Project Title: SOUND EKLIN 6359 PASEO DEL LAGO/HIGH PILE STORAGE
Applicant: Owner:
VIKING COMMERCIAL CONSTRUCTION ARDEN REALTY LTD PTNSHP
1825 ASTON AV P 0 BOX 4900 DEPT 201
CARLSBAD CA SCOTTSDALE, AZ
760 931 9990
Fees ($) Add'I Fees ($) Total ($) Balance ($)
308 0 308 0
about:blank 1/1
SEE PERMIT
CB110647
6359 PASEO DEL LAGO
SOUND ELKIN
FOR HIGH-PILED
COMBUSTIBLE
STORAGE , REPORT
06-09-2011
City of Carlsbad
Fire Department Permit Permit No: US110097
Job Address: 6359 PASEO DEL LAGO CBAD
Permit Type: HI Subtype: HPCSTOR
Parcel No: 2130920900 Lot #: 0
Fire Dept Ref#: U8110097 Building Permit#: CB110647
Location:
Project Title: SOUND EKLIN
Description: HIGH PILE STORAGE
Contractor:
VIKING COMMERCIAL CONSTRUCTION Phone: 760 931 9990
Fax:
1825 ASTON AV
CARLSBAD CA 92008
Status: ISSUED
Applied: 06/09/2011
Issued: 06/09/2011
Entered By: CDW
CbLk&k6lP
FLU brtXCCI ci4
cno 4-
Total Fees: $308.00 Total Payments To Date: $0.00
Permit Fee $308.00
Failed Inspection Fee $0.00
Other $0.00
Additional Fees S $0.00
TOTAL PERMIT FEES $308.00
NOTICE: Please take NOTICE that approval of your project includes the"Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as'fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
CORRECTION LIST 2 aLL ody
Page: 1 of 2
Daryl K. James & Associates, Inc. Re-Checked by: Anne Marie Bland
205 Colina Terrace Date: May 9., 2011
Vista, CA 92084
T. (760) 724-7001 Email: kitfire@sbcglobal.net
APPLICANT: Tina Bennett JURISDICTION: Carlsbad Fire Department
PROJECT NAME: Sound Eklin PROJECT ADDRESS: 6359 Paseo del Lago
PROJECT DESCRIPTION: CBI 10647 Two-Story Racking System
INSTRUCTIONS
This plan review has been conducted in order to verify conformance to minimum requirements of codes
adopted by the Carlsbad Fire Department.
The items below require correction, clarification or additional information before this plan check can be
approved for permit issuance.
Corrections or modifications to the plans must be clouded and provided with numbered deltas and revision
dates along with a descriptive narrative of corrections addressing all comments.
Please direct any questions regarding this review to: Anne Marie Bland 760434-7885 or
ambIand@pacbell.net
CORRECTED PLANS, DESCRIPTIVE NARRATIVE OF REVISIONS FOLLOWING EACH COMMENT ON
THIS FORM, AND A COPY OF BUILDING DEPARTMENT (EsGil) COMMENTS MUST BE SUBMITTED
DIRECTLY TO:
ANNE MARIE BLAND
4380 CARMEL DRIVE
CARLSBAD, CA 92010
COMMENTS emailed to: Tina Bennett [tbennett@rbn-design.com]
RESUBMITTAL REVIEW
Racking Plan - High-Piled Storage
Provide a High-Piled Storage Fire Code Compliance Report prepared by qualified person acceptable to
Carlsbad Fire Prevention. Report must detail storage arrangement, methods and commodities for
compliance with California Fire Code Chapter 23 and NFPA 13 standard.
Provide a floor plan showing location of proposed storage racks, aisles, cross aisles and access to exit
doors.
Show locations of smoke and heat vents. Indicate automatic operation temperature - fusible link.
See below
Rack!shelving plan scale (1/16) is incorrect. Please note correct scale.
Provide a floor plan showing locations of required smoke and heat vents. Based on the High-
Piled Storage Report prepared by Klausbruckner and Associates, smoke and heat vents are
required at a ratio of 1:50. Smoke and heat vent floor plan must also include the following
information:
Operation of vents - smoke and heat vents must be operated by approved automatic
and manual means. Note method of operation and temperature of automatic
operation. Vent operating element must be a higher temperature than the fire sprinkler
heads.
Listing of vents - smoke and heat vents shall be listed and labeled to indicate
compliance with FM 4430, /CC ES AC 331, or UL 793.
Location - vents required over the storage area and 15 feet beyond. Maximum
spacing of vents is 100 feet and maximum distance from vents to wall is 50 feet.
Page: 20f2
L3 Provide a site plan showing location of fire access roadways for the purpose of determining
location of required fire access doors. A minimum of one access door shall be provided in
each 100 lineal feet, or fraction thereof, of the exterior walls that face required fire apparatus
access roads. The required access doors shall be distributed such that the lineal distance
between adjacent access doors does not exceed 100 feet.
L3 Shelf storage - depending on fire sprinkler option chosen from the High-Piled Storage Report,
the following details must be shown in the shelving plan:
Option #2a - show required full height, solid vertical transverse barrier per NFPA 13
guidelines in back-to-back storage arrangement.
Or, Option #2b - show solid shelf, shelf storage not classified as back-to-back shelf
detail.
Or, Option #2c - Show grated shelving greater than 50% open, back-to-back storage
(see option #2a for back-to-back requirement) or, solid shelving not greater than 32
square feet with 3 inch gaps between shelves.