pipe thread connections per ISO 7/1 can be provided on
special request.
STANDARD RESPONSE SERIES TY-B UPRIGHT (TY1151} AND PENDENT (TY1251} SPRINKLERS
2.8 K-FACTOR, 112 INCH NPT
ESCUTCHEON
PLATE SEATING
SURFACE
2-3/16"
(55,6mm)
7/16" (11,1 mm)
NOMINAL
MAKE-IN
t
SSP DEFLECTOR*
PENDENT
1 -Frame
2 -Button
3 -Sealing
Assembly
4-Bulb
5 -Compression
Screw
STYLE 10
RECESSED
ESCUTCHEON
6-Deflector
FIGURE2
ssu*
DEFLECTOR
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
2-3/16"
(55,6mm)
1/2" NPT**
UPRIGHT
l
CROSS SECTION
* Temperature rating is Indicated on deflector or adjacent to
orttice seat on frame.
** Pipe thread connections per ISO 7/1 can be provided on
special request.
STANDARD RESPONSE SERIES TY-B UPRIGHT (TY3151} AND PENDENT (TY3251} SPRINKLERS
5.6 K-FACTOR, 112 INCH NPT
TFP151 Page 3 of 8
ESCUTCHEON
PLATE SEATING
SURFACE
1/2" (12,7 mm)
NOMINAL
MAKE-IN
STYLE40
RECESSED
ESCUTCHEON ssu*
DEFLECTOR
2-5/16"
(58,7 mm)
_J_
WRENCH
FLATS
2-1/4"
(57,2 mm)
s*
2
3
SSP DEFLECTOR*
PENDENT
2-7/8" (73,0 mm) DIA. ---1
RECESSED PENDENT
3/4" NPT**
UPRIGHT CROSS SECTION
1 -Frame
2 -Button
1 -Frame
2 -Button
3-sealing
Assembly
4-Bulb
5 -Compresskm
Screw
6 -Deflector
7 -Ejection
Spring
FIGURE3
* Temperature rating is indicated on deflector or adjacent to
orHice seat on frame.
** Pipe thread connections per 150 7/1 can be provided on
special request.
STANDARD RESPONSE SERIES TY-B UPRIGHT (TY4151) AND PENDENT (TY4251} SPRINKLERS
8.0 K-FACTOR, 314 INCH NPT
ESCUTCHEON
PLATE SEATING
SURFACE
2-1/4"
(57,2 mm)
7/16" (11,1 mm)
NOMINAL
MAKE-IN
l
ssp*
DEFLECTOR
ssu*
DEFLECTOR
* 6
5
2-3/16"
(55,6mm 4
2
7 3
PENDENT UPRIGHT
CROSS
SECTION
3 -Sealing
Assembly
4 -Bulb
5 -Compression
Screw
6 • Deflector
FIGURE4
* Temperature rating is indicated on deflector or adjacent to
orifice seat on frame.
** Pipe thread connections per 150 7/1 can be provided on
special request. •
STANDARD RESPONSE SERIES TY-B UPRIGHT (TY4851) AND PENDENT (TY4951} SPRINKLERS
8.0 K-FACTOR, 112 INCH NPT
Page 4 of 8 TFP151
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL CHROME WHITE"' LEAD WAX WAX OVER
LIQUID BRASS PLATED POLYESTER COATED COATED LEAD COATED
135•F151°c Orange
PENDENT 155°F/68°C Red
2.8 (TY1251) 1,2,3 NIA
1/2" and 175°F/79°C Yellow
NPT UPRIGHT 200°F/93°c Green
(TY1151) 286°F/141 •c Blue
360°F/182°C Mauve 1, 2
135•F151•c Orange
PENDENT 155°F/68°C Red (TY3251) 1,2,3,4,5,6, 7 1, 2, 3, 5 1, 2, 3, 5 1,2,3,5 and 175°F/79°c Yellow
UPRIGHT 200°F/93°C Green
5.6 (TY3151) 286°F/141°C Blue 1 ** ,2··, 3**, 5•• 1 **, 2*'°', 3**, 5••
1/2"
NPT 360°F/182°C Mauve NIA
135°F/57°C Orange
RECESSED 155°F/68°C Red PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 NIA
(TY3251)' 175°F/79°C Yellow
Figure4 200°F/93°C Green
135°F/51°c Orange
PENDENT 155°F/68°C Red (TY4251) 1, 2, 5 1, 2, 3, 5 1,2,5
and 175°F/79°c Yellow 1,2,3,4,5,6, 7
8.0 UPRIGHT 200°F/93°C Green
3/4" (TY4151) 286°F/141°C Blue 1**,2-, 3-*, s·· 1·-, 2 .. , 5••
NPT 360°F/182°C Mauve NIA
135°F/57°C Orange
RECESSED 155°F/68°C Red PENDENT 1, 2, 3, 4, 5 NIA
(TY4251)' 175°F/79°C Yellow
Figures 200°F/93°C Green
135°F/57°C Orange
PENDENT 155°F/68°C Red
8.0 (TY4951)
1/2" and 175°F/79°C Yellow 1,2,3,5 NIA
NPT UPRIGHT 200°F/93°C Green (TY4851) 286°F/141 •c Blue
360°F/182°C Mauve
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL).
2. Listed by Underwriters Laboratories, Inc. !or use In Csnsda (C-UL).
3. Approved by Factory Mutual Research Corporation (FM).
4. Approved by the Loss Prevention Cerllflcaflon Board (LPCB Ref. No. 007k/03).
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
7. Approved by the Loss_ Prevention Cerllflcatlon Board (LPCB Ref. No. 094a/05).
8. Where Polyes1er Coated, Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be UL and C-UL Listed, the
sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated, Wax Coaled, and Wax over Lead Coated
Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corroeion Resistant Sprinklers.
• Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 314" Total AdjUstment Recessed Escutcheon, as applicable.
•· 150°F/66°C Maximum Ceiling Temperature .
... Frame and deflector only. Listings and approvals apply to color (Special Order).
NIA: Not Avellable
TABI.EA
I.ABORATORY I.ISTINGS AND APPROVAI.S
TFP151
5/8±1/4'
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
CLOSURE
(73,0 mm) 3/4' (19, 1 mm)
2-7/8' DIA. ;l
2-1/4' DIA. 7 1/4' (6,4 mm)
(57,2mm) r I
FIGURES
1-1/4" (31,8 mm)
3/4" (19,1 mm)
SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 314 INCH TOTAL ADJUSTIIENT
STYLE 10 RECESSED ESCUTCHEON
5/8±1/4"
(15,9±6,4 mm)
CLOSURE
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8' DIA. =;l (73,0 mm) 3/4' (19, 1 mm)
2-1/4" DIA. ---j 1/4" (6,4 mm)
(57,2mm) JI
SERIES
TY-B
RGURE6
1-5/16' (33,3 mm)
13/16' (20,6 mm)
SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 314 INCH NPT
WRENCH RECESS
(END "B" USED FOR
3/4" NPT MODELS)
Page 5 of 8
RGURE7
W-TYPE 6 SPRINKLER
WRENCH
WRENCH
RECESS
D
PUSH WRENCH
INTO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURES
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Page &of 8
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, VdS, and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status.)
Maximum Working Pressure
175 psi (12, 1 bar)
Discharge Coefficient
K = 2.8 GPM/psi112 (40,3 LPM/bar112)
K = 5.6 GPM/psi112 (80,6 LPM/bar112\
K = 8.0 GPM/psi112 (115,2 LPM/bar112)
Temperature Ratings
Refer to Table A
Finishes
Sprinkler: Reessed Escutcheon: White
Coated, Chrome Plated, or Brass
Plated
Physical Characteristics
Frame . . . . . . . . . . . . . Bronze
Button . . . . . . . . . Brass/Copper
Sealing Assembly . . . . . . . . . .
. . . . . Beryllium Nickel w/Teflont
Bulb ............... Glass
Compression Screw . . . . . Bronze
Deflector . . . . . . . . . . . Copper
Bushing (K=2.8) . . . . . . . Bronze
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Series TY-B Pendent and Upright
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules rec-
ognized by the applicable Listing or
Approval agency (e.g., UL Listing is
based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM's Loss Prevention
Data Sheets). Only the Style 1 0 or 40
Recessed Escutcheon, as applicable,
is to be used for recessed pendent
installations.
Installation
The Series TY-B Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/57"C to 3132
inch (2,4 mm) for the 360°F/182°C
temperature ratings.
A leak tight 1 /2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A teak tight 314
inch NPT sprinkler joint should be ob-
tained with a torque of 1 O to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40, 7 Nm) of torque is to be used
to install sprinklers with 314 NPT con-
nections. Higher levels of torque may
distort the sprinkler Inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under-or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Serles TY-B Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 7),
except that an 8 or 1 O inch adjustable
Crescent wrench is to be used for wax
coated sprinklers. With reference to
Figures 1, 2, 3, and 4 the W-Type 7
Sprinkler Wrench or the adjustable
Crescent wrench, as applicable is to
be applied to the wrench flats.
When installing wax coated sprinklers
with the adjustable Crescent wrench,
additional care needs to be exercised
to prevent damage to the wax coating
on the sprinkler wrench flats or frame
arms and, consequenUy, exposure of
bare metal to the corrosive environ-
ment. The jaws of the wrench should
be opened sufficiently wide to pass
over the wrench flats without damag-
TFP151
ing the wax coating. Before wrench
tightening the sprinkler, the Jaws of the
wrench are to be adjusted to just con-
tact the sprinkler wrench flats. After
wrench tightening the sprinkler, loosen
the wrench jaws before removing the
wrench.
After installation, the sprinkler wrench
flats and frame arms must be in-
spected and the wax coating re-
touched (repaired) whenever the coat-
ing has been damaged and bare metal
is exposed. The wax coating on the
wrench flats can be retouched by gen-
tly applying a heated 1 /8 inch diameter
steel rod to the areas of wax that have
been damaged, to smooth it back over
areas where bare metal is exposed.
NOTES
Only retouching of the wax coating ap-
plied to the wrench flats and frame
arms is permitted, and the retouching
is to be performed only at the time of
the initial sprinkler installation.
The steel rod should be heated only to
the point at which it can begin to melt
the wax, and appropriate precautions
need to be taken, when handling the
heated rod, in order to prevent the
installer from being burned.
If attempts to retouch the wax coating
with complete coverage are unsuc-
cessful, additional wax can be ordered
in the form of a wax stick (the end of
which is color coded). Only the correct
color coded wax is to be used, and
retouching of wrench flats and frame
arms is only permitted at the time of
initial sprinkler installation. With the
steel rod heated as previously de-
scribed, touch the rod to the area re-
quiring additional wax with the rod an-
gled downward, and then touch the
wax stick to the rod approximately
one-haft inch away from the area re-
quiring retouching. The wax will melt
and run down onto the sprinkler.
The Serles TY-B Recessed Pendent
Sprinklers must be Installed in ac-
cordance with the following instruc-
tions.
Step A. After Installing the Style 1 o or
40 Mounting Plate, as applicable, over
the sprinkler threads and with pipe
thread sealant applied to the pipe
threads, hand tighten the sprinkler into
the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 8). With reference to Figure 3 or
4, the W-Type 7 Recessed Sprinkler
Wrench is to be applied to the sprinkler
wrench flats.
Step C. After the ceillng has been in-
TFP151
stalled or the finish coat has been ap-
plied, slide on the Style 1 O or 40 Clo-
sure over the Series TY-B Sprinkler
and push the Closure over the Mount-
ing Plate until its flange comes in con-
tact with the ceiling.
Care and
Maintenance
The Series TY-B Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers -before, during,
and after installation. Sprinklers dam-
aged by dropping, ~riking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the Installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as It may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service In accordance with
local requirements and/or national
codes.
Limited
Warranty
Page 7 of 8
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for It, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
~RS8u'c:%NiEs~t'A'-m.r?rS> [bRtf.
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FQREGQING WARRANTY ts MADE IN LIEU QF ANY AND ALL QTHER WARRANVESEXPRESS QR !MPLIEQ INCLUDING WARRANTIES
QF MERCHANTABILITY AND FIT-
NESS FDR A PARTICULAR PUB-
I!Ds.E.
Page 8 of 8 TFP151
P/N 57-XXX-X-XXX
I I
I MODEUSIN
SPRINKLER TEMPERATURE
RATING
530 2.8K UPRIGHT (1/2"NPT) TY1151 NATURAL BRASS 135 135°F/S1°c
531 2.8K PENDENT (1/2"NPT) TY1251 4 WHITE POL VESTER 155 155°F/68°C
570 5.6K UPRIGHT (1/2"NPT) TY3151 3 WHITE (RAL901 O)" 175 115°F/79°c
571 5.6K PENDENT (1/2"NPT) TY3251 9 CHROME PLATED 200 200°F/93°C
590 8.0K UPRIGHT (3/4"NPT) TY4151 7 LEAD COATED 286 286°F/141 °C
591 8.0K PENDENT (3/4 "NPT) TY4251 6 WAX COATED 360 360°F/182°C
286°F/141°C MAX.
560 8.0K UPRIGHT (1/2"NPT) TY4851
8 WAX OVER LEAD
561 8.0K PENDENT (1/2"NPT) TY4951 286°F/141 °C MAX.
TABLES
• Eastern Hemisphere sales only.
PART NUMBER SELECTION
SERIES TY-8 PENDENT AND UPRIGHT SPRINKLERS
Ordering
Procedure
When placing an order, indicate the full
product name. Refer to the Price List
for complete listing of Part Numbers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Stand-
ard Response, (specify K-factor),
(specify temperature rating), Series
TY-B (specify Pendent or Upright)
Sprinkler with (specify type of finish or
coating), PIN (specify from Table B).
Rece888d Escutcheon:
Specify: Style (specify) Recessed Es-
cutcheon with (specify finish), PIN
(specify).
1/2' (15 mm)
Style 10
Chrome Plated......... PIN 56-701-ll-()10
112" (15 mm)
Style 10
White Color
Coated . . . .. .. .. .. .. .. PIN 56-701-4-010
112• (15 mm)
Style 10
White RAL9010" . . . . . . . PIN 56-701-3--010
112" (15 mm)
Style 10
Brass Plated........... PIN 56-701-2-010
314" (20 mm)
Style 40
Chrome Plated......... P/N 56-700-9-010
314" (20 mm)
Style 40
White Color
Coated . .. .. . . .. .. . .. . PIN 56-700-4-010
314" (20mm)
Style 40
White RAL9010" . . . . . . . PIN 56-700-3--010
314" (20 mm)
Style 40
Brass Plated........... PIN 56-700-2-010
• Eastern Hemisphere sales only.
Sprlnkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
PIN 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
Wax Sticks:
(for retouching wrench damaged
wax coating)
Specify: (Specify color) color coded
Wax Stick for retouching (specify tem-
perature rating) temperature rated Se-
ries TY-B Sprinklers, PIN (specify).
Black for 135"F ............ PIN 56-065-1-135
Red for 155°F ............. PIN 56-065-1-155
Yellow for 175"F..... . . . . PIN 56-065-1-175
Blue for 200"F and
286"F ................. PIN 56-065-1-286
NOTES
Each wax stick is suitable for retouch-
ing up to twenty-five sprinklers.
The wax used for 286°F sprinklers is
the same as for 200°F sprinklers, and,
therefore, the 286°F sprinkler is limited
to the same maximum ceiling tempera-
ture as the 200°F sprinkler (i.e.,
1so°FJ.
TYCO FIRE PRODUCTS. 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
tqc:a I Fire & Building
/ Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series EC-8 -8.0 K-factor
Extended Coverage (l.ight Hazard}
Customer Servi
Tel: (414) 570-5000 / 00) 558-5236
Fax: (414) 570-5010/ 800) STT-1295
Pendent and Recessed Pendent Sprinklers
General
Description
The Series EC-8 Extended Coverage
Pendent Sprinklers are decorative
glass bulb sprinklers designed for use
in light hazard occupancies. They are
intended for use in automatic sprinkler
systems designed in accordance with
standard installation rules (e.g., NFPA
13) for a maximum coverage area of
400 ft2 (37,2 m2), as compared to the
maximum coverage area of 225 ft2
(20,6 m2) for standard coverage sprin-
klers used in light hazard occupancies.
The recessed version of the EC-8, in-
tended for use in areas with a finished
ceiling, uses either the two-piece Style
30 or 40 Recessed Escutcheon. The
Style 30 Recessed Escutcheon pro-
vides up to 1/2 inch (12, 7 mm) of total
adjustment from the flush pendent po-
sition, whereas, the Style 40 provides
3/4 inch (19, 1 mm) of vertical adjust-
ment from the flush pendent position.
The adjustment provided by the Re-
cessed Escutcheons reduces the ac-
curacy to which the fixed pipe drops to
the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to ex1end the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING' that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 6
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these corrosion resistant coatings
for any given corrosive environment.
The effects of ambient temperature,
concentration of chemicals, and
gas/chemical velocity, should be con-
sidered, as a minimum, along with the
corrosive nature of the chemical to
which the sprinklers will be exposed.
WARNINGS
The Series EC-8 Extended Coverage
Sprinklers described herein must be
installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
National Fire Protection Association,
in addition to the standards of any
other authorities having jurisdiction.
Failure to do so may Impair the per-
formance of thesa devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Number
TY4232 -Pendent, 8.0K
TY4232 is a redesignation for C4232.
JANUARY, 2005
Technic
Data
Approvals
UL and C-UL Listed. Mand NYC Ap-
proved. (Refer to Tab e A for complete
approval information including corro-
sion resistant statu . The approvals
apply to the service conditions indi-
cated in the Design riteria section.)
Maximum Working ressure
175 psi (12, 1 bar)
Discharge Coefflcle ts
K = 8.0 GPM/psl112
(115,2 LPM/bar112)
TFP223
Page 2 of 6
Components:
1 • Frame
2 • Button
3 • Sealing Assembly
4·Bulb 2
5 • Compression
Screw 3
6 • Deflector*
* Temperature rating is 4
Indicated on Deflector.
** Pipe thread
connections per ISO
7/1 can be provided
on special request
TFP223
FIGURE 1
SERIES EC-8 (TY4232) EXTENDED COVERAGE PENDENT SPRINKLERS
(See Note 4)
HAZARD TYPE TEMP. BULB NATURAL WHITE•
LIQUID BRASS POLYESTER
LIGHT PENDENT 135'F/57°C Orange
155'F/68°C Red 1, 2, 3 5
Refer lo Table B for UL and C-UL
Sensitivity Rating REC. PENDENT 135'F/57'C Orange
and w/ Style 30 Esc. 155'F/68'C Red 1, 2, 3 5
Refer to Table C for FM
Sensitivity Rating REC.PENDENT 135'F/57'C Orange
w/ Style 40 Esc. 1ss°FIss·c Red
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL).
2. Listed by Underwriters Laboratories, Inc. for use In Canada (C-UL).
3. Approved by Factory Mutual Research Corporation (FM).
4. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Resistant Sprinklers.
5. Approved by the City of New York under MEA 113-04-E.
•Frame and Deflector only. Listings and approvals apply to color (Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS
(Refer to the Design Criteria Section)
Temperature Ratings
135°F/57°C and 155°F/68°C
Finish
Sprinkler: Refer to Table A
Recessed Escutcheon: White Coaled,
Chrome Plated, and Brass Plated
Physical Characteristics
Frame . . . . . . . . . . . . Bronze
Button . . . . . . . . . . . . . Bronze
Sealing Assembly . . . . . . . . . .
. . . . . Beryllium Nickel w/Teflont
Bulb . . . . . . . . Glass (3 mm dia.)
Compression Screw . . .
................ Bronze
Deflector . . . . . . . . . . . . Brass
t Registered trademark of DuPont
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and flow water.
Design
Criteria
The Series EC-8 Extended Coverage
Pendent Sprinklers must only be in-
stalled in accordance with the applica-
ble UL and C-UL Listing or FM Ap-
proval requirements as indicated
below. Only the Style 30 or 40 Re-
cessed Escutcheon is to be used for
recessed installatio , as applicable
(Ref. Table A, B, and ).
UL and C-UL Llstln
Requirements
1. The Series EC-8
used for the cove
In Table D, based
minimum specifi
function of covera
ard group for all
the design area.
prlnklers may be
ge areas shown
n maintaining the
flow rate as a
e area and haz-
the sprinklers in
2. With respect to h at sensitivity, the
Series EC-8 Sprln lers can be used
with unobstructed onstruction con-
sisting of flat, s oth ceilings (in-
cluding bar Joists) with a maximum
pitch of one in si as defined and
permitted by NFP 13.
3. The minimum allo
TFP223
AREA STYLE
16 X 16 Pendent
16 X 16 Style 30 Recessed
16x 16 Style 40 Recessed
18 X 18 Pendent
18 X 18 Style 30 Recessed
18 X 18 Style 40 Recessed
20x20 Pendent
20x20 Style 30 Recessed
20x20 Style 40 Recessed
QR: Quick Response
SR: Standard Response
Ni A: Not Applicable
13s•F 1ss°F
QR OR
QR OR
QR OR
QR OR
OR SR
QR SR
OR SR
QR SR
SR SR
TABLES
SENSITIVITY RATING FOR UL AND C-UL LISTING
OF SERIES EC-8 SPRINKLERS
135°F 1ss°F
AREA STYLE
16 X 16 Pendent QR OR
16 X 16 Style 30 Recessed QR N/A
16 X 16 Style 40 Recessed N/A N/A
18 X 18 Pendent QR QR
18 X 18 Style 30 Recessed OR N/A
18 X 18 Style 30 Recessed NIA N/A
20x20 Pendent OR QR
20x20 Style 30 Recessed QR N/A
20x20 Style 40 Recessed NIA NIA
QR: Quick Response
SR: Standard Response
Ni A: Not Applicable
TABLEC
SENSITIVITY RATING FOR FM APPROVAL
OF SERIES EC-8 SPRINKLERS
tween the Series EC-8 Sprinklers, to
prevent cold soldering, is 8 feet (2,4
m).
4. The Series EC-8 Sprinklers are to be
installed in accordance with all other
requirements of NFPA 13 for ex-
tended coverage pendent sprin-
klers.
FM Approval
Requirements
The Series EC-8 Extended Coverage
Sprinklers are to be installed in ac-
cordance with the applicable Factory
Mutual Loss Prevention Data Sheet.
Information provided in the FM Loss
Prevention Data Sheets relate to, but
are not limited to, hydraulic design,
ceiling slope and obstructions, mini-
mum and maximum allowable spacing,
and deflector-to ceiling distance.
Page 3 of 6
lnstallat n
The Series EC-8 Sp inklers must be
installed in accordan with the follow-
ing instructions:
NOTi
Do not Install any bu/ type sprinkler if
the bulb is cracked o there is a loss of
I/quid from the bulb. Ith the sprinkler
held horizontally, a mall air bubble
should be present. T diameter of the
air bubble Is approxl ately 1/16 Inch
(1,6 mm).
A leak tight 3/4 Inch T sprinkler joint
should be obtained w th a torque of 10
to 20 ft.lbs. (13,4 to 2 ,8 Nm). A maxi-
mum of 30 ft.lbs. (40 7 Nm) of torque
is to be used to i tall sprinklers.
Higher levels of torq may distort the
sprinkler inlet with nsequent leak-
age or impairment of he sprinkler.
Do not attempt to co pensate for in-
sufficient adjustment fan Escutcheon
Plate by under-or o r-tightening the
Sprinkler. Readjust t e position of the
sprinkler fitting to sui
Step 1. The sprinkler ust be installed
with the deflector par llel to the mount-
ing surface. Pendent sprinklers must
be installed in the pe dent position.
Step 2. After installin the Style 30 or
40 mounting plate ( r other escutch-
eon, as applicable) er the sprinkler
pipe threads, and ith pipe thread
sealant applied to t e pipe threads,
hand tighten the s rinkler into the
sprinkler fitting.
Step 3. Wrench tight
klers using only the -Type 3 (End A)
Sprinkler Wrench. W ench tighten the
recessed pendent prinklers using
only the W-Type 4 S rinkler Wrench.
The wrench recess f the applicable
sprinkler wrench (Re . Figure 4 and 5)
is to be applied to the prinkler wrench
flats (Ref. Figure 1 ).
Page 4 of 6
DESCRIPTION
TY4232 (K=B.0) PENDENT
1 fl. = 0.3048 m
1 ft2 = 0.093 m2
1 gpm = 3. 785 1pm
1 psi = 0.06895 bar
1 gpmlft2 = 40. 7 4 mm/min
AREA
16 X 16
18 X 18
20x20
TABLED
GPM
26
33
40
PSI
10.6
17.0
25.0
FLOW CRITERIA FOR UL ANO C-UL LISTING
OF SERIES EC-8 SPRINKLERS
1/2±1/8'
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
\
(73,0mm)
2-1/4' DIA.
(57,2mm)
1/2' (12,7 mm)
1/4' (6,4 mm)
1-1/4' (31,8 mm)
1' (25,4 mm)
FIGURE2
SERIES EC-8 RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
9/16±1/4'
(14,3±6,4 mm)
FACE OF
SPRINKLER
FITTING
\
2-1/4' DIA.
(57,2 mm)
3/4' (19,1 mm)
1/4' (6,4 mm)
1-5/16' (33,3 mm)
13/16' (20,6 mm)
FIGURE3
SERIES EC-8 RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
TFP223
'FITTI E'
TOWARDS KLER
FIGUR 4
W-TYPE 3 SP INKLER
WREN H
, ----
' '
WRE CH
REC SS
fr ,_ -
® ,-----' ¢:I CD
,' ' ---1 _____ _:~~.I--...A
FIG
WRENCH
LUGS
W-TYPE4 SEO
SPRINKLE NCH
Care an
Mainten
The Series EC-8 Sp inklers must be
maintained and ser iced In accord-
ance with the followin instructions:
NO
Before closing a fire otectlon system
main control valve r maintenance
work on the fire prof tion system that
it controls, permissi n to shut down
the affected fire p~ action systems
must be obtained om the proper
authorities and all pa onnel who may
be affected by this a tion must be no-
tified.
Sprinklers that are lo nd to be leaking
or exhibiting visible s ns of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coat d, or otherwise
altered after leaving t e factory. Modi-
fied sprinklers mu t be replaced.
Sprinklers that have een exposed to
TFP223
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers -before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Rel. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verily the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per N FPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA .25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (1 0) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (1 O} years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FQREGQING WARRANTY IS MADE IN LIEU OF ANY AND ALL
OTHER WARRANT/ES EXPRESS QR
IMPLIED INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT• NESS FDR A PARTICULAR PUR-~
Page 5 of 6
Ordering
Procedu e
When placing an orde , indicate the full
product name. Pie se specify the
Sprinkler ldentificatio Number (SIN},
quantity, and tempera ure rating. Refer
to the Price List for c mplete listing of
Part Numbers.
Contact your local di ributor for avail-
ability.
Sprinkler Assemblie with NPT
Thread Connection
Specify: TY 4232, (sp cify temperature
rating), Extended C erage Pendent
Sprinkler with (spe ify finish), P/N
(specify).
135"F/57"C
Natural Brass ............. PSN 50-801-1-135
White Coated ............. PSN 50-801·4·135
White (RAL9010)" .......... PSN 50-801-3-135
Chrome Plated ............ PSN 50-801-9-135
155'F/68"C
Natural Brass ............. PSN 50-801-1-155
White Coated ............. PSN 50-801-4-155
White (RAL9010)" .......... PSN 50·801-3-155
Chrome Plated ............ PSN 50-801-9-155
"Eastern Hemisphere s les only.
Recessed Escutche n:
Specify: Style (30 o 40) Recessed
Escutcheon with (sp city finish), P/N
(specify).
Style 30 Receasad Eacutc eon
Chrome Plated ............ PSN 56· 705·9·01 1
White Color Coated ........ PSN 56-705-4-011
White (RAL9010)" .......... PSN 56-705·3·011
Brass Plated .............. PSN 56-705-2-011
Style 40 Recessed Eacutc eon
Chrome Plated ............ PSN 56-700-9-010
White Color Coated ........ PSN 56-700-4-01 0
White (RAL9010)" .......... PSN 58-700-3-010
Brass Plated .............. PSN 56-700-2-01 0
'Eastern Hemisphere
Sprinkler Wrench:
Specify: W-Type 3 S rinkler Wrench,
P/N 56-895-1-001
Specify: W-Type 4 R essed Sprinkler
Wrench, P/N 56-875· -001
Page 6 of 6 TFP223
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
46
INCORPORATED
CORONA, CA• (909) 737·5599
FIG. 68
WIDE THROAT TOP BEAM "C" CLAMP WITH LOCKNUT
Size Range -3/8 thru 7/8 inch rod.
Function -For attachment to structural shapes
requiring wider throat especially under roof with
bar joist construction. This clamp may be used in
the set screw down position only.
Approvals -Conforms to Manufacturers Stand-
ardization Society SP-69, type 19.
Finish -Plain and Electro-Galvanized.
Order By -Figure number, rod size, and finish.
Note -Do not overtighten set screw.
FIG. 69
BEAM CLAMP RETAINING STRAP
Size Range -3/8 thru 8 inch rod by 4 thru 14
inch length.
Material -Carbon Steel
Function -To offer more secure fastening of beam
clamp to beam when danger of movement might be
expected.
Approvals -Underwriters' Laboratories listed
when used with Tolco U.L. Listed Fig. 65 and 66
Universal Beam Clamp.
Finish -Mil. Galvanized and Stainless Steel.
Order By -Figure number, type, length "A", and
rod size being used with beam clamp.
Note -Minimum return on Strap: l".
TYPE
1
2
3
10
3/8 • 7/8
A
HOLE STOCK
SIZE SIZE A FINISH
7/16 16gaxl t Mil. Galv.
9/16 16~xt ·· ··, .. ;fJ· ,.{r,;g1;;;~,MJ1;;J3~bhi<,> .
11/16 14gaxl-1/4 t Mil. Galv.
13/16 149~4,:l/4}11\; .;;{,t~tftJ:Mi~i~iMYJ"3~'°;\,
specify 12gaxl-l/4 t Mil. Galv.
INCORPORATED
CORONA. CA• (909) 737-5599
FIG. 65 AND FIG. 66
45
REVERSIBLE C-TYPE BEAM CLAMPS -3/4" AND 1-1/4"
THROAT OPENINGS -~
Size Range • (Fig. 65) 3/8 thru 5/8 inch rod B --j c \
(1/2 thru 10 inch pipe). FIG. 65 ~
Size Range -(Fig. 66) 3/8 thru 5/8 inch rod 77"--A
(1/2 thru 10 inch pipe). D , I
Material -Carbon Steel with hardened cup point _L_ : :
set screw and jam nut. E
Function -Recommended for hanging from steel ,--
beam where flange thickness does not exceed 3/ 4" L_ ..J.-:l-/
(Fig. 65) or 1-1/4" (Fig. 66).
Features -All steel construction eliminates
structural deficiencies associated with casting type
beam clamps.
May be used on top or bottom flange of the beam.
(Beveled lip allows hanging from top flange where
clearance is limited.)
May be installed with set screw in up or down
position.
Offset design permits unlimited rod adjustment by
allowing the rod to be threaded completely through
the clamp.
Open design permits inspection of thread engage-
ment.
Application Note -Fig. 65: add 1-1/2" to rod
length when clamp is to be used in set screw up
position.
Fig. 66: add 2" to rod length when clamp is to be
used in set screw up position.
Approvals -Underwriters' Laboratories listed and
Factory Mutual Engineering approved. Conforms
to Federal Specification WW-H-171E, type 23, and
Manufacturers Standardization Society SP-69,
type 19 and 23. Exceeds requirements of the
National Fire Protection Association (NFPA),
Pamphlet #13, 3/8" rod will support 1/2 thru 4"
pipe, 1/2" rod will support 1/2 thru 8" pipe.
Finish • Plain, Electro-Galvanized, HOG, and
Stainless Steel.
Order By -Figure number, rod size, and finish.
.---
C
j_
F JQ __ Q~
I
ROD SIZE A
3/8
1/2
5/8
ROD
PIPE SIZE
1/2·4
5,.8
10
SIZE PIPE
A SIZE
B
1 • 3/16
1-1/2 ·'
1 • 1/2
B
FIG. 66
FIG. 65 TABLE
MAX. APPROX.
REC. WEIGHT C D E F LOAD LBS. PER 100
3/4 1 7 /16 1 1500 28
3/4 / 1.:, 9/iijtil,lJ.ilthti;;;Q~Pf,{ i~i:~;f,
3/4 1 9/16 1 -1/4
FIG. 66 TABLE
MAX. APPROX.
REC. WEIGHT
C D E F LOAD LBS. PER 100
3/8
1/2
5/8
1/2 · 4
5, 8-
10
1·3/161 • 1/4 1 7/16 1 1500 32
1-1;:2 ' 1 -i/4ri<}91.:1'6Bi1'tl:k4}<,il40ao;L:e; i6rlf i ··•
1 • 1/2 1 • 1/4 1 9/16 1 • 1/4
1'ia
INCORPORATED 120 CORONA, CA• (909) 737.5599
FIG. 1000
"FAST CLAMP" SWAY BRACE ATTACHMENT
Size Range • Pipe size to be braced: 1" through 8"
Sch. 10 and 40. Pipe size used for bracing: 1" and
1-1/4" Sch. 40 JPS.
Material • Carbon Steel
Function • For bracing pipe against sway and
seismic disturbance. The pipe attachment com•
ponent of a sway brace system: Fig. 1000 is used
in conjunction with a Tolco 900 Series Fitting and
joined together with bracing pipe per NFPA #13*,
forming a complete sway brace assembly.
Features • Can be used to brace Schedules 10 and
40 JPS.
Field adjustable, making critical pre-engineering of
bracing pipe unnecessary.
Unique design requires no threading of bracing
pipe.
Can be used as 4-way riser brace.
Can be used as longitudinal brace.
All steel construction eliminates structural
deficiencies associated with casting type sway
brace fittings.
Comes individually packaged with illustrated
installation instructions • sizes are clearly marked.
Steel leaf spring insert provided to assure installer
and inspector that necessary minimum torque
(5 lb/ft) has been achieved.
Application Note• Fast Clamp need not be field
assembled. Position Fast Clamp and tighten two
hex nuts until leaf spring flattens.
*Length of bracing pipe per National Fire
Protection Association, Pamphlet #13, paragraph
A-3-10.3.5: 1" Schedule 40 bracing pipe maximum
7'·2". l·l/4" Schedule 40 bracing pipe maximum
9'·2".
Approvals • Underwriters' Laboratories listed.
Note• Must be used with Tolco U.L. Listed 900
Series attachment.
Finish • Plain, Electro-Galvanized, HOG, and
Stainless Steel.
Order By • Order first by pipe size to be braced
followed by pipe size used for bracing, figure
number, and finish.
0 ~ )
/ ~
didi--
~~
\ I
------.
I ,
I
/ I I
I ! ___ _lj
__,,
Schedule-108/Schedule-409
Fully Listed and FM Approved Sprinkler Pipe
When you specify Schedule-10/Schedule-40 sprinkler pipe you get a UL listed and FM approved product. Although these
products do not require separate approvals, Schedule-1 O/Schedule-40 gives you the extra quality assurance you demand.
Our Sch-10 ( 111, "-8") pipe and Sch-40 (I"-2 i,,; ") pipe have passed the same thorough lab testing as our other listed pipe
products, and receive periodic mill inspections from both UL and FM agents to ensure consistent quality.
Galvanized Pipe
Schedule-I O/Schedule-40 product can be
"hot-dip" galvanized to meet FM
requirements for dry systems in
accordance with the zinc coating
specifications of ASTM A-123.
Superior Coating
Our advanced formula mill coating of-
fers a clean, durable surface. It is also
paint-ready for custom color applications
without special preparation.
The internal surface of all black Allied
Tube & Conduit Fire Sprinkler pipe
products up to 4 .5000" in diameter is
coated with our new Antibacterial For-
mula, "ABF". In scientific laboratory
test, ABS proved to have superior resis-
tance to microbial colonization of pipe
walls, thereby delaying or possibly pre-
venting the onset of Microbiologically
Influenced corrosion (MIC) when the
First Sprinkler System is first installed.
American Made
Meets "Buy American" requirement
and is available through distributors in
the USA, Canada and Mexico.
Specifications & Approvals
Schedule-10/Schedule-40 pipe are in
compliance with the following:
ASTM A-135, and NFPA 13. Both pipe
products have a working pressure rating
of300 psi maximum and also meet the
stringent requirement for the following
tests:
• Welded Outlets
• Hydrostatic Pressure
• Side Wall Rupture
• Vibration Test
NPS
ln;mm
1"
25
1¼"
32
1½"
40
2'
50
2½'
65
NPS
ln;mm
1'
25
1¼'
32
1½"
40
2'
50
2½"
65
3'
80
4"
90
5'
125
6'
150
8'
200
tqc:a I Row Control ~ allied
TUBE & CONDUIT
Sch-40 Specifications
Nominal 1.0. Wt. Wt. (H20 FIiied) Pcs/ WVl.lft (21') Wt/lift (24') WI,,1.ift(25'
ln;mm Lbs/Ft; Kglm Lbs/Ft; Kg/m Lift Lbs; Kg Lbs; Kg Lbs; Kg
1.049 1.680 2.05 70 2,470 2,822 2,940
26.6 2.5 3.05 70 1,120 1,280 1,334
1.380 2.270 2.93 51 2,431 2,778 2,894
35.1 4.36 4.36 51 1,103 1,260 1,313
1.610 2.720 3.61 44 2,513 2,872 2,992
40.9 4.0 5.37 44 1,140 1,303 1,357
2.067 3.650 5.13 30 2,300 2,628 2,738
52.5 5.4 7.63 30 1,043 1,192 1,242
2.469 5.790 7.86 19 2,310 2,640 2,750
62.7 8.6 11.73 19 1,048 1,197 1,247
Sch-1 O Specifications
Nominal 1.0. Wt. Wt. (H20 FIiied) Pcs/ Wlo'Lifl (21') WWII (24') Wt/lift (25'
ln;mm Lbs/Ft; Kg/m Lbs/Ft Kg/m Lift Lbs; Kg Lbs; Kg Lbs; Kg
1.097 1.400 1.81 91 2,675 3,053 3,185
27.9 2.1 2.70 91 1,213 1,385 1,445
1.442 1.810 2.52 61 2,319 2,664 2,760
36.6 2.7 3.75 61 1,052 1,208 1,252
1.682 2.080 3.04 61 2,664 3,045 3,172
42.7 3.1 4.52 61 1,208 1,381 1,439
2.157 2.640 4.22 37 2,051 2,344 2,442
54.8 3.9 6.28 37 930 1,063 1,108
2.635 3.530 5.89 30 2,224 2,542 2,648
66.9 5.3 8.77 30 1,009 1,153 1,201
3.260 4.330 7.94 19 1,728 1,975 2,057
82.8 6.4 11.82 19 784 896 933
4.260 5.610 11.78 19 2,238 2,558 2,665
108.2 8.3 17,53 19 1,015 1,160 1,209
5.295 7.77 17.33 10 1,632 1,865 1,943
134.5 11.56 25.80 10 740 846 881
6.357 9.290 23.03 10 1,951 2,230 2,322
161.5 13.8 34.27 10 885 1,012 1,053
8.249 16.490 40.15 7 2,424 2,770 2,885
209.5 24.5 59.75 7 1,100 1,256 1,309
®<8>@
Listed Approved Listed
16100 S. Lathrop • Harvey, IL 60426 Customer Service:
(800) 882-5543 11350 Norcom Rd.• Philadelphia, PA 19154
2525 N. 27th Ave. • Phoenix, "'2. 85009 Fax 708-339-1806
S5-3
FOR USE WITH WET OR DRY
SYSTEMS. GAUGES HAVE A
BRONZE BURSON TUBE
MOVEMENT IN A STAINLESS
STEEL PLATED CASE
(UNLESS OTHERWISE
NOTED). 3-1/2" DIAMETER.
U.L. AND F.M. APPROVED
(UNLESS OTHERWISE
NOTED).
• 1~aoo~s4a ◄i94
AR• = AS REQUIRED
Brecco Corporation
GAUGES
Part No.
GAAWSS350
GMSS250
GAWP200
GMWP350
► GAUGES <t.
Description Box/Case
0111
AIR/WATER 0-300 PSI 80 WI STAINLESS STEEL CASE
AIR WI RETARD 250 PSI
3-1/2" DIA. WI STAINLESS STEEL 80
CASE
2" RESIDENTIAL GAUGE 300 PSI 100 (NOT U.l. OR F.M APPROVED)
AIR/WATER WI PLASTIC CASE 60
Fu: 1-877-474-9248
breccocorp@earthlink. n~t
082000
INCORPORATED
CORONA, CA• (909)737-5599 30
FIG.909
NO,THREADSMVELSWAYBRACEAITACHMENT
Size Range -1 and 1-1/ 4 inch bracing pipe. For brace pipe
sizes larger than 1-1/4 inch use Talco Fig. 980.
Material -Carbon Steel, hardened cone point engaging
screw.
Function -The structural component of a sway and seismic
bracing system.
Features-
• No threading of the bracing pipe is required.
• Open design allows for easy inspection of pipe engagement.
• All steel construction eliminates deficiencies associated
with malleable type attachments.
• Fastener can be mounted to all surface angles.
Application Note -The Fig. 909 is used in conjunction
with the Tolco Fig. 1000 "Fast Clamp™", Fig. 2001, or Fig.
4(A) pipe clamp, and joined together with bracing pipe.
Install per NFPA # 13 and/ or Tolco's State of California
OSHPD Approved Seismic Restraint Manual.
Installation -Extend bracing pipe through opening.
Tighten cone point engaging screw until head bottoms out.
Approvals -Underwriters Laboratories Listed per 203A
(UL). Approved by State of California Office of Statewide
Health, Planning and Development (OSI-IPD).
Finish -Plain, Electro Galvanized and I-IDG.
Order By -Figure number, pipe size and finish.
Important Note -The Fig. 909 is precision
manufactured to perform its function as a critical
component of a complete bracing assembly.
To ensure performance, the U.L Listing requires
that the Fig. 909 must be used onlv with other
To/co bracing products.
NATIONAL AND INTERNATIONAL PA TENT
APPLICATIONS IN PROCESS.
MAX. MAX.
HORIZONTAL HORIZONTAL
DESIGN DESIGN PIPE LOAD LBS. LOAD LBS. APPROX.
SIZE A B H' W/WASHER \VT./100
l 6 1-5/8 17/32 2015 2765 91
1-1/4 6 1-5/8 17/32 2015 2765 97
• Available with hole sizes to accommodate up to 3/4" fastener.
Consult Factory
0
State of California
OSHPD
APPROVED
Standard washer (Fig. 115)
required for 2765 lb.
design load
INCORPORATED
CORONA, CA• (909) 737-5599
FIG. 4
STANDARD PIPE CLAMP
Size Range -1/2 thru 30 inch pipe.
Material • Carbon Steel
Function -To carry piping where little or no
insulation is required. For heavier loads, see
Fig.4H.
Approvals -Listed by Underwriters' Laboratories
2 -8 inch (1/2 -1-1/2 inch listed if E.G.). Approved
by Factory Mutual Engineering, 1/2 • 8 inch.
Federal Specification WW-H-171E, type 4, 1-1/2
thru 24 inch and Manufacturers Standardization
Society SP-69, type 4.
Maximum Temperature -750°F
Finish -Plain, Electro-Galvanized, HDG, and
Stainless Steel.
Order By -Figure number, pipe size, and finish.
4-1/4
16 10-1/4
20 28 12-1/2
D
--A
C
2
5/8x2-1/2
19
MAX. REC. LOAD LBS. APPROX. FOR SERVICE TEMP. WEIGHT
650"F 750°F PER 100
500 445 29
2490 2220
3060
INCORPORATED
CORONA. CA• (909) 737-5599
• I ' ', l' ' 1 ' -" I > \' l ••'-'' ! 1 , , , • ,
FIG. 51 AND FIG. 52
SIDE BEAM BRACKETS (CONT.)
H-3
H-1
--H-2 • __ _ H-1 j_
41
H-2 A
I t:=:::jp:::::=J__l I
[-l B I J
· A-C
FIG. 51 FIG. 52
FIG. 51 for NFPA Rod and Fastener Sizing
PIPE ROD HOLE SlZE SIZE SIZE A B C H-1 H-2
FIG. 52 • 6 Hole Bracket
HOLE SIZE
C A-1 'c__j
STOCK SIZE
3/16x2
APPROX.
WEIGHT
PER JOO
35
ROD
SIZE A B C H-1 H-2 H-3
STOCK
SIZE
APPROX.
WEIGIIT
PER 100
3/Sxl/2 2 1-1/16 2 9/16 7/16 9/32 3/16x2
FIG. 56
TAPPED SIDE BEAM CONNECTOR
Size Range • 1/2 thru 4 inch pipe (3/8 inch rod).
Material • Carbon Steel
Function -Practical and economical bracket used
to support hangers from steel or wood beams. Can
be used with concrete shot-type inserts. Tapped
hole allows easy adjustment of hanger rod.
Approvals -Underwriters' Laboratories listed and
factory Mutual Engineering approved for 1/2 • 4"
pipe.
Finish • Plain, Electro-Galvanized, HDG, and
Stainless Steel.
Order By -Figure number and finish.
Note -Per NFPA #13: 1/2 thru 2 inch pipe use 3/8
inch fastener; 2-1/2 thru 4 inch pipe use 1/2 inch
tastener.
PIPE
SIZE A
ROD
SIZE
B C D E
1/2 • 4 2-5/8 3/8 1 3/8 1-1/16
HOLE SIZE STOCK
F G H J SIZE
1-1/8 7 /16 9/16 1-1/4 1/4xl
APPROX.
WEIGHT
PER 100
20
35
Submittal Data Sheet
Super 40®/Dyna-Thread®
Full Line Sch-40 Replacement
Super -Hl/Dyn:1-Thrc:.1d sprinkler pipe represems an engineering udvnncemen1 for lhe sprinkler
pipt: induslry. II combin..:~ th..: s.1fe1y and longc::vi1y of trldirional Sch-40 pipe wich qualiry and
~upcrior h~'dn.1ulic adv.inrng~!\.
Comparison to Schedule 40 Super 40/Dynn-Threads inside diarnere.r is up <0 3.6%
larger th:.rn Sch--10 gi\·ing i1 Sllperior hydrnulics. Also, when used in combinmion wirh Dyna-Flow
prpe. down sizing of,en occurs. Super 40/Dyna-Thread is fully liSled ond approved UL, ULC, and
FM for fire sprinkler ;1pplica1ions. The life expectancy of Super 40/Dynu-Thre:id and Sch-40 ure
equal based on lhc calculaied wall thicknesses per UL (see CRR). The consis,enr qualiry of sreel
u-.ed 10 make Super .:ltJ/Dymt-Thread facili1,nes smooth threading and lower mnimenance co:,;1s.
The' t!.\lc'mW of Supc'r -lll/Dyna-Thre.td is prnrec1ed by a clean, dur;-ib\e mill couring for extemleJ
sl.dt life :tnd ~;1sy paim i1pplica1ic111. Wi1h its increased :,;1reng1h and lighter weight, Super40/
D\n.1-Thre:.h .. 1 reducr.s ins1,,ll,Hion fotigue ,md is iJeal for re1ro-fi1 applic;11ions. Corrusion
R,:..,l.'.tanL·e R:.11io 1CRR11s a UL. {Underwri1ers L1bormory) 1er111 for the t!s11111med life expt!cLancy
ol ._1 pipe juin1. Thi$ is based on 1hi! calcula1ed wall thickness Lll the base of 1he first exposed rhread .
.1:-:-.umeU IO be 1he \\c"~1kc:;t poim of the pipe leng1h. Super 40/Dyna-Thread ;rnd Sch-40 have 1he
.,ame c~1kul:.11ed \\·:.111 thicknesse:,; :.11 1his poinl and :.ire both Jssigned che Sj\1lf.? CRR of 1.00.
Comparison to L.W.T. Pipe More wall 1hickness a, ,he 1hread iCRR=l.00) gives
Super -Hl/Dyn..1-Thread be11er life expectnncy 1hun ligh1wall 1hreadable pipe join1s. Unlike
liµh1wa1I 1hrc-adahlc p1pe. Super 40/Dyna•Thread ha~ no thread gauge. warning. Super 40/
Dvnn-Thrc;.,d is ;.ipproved for standnrd hanger spacing ( 15 ft. O.C.J, can be used as eJnhqu:1ke
sway Qn.tcing. and is safe ID use as drops. Super 40/Dyna-Thread is snfer 10 weld on rhan nrnny
,.rnc-cua,ed lighrn·nll 1hreadable pipe products. Super 40/Dyno-Thread is more widely accepted
Lh;rn lighfwall lhreadable where Sch-40 is specified.
Slarnp Her•
Sp~ifications & Approvals
Super-tfl/Dy1rn-Thre~1d pipe is innnufacrured w
meer ASTM A 135. Grnde A and is in compliance
11 i1h NFPA-13. All sizes of Super 40/Dyna-Thrcad
are rared at 300 psi working pressure. Super 40/
Dvna-Thread is UL ,rnd ULC Listed for wer, dry
:.11id prc--:.1cuon sprinklc'r systems and FM Appro~•ed
fl,r u:-.e in we1 systems. Super 40/Dynu-Thread can
bl! .. hot-dip" gal\':mized 10 meet FM requirement
Specifications a:1nc11u •=M■111c
rl.,r Jry _.,y:;1ern.s. Super 40/Dyna-Thread is approveU
lor all threaded C\)upling:.; ;rnd ~ielded outlels und is
.--;L11wble for all roll-grooved, and plain-end fiuings.
(See lis1ing infonmnion).
Li.s1ud Lisied
Product
NPS
)( 1"
* 25
X 1 1/4"
* 32
X 1 1/2"
.40
?" X -
* 50
Nominal
l.D.
1.080
27.4
1.408
35.8
1.639
41.6
2.104
53.4
Wt/Ft Wt/Ft
H20 Filled
1.330 1.75
2.0 2.60
1.870 2.54
2.8 3.78
2.290 3.22
3.4 4.79
3.050 4.57
4.5 6.80
Pcs/ Wt/Litt Wt/Litt Wt/Lift
Lift 21.' 24' 25'
70 1955 2234 2327
70 887 1013 1056
51 2002 2288 2384
51 908 1038 1081
44 2115 2418 2519
44 959 1097 1143
30 1921 2196 2287
30 871 996 '.L037
A1neriqn Tube and Pipe was acquired b)' Allied 'rube :rnd Conduit on February 1, 1997. The engineered light wall and standard wall family or products alt~ough they
han' dillrrenl names are the same in all respects with regard to s1rength1 weight, bundle counl, lisLlngs and approrals. For example, Drn:i-Flow and Super Flo are 1he
s:tme producl as nre Dynn Thrend ::ind Super ~O. XL is manufnctured with Exterior galvanized coaling. BLT is manufactured with Bh:1ck lacquer c'oating. ;
Pro1ec1: Sprinkler Conlractor: Date:
Engineer: Specification Relerence· System Type:
Loca1,ons: Comments:
Grooved IPS Fittings
Victaulic fittings are designed specifically for use
in grooved piping systems.
Victaulic airers a broad line or
fittings in sizes through 2411
(600 mm) in a variety of straight
and reducing styles. Most standard
fittmgs are cast or durable ductile
iron to precise tolerances. Victaulic
standard fittings pressme ratmgs
conform to the ratings of Victaulic
Style 77 couplings.
All fittmgs are supplied with
grooves or shoulders to permit last
instaUat1on without field
preparation. The grooved design
permits fleXJbllity for easy
alignment. These fittJngs are not
intended for use with Victauh·c
couplings for plain end pipe (refer
to page 55 ior fittings available for
plam end applications).
Fittings are provided in vanous
materials including maUeable iron.
ductile iron. steel or s-egmentally'
welded steel dependmg on styles
and size. Fittings .are painted
orange enamel with galvanized
optionally available. contact
Victaulic for details.
Pipe
Victnulic filtings are designed
specificaUy for use in grooved
piping systems. Fittings are
provided grooved or with
shoulders conformmg to standard
steel pipe outside diameters. When
connecting wafer or lug-rype
butterfly valves directly to
Victaulic fittings with 741 or 743
Vic-Flange"' adapters. checl, disc
clearance dimensions with I.D
dimension ol fittmg.
Request 07.01.
Alternate Materials
Stainless Steel -Grooved end
fittings are available in Schedule 10
Type 316 stainless steel (Schedule
5, 40 and Type 304 optionally
available) m various sizes. Fitting
center-to-end dimensions will vary
depending upon wve and
schedule.
Request 17 .04 for details.
Aluminum -Grooved end fittings
are available in aluminum alloy 356
T6, in sizes from 1 -8" (25 -200
mm). Request 21.03 or contact
Victaulic for details.
Pipe
Alternate Styles
EndSeal® "ES" Fittings -
EndSeal fittings are available in 2 -
12" (50 -300 mm) for use with "ES"
grooved pipe and HP-70ES
EndSeal or Fire-R"' couplings.
"ES" fittings are painted green [or
easy identification. EndSeal (anj
standard) fittings may be easily
internally coated (by others) for
severe service requirements.
Always specif\• "ES EndSeal
fittings" when ordermg.
Request 07.04 !or information on
EndSeal fittings.
Fittings Machined for Rubb,ar
or Urethane Lining (MRL) -For
severe abrasive services, Victauhc
fittings may be rubber or urethane
lined (by others). Lining may bf'
inside diameter/end (abrasion
resistance) or wrap-around
(corrosion and/or abrasion)
machined.
Request 25.03 or contact Victaulic
for speclfic details.
Flow Data
Friction Resistance
lnches/m1T1 Equivalent FeeVmelers of Slraight Pipe Inches/mm Equivalenl FeeVmelers of Stralghl Pipe
Tl,e chart expresses the frictional
re3istance of various Victaulic
fittings as equivalent feet of
straight pipe. Fittings not listed
can be estimate,! from the data
given. for example. a 22%0 elbow
is apprOJarnately one-half the
resistance of a 45° elbow. Values of
m1d¥sizes can be interpolated.
H
90° Elbows
No. 100
No. 10 1)120
Norn. Aclual Sid. Long
Size Size Radius Radius
1 1.315 1.7 -
25 33 "/ Os
2 2.375 35 2.5
~10 60~ 11 0$
3:j: 3.000 4.3 -761 1 3
3 3.500 5.0 3.8 80 M9 1 5 , '}
4 4.500 6.8 5.0
100 1,i.1 3 ~I 1S
4.250 6.4 -41/, :j: 1080 1 B
5 5.563 8.5 -
12b 1,113 2.6
5¼t 5250 8.1 -1330 25 -
5½t 5.500 8.5 -1397 26 -
6 :j: 6.250 9.6 -1590 .2..9 --
# Contact V1ctaul1c for details + 0. D. Dimension.
45" Elbows Tees
No. 110
No. 11 lY.! D
Sid. Long
Radius Radius Branch Run
0.8 -4.2 1.7
Oc l 3 05
1.8 1.1 8.5 3.5
n :-i 03 2.6 11
2.1 -108 4.3 07 33 13
2.6 1.6 13.0 5.0
1.)8 05 40 15
3.4 2.1 16.0 6.8
10 Oti 'g 2.1
3 " -< -15.3 6.4 09 ➔ 7 20
4.2 -21.0 8.5
1.3 "" 26
4.1 -20.0 8.1
lti ti ;·~ ?.5
4.2 -21.0 8.5
1 3 "' .2.6
5.0 --25.0 10.0 1 5 76 30
90" Elbows 45° Elbows Tees
No. 100 No.110
No. 10 1½0 No.11 1½D
Norn. Actual Sid. Long Sid. Long
Size Size Radius Radius Radius Radius Branch Run
G 6.625 10.0 7.5 5.0 3.0 25.0 1(1.0
150 168 3 30 73 , 5 OH ,7 6 JO
6.500 9.6 -5.0 -25.0 10.0 6½:J: 105 1 ?.9 -1 ~~ 7 6 JO
B 8.625 13.0 9.8 6.5 4.0 33.0 1,:.0
200 ;2191 so 3.0 Q.D , 2 101 40
10 10.750 17.0 12.0 8.3 5.0 41.0 11·.o
?50 2730 52 37 2.5 1.5 1~.5 5.:2
12 12.750 20.0 14.5 10.0 6.0 50.0 20.0
SOD 3~3 9 6.1 J 4 30 1" 1!>2 G 1
14 14.000 # 23.0 # 18.0 60.0 17.0
350 3~ti G # 7.0 • ~-:i HI 3 ~ ~I
16 16.000 # 26.0 # 20.0 70.0 2(1,Q
,100 40G4 • 79 " 61 21 3 61
18 18.000 # 29.0 # 23.0 80.0 2~-.0
45l) .:.is·ro • 3.6 ' :o 24 4 70
20 20.000 ff 33.0 ff 26.0 90.0 25.0
500 ooso ,; 10 1 • 7.9 27 4 7.6
24 24.000 # 40.0 # 30.0 30.5 34.0
600 6100 • 12.2 ' 91 93 10..:1
e
t
t;W'k0ldlt'W2t t ti M!Cl?IXtt'MWr!»Wl
Style 07
Zero-Flex® Rigid Coupling
@@ ~
The unique angle· pad design of
Zero-Flex® Style 07 adjusts to
standard pipe and roll or cut
groove tolerances, positively
clamping the pipe to resist fiexural
and torsional loads. Wider l<ey
section fills more of the groove
area.
Request 06. 02.
,~'liWiollifi,IIJl.'il!il
Style 77
Standard
Flexible Coupling
®@ ~
Style 77 couplings are d,Jsigned
witi1 cross-ribbed constJ uction to
provide a strong component tor
pressure piping systems. Sizes
¾ -12" (20 -300 111111) are two-piece
housings. Sizes 14 -22"
(350 -550 mm) are cast in lour
identical segments, with larger
sizes cast in six segments.
Y----z r Request 06 04
X. / 1/ ~ / / Ill'
,./ ~--,.,,ev u~ ~ 'P. / ··~ ~· ~~5P . . .
2 ~ 12" Sizes 14-16~ Sizes 18 -24" Sizes ¼-12" Sizes 14 -22'' Sizes 24" Size
Norn. Max.. Dimensions -Inches/mm Aprx.
Size Work Press. Wgl. Each
Norn. Max. Dimensions -Inches/mm Aprx:.
Si:!:e Work Press. Wgt. Each
lnches/rnm PSl./k.Pa X y z Lbs./1\Q Inches/nun Ps1·11,;Pa X y z Lbs./t,g
1 750 2.45 4.13 1.88 1.G 1/, 1.000 2.13 3.63 1.75 1.1
'~> !'>1::1 ri:! 1\):j ..iB tl ~ " (ii)f)\"1 ;,J iP .I.I ll!•
11/J 750 2.60 4.00 1.68 1.6
.\.' :1 I ::i titi hP ,llJ ll ~-1 1,000 2.38 3,88 1.75 1.3
·•:--: 1i8\.)() tiO :):-: .1.1 {\(i
1½ 750 2.94 4.81 1.88 1.6 11/~ 1,000 2.63 4.63 1.75 2.0
"' :11,·.1 :, ,:·2 ·UJ " ti~X)(l d:" 111; -1-1 il!l
2 750 3.19 5.44 1.88 2.3 1½ 1.000 3.00 5.00 1.75 2.1
!1() .•l:"'.i :11 1·11 .1:: '" j\1 ti\}.)0 '(j 1:·· ,_, 111
2½ 750 3.88 6.13 1.88 2.8 2 1,000 3.63 5.63 1.75 2.6
,)~ ;;1,"J illl 1:i6 .1;: 1,.; :-:l' ti9t'li."'l i)~' U...i LI ,_
3* 750 4.25 5.75 1,86 3.6
~>l ;!, ,tm U6 .,: "\(i 2½ 1,000 4.25 6.25 1.75 3.1
<)~ tirlOO 1{):; h!l ., .. , 1-1
3 750 4.56 6.81 1.88 3.1
:10 '.>17!> lh) 1:-:4 ,111 I -1 H 1,000 4.31 6.31 1.75 3.6
d\lOtl llil hii.'r " 1tl
4 750 5.81 8.25 2.06 4.8 3 1,000 5.00 7.00 1.75 3.5
100 ::1-'.'.; 1-1tl 2'10 s' ?2 (It) ti~lCII) 1:?.-l ;;i ,, lli
4V.t 750 5.56 7.44 2.06 5.2
:il ~-'., l•ll 1119 !i'.' .' d
3½ 1,000 5.63 8.00 1.75 5.6
;in ,:~;oo 1-13 .0l).i ,_, .,
5 750 7.06 9.75 2.06 7.1
1 '!, :--1:-·5 17~1 _;-1~ !:>2 ,i_' 4 1,000 6.38 8.50 2.00 6.6
1i}I' d!)O;l 16:' -~ 7 ti :,1 :,o
SY. t 700 6.36 9.18 2.06 7.4
:!~1''!1 17.i '.:;:, 5~' 3-t. 4V.t 1,000 5.88 8.06 2.06 7.0
(.,~k)(l 1--1~1 l(t!l :,,' -·
5½t 700 6.94 9.42 2.06 7.6
kl':1 i ;n ,'.t) :;~ ,'-I 5 ·1,000 7.63 10.25 2.00 10.6
·.~J fr)l.lt) 1~)-i _\ill !d -1 H
6 700 8.00 10.75 2.06 8.7
l:Jll .iit!~> ~~03 :,::, 52 3-1 5¼:t: 1,000 7.34 9.20 2.06 10.0
u~no Hki .~Joi :1~• I!.•
61/, t 700 7.85 10.18 2.06 9.2 m.•~, 1~)9 '.''.1:"l S? F'
1,000 7.60 9.44 2.06 11.0 51/, t \i!)()\"1 l~l'.l .'W :12 :it)
6½t 700 8.00 10.75 2.06 7.2
-IS,'S ·1u:i ~.-.·:; !l? 32 6 1,000 9.00 11.50 2.00 11.8
1j{l m100 -'?!l .':l.' :,1 !l-1
8§ 600 10.25 nso 2.50 14.9
"\JO JUtl :'l-iO _j.\J ,i.cl li,'"
1,000 8.50 10.38 2.06 13.2
6%:t: ,i~.llX) ;.'lli .Jl~-1 1i1l
10 § 500 12.88 16.75 2.56 25.0
-~:-iU .kt!iO ?''"" i.>1~ 6'.) 1, ., 6,,t 1,000 9.19 11.50 2.06 13.2
li)OO .:.'3~) .·':12 :-2 \;(l
12 § 400 14.88 1850 2.56 28.2
;11,)l) .·'7:1ll ,;,-tl 1:\j O:i 1 ~' t! 8§ 800 11.38 14.50 2.38 20.1
,\)i.l ~'.lull n.i!l -~t,li ,;o !ll
14 300 16.19 19.75 2.94 32.8
.bl) .'11t;:) 011 :,P;> 7!, 14.1() 10 § 800 13.50 16.75 2.50 28.3
''.)(' :,~,Jl.1 :1.:1.1 ·•?~ ii-I I:n
16 300 18.38 21.75 2.94 41.2
-l()O 'Ill~~ -11;:-;,:i.:; .-!l HI':' 12 § 800 15.50 19.00 2.50 34.2
.illl'J ::ii;.10 .i9-1 JB3 t>-1 1:,:,
18 300 20.69 23.88 3.06 54.2 14 300 16,63 20.00 2.88 35.6
·1!>0 :'Oli:1 !_,",'li litX~ 7:"l /,1 t: :bl) '.(lt.)~ -t~:i !':-illl .-:~ lli 1
20 300 23.00 27.38 3.06 67.2 15 300 17.88 21.25 2.88 48.8
:1oi.1 XKi!i :)!14 ii!b /[1 :;() 5 :, -~-'))u'.; -1:>•l ,),\l) ; 3 .'' I
24 250 27.13 3150 3.13 76.2 16 300 19.00 22.38 2.88 51, 1
til)() 17~•:, ,i!.!) 20il 7~) .3-1 \~ ,!(if :.'Oo:i m3 '.1ti<l ., :':.l:'
::f: 0.0 01mens1on. • Reier lo notes on page 7 § Available lo J.I.S d1mens1on 18 300 21.25 24.38 3.13 64.4
.J!'itl -'0Ut> :,4{1 l~l\l -~, :•:J:'
20 300 23.50 27.50 3.13 91.2
!>00 :'(lt1;1 :1!l' (;\}9 -·!) '" t
22 300 25.63 30.00 3.13 92.0
!,~{) ..:tk'S lb1 ,,;? i"\) ... , :
24 250 27.63 31.38 3.13 94.0
L100 172:i :-o;.-;~F ;'~ I'.'{\
l OD. Dimension • Reier 10 notes on page 7 § Available to J.I S. d1men~Ion.
8
·-Su-per Flo®/Dyna-FIOW®
,..._Iigh Strength Steel Pipe·
The original high-strength lightwa/1 sprinkler pipe with hydraulics superior to Schedule-10.
Super Flo/Dyna-Flow pipe is the "original"
high-srrength lightwall sprinkler pipe.
Super Flo/Dyna-Flow has outstanding
hydraulic capabilities and is recognized
as the most popular alternative to
Schedule-IO pipe. Lightweight, easy to
cut and easy to handle for installation.
Super Flo/Dyna-Flow is a valuable
addition to any fire protection system.
Superior Hydraulics
With an inside diameter of up to 11 %
larger than Schedule-40 and up to 7%
larger than Schedule-10, Super Flo/
Dyna-Flow pipe hydraulics are exceptional.
,-ger I.D.s enable Super Flo/Dyna-Flow,
\ ui1d related components, to be down-
sized within the system, thus increasing
the potential for job cost savings. For
complete Hazen-Williams charts, refer to
"Super Flo/Dyna-Flow Hydraulic Data
Tables."
• Coatings & Fabrication •
Super Flo/Dyna-Flow products are coated
with an environmentally approved and
specially formulated modified-acrylic or
water-based coating. This durable coating
is paimable. The black coating acts as
an excellent primer and is resistant to
weathering and U.V. degradation from
outdoor storage.
Metallurgical properties provide excellent
fabrication characteristics for end prep
finishes, welding and roll grooving. No
.---P.cial process or equipment are needed
fabrication and installation.
Specifications x=lnDhllS •=MlltJlc
Product Nominal Wt;Ft Wt/Ft
NPS I.D. H20 Filled
X 1" 1.191 0.830 1.31
* 25 30.3 1.2 1.95
X 11/4" 1.536 1.059 1.87
"32 39.0 1.6 2,78
X 11/2" 1.728 1.667 2.71
*40 43.9 2.5 4.03
?" X -2.203 2.104 3.79
* 50 56.0 3.1 5.64
X 2 1/2" 2.703 2.564 5.10
*65 68.7 3.8 7.59
X 3" 3.314 3.387 7.18
* 80 84.2 5.0 10.69
X 4" 4.310 4.473 10.86
* 90 109.5 6.7 16.16
X 6" 6.403 7.714 21.70
*150 162.6 11.5 32.29
Specifications & Approvals
Super Flo/Dyna-Flow pipe is
manufactured to meet ASTM A-
795 Type E, Grade A and is in
compliance with NFPA-13 and
NFPA-14. All sizes of Dyna
Flow/Super Flo are UL Listed,
FM Approved and ULC Listed.
Listed Approved Listed
Super Flo/Dyna-Flow is UL/ULC
Listed for use with roll grooved,
plain-end couplings, and welded
joints for wet, dry, preaction and
deluge systems. It is FM Approved
for roll grooved, plain-end, and
welded joints for wet systems.
Refer to appropriate documentation
for up-to-date listing and approval
information. Super Flo/Dyna-Flow
is now available "hot-dip" galvanized
and has been specifically approved
by FM for dry systems uses.
Pcs/ Wt/Lift Wt/Lift Wt/Lift
Lift 21' 24' 25'
91 1586 1812 1888
91 719 822 856
61 1356 1550 1615
61 615 703 733
61 2135 2440 2542
61 968 1107 1153
37 1634 1868 1946
37 741 847 883
30 1615 1846 1923
30 733 837 872
19 1351 1544 1608
19 613 700 729
19 1784 2039 2124
19 809 925 963
10 1620 1851 1928
10 735 840 875
Additional Benefits
• Lightweight and easy to install,
resulting in more efficient use of
your freight and labor dollars.
• Provides stability needed to
comp! y with standard hanger
spacing (l5 ft 0.C.) per NFPA.
• Available in Standard lengths
for your convenience, or can be
ordered in cuscom lengths
upon approval.
• Fast cutting and welding, as well
as easy roll grooving and end
preparation.
• Available in Factory roll grooved
form for quicker shop turnaround.
• Clean, durable mill coating
provides longer "shelf life" and
;:icts as an excellent primer for
custom paint applications. ,G;S allied
TUBE & CONDUIT 16100 S. Lathrop
Harvey, IL 60426
11350 Norcom Rd.
Philadelphia, PA 19154
2525 N. 27th AYe.
Phoenix, AZ 85009
Customer Service:
1·800-797-6210
Fax 708-339-1806
INCORPORATED
CORONA, CA• (909) 737-6599
FIG. 99
ALL THREAD ROD CUT TO LENGTH
Size Range • 3/8 thru 7/8 inch rod in l inch
increments.
Material -Carbon Steel
Maximum Temperature -750°F
Finish • Plain, Electro-Galvanized, and Stainless
Steel.
Order By -Figure number, rod diameter, rod
length, and finish.
ROD SIZE
3/8
1/2
5/8
3/4
7/8
MAX. REC. LOAD LBS,
FOR SERVICE TEMPS,
650"F 750'F
610 540
1130 1010
1810 1610
2710 2420
3770 3360
{!'.'.'.!I ( i If I 14 I I 111 ! 11 i I; I 11 f,,,,, 111,1111, I',,: I !,Jli If ii ;t:J ::i, /i/ijJ)/1:
FIG. 100
ALL THREAD ROD FULL LENGTHS
Size Range -1/4 thru 1-1/2 inch rod in 10'-0"
lengths.
Material -Carbon Steel
Maximum Temperature • 750°F
Finish -Plain, Electro-Galvanized, and Stainless
Steel.
Order By -Figure number, rod diameter, and
finish.
MAX. REC. LOAD LBS. APPROX.
ROD FOR SERVICE TEMPS WEIGHT SIZE 650'F 750'F PER 100 FT.
53
lNCOl'IPOl'IATf:D
COAONA, CA• (909) 737.5599
FIG. 2 ADJUSTABLE RING HANGER
15
FIG. 2 NFPA ADJUSTABLE RING HANGER WITH REDUCED ROD SIZE
Size Range -1/2 thru 6 inch pipe.
Material -Carbon Steel, Mil. Galvanized to G-90
specification.
Function -For general piping purposes. Knurled
swivel nut design permits hanger adjustment after
installation. Spring tension on swivel nut holds it
securely in hanger before installation. Swivel nut
easily removed.
Approvals -Underwriters' Laboratories listed and
Factory Mutual Engineering approved. Conforms
to Federal Specification WW-H-l 71E, type 10, and
Manufacturers Standardization Society SP-69,
type 10.
Maximum Temperature -650°F
Finish -Mil. Galvanized and Stainless Steel.
Order By -Figure number and pipe size.
PIPE
SIZE
ROD
SIZE A B C
A
STOCK
SIZE
MAX.
REC.
LOAD LBS.
C
APPROX. WEIGHT PER 100 FIG. 2
FIG. 2 NFPA
1/2 3/8 3-1/8 2-5/8 1-3/8 16ga X 1 400 17 17
:o..,~-~Lll:;;;:>S/a.;;J;;(,aill&,;.,;:\i.~,l/2.,;c~il~ll~-:;,;i~i,,.19.s1,;i.l.J,,:,;i.,;~;~,-,APQ;,; 1},i,L2,.,:~1'222~i.il"iiJ1\.;;,'Wit
1 3/8 3-3/8 2-5/8 1-1/8 16ga X 1 400 18 18
,.;.h.+L4:~:J:,S;$J~\iii¼J,9JL4'..,.J.l1:2.:,7/&:ei.!j;,]:iJ.Jtb,;0,1:J~si\JJ:1:lLs,L:.;:c:·._ .. ::;499_;;:,_.,,.;.:~-""';.._.;;;;}:.d2i;::Jii£t~~
1-1/2 3/8 3-7/8 2-7/8 1 16gaxl 400 21 21
. :. ~,_.,; :. ' .1L2l.~:; '.,5i,\c'.,'!\'.iiL~;;;'..L~: ~;;,;JL~:1;X0l'.s:i:.~: .,~;jdgiJ~Kk:. ,.. ,L. • • • .. 4QQ ~"-;.,"'~' , . "L,&~-~i i,i/',;)~;.;;;~;].;lfuJ
2-1/2 1/2* 5-3/4 4-1/4 1-5/8 14ga X 1-3/16 600 41 40
:_3_.;,,; .: ,-,; : .JL?t~:.s!i,.§'.:•.L: ; ~:.,. c::,.;,,f J/s},:;c;,;-,, :}-ig4i,\i,:--,l1;i[¥1:i3/~.9~ . "' ·/\$9.0 . .-, ,;/t,,, _;;:; it:il.t:i::tJiii~.QJiii;\;;;;rJJ§iiliJ
3-1/2 1/2* 7-3/8 5-1/4 2-1/8 14gaXl-3/16 600 52 50
i 4, ': i ·: ,f:',_,: :. • $1P)•r,.•;:;;,;· 7/~18.!;;>::):il; ,i .•\·;'.,i,tiiilr:5<8:'IM;:-1): 1.4°a,xJ, l/4 : ;••. · ·1000·•··:•;. -.~, ,•.;_:•.;,,,,;; ;,,59. •.b~):~'''.i:'\~,;,i,,!#\;,~·:;p;9.•.i:i.. ,.,\i,· . .,..•"-"•~-.i:~o,,1'1>,l~~"J'u,-., _,....,\.._.w.:;rl..~, .... ;,..il.,~.1:¢ ... ,<.;".._.~~i.n;,.,,li_:,__;,>1.~-'-'---,.t,1, .• ,-'&i,~..,_:..&,c.~:.,,:,,,.,L.,:._.o •a.••·· ,:,,.~>.Cl<-'>,.r,,.__,.,~~~~•'-""'~•-"• -.-;..liat'loa.-~ ~IIJII
5 5/8** 9 6-1/8 2-1/4 12gaxl-l/4 1250 97 95
·. f;i· .. ,. ·;,•<:.·!3/4~~:,-·::~,.~/8.'·' .. :;-.(>,'•l.J;?•···•)i. klll&1:,'\•.:c~:J?aa>: kJ:/4 .. ··• .;·., .125Q ·, .. ,•:.:· ,;,;:J~Q' .. :;;;;::,;;~.;,1::.,.<i-l~'.,,:1Qg,,f</
"'3/8" nut ia used when NFPA rod sizing ia; requested,
"" l/2" nut is used when NF PA rod sizing is requested.
LIFEGUARD FIRE PROTECTION, INC.
2605 TEMPLE HEIGHTS DR. STE: F, OCEANSIDE, CA 92056
(760) 806-9997 • FAX (760) 806-4813
Hydraulic Design Information Sheet
Name: GREYHA WK BUSINESS PARK Date: October 3, 2005
Location: 3220 GREYHA WK CT.
Building: _D:::....:-E=---------=----------------System No. ..:..R:.::0::..:0::..:F:..._ ____ _
Contractor: LIFEGUARD FIRE PROTECTION, INC. Contract No.
Calculated By: LCH Drawing No. _3:......::O..:.F....:3;__ ____ _
Construction: t8J Combustible O Non-Combustible Ceiling Height ....:2::.:1:..-..:..0 ___ _ Ft.
SYSTEM DESIGN
~ NFPA 13: LJ Light Hazard Ordinary Hazard Group LJ I lJ 2 0 3 r8J Extra Hazard
0 NFPA231 0 NFPA231C: Figure: Curve:
D Other (Specify)
□Specific Ruling Made By Date
Area of Sprinkler Operation 3000 System TYJ1e
Density .45 [8J Wet □Dry D Deluge D Pre-Action
Area Per Sprinkler 100 S.F. MAX. SRrinkler or Nozzle
Hose Allowance GPM: Inside 100 Make TYCO Model ELO231-B
Hose Allowance GPM: Outside 400 Size ¾ K-factor: 11.2
Rack Sprinkler Allowance NIA Temnerature Rating 286DEG.
CALCULATION SUMMARY
GPM Required 1654.86 PSI Required 61.36 At Base of Riser ------------------" C" Factor Used: Overhead 120 Under ound 150
WATER SUPPLY
Water Flow Test PumRData Tank or Reservoir
Date& Time 8-3-05 I 1:50 PM Rated Capacity Capacity
Static PSI 122 At PSI Elevation
Residual PSI 116 Elevation .
GPMFlowing 1500 Well
Elevation 0 Proof Flow GPM
Location SITE
Source of Information LIFEGUARD FIRE WITH CARLSBAD FIRE DEPT.
rrnn II JI l y-<I.TAD A r,p
Commodity Class Location
Storage Height Area Aisle Width
Storage Method: Solid Piled % Palletized %Rack
Rack D SingleRow D Conventional Pallet D Automatic Storage D Encapsulated D Double Row D Slave Pallet 0 Solid Shelving D Non-Encapsulated D Multiple Row D Open
Flue SRacing In Inches Clearan1,:e From ToR of Storage to Ceiling
Longitudinal Transverse Ft. In.
Horizontal Barriers Provided
greyhawk bldg d-e roof .45/3000
250
240
230
220
210
200
190
180
170
160
150
140
130
120
11➔ •
100
90
80
70
60
50
40
30
20
10
J..,,
,_,.
✓
u~al!-V
~ @.
oY ~
0250 500 750 1000
System Demand ..
Sprinkler Demand 82.86 PSI
~dditional Flows
Hose at Source
Total Demand 86.72 PSI
•
/~
,/ .....
,_,. V
1250 1500
@ 1554.86 GPM
500.00 GPM
0.00 GPM
@ 2054.86 GPM
-• H0988
1750
Water Flow (GPM)
Sigma Dynamic• Corporation
7700 Supply/ Demand Graph
I I
Margin
Pressure 13.42 PSI
Flow 1232.09 GPM
4 i ~
~
I
2000 2250
Water Supply ..
Static 109.80 PSI
Residual 104.40 PSI
Elevation 0.00 PSI
@ 1500.00 GPM
'--
~
N1.85
2500
SUBMITTAL SERIAL NO:4144HY1 10-03-2005 PAGE 1
greyhawk bldg d-e roof .45/3000
FLOW TEST RESULTS
Water Supply
STATIC 109.80 PSI
RESIDUAL 104.40 PSI @ 1500.00 GPM
CITY PRESSURE AVAILABLE AT 2054.9 GPM 100.13 PSI
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K-FACTOR PRESSURE ----------------
100 63.31 43.20 11.20 31. 95
101 52.65 43.20 11.20 22.10
102 52.50 43.20 11.20 21.98
103 52.46 43.20 11.20 21.94
104 62.23 43.20 11. 20 30.87
105 49.94 43.20 11.20 19.88
106 49.80 43.20 11.20 19.77
107 49.77 43.20 11.20 19.74
108 61.59 43.20 11.20 30.24
109 47.78 43.20 11.20 18.20
110 47.65 43.20 11.20 18.10
111 47.61 43.20 11.20 18.07
112 61.29 43.20 11.20 29.95
113 46.12 43.20 11.20 16.96
114 46.00 43.20 11.20 16.87
115 45.96 43.20 11.20 16.84
116 61. 21 43.20 11.20 29.86
117 44.92 43.20 11.20 16.09
118 44.80 43.20 11.20 16.00
119 44.76 43.20 11.20 15.97
121 44.12 43.20 11.20 15.52
122 44.00 43.20 11.20 15.43
123 43.96 43.20 11.20 15.41
125 43.65 43.20 11.20 15.19
126 43.52 43.20 11.20 15.10
127 43.49 43.20 11.20 15.08
129 43.42 43.20 11.20 15.03
130 43.30 43.20 11.20 14.94
131 43.26 43.20 11.20 14.92
SUBMITTAL SERIAL NO:4144HY1
greyhawk bldg d-e roof .45/3000
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K-FACTOR --------
133 43.36 43.20 11. 20
134 43.23 43.20 11.20
135 43.20 43.20 11.20
TOTAL WATER REQUIRED FOR SYSTEM
OUTFLOWS AT 8
OUTFLOWS AT 22
TOTAL WATER REQUIREMENT
PRESSURE REQUIRED AT 0
MAXIMUM PRESSURE UNBALANCE IN LOOPS
MAXIMUM VELOCITY FROM 26 TO 36
PRESSURE --------
14.99
14.90
14.88
1554.86 GPM
400.00 GPM
100.00 GPM
2054.86 GPM
86.72 PSI
0.00 PSI
23.26 FPS
10-03-2005 PAGE 2
SUBMI'ITAL SERIAL N0:4144HY1 10-03-2005 PAGE 3
greyhawk bldg d-e roof .45/3000
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
131 135 2.703 L 8.00 C=120 PT 14.88 (135)
Q 43.20 F==O F 0.00 PE 0.00
BN T 8.00 0.0054 PF 0.04
127 131DQ 43.26 2.703 L 8.00 C=120 PT 14.92 (131)
Q 86.46 F=O F 0.00 PE 0.00
BN T 8.00 0.0194 PF 0.16
123 127DQ 43.49 2.703 L 8.00 C=120 PT 15.08 (127)
Q 129.95 F=O F 0.00 PE 0.00
BN T 8.00 0.0413 PF 0.33
119 123DQ 43.96 2.703 L 8.00 C=120 PT 15.41 (123)
Q 173.91 F=O F 0.00 PE 0.00
BN T 8.00 0.0708 PF 0.57
115 119DQ 44.76 2.703 L 8.00 C=120 PT 15.98 (119)
Q 218.67 F=O F 0.00 PE 0.00
BN T 8.00 0.1082 PF 0.87
111 115DQ 45.96 2.703 L 8.00 C=120 PT 16.85 (115)
Q 264.63 F=O F 0.00 PE 0.00
BN T 8.00 0.1540 PF 1.23
107 lllDQ 47.61 2.703 L 8.00 C=120 PT 18.08 (111)
Q 312.24 F=O F 0.00 PE 0.00
BN T 8.00 0.2091 PF 1.67
103 107DQ 49.77 2.703 L 8.00 C=120 PT 19.75 (107)
Q 362.01 F=O F 0.00 PE 0.00
BN T 8.00 0.2749 PF 2.20
38 103DQ 52.46 2.703 L 28.25 C=120 PT 21.95 (103)
Q 414.47 F=T F 16.70 PE 0.00
BN T 44.95 0.3531 PF 15.87
28 38 2.703 L 0.83 C=120 PT 37.82 38)
Q 414.47 F=T F 16.70 PE 0.36
NR T 17.53 0.3531 PF 6.19
PT 44.37 28) ------------------130 134 2.703 L 8.00 C==120 PT 14.90 (134)
Q 43.23 F=O F 0.00 PE 0.00
BN T 8.00 0.0054 PF 0.04
126 l30DQ 43.30 2.703 L 8.00 C=l20 PT 14.94 (130)
Q 86.53 F=O F 0.00 PE 0.00
BN T 8.00 0.0195 PF 0.16
SUBMI'ITAL SERIAL NO:4144HY1 10-03-2005 PAGE 4
greyhawk bldg d-e roof .45/3000
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
122 126DQ 43.52 2.703 L 8.00 C=120 PT 15.10 (126)
Q 130.05 F=O F 0.00 PE 0.00
BN T 8.00 0.0414 PF 0.33
118 122DQ 44.00 2.703 L 8.00 C=120 PT 15.43 (122)
Q 174.05 F=O F 0.00 PE 0.00
BN T 8.00 0.0709 PF 0.57
114 118DQ 44.80 2.703 L 8.00 C=l20 PT 16.00 (118)
Q 218.85 F=O F 0.00 PE 0.00
BN T 8.00 0.1083 PF 0.87
110 114DQ 46.00 2.703 L 8.00 C=120 PT 16.87 (114)
Q 264.84 F=O F 0.00 PE 0.00
BN T 8.00 0.1542 PF 1.23
106 llODQ 47.65 2.703 L 8.00 C=120 PT 18.10 (110)
Q 312.49 F=O F 0.00 PE 0.00
BN T 8.00 0.2094 PF 1.68
102 106DQ 49.80 2.703 L 8.00 C=120 PT 19.78 (106)
Q 362.29 F=O F 0.00 PE 0.00
BN T 8.00 0.2753 PF 2.20
37 102DQ 52.50 2.703 L 28.25 C=120 PT 21.98 (102)
Q 414.80 F=T F 16.70 PE 0.00
BN T 44.95 0.3536 PF 15.89
27 37 2.703 L 0.83 C=l20 PT 37.87 37)
Q 414.80 F=T F 16.70 PE 0.36
NR T 17.53 0.3536 PF 6.20
PT 44.43 ( 27)
------------------129 133 2.703 L 8.00 C=120 PT 14.99 (133)
Q 43.36 F=0 F o.oo PE 0.00
BN T 8.00 0.0054 PF 0.04
125 129DQ 43.42 2.703 L 8.00 C=l20 PT 15.03 (129)
Q 86.78 F=O F 0.00 PE 0.00
BN T 8.00 0.0196 PF 0.16
121 125DQ 43.65 2.703 L 8.00 C=120 PT 15.19 (125)
Q 130.42 F=O F 0.00 PE 0.00
BN T 8.00 0.0416 PF 0.33
117 121DQ 44.12 2.703 L 8.00 C=l20 PT 15.52 (121)
Q 174.54 F=O F 0.00 PE 0.00
BN T 8.00 0.0713 PF 0.57
SUBMI'ITAL SERIAL NO:4144HY1 10-03-2005 PAGE 5
greyhawk bldg d-e roof .45/3000
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Sununary
From To GPM IN Devices Ft PSI/Ft PSI
113 117DQ 44.92 2.703 L 8.00 C=l20 PT 16.09 (117)
Q 219.47 F=0 F 0.00 PE 0.00
BN T 8.00 0.1089 PF 0.87
109 113DQ 46.13 2.703 L 8.00 C=120 PT 16.96 (113)
Q 265.59 F=0 F 0.00 PE 0.00
BN T 8.00 0.1550 PF 1.24
105 109DQ 47.78 2.703 L 8.00 C=120 PT 18.20 (109)
Q 313.38 F=0 F 0.00 PE 0.00
BN T 8.00 0.2105 PF 1.68
101 105DQ 49.94 2.703 L 8.00 C=120 PT 19.88 (105)
Q 363.32 F=0 F 0.00 PE 0.00
BN T 8.00 0.2768 PF 2.21
36 l0lDQ 52.65 2.703 L 28.25 C=120 PT 22.09 (101)
Q 415.97 F=T F 16.70 PE 0.00
BN T 44.95 0.3555 PF 15.98
26 36 2.703 L 0.83 C=l20 PT 38.07 ( 36)
Q 415.97 F=T F 16.70 PE 0.36
NR T 17.53 0.3555 PF 6.23
PT 44.66 26)
------------------112 116 2.703 L 8.00 C=l20 PT 29.86 (116)
Q 61.21 F=0 F 0.00 PE 0.00
BN T 8.00 0.0103 PF 0.08
108 112DQ 61.29 2.703 L 8.00 C=120 PT 29.94 (112)
Q 122.49 F=0 F 0.00 PE 0.00
BN T 8.00 0.0370 PF 0.30
104 108DQ 61.59 2.703 L 8.00 C=l20 PT 30.24 (108)
Q 184.09 F=0 F 0.00 PE 0.00
BN T 8.00 0.0787 PF 0.63
100 104DQ 62.23 2.703 L 8.00 C=l20 PT 30.87 (104)
Q 246.32 F=0 F 0.00 PE 0.00
BN T 8.00 0.1348 PF 1.08
35 l00DQ 63.31 2.703 L 28.25 C=l20 PT 31.95 (100)
Q 309.62 F=T F 16.70 PE 0.00
BN T 44.95 0.2059 PF 9.26
25 35 2.703 L 0.83 C=120 PT 41.21 35)
Q 309.62 F=T F 16.70 PE 0.36
NR T 17.53 0.2059 PF 3.61
PT 45.18 25)
SUBMITTAL SERIAL NO:4144HY1 10-03-2005 PAGE 6
greyhawk bldg d-e roof .45/3000
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
------------------11 8 7.758 L 145.00 C=150 PT 80.02 8)
Q 572.02 F=GV,T F 58.94 PE 0.00
LU T 203.94 0.0025 PF 0.51
4 ll 7.758 L 120.00 C=l50 PT 80.53 11)
Q 572.02 F=T,GV,EE F 72.53 PE 0.00
LU T 192.53 0.0025 PF 0.48
PT 81.01 { 4)
------------------9 8 7.758 L 259.00 C=150 PT 80.02 { 8)
Q 1135.40 F=2GV,2EE F 39.26 PE 0.00
LU T 298.26 0.0089 PF 2.65
12 9DQ -978.02 7.758 L 80.00 C=150 PT 82.67 9)
Q 157.38 F=GV,T F 58.94 PE 0.00
LU T 138.94 0.0002 PF 0.03
3 12 7.758 L 215.00 C=150 PT 82.70 12)
Q 157.38 F=T,GV F 58.94 PE 0.00
LU T 273.94 0.0002 PF 0.05
PT 82.75 3) ------------------10 9 7.758 L 160.00 C=150 PT 82.67 9)
Q 978.02 F=GV F 6.04 PE 0.00
LU T 166.04 0.0067 PF 1.11
1 10 7.758 L 326.00 C=150 PT 83.78 10)
Q 978.02 F=2EE,4GV,T F 104.24 PE 0.00
LU T 430.24 0.0067 PF 2.88
PT 86.66 l) ------------------7 8 7.758 L 382.00 C=150 PT 80.02 8) Q 347.44 F=T,GV F 58.94 PE 0.00 LU T 440.94 0.0010 PF 0.44
6 7 7.758 L 40.00 C=l50 PT 80.46 7)
Q 347.44 F=O F 0.00 PE 0.00
LU T 40.00 0.0010 PF 0.04
5 6 7.758 L 157.00 C=l50 PT so.so 6) Q 347.44 F=GV,2EE F 33.22 PE 0.00
LU T 190.22 0.0010 PF 0.19
4 5 7.758 L 320.00 C=150 PT 80.69 5) Q 347.44 F=GV F 6.04 PE 0.00 LU T 326.04 0.0010 PF 0.33
SUBMITTAL SERIAL NO:4144HY1 10-03-2005 PAGE 7
greyhawk bldg d-e roof .45/3000
Location Flow Pipe Fittings Equiv Friction Pressure
in Size & Length Loss Summary
From To GPM IN Devices Ft PSI/Ft PSI
3 4DQ 572.02 7.758 L 266.00 C=150 PT 81.02 4)
Q 919.46 F=2GV,EE F 25.67 PE 0.00
LU T 291.67 0.0060 PF 1. 75
2 3DQ 157.38 7.758 L 75.00 C=l50 PT 82.77 3)
Q 1076.84 F=GV F 6.04 PE 0.00
LU T 81.04 0.0080 PF 0.65
1 2 7.758 L 314.00 C=l50 PT 83.42 2)
Q 1076.84 F=2GV, T, 2EE F 92.16 PE 0.00
LU T 406.16 0.0080 PF 3.25
PT 86.67 1)
------------------27 28 6.357 L 12.00 C=l20 PT 44.37 28)
Q 414.47 F=0 F 0.00 PE 0.00
FMl T 12.00 0.0055 PF 0.07
26 27DQ 414.80 6.357 L 12.00 C=l20 PT 44.44 ( 27)
Q 829.27 F=0 F 0.00 PE 0.00
FMl T 12.00 0.0198 PF 0.24
25 26DQ 415.97 6.357 L 12.00 C=120 PT 44.68 ( 26)
Q 1245.24 F=0 F 0.00 PE 0.00
FMl T 12.00 0.0420 PF 0.50
24 25DQ 309.62 6.357 L 6.00 C=120 PT 45.18 ( 25)
Q 1554.86 F=T F 31.43 PE 0.00
FMl T 37.43 0.0633 PF 2.37
23 24 6.357 L 45.75 C=120 PT 47.55 ( 24)
Q 1554.86 F=0 F 0.00 PE 0.00
FM T 45.75 0.0633 PF 2.90
22 23 6.357 L 20.50 C=120 PT 50.45 ( 23)
Q 1554.86 F=2E F 25.14 PE 8.02
FR T 45.64 0.0633 PF 2.89
21 22DQ 100.00 8.450 L 7.00 C=l40 PT 61.36 ( 22)
Q 1654.86 F=2E F 63.24 PE 0.00
UN T 70.24 0.0134 PF 0.94
20 21 7.758 L 95.00 C=l50 PT 62.30 ( 21)
Q 1654.86 F=T,4EE,E F 134.44 PE 4.66
UN T 229.44 0.0178 PF 4.08
COMMENT: elevation difference from flow tes taken here
15 20 7.758 L 10.00 C=l50 PT 71.04 ( 20)
Q 1654.86 F=4E,DCA F 108.72 PE 0.00
UN T 118.72 0.0178 PF 2.11
8 11 DOUBLE CHECK DETECTOR ASSEMBLY 3.83
SUBMITI'AL SERIAL NO:4144HY1
greyhawk bldg d-e roof .45/3000
Location Flow
in
From To GPM
8 15
Q 1654.86
0 1
Q 2054.86
Pipe
Size
IN
7.758
UN
7.758
UN
Fittings
&
Devices
F=T,GV,E
L
F
T
L
F
T
Equiv Friction
Length Loss
Ft PSI/Ft
85.00 C=150
86.12
171.12 0.0178
1.00 C=lS0
0.00
1.00 0.0266
10-03-2005 PAGE 8
PT
PE
PF
PT
PT
PE
PF
PT
Pressure
Summary
PSI
76.97
0.00
3.05
76.20
86.69
0.00
0.03
86.72
15)
8)
1)
0)