HomeMy WebLinkAbout6359 PASEO DEL LAGO; ; AS160078; Permit2/15/24,11:20 AM ASI 60078 Permit Data
City of Carlsbad
Sprinkler Permit
6359 PASEO DEL
Job Address:
LAGO
Permit Type: SPRINK
Parcel No: 2130920900
Lot #: 0
Reference No.:
Permit No: AS160078
Status: ISSUED
Applied 3/31/2016
Approved: 4/18/2016
Issued: 4/18/2016
PC #: Inspector:
Project Title: FASHIONPHILE T.I. INSTALL NEW CONCEALED PENDENTS
Applicant:
TOTAL FIRE PROTECTION, INC
STE. 244
1611-AS. MELROSE DR.
VISTA, CA
760-525-4329
Owner:
PALOMAR B LC L L C
C/O BIXBY LAND CO
2211 MICHELSON DR #500
IRVINE CA
Fees ($) Add'l Fees ($) Total ($) Balance ($)
438 0 438 0
about:blank 1/1
'U
MATERIAL DATA SUBMITTAL
Fashionphile
6359 Paseo Del Lago
Carlsbad, CA 92011
Page * Description Manufacturer 1-2 Pipe Allied Dyna-Thread Pipe
3-10 Fittings Tyco Ductile Iron Fittings
11-12 Mechanical Tee Tyco Fig 40-5 Strap Tee
13-19 Sprinkler Reliable F I FR56 Sprinkler
20-23 Sprinkler Reliable F I FR56 Sprinkler
24 Hanger Afcon Fig. 300 Ring Hanger
25 Hanger Afcon Fig 655 All Thread Rod
26-27 Attachment Sammy Wood Vertical Mount
Total Fire Protection, Inc.
1611 A S. Melrose Dr. #244
Vista, CA 92081
(760)525-4329 fax (877) 724-4329
C16-955387
tfpjohnc@gmail.com
AS1 60078
6359 PASEO DEL LAGO
DynamThread 0
Full Line Sch-40 Replacement
Dyna-Thread offers the life expectancy of Sch40 with superior hydraulics and greater value.
Dyna-Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry. It combines the safety
and longevity of traditional Sch-40 pipe with quality and superior hydraulic advantages.
Comparison to Schedule 40
Dyna-Thread's inside diameter is up
to 3.6% larger than Sch-40 giving it
superior hydraulics. And, when used
in combination with Dyna-Flow pipe,
down sizing often occurs.
Dyna-Thread is fully listed and
approved by UL. ULC, and FM for
fire sprinkler applications.
The life expectancy of Dyna-Thread
and Sch-40 are equal based on the
calculated wall thicknesses per UL.
The consistent quality of steel used to
make Dyna-Thread facilitates smooth
threading and lower maintenance
costs.
The exterior of Dyna-Thread is
protected by a clean, durable mill
coating for extended shelf life and
easy paint application.
(9 <~> 8
Listed Approved Listed
With its increased strength and lighter
weight, Dyna-Thread reduces
installation fatigue and is ideal for
retro-fit applications.
Corrosion Resistance Ratio (CRR) is a
UL (Underwriters Laboratory) term for
the estimated life expectancy of a pipe
joint. This is based on the calculated
wall thickness at the base of the first
exposed thread, assumed to be the
weakest point of the pipe length. Dyna-
Thread and Sch-40 have the same
calculated wall thicknesses at this point
and are both assigned the same CRR of
1.00.
The internal surface of all black Allied
Tube & Conduit Fire Sprinkler pipe
products up to 4.5000" in diameter is
coated with our new Antibacterial
Formula, "ABF'. In scientific laboratory
test, ABS proved to have superior
resistance to microbial colonization of
pipe walls, thereby delaying or possibly
preventing the onset of
Microbiologically Influenced corrosion
(MIC) when the First Sprinkler System
is first installed.
More wall thickness at the thread
(CRR=1.00) gives Dyna-Thread
better life expectancy than lightwall
threadable pipe joints.
Unlike lightwall threadable pipe,
Dyna-Thread has no thread gauge
warning.
Dyna-Thread is approved for
standard hanger spacing (15 ft.
O.C.), can be used as earthquake
sway bracing, and is safe to use as
drops.
Dyna-Thread is safer to weld on.
Dyna-Thread is more widely
accepted than lightwall threadable
where Sch-40 is specified.
Super 40/Dyna-Thread pipe is
manufactured to meet: ASTM A-135,
Grade A and is in compliance with
NFPA-13. All sizes of Super 40/Dyna-
Thread are rated at 300 psi working
pressure. Super 40/Dyna-Thread is UL
and ULC Listed for wet, dry deluge and
pre-action sprinkler systems and FM
Approved for use in wet systems. Super
40/Dyna-Thread can be "hot-dip"
galvanized to meet FM requirement for
dry systems. Super 40/Dyna-Thread is
approved for all threaded couplings and
welded outlets and is suitable for all
roll-grooved, and plain-end fittings.
(See listing information).
Specifications
tIPS Naminall.D. WI. WI. (H20 Filled) PcW WtI[ift (21') WULIfI (241) WULIft (25')
In; mm In; mm LbrIFt Kg/rn Lbs/Fl; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs Kg
1.080 1.330 1.75 70 1955 2234 232
25 274 2.0 2.60 70 887 1013 105
1W 1.408 1.870 2.54 51 2002 2288 2384
32 35.8 2.8 3.78 51 908 1038 108
1W 1.639 2.290 3.22 44 2115 2418 251
40 41.6 3.4 4.79 44 959 1097 114
2.104 3.050 4.57 30 1921 2196 228
50 53.4 4.5 6.80 30 871 996 103
16100 S. Lathrop Harvey, IL 60426 tqco/Rowconrn.I Qr flied 11350 Norcom Rd. Philadelphia, PA 19154
TUBE & CONDUIT 2525 N. 27th Ave. . Phoenix, AZ 85009
Customer Service:
(800) 882-5543
Fax 708-339-1800
S3-3
Submittal Data Sheet DynaThreadG
Full Line Sch-40 Replacement
Dyna-Thread sprinkler pipe represents an engineering advancement for the sprinkler
pipe industry. It combines the safety and longevity of traditional Sch-40 pipe with
quality and superior hydraulic advantages.
Comparison to Schedule 40 Dyna-Threads inside diameter is up to 3.6% larger than
Sch40 giving it superior hydraulics. Also, when used in combination with Dyna-Flow
pipe, down sizing often occurs. Dyna-Thread is fully listed and approved UL, ULC,
and FM for fire sprinkler applications. The life expectancy of Dyna-Thread and Sch-40
are equal based on the calculated wall thicknesses per UL. The consistent quality of
steel used to make Dyna-Thread facilitates smooth threading and lower maintenance
costs. The exterior of Dyna-Thread is protected by a clean, durable mill coating for
extended shelf life and easy paint application. With its increased strength and lighter
weight, Dyna-Thread reduces installation fatigue and is ideal for retro-fit applications.
Corrosion Resistance Ratio (CRR) is a UL (Underwriters Laboratory) term for the
estimated life expectancy of a pipe joint. This is based on the calculated wall thickness
at the base of the first exposed thread, assumed to be the weakest point of the pipe
length. Dyna-Thread and Sch40 have the same calculated wall thicknesses at this
point and are both assigned the same CRR of 1.00.
Comparison to L.W.T. Pipe More wall thickness at the thread (CRR=l .00) gives
Dyna-Thread better life expectancy than lightwall threadable pipe joints. Unlike
lightwall threadable pipe Dyna-Thread has no thread gauge warning. Dyna-Thread is
approved for standard hanger spacing (15 ft. O.C.), can be used as earthquake sway
bracing, and is safe to use as drops. Dyna-Thread is safer to weld on than many zinc-
coated lightwall threadable pipe products. Dyna-Thread is more widely accepted than
lightwall threadable where Sch40 is specified.
Stamp Here
Specifications & Approvals Super 40/
Dyna-Thread pipe is manufactured to
meet: ASTM A 135, Grade A and is in
compliance with NFPA-13. All sizes of
Super 40/Dyna-Thread are rated at 300
psi working pressure. Super 40/ Dyna-
Thread is UL and ULC Listed for wet,
dry and pre-action sprinkler systems and
FM Approved for use in wet systems.
Super 40/Dyna-Thread can be "hot-dip"
galvanized to meet FM requirement for
dry systems. Super 40/Dyna-Thread is
approved for all threaded couplings and
welded outlets and is suitable for all roll-
Specifications
lIPS Nominal I.D. WI. WI. (1120 Riled) PcW Wts1Jlt (21') WUUft (241) WIsUft (25'
In; mm In; mm Lbs/Fl; Kg/rn Lbs/Fl; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1.080 1.330 1.75 70 1955 2234 232
25 27.4 2.0 2.60 70 887 1013 105
1W 1.408 1.870 2.54 51 2002 2288 2384
32 35.8 2.8 3.78 51 908 1038 108
1W 1.639 2.290 3.22 44 2115 2418 2519
40 41.6 3.4 4.79 44 959 1097 114.
2.104 3.050 4.57 30 1921 2196 228
50 53.4 4.5 6.80 30 871 996 103
grooved, and plain-end fittings. (See American Tube and Pipe was acquired by Allied Tube and Conduit on February 1,
listing information). 1997. The engineered lightwall and standard wall family of products although they
The internal surface of all black Fire have different names are the same in all respects with regard to strength, weight,
Sprinkler pipe up to 4.5000" in diameter bundle count, listings and approvals. For example,
shall be coated with Allied Tube & Dyna-Flow and Super Flo are the same product as
Conduit Antibacterial Formula 'ABF". are Dyna Thread and Super 40. XL is manufactured (I) <e>(j) with Exterior galvanized coating. BIT is
manufactured with Black lacquer coating. Listed Approved Listed
Project: Sprinkler Contractor: Date:
Engineer: Specification Reference: System Type:
Locations: Comments: 2
S3 -4
tLfco /Fire & Building
/ Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Pipe Fittings
NPT Threaded,
Ductile Iron
General
Description
The Tyco* Series 800 Threaded Pipe
Fittings and California Tees & Elbows
are manufactured from ductile iron.
They are stronger and more corrosion
resistant than cast iron fittings. The
additional strength is provided by the
ductile properties and by adding mag-
nesium while the iron is being poured
into the final cast shape. Although
lighter than standard cast iron, the fit-
tings have an added advantage of be-
ing less susceptible to cracking due to
their added strength.
The Series 800, California, and Figure
719 Threaded Pipe Fittings are a re-
designation for the Central Series 800,
California, and Figure 719 Threaded
Pipe Fittings.
WARNINGS
The Threaded Pipe Fittings described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Pro-
tection Association, In addition to the
standards of any other authorities hav-
ing junsdiction. Failure to do so may
impair the performance of these
devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Technical
Data-
Approvals:
UL Usted and FM Approved
Maximum Working Pressure:
Series 800 and California Fittings:
250 psi (17,2 bar)
Figure 719 Plug:
250 psi (17.2 bar)
Material:
Series 800 and California Fittings:
Ductile Iron
Figure 719 Plug:
Cast Iron
Pipe Thread:
NPT per ANSI B1.20.1
Installation
Apply Teflont tape or high quality pipe
joint compound on male pipe threads
and tighten two to three turns beyond
hand tight.
NOTE
Installers who have not used ductile
iron threaded fittings should be in-
structed that the fittings are stron-
ger than the pipe and overtightening
the fitting can create leaks and cause
damage to pipe threads. In general,
there is about one-half turn difference
between cast iron and ductile iron fit-
tings. Apply Teflon tape or high qual-
ity pipe joint compound on the male
pipe threads and tighten two to three
turns beyond hand tight. If an auto-
matic make-on machine is being used,
please exercise caution in setting the
machine to the proper parameters pri-
or to tightening fittings onto the male
pipe threads.
Limited
Warranty
Products manufactured by Tyco Fire
& Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years from
date of shipment by TFBP. No warran-
ty Is given for products or components
manufactured by companies not af-
filiated by ownership with TFBP or for products and components which have
been subject to misuse, improper in-
stallation, corrosion, or which have not
been installed, maintained, modified or
repaired in accordance with applicable
Standards of the National Are Protec-
tion Association, and/or the standards
of any other Authorities Having Juris-
diction. Materials found by TFBP to be
defective shall be either repaired or re-
placed, at TFBP's sole option. TFBP
neither assumes, nor authorizes any
person to assume for it, any other ob-
ligation in connection with the sale of
products or parts of products. TFBP
shall not be responsible for sprinkler
system design errors or Inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was Informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
The foregoing warranty is made In lieu
of any and all other warranties. ex-
ores or implied, including warranties
of merchantability and fitness for a
carticular curoose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made In contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Please specify the
quantity, figure number, wall thickness,
and size.
Page 1 of 10 JANUARY, 2008
'registered trademark of E. I. du Pont de (()) Nemours and Company or Its affiliates.
TFPI7IO
Page 2of 10 TFPI7I0
E
A
FIGURE 811 FIGURE 813
90° ELBOW 450 ELBOW
NOMINAL DIMENSIONS FIGURES 811 & 813
Figure 811
B Approx. A B
Inches Weight Part Inches Inches
(mm)
Lbs. Number (mm) (mm)
(kg)
0.56 0.24 86206 0.88 0.38
(14,2) (0111) (22,4) (9,7)
0.75 0.40 86205 1.00 0.44
(19,0) (0118) (25,4) (11,2)
0.81
(20,6)
0.64
(0,29)
86200 1.13
(28,7)
0.81
(20,6)
1.06 0.95 86201 1.31 0.63
(26,9) (0,43)(33,3) (1610)
1.19 1.24 86202 1.44 0.69
(30,2) (0,56) (36,6) (17,5)
1.50 1.74 86203 1.68 0.94
(3811) (0,79) (427) (23.9)
1.56 3.28 86204 1.94 1.00
(39,6) (1,49)
TABLE I
Nominal Pipe
Size Figure 813
ANSI A Approx.
Inches Inches Weight Part
ON (mm) Lbs. Number
(kg)
1/2 1.13 0.22 86780 DN15 (28,7) (0109)
3/4 1.31 0.33 86781 DN20 (33,3) (0,15)
1
0N25
1.50
(38,1)
0.48
(0,21) 86280
1-1/4 1.75 0.73 86281 DN32 (44.5) (0,33)
1-1/2 1.94 0.93 86282 DN40 (49,3) (0,42)
2 2.25 1.55 86283 0N50 (57,1) (0.70)
2-1/2 2.89 2.70 DN65 (68,3) (49,3) (25,4) (1.22) 86782
TFPI7IO Page 3 of 10
FIGURE 812
900 REDUCING ELBOW
Nominal Pipe Figure 812 Size
ANSI A B C D Approx.
Inches Inches Is Is Inches Weight
Lbs.
Part
Number ON (mm) (mm) (mm) (mm) (kg)
3/4 x 1/2 1.19 1.19 0.63 0.63 0.33
DN20x 16 (30,2) (30,2) (16,0) (16,0) (0115) 86342
I x1/2 1.25 1.38 0.56 0.81 0.44 86210 DN25 x 15 (31,8) (35,1) (14,2) (20.6) (0,20)
I x3/4 1.38 1.44 0.69 0.88 0.53
DN25 x 20 (35.1) (36,6) (17,5) (22,4) (0,24) 86211
1-1/4x 1/2 1.31 1.50 0.63 0.94 0.64
DN32 x 15 (33,3) (38,1) (16,0) (23,9) (0,29) 86212
1-1/4x3/4 1.44 1.63 0.75 1.06 0.75 86213 0N32 x 20 (36,6) (41,4) (19,0) (26,9) (0,34)
1-1/4x 1 1.56 1.68 0.88 1.00 0.77
DN32 x 25 (39,6) (42,7) (22,4 (25,4) (0,35) 86214
1i/2x3/4 1.50 135 0.75 1.19 0.95 86221 0N40 x 20 (38.1) (44,4) (19.0) (30,2) (0,43)
1-1/2x 1 1.63 1.81 0.88 1.13 0.99 86215 0N40 x 25 (41.4) (46.0) (22,4) (28,7) (0,45)
1-1/2x1-1/4 1.81 1.88 1.13 1.19 1.14 86216 DN40 x32 (46,0) (47,8) (28,7) (30,2) (0,52)
2x314 1.63 1.94 0.88 1.38 1.39 86217 DN50x20 (41,4) (49,3) (22.4) (35,1) (0.63)
2x1 1.75 2.06 2.00 1.31 1.58 86218 DNSO x 25 (44,4) (52,3) (50,8) (33,3) (0,72)
2x1-112 2.00 2.19 1.25 1.44 1.67 86220 DN50 x 40 (50,8) (55,6) (31.8) (36,6) (0.76)
2-1/2 x 2 2.38 2.63 1.25 1.88 3.01
DN65 x 50 (60.5) (66.8) (31.8) (47,8) (1.36) 86262
TABLE 2
NOMINAL DIMENSIONS FIGURE 812
TFPI7I0 Page 5 o 10
Approx.
Weight Part
Lbs. Number
(kg)
0.18 72779 (0108)
0.26 72778 (0111)
0.44 72755 (0,20)
0.54 72754 (0,24)
0.71 72753 (0,32)
1.15 72752 (0,52)
2.29 72758 (1,04)
T-1
13
I_Al
N 1
_ JJiI I-F-- ':
FIGURE 814 FIGURE 818
IRON TEE STRAIGHT COUPLING
Size
Nominal Pipe Figure 814 Figure 818
A B Approx. A B ANSI Inches Inches Inches Weight Part Inches Inches DN (mm) (mm) Lbs. Number (mm) (mm)
(kg)
1/2 1.13 0.56 0.33 86340 1.38 0.31
0N15 (28.7) (14,2) (0,15) (35,1) (79)
3/4 1.31 0.75 0.50 86341 1.63 0.56
0N20 (33,3) (19,0) (0.23) (41,4) (14,0)
1 1.50 0.81 0.85 86230 1.75 0.38
DN25 (38,1) (20,6) (0,38) (44,4) (9,7)
1-1/4 1.75 1.06 1.30 86231 2.00 0.56
DN32 (44,4) (26,9) (0,59) (50,8) (14,0)
1-1/2 1.94 1.19 1.63 86232 2.19 0.75
DN40 (49,3) (30,2) (0,74) (55,6) (19,0)
2 2.25 1.50 2.63 86233 2.63 1.13
DN50 (57,1) (38,1) (1119) (66,8) (28,7)
2-1/2 2.69 1.56 4.55 86234 3.00 0.75
DN65 (68,3) (39,6) (2,06) (76,2) (19,0)
TABLE 4
NOMINAL DIMENSIONS FIGURES 814 & 818
TFPI7I0 Page 6of 10
Page 7 of 10 TFPI7IO
FIGURE 815
REDUCING TEE
Nominal Pipe Size Figure 815
ANSI Inches A B C D E F Approx.
Weight Part DN Inches Inches Inches inches Inches inches
(mm) (mm) (mm) (mm) (mm) (mm) Lbs. Number
(kg)
1-1/2 x 1-1/4 x 1/2 1.44 1.31 1.69 0.69 0.63 1.13 1.03 DN40 x 32 x 15 (36.6) (33.3) (42.9) (17.5) (16.0) (28.1) (0.47)
86257
1-1/2 x 1-1/4 x 3/4 1.50 1.44 1.75 0.75 0.75 1.19 1.10 DN40x32x20 (38.1) (36.6) (44.5) (19.0) (19.0) (30.1) (0.50)
86258
1-1/2x 1-1/4x 1 1.63 1.56 1.81 0.88 0.88 1.13 1.31 DN40 x 32 x 25 (41.4) (39.7) (46.0) (22.4) (22.4) (28.7) (0.59) 86259
1-1/2x1-1/4x2 2.19 2.13 2.00 1.44 1.44 1.25 1.94 0N40 x 32 x 50 (55.6) (54.1) (50.8) (36.6) (36.6) (57.1) (0.88) 86260
14/2 x 1-1/2 x 1/2 1.44 1.44 1.69 0.69 0.69 1.13 1.14 DN40 x 40 x 15 (36.6) (36 (42.9) (17.5) (17.5) 86261.6) (28.7) (0.52)
14/2x14/2x3/4 1.50 1.50 1.75 0.75 0.75 1.19 1.23 DN40 x 40 x 20 (38.1) (38.1) (44.4) (19.0) (19.0) (30.1) (0.56)
86262
1-1/2 x 1-1/2 x 1 1.63 1.63 1.81 0.88 0.88 1.13 1.38 DN40 x 40 x 25 (41.2) (41.2) (46.0) (22.4) (22,4) (28.7) (0.62) 86263
1-1/2x1-1/2x1-1/4 1.81 1.81 1.88 1.06 1.06 1.19 1.50 _______
DN40 x40 x32 (46.0) (46.0) (47.6) (27.0) (27.0) (30.1) (0.68) 86264
1-1/2x1-1/2x2 2.19 2.19 2.00 1.44 1.44 1.25 2.00 DN40 x 40 x 50 (55.5) (55.5) (50.8) (36,6) (36.6) (31.7) (0.91) 86265 2x1 x2 2.25 2.00 2.25 1.50 1.31 1.50 2.18 DNSO x 25 x 50 (57.2) (50.8) (57.2) (38.1) (33.3) (38.1) (0.99)
86266
2 x 1-1/4 x 2 2.25 2.13 2.25 1.50 1.44 1.50 2.31 DN50 x 32 x 50 (57.2) (54.1) (57.2) (38.1) (36.6) (38.1) (1.05) 86267
2x1-1/2x1/2 1.50 1.44 1.88 0.75 0.69 1.31 1.50 DN50 x 40 x 15 (38.1) (36.6) (47.8) (19.0) (17.5) (33.3) (0.68) 86268
2x1-112x3!4 1.63 1.50 1.94 0.88 0.75 1.38 1.61
DN50 x 40 x 20 (41.4) (38.1) (49.3) (22.4) (19.0) (35.0) (0,73) 86269
2 x 1-1/2 xl 1.75 1.63 2.00 1.00 0.88 1.31 1.65 DN50 x40 x 25 (44.5) (41.4) (50.8) (25.4) (22.4) (33.3) (0.75) 86270
2 x 1-1/2 x 1-1/2 2.06 1.94 2,19 1.31 1.19 1.44 2.03 0N50 x 40 x 40 (52.4) (49.2) (55.5) (33.3) (30.2) (36.6)
86272
2x1-1/2x2 2.25 2.19 2.50 1.50 1.44 1.50 2.37 DN50 x 40 x 50 (57.1) (55.5) (63.5) (38,1) (36.6) 138.11 (1.07)
86273
2x2x1/2 1.50 1.50 1.88 0.75 0.75 1.31 1.50
DNSO x 50 x 1 (38.1) (38.1) (47.8) (19.0) (19.0) (33.3) (0.68) 86222
2x2x314 1.63 1.63 1.94 0.88 0.88 1.38 1.67 86223 DN50 x 50 x 20 (41.4) (41,4) (46.3) (22.4) (22.4) (35.0) (0.76)
2x2x1 1.75 1.75 2.00 1.00 1.00 1.31 1.91 DN50 x 50 x 25 (44.5) (44.5) (50.8) (25.4) (25.4) (33.3) (0.86) 86224
2x2x 1-1/4 1.88 1.88 2.13 1.13 1.13 1.44 2,05 DN50 x 50 x 32 (478) (47.8) (54.1) (28.7) (28.7) (36.6) (0.93) 86225
2x2x1-1/2 2.00 2.00 2.19 1.25 1.25 1.50 2.11 DNSO x 50 x 40 (50.8) (50.8) (55.6) (31.8) (31.8) (38.1) (0196) 86226
2x2x2-112 2.63 2.63 2.38 1.75 1.88 1.44 3.67
DN50x 50 x 65 (68.8) (66.8) (60.5) (44.5) (47.8) (36.6) (1.66)
86227
2-1/2 x 2 x 3/4 1.75 1.63 2.31 0.63 0.88 1.75 2.22 DN65x 50x20 (44.5) (41.4) (58,7) (15.9) (22.4) (44.5) 1 (1.01) 1 86274
TABLE 5(2 0F2)
NOMINAL DIMENSIONS FIGURE 815
Page 8 of 10 TFPI7IO
Em:ft~l~
FIGURE 820 FIGURE 830 FIGURE 719
CAP BRASS SEAT UNION PLUG
Nominal Pipe
Size Figure 820 Figure 830 Figure 719
ANSI A Approx. A B Approx. Approx
Inches Inches Weight Part Inches Inches Weight Part Ines Weight Part
ON (mm)
Lbs. Number (mm) (mm) Lbs. Number (mm) Lbs. Number
(kg) (kg) (kg)
112 0.88 0.15 72776 1.86 0.81 0.47 86207 0.94 0.10 86292 DN15 (22,4) (0.06) (478) (20,6) (0,21) (23,9) (0,04)
3/4 1.00. 0.22 72777 2.00 0.94 0.66 86275 1.13 0.18 86293 0N20 (25,4). (0,10) (50,8) (23,9) (0,30) (28,7) (0,08)
1 1.18 0.33 72824 2.19 0.81 1.08 86276 1.25 0.28 86294 DN25 (30,0) (0,15) (55,6) (20,6) (0,49) (31,7) (0,13)
1-1/4 1.31 0.54 72756 2.50 1.06 1.54 86277 1.38 0.50 86295 DN32 (33,3) (0.24) (63,5) (26,9) (0,70) (35,1) (0,23)
1-1/2 1.38 0.68 72822 2.63 1.19 2.03 86278 1.44 0.70 86296 DN40 (35,1) (0,31) (66.8) (30,2) (0,92) (36,6) (0,32)
2 1.50 0.95 72823 3.13 1.63 3.15 86279 .1.50 0.90 86297 DN50 (38,1) (0,43)
_
(79,5) (41,4) (1,43) (38,1) (0,41)
2-1/2 1.75 1.80 72825 - - - - - - - DN65 (44,5) (0,82)
TABLE 6
NOMINAL DIMENSIONS FIGURES 820,830 & 719
TFPI7IO Page 9 of 10
FIGURE 825 FIGURE 827 FIGURE 816
EXTENSION PIECE HEX BUSHING REDUCING COUPUNG
Nominal Pipe Figure 825 Figure 827 Figure 816
Size Extension Piece Hex Bushing Reducing Coupling
A Approx. A Approx. A B ANSI Inches Inches Weight Part Inches Weight Part Inches Inches Weight Part
ON (mm) Lbs. Number (mm) Lbs. Number (mm) (mm) Lbs. Number
(kg) (kg) (kg)
112x112 1.50 0.20 72751 - - - - - - - DN15 x 15 (38.1) (0.09)
1/2 x 1/2 2.00 0.27
72980 - - - - - - - DN15 x 15 (50.8) (0,12)
3/4 x 3/4 1.50 0.22 72981 - - - - - - - DN20 x 20 (38,1) (0110)
3/4 x 3/4 2.00 0.31 73982 0N20 x 20 (50,8) (0,14) - - - - -
3/4 x 1/2 1.75 0.69 0.38 86772 DN20 x 15 - - - - - - (43,2) (17,5) (0,17)
I x1/2 1.06 0.22 72726 1.69 0.50 0.38 86228 DN25 x 15 - - - (26,9) (010) (42,9) (12,7) (0,17)
I x3/4 1.06 0.18 72762 1.75 0.50 0.53 86229 DN25 x 20 - - - (26,9) (0,08) (43,2) (12,7) (0,24)
1-114x1 1.19 0.31 72763 - - - - DN32x25 - - - (30,2) (014)
1-1/2 x 1.25 0.53 72757 - - - - DN40 x 25 - - (31,7) (0,24)
1-1/2x1-1/4 1.25 0.35 72764 - - - - DN40 x 32 - - - (31,7) (0110)
2 xl 1.38 0.75 72759 - - - - DN50 x 25 - - - (35,1) (0,34)
2x1-1/4 1.38 0.69 72761 - - - - DN5O x 32 - - - (35,1) (0,31)
2x1-1/2 1.38 0.62 72775 - - - - DN50 x 40 - - - (35,1) (0.28)
TABLE 7
NOMINAL DIMENSIONS FIGURE 825,827 & 816
01
Housing: Ductile iron conforming to
ASTM A-536, Grade 65-45-12
Protective Coatings:
Clear rust inhibitive coating
Zinc electroplated conforming to
ASTM 8-633, Type Ill Service 2 (optional)
U-Bolt: Carbon steel conforming to
ASTM A-307, Grade A, Zinc electroplated
Nuts: Carbon steel conforming to
ASTM A-307, Grade A, Zinc electroplated
Gasket: (specify when ordering)
Grade "E" EPDM green color code.
(See Data Sheet TFP1895 for aid in selecting
LlstlnglApproval inrormation proper gasket)
General
Description
twee/'Ffre & Building
rnducts
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
www.tyco-fire.com
Grinnell Grooved Fire Protection Products
Figure 40-5
Strap
The Fugure40-5 Strap Is aneconomicalaltemative
to welded pipe outlets on steel pipe.
The Figure 40-5 Strap may be used with full
lengths of pipe and eliminates threading and
welding, decreasing waste and installation time.
The 40-5 Strap maybe used in wet, dry pipe and
deluge systems.
WARNING
The Figure 40-5 Strap described herein must be
installed and maintained in compliance with this
document, as wallas withtheapplicable standards
of the National Fire Protection Association, in
addition tothe standards ofany 01herauthorities
ha vingjurisdiction. Failure to do so may impair
the palformance of this device.
The owner is responsible for maintaining their
fire protection system and devices in proper
operating condition. The installing contractor or
sprinklermanufacturershouldbecontacted with
any questions.
Technical
Data
Figure: 40-5
Outlet: Threaded
Approvals: UL FM, ULC. and VdS;
See Fire Protection Submittal Sheet for exact
Listing/Approval information.
Ordering
Procedure
When placing an order, indicate the full product
name. Please specifythe quantity,figure number,
type of gasket, Grade "E" EPDM, and size.
Grinnell Grooved Piping Products, valves,
accessories and other products are available
throughoutthe U.S., Canada, and intemationally,
through a network of distribution centers. You
may write directly or call 215-362-0700 for the
distributor nearest you.
Care and
Maintenance
The owner is responsible for the inspection,
testing, and maintenance of their tire protection
system and devices in accordance with the
applicablestandards of the National Fire Protection
Association (e.g., NFPA 25), in addition to the
standards of any authority having jurisdiction.
The installing contractoror product manufacturer
should be contacted relative to any questions.
Any impairment must be Immediately corrected.
It is recommended that automatic sprinkler
systems be Inspected, tested, and maintained by
a qualified inspection Service.
Limited
Warranty
Products manufactured by Tyco Fire Products are
warranted solely to the original Buyer for ten (10)
years against defects in material and workmanship
when paid brand property installed and maintained
under normal use and service. This warranty will
expireten (10) years from date of shipment by Tyco
Fire Products. No warranty is given for products or
components manufactured by companies not
affiliated byownershipwfthTyco Fire Products orfor
products and componentswhlch have been subject
to misuse, improperinstallation.corrosion, orwhich
have not been installed, maintained, modified or
repaired in acconlancewith applicable Standards of
the National Fire Protection Association (NFPA),
and/or the standards of any otherAuthoritiesHaving
Jurisdiction. Materials found byTyco Fire Products
tobedefectiveshallbeeltherrepairedorreplaced,at
Tyco Fire Products' sole option. Tyco Fire Products
neither assumes, nor authorizes any person to
assumeforit,anyotherobligationinconnectionwith
the sale of products or parts of products. Tyco Fire
Productsshaflnotberesponsib!eforsprinklersystem
deslgnerrorsorinaocurateorincompleteinformation
supplied by Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE PRODUCTS BE
LIABLE, IN CONTRACT, TORT, STRICT LIABILITY
OR UNDER ANY OTHER LEGAL THEORY, FOR
INCIDENTAL INDIRECT, SPECIAL OR
CONSEQUENTIALDAMAGES,INCLUDINGBUTNOT
LIMITED TO LABOR CHARGES, REGARDLESS OF
WHETHERIYCOFIREPROOLJCTSWASINFORMED
ABOUT THE POSSIBILITY OF SUCH DAMAGES,
AND INNO EVEIff SHALLTYCO FIRE PRODUCTS'
LIABILITY EXCEED AN AMOUNT EQUAL TO THE
SALES PRICE.
11NI WAFa%4NIYNIMAfELVLIWOF
ANYAND ALL O1ND WAND4N7NDEOR
IMPLIED, INCLUDING WARRANTIES OF
MERCILINTARIIJTY AND FITh'ESS FOR A
Page 1 of 2 September 2004 TFPI 720
Pipe Nominal Dimensions Hole Net
Size Size WI. A B C D
Run x Inches Inches Inches Inches Inches Lbs.
Branch mm mm mm mm mm Kg.
11/4° X 1/211 2.00 1.50 3.50 1.20 1/io 0.84
50.8 38.1 88.9 30.5 1 30.2 0.4
11/4° 2.00 1.50 3.50 1.20 1/ie 0.88
50.8 38.1 88.9 30.5 30.2 0.4
1V4" X 1 2.31 1.68 3.50 1.20 13'is 1.13
58.7 42.7 88.9 30.5 30.2 0.5
1V2' X V2° 2.12 1.62 3.50 1.32 13/is 0.84
53.8 41.1 88.9 33.5 30.2 0.4
lh/2U x 3/4 2.12 1.62 3.50 1.32 1/I6 0.88
53.8 41.1 88.9 33.5 30.2 0.4
11/2° X ., 2.43 1.80 3.50 1.32 13M 1.13
61.7 45.7 88.9 33.5 30.2 0.5
21 X 'Ie° 2.36 1.86 3.74 1.55 13AG 0.88
.59.9 47.2 95.0 39.4 30.2 0.4
20 x 3/lI 2.38 1.86 3.74 1.55 1/16 0.95
59.9 47.2 95.0 39.4 30.2 0.4
2x i° 2.67 2.04 3.74 1.55 Wis 1.16
67.8 51.8 95.0 39.4 30.2 0.5
2/2° X 1/2U 2.61 2.11 4.25 1.80 1/I6 0.90
66.3 53.6 108.01 45.7 30.2 1 0.4
211? X3/4° 2.61 2.11 4.25 1.80 lYie 0.99
66.3 53.6 108.0 45.7 30.2 0.4
21/2° x 10 2.92 2.29 4.25 1.80 Wis 1.21
74.2 58.2 108.0 45.7 30.2 0.5
Item Description
1 Housing
2 Gasket
3 Flanged Nut
4 U-Bolt
Fitting
Size
Equivalent Length
(1 inch pipe)
1'/4°X 1° 8
11/2°X 1 6
2°xl° 6
21/2U x 11 4
The friction loss for these outlets is specified In
equivalent length of 1 inch Schedule 40 (C=120) pipe.
Page 2 of 2 TFP172O
Figure 40.5 Strap
The 1 inch outlets can be used with a nipple leading Note: Outlet threads conforming to ISO 7-1 are available, contact
directly to a sprinkler. These fittings should be used Tyco Fire Products.
for hydraulically calculated systems only.
12
General Notes: it Is the DesIgners responsibility to select products suitable for the intended service and to ensure IS that pressure ratings and performance data is not exceeded. Always read and understand the installation 9001 instructions (IH-1000). Never remove any piping component or corrector modify any piping deficiencies without
first depressurizing and draining the system. Material and gasket selection should be verified lobe compatible
for the specific application. . Certified Company
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19946 Printed U.S.A.
Bulletin 013 Rev. L
Re - ® Models Fl Series
Standard Response iable
Standard Spray
Model F156 Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
Model F156 Recessed Sprinkler Types
Pendent/F1/F2/FP
Horizontal Sidewall
Model F142, F1XLH & F128 Sprinkler Types
Standard Upright
Standard Pendent
Model F142, F1XLH & F128 Recessed Sprinkler
Types
Pendent/Fl/F2/FP
Approval Organizations
Underwriters Laboratories Inc. and certified for
Canada (cULus)
Factory Mutual Approvals (FM)
Loss Prevention Council (LPCB, UK)
VdS Schadenverhutung GmbH
EC Certificate: 0786-CPD-40237 (RA1314)
0786-C PD-40253 (RA 1 325)
0786-CPD-40254 (RA1 375)
UL Listing Category
Sprinklers, Automatic & Open (VNIV)
Product Description
The F156, F142, F1XLH & F128 Series Glass Bulb
Sprinkler combines the durability of a standard sprinkler
with the attractive low profile of a decorative sprinkler.
Whether installed on exposed piping or in an office ceil-
ing, it is functional and attractive.
Beautifully versatile is the description for the Reliable
Models F156, F142, F1XLH & F128 Series Recessed
glass bulb sprinkler. Recessing the F156, F142, F1XLH &
F128 Series enhances its already low profile decorative
appearance, and facilitates a rapid and perfect installa-
tion.
The recessed escutcheon of the Models F156, F142,
F1XLH & F128 are highly adjustable. The two piece con-
struction makes field installation a very easy and rapid
task. This also allows ceiling panels to later be removed
without shutting down the fire protection system, thus fa-
cilitating maintenance of above ceiling services.
YjU
Upright Pendent Conventional
Vertical Sidewall Horizontal Sidewall Recessed
PendentiF1lF2
Recessed Recessed XLH Upright
Horizontal Sidewall PendentlFP
XLH Pendent XLH Recessed
Pendent F1/172 Pendent FP
The F156, F142, F1XLH & F128 Series Automatic Sprin-
kler utilizes a 5.0 mm frangible glass bulb. The glass bulb
consists of an accurately controlled amount of special
fluid hermetically sealed inside a precisely manufactured
glass capsule. This glass bulb is specially constructed to
provide fast thermal response.
At normal temperatures, the glass bulb contains the
fluid in both the liquid phase and in the vapor phase. The
vapor phase can be seen as a small bubble. As heat is
applied, the liquid expands forcing the bubble smaller
and smaller as the liquid pressure increases. Continued
heating forces the liquid to push out against the bulb,
causing the glass to shatter, opening the waterway and
allowing the deflector to distribute the discharging water.
The F156, F142, F1XLH & F128 Series Sprinkler tem-
perature rating is identified by the color of the glass bulb
capsule as well as frame color where applicable.
Reliable Automatic Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Pin tie
(XLH Only)
Deflector
Load Screw
Washer
Bulb
Frame
Cup
0 13FG04
Model F142, F1XLH Upright
Technical data:
Models Discharge Coefficient Response Thread Max.
Working
Mm.
Working Temperature Finish Size Pressure Pressure Rating
F156 K5.6
1/2" NPT See See F142
1XLH 4.2 Standard (R1/2) 175 PSI 7 PSI "Temperature "Finish Table" Ratings" Table
L
F K
F128 K2.8
Material Data:
Frame Deflector Load Screw Pintle Cup Washer Bulb
DZR Brass
CDA Alloy 260,
CDA Alloy 220 CDA Alloy 360 CDA Alloy 360 CDA Alloy 651 Nickel Alloy 440 or Alloy 360
QM Brass or or or or coated with PTFE Adhesive Glass
CDA Alloy 510 CDA Alloy 544 CDA Alloy 544 CDA Alloy 693 Tape
Model F156, Upright, Pendent & Conventional Sprinklers
Model F142, F1XLH & F128 Upright & Pendent Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread
Size
1 Nominal K Factor
_____________
Sprinkler
Height
Approval
Organization
Sprinkler Identification Number
(SIN)
US I Metric Uriht I Pendent
Standard-UprIght (SSU) and ,endent Deflectors Marked to Indicate Position
1/2" (15mm) " 1/2" NPT (R1/2) 5.6 I 80 2.25" (57mm) 1.2.3.4.5 RA1325(2X3)(5X°) I RA1314 25
7/16" (10mm) 1/2" NPT (R1/2) 4.2 I 60 2.25" (57mm) 1 RA1323(2X6) I RA1313
3/8 (10mm)— 1/2" NPT (R1/2) 2.8 I 40 2.25" (57mm) 1 RA132106) I RA1311
Conventional-Install in Upright or Pendent Position
15mm (1) I 1/2" NPT (R1/2) I 5.6 I 80 I 57mm I 3. 4. 5 I RA13755
Refer to Bulletin 024 for Special Response Sprinklers (Fl S5-56)
cULus Listed corrosion resistant (Polyester coated) sprinkler.
Polyester coated FM Approved sprinkler.
(4)_____
(5) Polyester coated LPCB & VdS approved sprinkler RA1325, RA1314 & RA1375.
Electroless Nickel PTFE (Teflon)* Plated - UL listed Corrosion Resistant
Upright Pendent Conventional
Model F156, F142, F1XLH & F128 Recessed Pendent Sprinklers'
Installation Wrench: Model GFR2 Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread
Size
K Factor Sprinkler
Height
Sprinkler Identification Number
(SIN) US Metric
1/2" (15mm) 1/2" NPT (R1/2) 5.6 80 2.25" (57mm) RA13142
7/16" (10mm) 1/2" NPT (131/2) 4.2 60 2.25" (57mm) RA1313'2
3/8" (10mm) 1/2" NPT (R1/2) 2.8 40 2.25" (57mm) RA13112
Refer to escutcheon data table for approvals & dimensions
Electroless Nickel PTFE (Teflon)* Plated - cULus listed Corrosion Resistant
1 1102 Hi — (57.1w.,)
r1,
flAHLHiLA 1010 ff SPIMMIEV 'I F & RYflW
I ID rAOL Of COLM HI,IDHy F, ,jmn
- -
1L AT RE= -
ff
Il. AT H10HM OLS -
IWcUdlV - I flDflI 1i2712.1I,,,,) I
_________ _______
Ar IlUIdIDI 10 • 7/81222,1,,) Ar IHH4l8S AEU - laT.lJr.,,) 10 mEHI
AT FSUIHAI REOL - I-I/a 21414,,,, AT 1010W -
RECESSED PENDENT win OR F2 ESCUTCHEON 'S'HWIIHI LOT Ill AH14D VW F1 ISMINCHM
Model F156, F142, F1XLH & F128 Fl or F2
*DuPont Registered Trademark
,•x I/2R60UC671
2 AAW HA. (627am) HOLE 10 CEIlING
2 5/I6 DLI. (5147—) Cup
FACE OF F7ThL'C ID lICE OF CEIlING OWWRON IT W.XWAUU RECESS - I-I/a7J&14aJ
2 URAMUM RLS - 1125.4w,,)
A r W1MIUII RECESS - P/I87I4J..,,j I AT MIMMUM RECESS - 1125.4w,,)
F7- _
RECESSED PENDENT W/FP ESCUTCHEON o,
SPRINIELER NOT FM AOUED 4DM FP 13CUTCHM
Model F156, F142, F1XLH & F128 FP
3.
Vertical Sidewall
Model F156 Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
U.S. Patent No. 6,374,920
Sprinkler Type Deflector to Ceiling Distance
(Mm. - Max.)
Upright 4" (102mm) - 12" (305mm)
Pendent 4" (102mm) - 12" (305mm)
Installation Data:
Nominal
Orifice I Thread Size
I Nominal K Factor Sprinkler
Height
Approval
Organizations
I Sprinkler I
Identification I
I I
i I US
I
I Metric i Numbers (SIN)
½" (15mm) ½" NPT (R1/2) 5.6 8.0 2.25" (57mm) 1, 2, 3 RA1385(1X2)(3)(4)
"LPC Approval is pendent only, 57°C through 141°C ratings.
(2)cULus Listed corrosion resistant (Polyester coated) sprinkler.
(3)cULus Listed & FM Approved corrosion resistant for lead, wax and wax over lead.
'4TElectroless Nickel PTFE (Teflone)* Plated - cULus listed Corrosion Resistant
Model F156 Horizontal Sidewall Sprinkler
Deflector: HSW
Installation Wrench: Model D Sprinkler Wrench
FACE OF FITTING To FACE OF CEIUNG DIMENSION
Fl ESCtflCHEGAA
AT MAXIMUM RECESS 1725.4mm)
AT MINIMUM RECESS 3/879.5mm]
F2 ESCUTCHEON
AT MAXIMUM RECESS - 3/4719mm]
AT MINIMUM RECESS - 3/879.5mm]
r2 114" HOLE ON.
(5 7.2mm]
X 1/2 REDUCER -
2 27/32 DIA
(72.2mm)
I ()
4-12
(101.6mm-304.8mm] CETUNG TO
DEFLECTOR
TURN COLLAR UNTiL -'
TIGHT AGAINST SPRINKLER I Fl ESCUTCHEON WRENCH BOSS.
.7/4719mm) ADJUSTMENT
1/2712.7mm) ADJUSTMENT
Fl ESCUTCHEON
AT MAXIMUM RECESS - 1-3/8734.9mm)
AT MINIMUM RECESS - 2-1/16752.4mm)
F2 ESCUTCHEON
AT MAXIMUM RECESS - 1-5/8741.3mm)
AT MINIMUM RECESS 2-1/16752.4mm1
RECESSED HSW W/FI OR F2 ESCUTCHEON
(I) FM APPROVED FOR 4 - 6 (101.6MM - 152.4MM) CEILING TO DEFLECTOR.
Horizontal Sidewall Note: For Recessed HSW Sprinklers use installation wrench GFR2.
FM and cULus permits use with Fl or F2 escutcheons for
Installation Data:Horizontal Sidewall
"Light Hazard" only.
Nominal K Factor
__________________
Sprinkler
Height Approval Organizations Sprinkler
Nominal Orifice Thread Size Identification
US I Metric Light Hazard I Ordinary Numbers (SIN) Hazard
½" (15mm) ½" NPT (R1/2) 5.6 80 2.63" (67mm) 1,2 1 RA1335(1X2)(3X4)
11cULus Listed corrosion resistant (Polyester coated) sprinkler.
cULus Listed & FM Approved corrosion resistant for lead, wax and wax over lead.
Polyester coated FM approved sprinkler.
Electroless Nickel PTFE (TeflonB)* Plated - cULus listed Corrosion Resistant
*DuPont Registered Trademark
4.
Application
Model F156, F142, F1XLH, F128 & Model F156, F142, F1XLH &
F128 Recessed sprinklers are used in fixed fire protection systems:
Wet, Dry Deluge or Preaction. Care must exercised that the orifice
size, temperature rating, deflector style and spnnkJer type are in ac-
cordance with the latest published standards of the National Are
Protection Association or the approving Authority Having Jurisdic-
tion Installation.
Installaftri
Model F156, F142, F1XLH & F128 Series sprinklers are standard
response sprinklers intended for installation as specified in NFPA
13. They must also be installed with the Model D Sprinkler Wrench
specifically designed by Reliable for use with these sprinklers.
The Model F156, F142, F1XLH & F128 Recessed Sprinklers
are to be installed with a maximum recess of 3A inch (19mm). The
Model Fl, F2, and FP Escutcheon illustrated are the only recessed
escutcheon to be used with the Model F156, F142, F1XLH & F128
Recessed Sprinklers. The use of any other recessed escutcheon
will void all approvals and negate all warranties. When installing
Model F156, F142, F1XLH & F128 Recessed Sprinklers use the
Model GFR2 Sprinkler Wrench. Any other type of wrench may
damage these sprinklers.
Note: A leak tight 1/2" NFl (R112) sprinkler joint can be obtained with
a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not tighten sprinklers
over maximum recommended torque. It may cause leakage or
impairment of the sprinklers.
Glass bulb sprinklers have orange covers to protect the bulb dur-
ing the installation process. REMOVE THIS PROTECTION ONLY
AFTER THE SYSTEM HAS BEEN HYDROSTATICALLY TESTED
AND, WHEN APPLICABLE, THE ESCUTCHEONS HAVE BEEN
INSTALLED. RASCO wrenches are designed to install sprinklers
when covers are in place.
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
Orifice Size
Deflector Type
Temperature Rating:
- Specify when ordering
- Model F156 Pendent Sprinkler
Sprinkler Finish
Escutcheon Finish (where applicable)
Note: When Models F156, F142, F1XLH & F128 Recessed Sprinklers
are ordered, the sprinklers and escutcheons are packaged separately.
Escutcheon Data (1)
(') SIN: RA1335 - cULus and FM permits use with Fl or F2 escutcheons for light
hazard only.
Maintenance
The Model F156, F142, F1XLH & Model F156, F142, F1X-
LH & F128 Recessed Sprinklers should be inspected and
the sprinkler system maintained in accordance with NFPA
25. Do not clean sprinklers with soap and water, ammonia
or any other cleaning fluid. Remove any sprinkler which has
been painted (other than factory applied) or damaged in
any way. A stock of spare sprinklers should be maintained
to allow quick replacement of damaged or operated sprin-
klers. Prior to installation, sprinklers should be maintained
in the original cartons and packaging until used to minimize
the potential for damage to sprinklers that would cause im-
proper operation or non-operation.
Temperature Ratings
Classification
Sprinkler
Temperature Max. Ambient
Temp.
Bulb
Color
Ordinary 57 135 100°F (38°C) Orange
Ordinary 68 155 100°F (38°C) Red
Intermediate 79 175 150°F (66°C) Yellow
Intermediate 93 200 150°F (66°C) Green
High" 141 286 225°F (107°C) Blue
Extra High' 182 360 300°F (149°C) Mauve
Ultra Hi-gh (1)(2) 1 260 1 500 1 475°F (246°C) I Black
Not available for recessed Sprinklers.
(2) cULus listed for SIN RA1325 and RA1314 only.
Maximum Working Pressure
175 psi (12 bar)
100% Factory tested hydrostatically to 500 psi (34.5 bar)
Finish(')
Standard Finishes
Sprinkler Escutcheon
Bronze Brass
Chrome Chrome
Polyester Coated (6X7)(9) White Painted Special Application Finishes
Sprinkler Escutcheon
Electroless Nickel PTFE(refion°)°) Electroless Nickel PTFE (Teflon®)*
Bright Brass(2) Bright Brass
Black Plated Black Plated
Black Paint(3X9) Black Paint
Off White (3X9) Off White
Chrome Dull Chrome Dull
Lead Plated(3X4)(8)
Wax Coated(3X4)(5X8)
Wax Over Lead(3X4X5X8)
Other colors and finishes are available on special order. Consult factory for
details. Custom color painted sprinklers may not retain their UL Corrosion
resistance listing.
200°F (93°C) maximum.
UL and ULC listed only.
(4) 155°F to 200°F (68°C to 93°C) ratings only.
5 286°F(141°C) sprinklers may be coated for ambient conditions not exceeding
150°F (66°C).
cULus listed "corrosion resistant" applies to SIN Number RA1325 (Upright)
RA1323 (upright), RA1321(Uphght), RA1335 (HSW), RA1385(VSYv and
RA1314 (Pendent) in standard black or white. Corrosion resistance in other
polyester colors is available upon request.
FM Approved finish as "Polyester Coated" applies to SIN number RA1314,
RA1335 & RA1325 in standard black or white.
FM Approved finish applies only to SIN number RA1335 & RA1385.
LPCB and VdS Approved finish applies only to RA1325, RA1314 and RA1375.
'°cULus listed Corrosion Resistant applies to SIN RA1325 ,RA1314 ,RA1323,
RA1313 ,RA1321, RA1311, RA1385 and RA1335
*DuPont Registered Trademark
5.
Reliable...For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
Automatic sprinklers
Flush automatic sprinklers
Recessed automatic sprinklers
Concealed automatic sprinklers
Adjustable automatic sprinklers
Dry automatic sprinklers
Intermediate level sprinklers
Open sprinklers
Spray nozzles
Alarm valves
Retarding chambers
Dry pipe valves
Accelerators for dry pipe valves
Mechanical sprinkler alarms
Electrical sprinkler alarm switches
Water flow detectors
Deluge valves
Detector check valves
Check valves
Electrical system
Sprinkler emergency cabinets
Sprinkler wrenches
Sprinkler escutcheons and guards
Inspectors test connections
'Sight drains
Ball drips and drum drips
Control valve seals
Air maintenance devices
Air compressors
Pressure gauges
Identification signs
Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
Reliable Automatic Sprinkler Co., Inc. Recycled
1%1MJ13bJ (800) 431-1588 Sales Offices w Paper
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices Revision lines indicate updated or new data.
www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 04/15 PIN 9999970299
Model G5-80, Model G5-56,
Model G542, Model G5-28
Quick Response Concealed
Automatic Sprinkler
Bulletin 034 Rev. D
11abile
UL Quick Response
FM Standard Response
Concealed Sprinkler With a
3/4 (19mm) Adjustment
Features
Cover plate attachment (Plain or Perforated) with
3A" (19mm) assembly adjustment.
Smooth aesthetic ceiling profile.
Factory installed protective cap.
Available in Chrome and White as Standard Finish-
es. Special Application Finishes are also available.
Ordinary and Intermediate temperature rating.
For additional Sprinklers refer to Bulletin 154 for
Technical Specification and Approvals
Approvals & Listings
1. Underwriters Laboratories Inc. and cULus -
Quick Response
G5-80, G5-56 - Light Hazard and Ordinary
Hazard Occupancies
G5-42 - Light Hazard Occupancies
G5-28 - Light Hazard Occupancies
2. Factory Mutual Research Corp. (FM) -
Standard Response (See Page 3)
G5-56 & G5-28 only.
See the most recent FM Global Property
Loss Prevention Data Sheets for installation
and use guidelines.
3. Loss Prevention Council (LPCB, UK) -
Standard Response
G5-56 - Light Hazard and Ordinary Hazard
Occupancies
vds SchadenverhUtung GmbH -
Standard Response
EC-Certificate of Conformity 0832-CPD-2062
U.S. Patent number 6,554,077.
Application
The Reliable Model G5-80, G5-56, G5-42 and G5-28 are
the most versatile quick response concealed sprinklers avail-
able. it provides the best form of fire protection while offering
an attractive appearance and 3/4" (19mm) of cover adjust-
ment for ease of installation. The small diameter cover plate
assembly is easily attached and blends into the ceiling, con-
cealing the most dependable fire protection available, an au-
tomatic sprinkler system.
Plain Cover Plate
Perforated Cover Plate
The Model G5-80, G5-56, G5-42 and G5-28 are designed
for use where aesthetic appearance is important. Offices, hos-
pitals, motels and restaurants are but a few of the applications
where it can be used.
The Model G5-80, G5-56, G5-42 and G5-28 are UL Listed
Quick Response Concealed sprinklers intended for use in
accordance with NFPA 13. FM Approves the G5-56 and the
G5-28 sprinkler as a standard response concealed sprinkler
intended for use in accordance with FM Loss Prevention Data
Sheet 2.0.
Product Description
The Reliable Model G5-80, G5-56, G5-42 and G5-28 uses
a proven quick response fusible element in a standard style
sprinkler frame with a drop-down deflector. This assembly is
recessed into the ceiling and concealed by a flat cover plate
assembly. The threaded engagement provides 34" (19mm) of
cover adjustment. The flat cover plate is attached to the skirt
using either 135°F (57°C) or 165°F (74°C) ordinary tempera-
ture classification solder.
When the ceiling temperature rises, the solder holding the
flat cover plate melts, the flat cover plate released thus expos-
ing the sprinkler inside to the rising ambient temperature.
The subsequent fusing of the element opens the waterway
and causes the deflector to distribute the water. Any secure
engagement between the cover plate and cup will assure that
the drop-down deflector is properly located below the ceiling.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Installation
Do not install the G5-80, G5-56, G5-42 and 135-28 in ceilings
which have positive pressure in the space above.
Cut a 2" inch (67mm) diameter hole is cut in the ceiling, the
sprinkler is easily installed with the Model FC Wrench. The
wrench has a socket drwe which is inserted into the body of
the sprinkler. When installing a sprinkler the wrench is first
positioned into the sprinkler/cup assembly until the wrench
socket engages the body of the sprinkler. The sprinkler is
then tightened into the pipe fitting. When inserting or remov-
ing the wrench from the sprinkler/cup assembly, care should
be taken to prevent damage to the sprinkler. DO NOT
WRENCH ON ANY OTHER PART OF THE SPRINKLER!
CUP ASSEMBLY. Install the cover plate by hand turning the
cover in the clockwise direction until it is tight against the ceil-
ing.
A protective cap is provided to protect the drop-down sprinkler
deflector from damage which could occur during construction
before the cover plate is installed. The cap is factory installed
inside the sprinkler cup. Remove cap to install sprinkler, then re-
install cap until the cover plate is installed.
Maintenance
The Model 135-80, G5-56, G5-42 and G5-28 should be in-
spected and the sprinkler system maintained in accordance
with NFPA 25. Do not clean sprinklers with soap and water, am-
monia or any other cleaning fluids. Remove any sprinkler that
has been painted (other than factory applied) or damaged in
any way. Concealed sprinklers cover plates can not be painted
in the field, after installation or have any other coating applied
other than the factory finish. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or oper-
ated sprinklers. Prior to installation, sprinklers should be main-
tained in the original cartons, and packaging to minimize the
potential for damage to sprinklers that would cause improper
operation or non-operation.
Ordering Information
Sprinkler Model
Nominal Orifice
Flat Cover Plate
Plain or Perforated
Flat Cover Plate
Assembly Finish
Inlet Type
Cover Plate Finishes(l)
Standard Finishes
Chrome
White Paint
Special Application
Finishes(2)
Bright Brass
Finished Bronze
Black Plating
Black Paint
Off White
Satin Chrome
" Other finishes and colors are
available on special order.
Consult factory for details.
Coverplate custom paint is
semi-gloss, unless specified
otherwise.
(2) For the perforated style cover-
plate, consult factory for avail-
ability on these and other cus-
tom finishes.
Maximum Working Pressure
175 psi (12 bar)
100% Factory tested Hydrostatically to 500 psi (34.5 bar)
Temperature Rating
Classification I Sprinkler I I Cover Max. Ambient I
I I Temp.
Ordinary 1650F/740C I 1350F1570C I 100°F/380C I
Intermediate I 212017/1000C 1650F/740C 1500F/660C
U
I adi
iaOVg.
Model FC SDrinkler
UL Listing Category
Sprinklers, Automatic and
Open
Quick Response Sprinkler
UL Guide Number
VNIV
2.
Technical Data
Sprinkler
Model Sprinkler Inlet Total
Adjustment
Nominal
Orifice
Nominal
K Factor Thread
Metric
A Approvals Sprinkler
Identification (SIN) US
G5-80 Non Adjustable 3/4" (19mm) 17% (15mm) 8.0 115 34" NPT (R3%) 1 RA3412
G5-56 Non Adjustable 3/4" (19mm) i/a" (15mm) 5.6 80 ½' NPT (RIM 1,2,3,4.5 RA3415
G5-42 Non Adjustable 3/4" (19mm) /io" (10mm) 4.2 60 ½' NPT (R½) 1 RA3413
G5-28 Non Adjustable 34" (19mm) 3%' (10mm) 2.8 1 40 ½" NPT (R'/2) 1,2 RA3411
For VdS Approval, temperature rating sprinkler 1650F/740c and cover plate 1350171570C only!
x 7/2" REDUCING 1" TEE OR ELBOW TEE OR ELBOW x 3/4" REDUCING G5-80 ONLY
II'
(66.55mm)
4" (58.42mm) 014 - HOLE IN CEILING
CUP
I I I I I
(19.05mm) MAX.
COVER ADJUSTMENT
___ FACE OF FITTING TO FACE OF CEILING
1/4 MIN
DIMENSION
TO CEILING ________ .
2-7/4" (57 75mm) MAX.
(6.35
I
_/
1" (25.4mm) MAX. DROPPED DEFLECTOR ____________ ________
_________ _____ k
FL4r COVER PLATE .,./ _/ (84.2 7mmJDIA .4 '
'
(4.96mm)
—CEILING ASSEMBLY
SPRINKLER
O34FG9iO COVER PLATE. 3/4"[19.05mm]ADJUSTMENT
oiice
FOR USE AS A REPLACEMENT OF MODEL G4A SPRINKLERS
I" x 7/2" REDUCING TEE OR ELBOW
11I]L:-_rTTJ
RELIABLE P/N 6999997900 Ii
X " BRASS NIPPLE EXT.
4" (58.42mm) 014
CUP
" (19.05mm) MAX.
COVER ADJUSTMENT
ii .
7/4' (6.35mm) Al/N. TO CEILING
7" (25.4mm) MAX.
DROPPED DEFLECTOR
10 CEIUNG
- 2k" (66.55mm)
HOLE IN CEILING
3-1/76" (77.72mm) MAX.
FACE OF F7T11NC 10 FACE OF CEILING DIMENSION
2-7/4"(57.15mm) MAX.
FACE OF NIPPLE EX1 70 FACE OF CEILING DIMENSION
/7
FLAT COVER PLATE 4' (84.27mm) 01k
,' (4.96mm)
SPRINKLER
Offum COVER PLATE. 3/4"[19.05mm]ADJUSTMENT
Testing has shown that use of a "nipple extension" will not affect the listing of the sprinkler.
For RETROFIT installations, per NFPA 13(2010) section 8.15.19.4, which allows the use of nipples as the same pipe
thread size as the existing outlet when revamping existing systems".
Do not exceed 8-18 ft-lbs of torque during installation.
3.
Reliable...For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
Automatic sprinklers
Flush automatic sprinklers
Recessed automatic sprinklers
Concealed automatic sprinklers
Adjustable automatic sprinklers
Dry automatic sprinklers
Intermediate level sprinklers
Open sprinklers
Spray nozzles
Alarm valves
Retarding chambers
Dry pipe valves
Accelerators for dry pipe valves
Mechanical sprinkler alarms
Electrical sprinkler alarm switches
Water flow detectors
Deluge valves
Detector check valves
Check valves
Electrical system
Sprinkler emergency cabinets
Sprinkler wrenches
Sprinkler escutcheons and guards
Inspectors test connections
Sight drains
Ball drips and drum drips
Control valve seals
Air maintenance devices
Air compressors
Pressure gauges
Identification signs
Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
Reliable Automatic Sprinkler Co., Inc. Recycled
(800) 431-1588 Sales Offices ' Paper Reliabil (800) 848-6051 Sales Fax Revision lines indicate updated or new data. (914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 11/14 P/N 9999970421
IMPERIAL MAX REC.
LOAD LBS.
METRIC'
PIPE PiPe ROD
1/2
IS
400 10
314 318
!3W8
400 20 To-
400 25 10
11/4 afa 400
-_32 - _!!L
11/2 318 400 40 10
2 318 400 50 10
21/2 318 600 65 io
600 80 10
3112 318 600 10
3/8 1000 100 in
5 112 1250 125 12
6 112 1250 150 12
8 lj2 1250 2W 12
Order Part #300m
Note: 1/2° Ring Hanger not <FM> approved
8
300
RING HANGER
zS A)US I thru 4 Inch pipe 112 and 314 inch pipe
5 thru 8 Inch pipe
SIZE - 1/2 thru 8 inch pipe.
MATERIAL - Carbon Steel, Mu. Galvanized to G-90 specification.
FINISH - Mil. Galvanized and Stainless Steel.
LISTING - UL in US and CANADA.
APPROVAL - Factory Mutual Research.
CONFORMS WITH: Federal Specification WW-H-171(Type 10),
Manufacturers Standardization Society ANSI/MSS-SP-58 (Type 10); install
in accordance with ANSI/MSS- SP-69.
MAXIMUM TEMPERATURE - 650°F.
FUNCTION - For fire sprinkler and general piping purposes.
Swivel nut permits hanger adjustment after installation.
FEATURES -
1 thru 4 inch:
* Offset edge for EASY pipe insertion.
1 thru8 inch:
* Full length knurl on swivel nut for better grip.
UNIQUE FEATURES
1 thru3 inch:
* UL listed to accept AFCON#3 10 Surge Restrainer.
Swivel nut
Retained in ring to keep the assembly intact prior to installation.
Removed easily if needed.
* UL listed for use on CPVC pipe.
ORDERING - Part # and pipe size.
Index
02/01
655
ALL THREADED ROD CUT TO LENGTH
ROD
SIZE
MAX. REC.
FOR SERVICE
LOAD LBS.
TEMP.
650°F 750°F
3/8 610 540
1/2 1130 1010
5/8 1810 1610
3/4 2710 2420
7/8 3770 3360
NOTE; maximum Temperature: 750°F
SIZE - 3/8 thru 7/8 inch rod in linch
increments.
MATERIAL - Carbon Steel.
FINISH - Plain, Electro-Galvanized and
Stainless Steel.
ORDERING - Part #, rod diameter, rod
length and finish.
2/00 8
reft.4 Nut Driwr (kern #100)
Weight Model Shk Lgth Shk Tha Box Qty (per 100) Case Qty
20 GST.750 3/4 1/4 100 4.75 1000
21 GST 100 1 1/4 100 5.00 1000
22 GST 200 1 2 1/4 100 6.50 1000
23 GST 300 1 3 1/4 100 7.50 1000
24 GST 600 1 6 1/4 50 9.00 500
WOOD - Sammys
i
#14
(item#100.bladc)
Sammys 114", 318" rod
Minimum 2" imbedment into base For vertical use. material for NFPA13compliance Install in canter ofiowerface.
Notieasthan
2" nominal width
(1112")
oist I Truss
jas manufacturer for
ed Installation point.
Fig may be required
us ff27 and #O6
Tools available on page 9.
q Wood Joist
Use #14 Nut Drner (Item #100)
Appromis
_______
Item # Model
_________
Shk 14th Shk Din
______
FM Test
Load, lb.
ULlest
Load lb.
UIJFM
Pipe Size
Actual Pullout Box Qty
10 GST.75 3/4 1/4 564#-6 Ply 100
NFPA 11 GST 10 1 1/4 7/16 OSR 210# -
670ff - 3/4" Ply 100
UL.FM.NFPA 12 GST 20 2 1/4 9404 850ff 3/4-21/2 1760ff - Fir 100
UL'NtI'A * 27 GST25-380 21/2 3/8 1500ff 4 2113ff-Fir 50
UL•FM'NFPA 13 GST30 3 1/4 1475ff 1500ff 3/4-4 2060ff- Fir 100
NEPA 403 GST40 4 1/4 2180ff- Fir 50
NPPA 14 GST60 6 1/4 2230ff-Fir 50
HETITIMM
r5e#14SW
Model Shk Lgth Shk Dia
Nut Driwr (Item #101)
Weight Actual Pullout Box Qty (per 1O) Case Qty
S GST2 2 1/4 1760ff-Fir 50 7.00 500
* 06 GST 2.5-380 2 1/2 3/8 2113# - Fir 50 10.00 500
15 CST3 3 1/4 2275ff-Fir 50 10.50 500
16 GST4 4 1/4 2180ff-Fir 50 10.60 500
17 GST6 6 1/4 2230ff-Fir 50 10.95 500
i
#I4SW
(Item #1O1.red)
Sldcwinders&
Sammys 112" rod
--..-
-
- -- -
-
-iF-.
Wood Flooring
Double Sheetrock Ceiling
Page 4 Note: Screw must be installed with appropriate nut driwar to comply with warranty
#14
(Item#IOO.Ci&*)
Sammys 114", 318" red
A Prestressed Concrete
(:D Page 5
WOOD —Sidewinders
I Use #I4SW Nut I)riwr (Item #101)
Ite Model Shk Lgth1 Shk Dia Actual
Shear/Pullout Box Case QtyI
I Weight
I (per 100) I I I 4016 ISWG100I 1 1/4 I 100 I 7.50 I 1000 I
I 300 ISWG200I 2 114 17254-Fir 100 8.00 1000
WSII11.1RIIm1umkL.Jllms1rnm1.
Use#14SW Nut Driwr (Item #101)
Approals Item #
___________________ I Model Shk Lgth Shk Dia UL Test
Load lb.
IJIJFM
Pipe Size
Actual
Shear/Pullout Box Qty Weight
(per 100)
18 1SWG10 1 1/4 100 6.00
UL•NPPA 19 JSWG20 2 1/4 12504 3 17250 - Fir 100 7.00
LIL.NFPA * 26 Iswc 25-380 21/2 3/8 1 15004 4 22494- Fir 50 10.25
25 ISWG30 3 1/4 50 1 8.50
Not less than 2" nominal width (1112") up
________ to 3112" pipe; not lass than 3" nominal
r-i w1dth4"&5'pipe
FloorJoist r ___
TJI Joist I Truss
Consult miss manufacturarfor
recommended lnstallalion point.
*pre.drilljng may be required
for item #26.
Tools available on page 9.
di
SHEETROCK
Minimum 2112" from bottom for
branch lines. Minimum 3" from
bottom for main lines. Exception:
This requirement shall not apply to
2" orthlcker nailing stflpa resting
on top of steel beams.
- Toggle
Use #14 Nut Driver (Item #100)
Item# Model
I
IshkthI
I
Shk Dia Actual Pullout Box Qty Weight Case Qty (per 100)
71 SST300 3 1/4 4501/ Lath & Plaster 50 12.00 500 404# 2 Layers 5/8 Rock
IUse #14 Nut Driwr(ltein#100)
Item# Model IShkLgth Shk Dia Actual Pullout Pkg Qty Weight Case Qty (per 100)
70 SST3O 3 1/4 450# Lath & Plaster 50 12.00 500 40411 2 Layers 5/8 Rock
Note: Screws most be installed with appmp,fatenuld*srmcompfr with warranty
it