HomeMy WebLinkAbout5966 LA PLACE CT; ; AS120028; Permit3/12/24, 2:53 PM AS120028 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address: 5966 LA PLACE CT
Permit Type: SPRINK
Parcel No: 2120620600
Lot #: 0
Reference No.:
PC #:
Project Title: THE CAMPUS T.l.
Permit No: AS120028
Status: PENDING
Applied 3/1/2012
Approved:
Issued:
Inspector:
Applicant:
PACIFIC FIRE SYSTEMS, INC.
13142 NELSON LANE
POWAY, CA
858-722-9865
Owner:
CAMPUS CARLSBAD L L C
C/O NEWPORT NATIONAL CORP
1525 FARADAY AVE #100
CARLSBAD CA
Fees ($) Add'l Fees ($) Total ($) Balance ($)
262 0 262 0
about:blank 1/1
Ast2zon
MATERIAL DATA SUBMITTAL
The Campus Building 5966 Suite #100
Tenant Improvement
5966 La Place Court
Carlsbad, CA 92008
c.
FIRE SYSTEMS INC.
Pacific Fire Systems, Inc.
13142 Nelson Lane
Poway, CA 92064
858-722-9865 Phone 9 866-318-6930 Fax
tqC0 Fire Suppression
& Building Products
Technical Services 800-381-93121+1-401-781-8220
www.tyco-fire.com
Series TYFRB — 28, 4.2,1 5.6, and 80 K-Factor
Upright, Penden , and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The TYCO Series TY-FRB, 2.8, 4.2,5.6,
and 8.0 K-factor, Upright and Pendent
Sprinklers described in this data sheet
are quick response, standard coveraQe,
decorative 3 mm glass bulb-tyC
1ighjt/6r
ry
sprinklers designed for use i
ordinary hazard, commercial an-
des such as banks, hotels, and shop-
ping malls.
The recessed version of the Series TV-
FRB Pendent Sprinkler, where applica-
ble, is intended for use in areas with a
finished ceiling. This recessed pendent
sprinkler uses one of the following,
A two-piece Style 10 (1/2 inch NPT)
or Style 40(3/4 inch NPT) Recessed
Escutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a
A two-piece Style 20 (1/2 inch NPT)
or Style 30(3/4 inch NPT) Recessed
Escutcheon with 1/4 inch (6,4 mm) of
recessed adjustment or up to 1/2 inch
(12,7 mm) of total adjustment from the
flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
IMPORTANT
Always refer to Technical Data
Sheet 77=P700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and
Installation of sprinkler systems and
components Improper handling and
Installation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
Page 1 of 10
Corrosion-resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be obtained
when exposed to corrosive atmo-
spheres. Although corrosion-resistant
coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently,
it is recommended that the end user
be consulted with respect to the suit-
ability of these coatings for any given
corrosive environment. The effects of
ambient temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level of the Series TV-
FRB Pendent Sprinklers is detailed
in Technical Data Sheet 1FP356, and
Sprinkler Guards are detailed in Tech-
nical Data Sheet TFP780.
NOTICE
The Series TY-FRB Concealed Pendant
Sprinklers described herein must be
Installed and maintained in compliance
with this document and with the appli-
cable standards of the National Fire
Protection Association, in addition to
the standards of any authorities having
Jurisdiction. Failure to do so may impair
the performance of these devices.
Owners are responsible for maintaining
their fire protection system and devices
in proper operating condition. The
installing contractor or sprinkler manu-
facturer should be contacted with any
questions.
JULY 2010
Model/Sprinkler
Identification
Number (SIN)
TV1131: Upright 2.8K, 1/2- NPT
1Y1231: Pendent 2.8K, 1/2 NPT
TY2131: Upright 4.2K, 112w NPT
1Y2231: Pendent 4.2K, 1/2 NPT
7.31-31Upright 5.6K, 1/2 NPT
cJY3231:jPendent 5.6K, 1/2 NPT
TY4t31 Upright 8.0K, 3/4 NPT
TY4231: Pendant 8.0K, 3/4 NPT
TV4831: Upright* 8.0K, 112 NPT
1Y4931: Pendent* 8.0K, 1/2 NPT
'Eastern HemIsphere Sales Only
TFPI7I
STYLE 10 or 20
RECESSED
ESCUTCHEON
TFPI7I
Page 2 of 10
t
6*
5
7/16"
4 (11,1 mm) 2-1/4" I
NOMINAL (57,2mm)
2 MAKE-IN
2-3/16" 1-9/16"
(55,6 mm) WRENCH (39,7 mm)
FLATS
I
1/2" NPT SSP DEFLECTOR * -.--_ 2-7/8" (73,0 mm) DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
1 -Frame 3 - Sealing 4 - Bulb 6 - Deflector
Assembly * Temperature rating is indicated on deflector or adjacent to
2 - Button - Compression 7 - Bushing orifice seat on frame. Screw
FIGURE 1
QUICK RESPONSE SERIES TY.FRB UPRIGHT (TYII3I) AND PENDENT (TY1231) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
SSU *
DEFLECTOR
7/16"(11,1 mm)
NOMINAL
MAKE-IN 1 NPT
ESCUTCHEON
PLATE SEATING
SURFACE
2-3/16"
(55,6 mm)
7/16" (11,1 mm)
SSU * NOMINAL
DEFLECTOR MAKE-IN
6*
t 7/16" I (11,1 mm)
4 I NOMINAL
MAKE-IN
_
2 , 2-3/18"
(55,6 mm) WRENCH
FLATS
1/2" NPT
CROSS SECTION UPRIGHT
ESCUTCHEON
PLATE SEATING
iir SURFACE
SSP DEFLECTOR*
PENDENT
STYLE 10 or 20
RECESSED
ESCUTCHEON
2-7/8" (73,0mm) DIA.
RECESSED PENDENT
1 - Frame 3-Sealing 4-Bulb 6-Deflector Assembly "Temperature rating is indicated on deflector or adjacent to
2 - Button 5 - Compression orifice seat on frame. Screw
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT ('772131) AND PENDENT (TY2231) SPRINKLERS 42 K-FACTOR, 112 INCH NPT
TFPI7I
Page 3 of 10
7/16(11,1 mm) ESCUTCHEON STYLE 10 0r20
SSU * NOMINAL 1/2 PLATE SEATING RECESSED
DEFLECTOR MAKE-IN NPT SURFACE ESCUTCHEON
6*
7/16 5
3/16
NOMINAL
f
(55,6 mm)
1 (11,1 mm)t
,,
2-
MAKE-IN
2 2-3116"
_______ (55,6 mm)
FLATS
1-1/2° I
_______ (38,1 mm) I
1/2° NPT SSP DEFLECTOR* 2-7/8° (73,0 mm) DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
1 - Frame 3-Sealing 4-Bulb 6- Deflector * Assembly Temperature rating is indicated on deflector or adjacent to
2- Button 5-Compression orifice seat on frame. Screw
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TV3131) AND PENDENT (f3231) SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT
1/2' (12,7 mm) ESCUTCHEON STYLE 30 or 40
SSU * NOMINAL PLATE SEATING RECESSED
DEFLECTOR MAKE-IN NPT SURFACE ESCUTCHEON
6*
5 1/2"
2J160 I (12,7 mm)
4 NOMINAL
I
___________
(58,7 mm)
MAKE-IN
2 2-1/4" 1-9/16" I I
3(57,2mm) (39,7 mm) I
f 3/40 NPT SSP DEFLECTOR * L-_ 2-7/8"(73,0 mm) DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
1 - Frame 3-Sealing 4-Bulb 6- Deflector
Assembly "Temperature rating is indicated on deflector or adjacent to
2 - Button 5 - Compression orifice seat on frame. Screw
FIGURE 4
QUICK RESPONSE SERIES TYFRB UPRIGHT (TY4131) AND PENDENT (7Y4231) SPRINKLERS
8.0 K-FACTOR, 314 INCH NPT
TFPI7I
Page 4 of 10
7/16' (11,1 mm)
SSU * NOMINAL
DEFLECTOR MAKE-IN 1/2'
NPT
6* ____________ i I
_T 1 7/16' I (11,1 mm) _____________ 21/4"
I
NOMINAL
(57,2 mm)
22_
__
MAKE-IN
-3/16' 1-9/16'
(55,6 mm) _____ WRENCH (39,7 mm) I
FLATS
___
SSP*_-
CROSS 1/2' NPT DEFLECTOR
SECTION UPRIGHT PENDENT
1 -Frame 3 - Sealing 4 - Bulb 6- Deflector 'Temperature rating Is Indicated on deflector or adjacent to
2 - Button
Assembly 5 - Compression
Screw orifice seat on frame.
FIGURE 5
QUICK RESPONSE SERIES TY.FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS 8.0 K-FACTOR, 1/2 INCH NPT
Technical
Data
Approvals
UL and C-UL Listed
FM, LPCB, and NYC Approved
Refer to Table A and B for complete
approval information including
corrosion-resistant status.
Maximum Working Pressure
Refer to Table C.
Discharge Coefficient
K=2.8 GPM/psi'/2 (40,3 LPM/bar112)
K=4.2 GPM/ps11l2 (60,5 LPM/barl 2)
K=5.6 GPMIpsi1/2 (80,6 LPM/bar"2)
K=8.0 GPM/psi'/2 (115,2 LPM/bart/2)
Temperature Rating
Refer to Table A and B.
Finishes
Sprinkler: Refer to Table A and B.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated.
Physical Characteristics
Frame...................Bronze
Button..............Brass/Copper
Sealing Assembly.........Beryllium
Nickel w/Teflont
Bulb ......................Glass
Compression Screw........Bronze
Deflector ........... Copper/Bronze
Bushing (K=2.8) ...........Bronze
t Registered Tradema,lc of Dupont
Operation
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB Pendent
and Upright Sprinklers are intended
for fire protection systems designed in
accordance with the standard Installa-
tion rules recognized by the applicable
Listing or Approval agency (such as, UL
Listing is based on the requirements of
NFPA 13, and FM Approval Is based on
the requirements of FM's Loss Preven-
tion Data Sheets). Only the Style 10,
20, 30, or 40 Recessed Escutcheon, as
applicable, Is to be used for recessed
pendent Installations.
Installation
The TYCO Series TY-FRB Sprinklers
must be Installed in accordance with
the following instructions.
NOTICE
Do not install any bulb-type sprinkler if
the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bub-
ble should be present. The diameter
of the air bubble is approximately 1/16
inch (1,6 mm) for the 1350F/570C and
3/32 inch (2,4 mm) for the 2860F/141°C
temperature ratings.
Obtain a leak-tight 1/2 Inch NPTsprin-
kier joint by applying a minimum to
maximum torque of 7 to 14 ft.Ibs. (9,5
to 19,0 Nm). Higher levels of torque
can distort the sprinkler Inlet with con-
sequent leakage or impairment of the
sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Escutch-
eon Plate by under- or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler filling to suit.
The Series TY-FRB Pendent and
Upright Sprinklers must be installed
in accordance with the following
instructions.
Install Pendent sprinklers In the
pendent position. Install upright
sprinklers in the upright position.
With pipe-thread sealant applied to
the pipe threads, hand-tighten the
sprinkler into the sprinkler fitting.
Tighten the sprinkler into the sprin-
kler fitting using only the W-Type 6
Sprinkler Wrench (Figure 14). With
reference to Figures 1 through
5, apply the W-Tipe 6 Sprinkler
Wrench to the sprinkler wrench
flats.
TFPI7I
Page 5 of 10
SPRINKLER FINISH (See Note 5)
K
FACTOR TYPE TEMPERATURE BULB LIQUID
COLOR
NATURAL
BRASS
I CHROME
PLATED I WHITE I POLYESTER
2.8
1/2" NPT
PENDENT
(TY1231)
and
UPRIGHT
(TY1I3I)
135"F/57°C Orange
1, 2, 3, 4
155"F/68°C Red
175°F/79°C Yellow
200°F/93"C Green
286"F/141°C Blue
RECESSED
PENDENT (TY1231)*
Figure 6
135°F/57"C Orange
1,2,4
155"F/68"C Red
175°F/79"C Yellow
200°F/93"C Green
RECESSED
PENDENT
(TY1231)**
Figure 7
135"F/57°C Orange
1550F/68"C Red
175"F/79°C Yellow
200°F/93"C Green
4.2
1/2" NPT
PENDENT
(1Y2231)
and
UPRIGHT
(TY2131)
135°F/57"C Orange
1,2
155"F/68°C Red
175"F/79°C Yellow
200°F/93°C Green
286"F/141"C Blue
RECESSED
PENDENT (TY2231)*
Figure 8
135°F/57"C Orange
1550F/68°C Red
175"F/79°C Yellow
200°F/93°C Green
RECESSED
PENDENT (TY2231)**
Figure 9
135°F/57°C Orange
155"F/68°C Red
175°F/79"C Yellow
200"F/93"C Green
NOTES: Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the City of New York under MEA 354-01-E.
Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
* Installed with Style 10(1/2" NPT) or Style 40(3/4" NP1) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
Installed with Style 20(1/2" NPT) or Style 30(3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLEA
LABORATORY LISTINGS AND APPROVALS FOR
28 AND 4.2 K-FACTOR SPRINKLERS
TFPI7I
Page 6 of 10
SPRINKLER FINISH (See Note 8)
K
FACTOR TYPE TEMPERATURE BULB LIQUID
COLOR
NATURAL
BRASS
I CHROME
PLATED
I WHITE***
I POLYESTER
LEAD
COATED
5.6
1/2" NPT
PENDENT
(TY3231)
and
UPRIGHT
(TY3131)
135°F/57C Orange
1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5
155°F/68°C Red
175F/79C Yellow
200F/93C Green
286*F/141C Blue
RECESSED
PENDENT (TY3231)*
Figure 10
1350F/57°C Orange
1, 2, 4, 5
Blue
N/A
155F/88°C Red
175°F/79°C Yellow
200F/93C Green
288F/141C
RECESSED
PENDENT (TY3231)**
Figure 11
1359F/570C Orange
1, 2, 3, 4, 5
Blue
N/A
155°F/68°C Red
175F/79°C Yellow
20017/930C Green
286F/141°C
8.0
3/4" NPT
PENDENT
(TY4231)
and
UPRIGHT
(1Y4131)
135°F/57°C Orange
1, 2, 3, 4, 5, 6, 7 1, 2, 5
- 155017/680C Red
1759F/79°C Yellow
200F/93°C Green
286°F/141°C Blue
RECESSED
PENDENT (1Y4231)*
Figure 12
135°F/57°C Orange
1, 2, 5 N/A
155°F/68C Red
175F/79°C Yellow
200°F/93°C Green
286°F/141°C Blue
RECESSED
PENDENT (TY4231)**
Figure 13
135°F/57C Orange
1,2,3,5
Blue
N/A
155°F/68C Red
175F/79C Yellow
2000F/93°C Green
286°F/141C -
80
1/211 NPT
PENDENT
(TY4931)
and
UPRIGHT
(TY4831)
135F/57C Orange
1, 2, 4, 5, 6 1, 2, 5
1550F/68C Red
1750F/79°C Yellow
200F/93C Green
286°F/141°C Blue
NOTES:
Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories. Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FNfl as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. However, LPCB does not rate the thermal sensitivity of recessed sprinklers.
Approved by the City of New York under MM 354-01-E.
VdS Approved (For details, contact Tyco Fire Suppression & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377.)
Approved by the Loss Prevention Certification Board PCB Ref. No. 094a/06) as Quick Response Sprinklers.
Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. Where Lead-Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion-ResIstant Sprinklers.
* Installed with Style 10(1/2" NPT) or Style 40(3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
__Installed with Style 20(1/2" NPT) or Style 30(3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
-- Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS FOR
5.6 AND 8.0 K-FACTOR SPRINKLERS
TFPI7I
Page 7 of 10
SPRINKLER FINISH
K TYPE NATURAL I CHROME I WHITE LEAD FACTOR BRASS PLATED POLYESTER COATED
PENDENT (1Y1231)
and
28 UPRIGHT (TY1131)
1/2" NPT 75 PSI (12,1 BAR) N/A
RECESSED
PENDENT (TY1231)
PENDENT (TY2231)
and
4.2 UPRIGHT (TY2131)
1/2" NPT 175 PSI (12,1 BAR) N/A
RECESSED
PENDENT (TY2231)
PENDENT (TY3231) 175 PSI
5.6
and
UPRIGHT (TY3131) 250 PSI (17,2 BAR) (12,1 BAR)
1/2" NPT OR 175 PSI (12,1 BAR)
RECESSED (SEE NOTE 1)
PENDENT (TY3231) N/A
PENDENT (TY4231) 175 PSI
8.0
and
UPRIGHT (TY4131) (12,1 BAR)
3/4" NPT 175 PSI (12,1 BAR)
RECESSED N/A PENDENT (TY4231)
8.0 PENDENT (TY4931) 175 PSI 1/2" NPT and UPRIGHT (TY4831) 175 PSI (12,1 BAR) (12,1 BAR)
NOTES: 1. The maximum working pressure of 250 psi (17,2 bar) Only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in Canada (C-UL); and, the Approval by the City of New York.
The Series TV-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
After installing the Style 10, 20, 30,
or 40 Mounting Plate, as applica-
ble, over the sprinkler threads and
with pipe-thread sealant applied to
the pipe threads, hand-tighten the
sprinkler into the sprinkler fitting.
Tighten the sprinkler Into the sprin-
kler fitting using only the W-Type 7
Recessed Sprinkler Wrench (Fig-
ure 15). With reference to Figures 1
to 4, apply the W-Type 7 Recessed
Sprinkler Wrench to the sprinkler
wrench flats.
After ceiling installation and finish-
ing, slide on the Style 10, 20, 30, or
40 Closure over the Series TY-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
TABLE C
MAXIMUM WORKING PRESSURE
Care and
Maintenance
The TYCO Series TY-FRB must be
maintained and serviced in accordance
with the following instructions.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
Exercise care to avoid damage to
sprinklers before, during, and after
installation. Never paint, plate, coat,
or otherwise alter automatic sprinklers
after they leave the factory.
Replace sprinklers that:
were modified or over-heated.
were damaged by dropping, striking,
wrench twisting, wrench slippage, or the like.
are leaking or exhibiting visible signs
of corrosion.
were exposed to corrosive products
of combustion but have not oper-
ated, if you cannot easily remove
combustion by-products with a cloth.
have a cracked bulb or have lost liq-
uid from the bulb. Refer to the Instal-
lation section in this data sheet.
TFPI7I
Page 8 of 10
2-7/8 DIA. - (73,0 mm) 3/4' (19,1 mm)
(15,9±6,4 mm) 2-1/4" DIA. 1/4' (6,4 mm)
FACE OF (57,2 MOUNTING SPRINKLER PLATE FITTING
1/8
/
(3,2 mm)
/1 MOUNTING /
SURFACE
CLOSURE SERIES 1-5/16'( 33,3 mm)
TY-FRB 13/16' (20,6 mm)
FIGURE 6
SERIES 7Y-FRB RECESSED PENDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
2-7/8" DIA. -
5/8±1/4" (73,0 mm) I (19,1 mm) I (15,9±6,4 mm) 2-1/4' DIA. I 1/4"(6,4 m
FACE OF
l
I
(57,2 mm) MOUNTING SPRINKLER
-
PLATE I FITTING
1/8"
(3,2 mm)
I
\/I
_
$ MOUNTING
SURFACE
SERIES 1-1/4"(31,8 mm) CLOSURE TY-FRB 3/4"(19,1 mm)
FIGURES
SERIES TY.FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
2-7/8" DIA.
-
1/2±1/8"
(73,0 mm) I 1/2' (12,7 mm) r (12,7±3,2mm) 2-1/4' DIA. 1/4" (6,4 mm) I
FACE OF 57,2 mm) MOUNTING I I SPRINKLER / PLATE I FITTING
I 1/8' I
/
(3,2 mm) I
_______
$
MOUNTING /
-5I16"(33,3 mm)
SURFACE
,,,,,
/
{ CLOSURE SERIES TY-FRB 1-1/16"(27,0 mm)
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
2-7/8' DIA.
-
1/2±1/8'
(73,0 mm) I 1/2'(12,7 mm) r (12,7±3,2 mm) 2-1/4" DIA. 1/4' (6,4 mm) I
FACE OF (57,2 mm) MOUNTING
/
I
SPRINKLER PLATE
i FITTING
1/8'
(3,2 mm)
t
I
I \
MOUNTING I I
SURFACE
SERIES 1-1/4' (31,8 mm) CLOSURE TY-FRB 1' (25,4 mm)
FIGURE 9
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
Initial and frequent visual inspections of
random samples are recommended for
corrosion-resistant sprinklers to verify
the integrity of the corrosion-resistant
material of construction. Thereafter,
annual inspections per NFPA 25 should
suffice.
Inspections of corrosion-resistant
sprinklers are recommended at close
range, instead of from the floor level
per NFPA. Inspection at close range
can better determine the exact sprin-
kler condition and the long-term integ-
rity of the corrosion-resistant material,
which can be affected by the corrosive
conditions present.
Responsibility lies with the owner for
the Inspection, testing, and mainte-
nance of their fire protection system
and devices in compliance with this
document, as well as with the appli-
cable standards of the National Fire
Protection Association (for example,
NFPA 25), in addition to the standards
of any other authorities having jurisdic-
tion. Contact the installing contractor or
sprinkler manufacturer regarding any
questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service In accordance with local
requirements and/or national codes.
Care must be exercised to avoid dam-
age to the sprinklers -before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be
replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Initial and frequent visual inspections of
random samples are recommended for
corrosion-resistant sprinklers to verify
the integrity of the corrosion-resistant
material of construction. Thereafter,
annual inspections per NFPA 25 should
suffice.
f \
MOUNTING
SURFACE
CLOSURE SERIES 1-1/4"(31,8 mm)
1° (25,4 mm)
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8' DIA.
(73,0 mm) 3/4'(19,1 mm)
2-1/4° DIA. 1/4"(6,4 mm)
I (57,2 mm) MOUNTING
PLATE
MOUNTING
SURFACE
5/8±1/4'
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
1/2±1/8'
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
2-7/8' DIA.
(73,0 mm)
2-1/4° DIA.
(57,2 mm)
1/2'(12,7mm)
1/4"(6,4 mm)
MOUNTING
- PLATE
1/8°
(3,2 mm)
t \
MOUNTING
SURFACE
TFPI7I
Page 9of 10
2-7/8' DIA.
(73,0 mm) 3/4' (19,1 mm) 5/8±1/4
-
(15,9± 2-1/4' DIA. 6,4 mm) 1/4' (6,4 mm) I
FACE OF ' MOUNTING mm
_
SPRINKLER PLATE FITTING
1/8'
(3,2 mm)
/
MOUNTING
SURFACE
,
/
CLOSURE SERIES 1-1/4° (31,8 mm)
TY-FRB 3/4"(19,1 mm)
FIGURE 10
SERIES TY.FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
1/2±1/8
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
2-7/8' DIA.
(73,0 mm) I 1/2"(12,7 mm)
2-1/4° DIA. 1/4"(6,4 mm) I
(572 mm)
MOUNTING
PLATE
7j
CLOSURE SERIES 1-5/16° (33,3 mm) CLOSURE SERIES 1-6/16'(33,3 mm
TY-FRB 13116"(20,6 mm) TY-FRB 1-1/16"(27,0 mm)
FIGURE 12
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
FIGURE 13
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
Inspections of corrosion-resistant
sprinklers are recommended at close
range, instead of from the floor level
per NFPA. Inspection at close range
can better determine the exact sprin-
kler condition and the long-term integ-
rity of the corrosion-resistant material,
which can be affected by the corrosive
conditions present.
WRENCH RECESS
(END 'A' USED FOR
1/2' NPT MODELS)
WRENCH RECESS
(END 'B' USED FOR
3/4' NPT MODELS)
FIGURE 14
W-TYPE 6 SPRINKLER
WRENCH
WRENCH
RECESS
6
t
PUSH WRENCH IN TO
ENSURE ENGAGEMENT WITH
SPRINKLER WRENCHING AREA
FIGURE 15
W-TYPE 7 RECESSED
SPRINKLER WRENCH
TFPI7I
Page 10 of 10
P/N 57- XXX- X- XXX
L
FmODZ;IN]
330 2.8K UPRIGHT (1/2°NP1) TY1131
331 2.81< PENDENT (1/2°NPT) TY1231
340 4.21< UPRIGHT (1/2°NPI) TY2131
341 4.2K PENDENT (1/2°NPT) 1Y2231
370 5.61< UPRIGHT (1/2°NPT) TY3131
371 5.6K PENDENT (112"NPT) TY3231
390 8.01< UPRIGHT (314°NPT) 1Y4131
391 8.01< PENDENT (3/4°NPT) TY4231
360 8.0K UPRIGHT (1/2°NPT) 1Y4831°
381 8.0K PENDENT (1/2°NPT) TY4931°
SPRINKLER I TEMPERATURE
L FINISH RATINGS
1 NATURAL BRASS 135 135°F (57°C)
4 WHITE POLYESTER 155 155°F (68°C)
3 WHITE (RAL9010)' 175 175°F (79°C)
9 I CHROME PLATED 200 200°F 3°C)
7 I LEAD COATED I I 286 1 286°F (141°C)
* Eastern Hemisphere sales only.
TABLED
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire
Suppression & Building Products
(TFSBP) are warranted solely to the
original Buyer for ten (10) years against
defects in material and workmanship
when paid for and properly installed
and maintained under normal use and
service. This warranty will expire ten
(10) years from date of shipment by
TFSBP. No warranty is given for prod-
ucts or components manufactured by
companies not affiliated by ownership
with TFSBP or for products and com-
ponents which have been subject to
misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in
accordance with applicable Standards
of the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by TFSBP to be defective
shall be either repaired or replaced, at
TFSBP's sole option. TFSBP neither
assumes, nor authorizes any person
to assume for It, any other obligation in
connection with the sale of products or
parts of products. TFSBP shall not be
responsible for sprinkler system design
errors or inaccurate or incomplete Infor-
mation supplied by Buyer or Buyer's
representatives.
In no event shall TFSBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
Indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFSBP
was informed about the possibility of
such damages, and in no event shall
TFSBP's liability exceed an amount
equal to the sales price.
The foregoing warranty Is made In lieu
of any and all other warranties, exoress
or implied, including warranties of mer-
chantabilthLandlitness for a oarticular
This limited warranty sets forth the
exclusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim is
made in contract, tort, strict liability or
any other legal theory.
This warranty will apply to the full
extent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and Part
Number (P(N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table D).
Recessed Escutcheon:
Specify: Style (10, 20, 30, or 40)
Recessed Escutcheon with (specify*)
finish, P/N (specify*).
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
* Refer to Technical Data Sheet TFP770.
Copyright 02007-2010 Tyco Fire Suppression & Building Products. All rights reserved.
tqCD /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312 1 Fax: (800) 791-5500
Series RFII 5,6 K-factor
"Royal Flush II" Pendent Concealed Sprinklers
Quick & Standard Response, Standard Coverage
General
Description
The Series RFll Quick Response
(3 mm bulb) & Standard Response (5
mm bulb), 5.6 K-Factor, Royal Flush
II" Concealed Pendent Sprinklers are
decorative sprinklers featuring a flat
cover plate designed to conceal the
sprinkler. It is the best choice for archi-
tecturally sensitive areas such as hotel
lobbies, office buildings, churches,
and restaurants.
Each unit includes a Cover Plate As-
sembly that conceals the sprinkler op-
erating components above the ceiling.
The separable two-piece design of the
Cover Plate and Support Cup Assem-
blies allows installation of the sprin-
klers and pressure testing of the fire
protection system prior to installation
of a suspended ceiling or application
of the finish coating to a fixed ceiling.
They also permit removal of sus-
pended ceiling panels for access to
building service equipment without
having to first shut down the fire pro-
tection system and remove sprinklers.
Also, the separable two-piece design
of the the Sprinkler provides for 112
inch (12,7 mm) of vertical adjustment,
to reduce the accuracy to which the
length of fixed pipe drops to the sprin-
klers must be cut.
The Series RFll Sprinklers are
shipped with a Disposable Protective
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the INSTALLER
WARNING that provides cautions
with respect to handling and Instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
Cap. The Protective Cap is temporarily
removed for installation, and then it
can be replaced to help protect the
sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro-
tective Cap can also be used to mark
the center of the ceiling hole into plas-
ter board, ceiling tiles, etc. by gently
pushing the ceiling product against the
Protective Cap. When the ceiling in-
stallation Is complete the Protective
Cap is removed and the cover Plate
Assembly Installed.
As an option, the Series RFll Standard
Response (5 mm bulb) Royal Flush 11
Concealed Pendent Sprinklers maybe
fitted with a silicone Air and Dust Seal
(Ref. Fig. 5). The Air and Dust Seal is
intended for sensitive areas where it is
desirable to stop air and dust travel
through the cover plate from the area
above the ceiling.
WARNINGS The Series RFll Concealed Pendent
Sprinklers described herein must be
installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
National Fire Protection Association,
In addition to the standards of any
other authorities having jurisdiction.
Failure to do so may impair the per-
formance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY3551 (5 mm bulb)
bulb)
JANUARY, 2008
Technical
Data
Approvals for Series RFll
UL and C-UL Listed. FM Approved.
NYC under MEA 353-01-E. LPCB
(Ref. No. 094aI09 for TY3551 & 094a110 for TY3531) Approved.
The approvals apply only to the serv-ice conditions indicated in the Design
Criteria section.
Approvals for Air & Dust Seal
(Part #10908100)
UL and C-UL Listed for use with the
RFlI (TY3551) Standard Response
Concealed Sprinkler.
Maximum Working Pressure:
Maximum 250 psi (17,3 bar) by UL,
C-UL, and NYC. Maximum 175 psi
(12,1 bar) by FM and LPCB.
Temperature Ratings
15517/68C Sprinkler - 135F/57C Plate 20017I93C Sprinkler - 165F/74C Plate
Discharge Coefficient
K = 5.6 GPM/psi1l2 (80,6 LPMIbarl'2)
Adjustment
1/2 inch (12,7 mm)
Finishes
Cover Plate: Chrome Plated, Brass
Plated, or White Painted (Custom
paint matches and colors other than
white are available on request.)
TFPI8I
.; Pagte2of4 TFPI8I
112' NPT SEALING
ASSEMBLY
FRAME
CAP
suor
CUP WITH BULB ROLL FORMED - THREADS
- COMPRESSION
SCREW -
GUIDE —
PINS (2)
DEFLECTOR
(DROPPED DEFLECTOR H1- POSI11ON)
SPRINKI.ERISUPPORT CUP
I ASSEMBLY
THREAD INTO U RETAINER SUPPORT CUP II WITh ThREAD UNTIL MOUNTING 0 0 DIMPLES SURFACE IS
FLUSH WITH EJECTION CEILING
lL
SPRING
_
SOWER COVER TABS (3) COVER PLATEIRETAINER PLATE ASSEMBLY
FIGURE 1
SERIES RFII CONCEALED SPRINKLER
ASSEMBLY
Physical Characteristics
Frame ............Bronze
Support Cup . Chrome
.
Plated Steel Guide Pins ......Stainless Steel
Deflector ...........Bronze
Compression Screw ......Brass
Bulb ...............Glass
Cap ........Bronze or Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflon*
Cover Plate ...........Brass
Retainer ............Brass
Ejection Spring. . . . Stainless Steel
Patents
U.S.A. 4,014,388
Operation
When exposed to heat from a fire, the
Cover Plate, which is normally sol-
dered to the Retainer at three points,
falls away to expose the Sprinkler As-
sembly. At this point the Deflector sup-
ported by the Guide Pins drops down
to its operational position.
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, activating the sprinkler and
allowing water to flow.
Design
Criteria
The RFII (1Y3551), 5 mm Bulb Type,
Concealed Pendent Sprinklers are UL
and C-UL Listed as standard response
- standard spray sprinklers for use in
accordance with the current NFPA
standard. They are FM Approved as
standard response - standard spray sprinklers for use in accordance with
the current FM Loss Prevention Data
Sheets.
The RFII (TY3531) 3 mm Bulb Type,
Concealed Pendent Sprinklers are UL
and C-UL Listed as quick response - standard spray sprinklers for use in
accordance with the current NFPA
standard. They are FM Approved as
standard response - standard spray sprinklers for use in accordance with
the current FM Loss Prevention Data
Sheets.
The Series RFll Concealed Pendent
Sprinklers are only listed and ap-
proved with the Series RFll Concealed
Cover Plates having a metallic or white
painted finish.
The Series RFll must not be used in
applications where the air pressure
above the ceiling is greater than that
below. Down drafts through the Sup-
port Cup could delay sprinkler opera-
tion In a fire situation.
Installation
The Series RFll must be installed in
accordance with the following instruc-
tions:
!Ii4i
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 155°F/68°C and 3/32
Inch (2,4 mm) for the 200°F/930C tem-perature ratings.
A 1/2 inch NPT sprinkler joint should
be obtained with a minimum to maxi-
mum torque of 7 to 14 ft.Ibs. (9,5 to
19,0 Nm). Higher levels of torque may
distort the sprinkler inlet with conse-
quent leakage or impairment of the
sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in the Sprinkler
Assembly by under- or over-tightening
the Sprinkler/Support Cup Assembly.
Readjust the position of the sprinkler
fitting to suit.
Step 1. The sprinkler must only be
installed in the pendent position and
with the centerline of the sprinkler per-
pendicular to the mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 4. Wrench tighten the sprinkler
using only the RFll Sprinkler Wrench
(Ref. Figure 3). The RFll Sprinkler
Wrench is to be applied to the Sprin-
kler as shown in Figure 3.
Step 5. Replace the Protective Cap
(Ref. Figure 4) by pushing it upwards
until it bottoms out against the Support
Cup. The Protective Cap helps prevent
damage to the Deflector and Arms dur-
ing ceiling installation and/or during
application of the finish coating of the
ceiling. It may also be used to locate
the center of the clearance hole by
gently pushing the ceiling material up
against the center point of the Protec-
tive Cap.
NOTE As long as the Protective Cap remains
in place, the system is considered to
be "Out of Service".
* Registered Trademark of DuPont
\ -\__j L -------- I I
3/16" to 11/16" MANUFACTURER DEFLECTOR COVER PLATE (4.8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER REFERENCE 3/32" (24 mm) POSITION ASSEMBLY
COVER PLATE COVER PLATE PROFILE DEPTH DIAMETER DIMENSION B DIMENSION A
3-1/4" (82,6 mm) C: 2-3/8" to 2-5/8" (60,3 to 66,7 mm)
3116"(4.8 mm) D: 1-3/4" to 2-114"(44,5 to 57,2 mm)
FIGURE 2
SERIES RFII CONCEALED SPRINKLER
INSTALLATION DIMENSIONS
TFPi81 Page 3 of 4
FACE OF CLEARANCE HOLE SPRINKLER DIAMETER FITTING
SPRINKLER
SUPPORT CUP
ASSEMBLY
L!SIoNC 1/2" (12,7 mm)
THREADED D ADJUSTMENT -
I FACE OF CEILING I RETAINING RING I MOUNTING I SURFACE '771
FRAME
ARM
SUPPORT
CUP
IIMR
IUL frji
SQUARE
ALIGN
ARROWS WrrH
FRAMEARMS
ACCEPTS
DRIVE
FIGURE 3
RF11 SPRINKLER WRENCH
Step 6. After the ceiling has been com-
pleted with the 2-1/2 inch (63,5 mm)
diameter clearance hole and In prepa-
ration for installing the Cover Plate As-
sembly, remove and discard the Pro-
tective Cap, and verify that the
Deflector moves up and down freely. If
the Sprinkler has been damaged and
the Deflector does not move up and
down freely, replace the entire Sprin-
kler assembly. Do not attempt to mod-
ify or repair a damaged sprinkler.
Step 7. When installing an Air and
Dust Seal, refer to Figure 5, otherwise
proceed to Step 8. To attach the Air
and Dust Seal, verify the angle of the
outside edge of the seal is oriented
according to Figure 5. Start the edge
of the Retainer in the grooved slot of
the Air and Dust Seal and continue
around the retainer until the entire Air
and Dust Seal is engaged.
NOTE
The Air and Dust Seal Is only to be
installed on the periphery of the Re-
tainer.
Step S. Screw on the Cover Plate/Re-
tainer Assembly until the Retainer - Figure 2 (or Air and Dust Seal - Figure 5) contacts with the ceiling. Do not
continue to screw on the Cover
Plate/Retainer Assembly such that it
lifts a ceiling panel out of its normal position. If the Cover Plate/Retainer
Assembly cannot be engaged with the
Support Cup or the Cover Plate/Re-
tainer Assembl y cannot be engaged
sufficiently to contact the ceiling, the
Sprinkler Fitting must be repositioned.
Care and
Maintenance
The Series RFll must be maintained
and serviced in accordance with the
following instructions:
NOTES
Absence of the Cover Plate Assembly
may delay sprinkler operation in a fire
situation.
. Page4of4 TFPIBI
When properly installed, there is a
nominal 3/32 inch (2,4 mm) air gap
between the lip of the Cover Plate and
the ceiling, as shown In Figure 2. This
air gap is necessary for proper opera-
tion of the sprinkler. If the ceiling is to
be repainted after the installation of
the Sprinkler, care must be exercised
to ensure that the new paint does NOT
seal off any of the air gap.
Factory painted Cover Plates MUST
NOT be repainted. They should be re-
placed, if necessary, by factory
painted units.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system That
it controls, permission to shutdown the
affected fire protection system must be
obtained from the proper authorities
and all personnel who maybe affected
by this action must be notified.
Sprinklers that are found to be leaking or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during, and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
If a sprinkler must be removed, do not
reinstall it or a replacement without
reinstalling the Cover Plate Assembly.
If a Cover Plate Assembly becomes
dislodged during service, replace it im-
mediately.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualified Inspection Service in accord-
once with local requirements and/or
national codes.
Limited
Warranty
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental, Indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was Informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties. ex-
pressor Implied. induding warranties
of merchantability and fitness for a
particular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
a*hnr lanai •kaan,
White (RALSOIO) 56-792-3-135 56-792-3-165 Bright White 58-792.4-135 56-792.4-165 Off White 56-792-6-135 58-792.5-165 Black 58-792.6-135 56-79241-165 Custom 56-792-X-135 56-792-X-165
For use with 166F/68C sprinlders. For use with 200F/93C spnnlders. * Eastern Hemisphere sales only
Sprinkler Wrench:
Specify: RFII Sprinkler Wrench,
P/N 56-000-1-075.
Air and Dust Seal:
Specify: Air and Dust Seal,
P/N 56-908-1-001.
Products manufactured by Tyco Fire & " a"WN'U' ' Building Products (TFBP) are war- This warranty will apply to the full ex- ranted solely to the original Buyer for tent permitted bylaw. The invalidity, in ten (10) years against defects in mate- whole or part, of any portion of this rial and workmanship when paid for warranty will not affect the remainder
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years Ordering
from date of shipment by TFBP. No Procedure warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP When placing an order, indicate the
o r for products and components which full product name. Contact your local
distributor for availability. have been subject to misuse, improper
installation, corrosion, or which have Sprinkler Assembly:
not been installed, maintained, moth- Specify: (SIN), (specify temperature
fled or repaired in accordance with ap- rating) Series RFII Concealed Pen-
plicable Standards of the National Fire dent Sprinkler, P/N (specify).
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
165F168C 200F193C TIMM 51-790-1-155 51.790-1-200
by TFBP to be defective shall be either 51-792-1-155 51-792-1-200
repaired or replaced, at TFBP's sole Separately Ordered Cover Plate: option. TFBP neither assumes, nor Specify: (specify temperature rating) authorizes any person to assume for it, Series RFII Concealed Cover Plate any other obligation in connection with
the sale of products or parts of prod- with (specify finish), P/N (specify).
ucts. TFBP shall not be responsible for 13!57C(a) 165F174C(b) sprinkler system design errors or mac- Brass 56-192-1-135 56-792-1-165 curate or incomplete information sup- Bright Brass 56-792-2-135 56-792-2-165 plied by Buyer or Buyer's repre- Chrome 56-792-9-135 58-792-9-165 Brushed Chrome 56-792-8-135W792-8-165 sentatives. Wl,fa 0J4 56..79JL1
0 2114118 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
SMITH ,. COOPER
<~@> INTERNATIONAL
Ductile Iron Threaded Fittings
C & US * ALL FITTINGS 1000/6 AIR TESTED * ASME/ ANSI B16.3
* ISO 900F.2000 MANUFACTURER * ASTM A536 Grade 6545,12
LISTED * LISTED/APPROVED AT 500 PSI * ASME/ ANSI B 1.20.1 pi'ciovo
Thwfilp lynn Riill Uic1 Te
Figure 35BT
i 0 I .-A--a.t
Lit
Size A B I C
3/4x314x1 1.45 i& 17 0.68
I x 1 x 1-1/4 1.67 1.67 1.58 0.97
1x1x1-112 1.80 1.80 1.65 1.14
-114 x I x 1-1/2 1.88 1.80 1.82 1.43
-1/4x1-1/4x1-112 1.88 1.88 1.82 1.52
-1/4x1-1/4x2 2.10 2.10 1.90 2.00
-112x1-1/4x2 2.16 2.10 2.02 1.94
-112x1-112x2 2.16 2.16 2.02 2.00
2 x 2 x 2-1/2 260 260 2.39 3.67
fliwIi1 Irvn-n T1v R.ilii4na ('mIT1ino
Figure 35RC size T WF
II
I I A
1 x 1/2 1.69 0.40
1x3/4 1.69 0.38
1-114x314 2.06 0.53
2 x 1(not hex) 2.81 0.53
Th.41D TW%YI 2,- fladiig'i,ia ('1Tic
Figure 35X Size A I.1.. .!t
-A•-*--A-.
e
1 1.50 1.50 0.97
1-1/4 1.75 1.75 1.59
1-1/2 1.94 194 189
2 2.25 2.25 2.93
Figure 35 M
Size A _B Wgt
1-1/4x1 1.67 1.58 1.25
1-1/2x1 1.80 1.65 1.48
2x1 2.02 1.73 2.64
Mirglp lrnn Phioi
Figure 35SF Size T Wgt
• I A
1/2 0.94 0.10
1 1.25 0.28
1-1/4 1.37 0.50
1-1/2 1.441 0.70
2 150090
.4.U,. Tw.,., P.,.n TD iaiire SRT
Size A 1 0 C W
3M x 3/4 x 1/2 1.20 1.20 TT 0.46
I x 1/2 x I 1.50 1.36 1.50 010
1x314x3/4 1.38 1.31 1.45 0.68
I x 3M x 1 1.50 1.45 1.50 0.77
1 x I x 112 1.26 1.26 1.36 0.66
I x I x 3/4 1.38 1.38 1.45 0.73
1-1/4x1/2x1-1/4 1.75 1.53 1.75 1.04
1-1/4x 3/4 x1-1/4 1.75 1.62 1.75 1.09
1-1/4x 1 x1/2 1.341 1.26 1.53 1 0.81
-114x I x 3/4 1.451 1.38 1.63 0.90
-114x 1 x 1.581 1.50 1.69 1.03
-1/4xlx1-1/4 1.75 1.69 1.75 1.10
-114x1-1Mx1/2 1.34 1.34 1.53 0.87
1-1/4x1-1/4x3/4 1.45 1.45 1.62 0.96
1-1/4x1-114x1 1.58 1.581 1.67 1.10
i-1/2x1/2x1-114 IT i 1.7
1-1/2x 1/2 x 1-1/2 1.94 1.66 1.94 1.42
1-1/2x3/4x1-1/4 1.94 1.66 1.88 1.42
1-1/2x3/4x1-1/2 1.94 1.75 1.94 1.47
1-1/2x1x1/2 1.44 1.25 1.69 0.97
1-1/2x1x314 1.50 1.44 1.75 1.14
1-1/2xlx1 1.65 1.50 1.80 1.14
1-1/2x1 x1-1/4 1.821 1.67 1.88 1.47
1-1/2x1x1-1/2 1.94 1.80 1.94 1.52
1-1/2x1-1/4x1/2 1.41 1.34 1.66 1.03
1-1/2x1-1/4x3/4 1.52 1.45 1.75 1.10
1-1/2x1-1/4x1 1.65 1.58 1.80 1.31
1-1/2x1-1/4x1-1/4 1.82 1.75 1.88 1.52
1-1/2x1-1/4x1-1/2 1.94 1.88 1.94 1.50
1-1/2x1-1/2x1/2 1.41 1.41 1.66 1.14
1-1/2x1-1/2x3/4 1.52 1.52 1.75 1.23
1-1/2x 1-1/2x 1 1.65 1.65 1.80 1.38
1-1/2x1-1/2x1-1/4 1.5
x I x 2 2. 2 T! 2.18
x1-114x2 2.25 2.10 2.25 2.31
x 1-1/2 x 1/2 T T T5
2 x 1-1/2 x 3/4 '1.60 . TT TT
x -1/2x1 1.73 1.65 2.02 1.65
2x -1/2x1-1/4 1.90 1.82 2.10 2.03
x ,-1/2 x 1-1/2 2.02 ..94 2.16 2.37
x 1-1/2 x2 2.25 2.16 2.25 2.53
2x2x1/2 1.49 1.49 1.88 1.50
x2x3/4 1.60 1.60 1.97 1.67
x2x 1 1.73 1.73 2.02 1.91
x 2 x 1-1/4 1.90 1.90 2.10 2.05
x2x1-112 r2.02 2.02 2.16 2.11
SMITH - COOPER
<@> INTERNATIONAL <@>
Ductile Iron Threaded Fittings
®us
* ALL FITTINGS 100% A .3 TESTED *IE/&JSI B16 <<> * ISO 9001:2000 MANUFACTURER * ASTM A536 Grade 65,45,12
USTED * LISTED/APPROVED AT 500 PSI * ASME/ ANSI B 1.20.1 APPROVED
Y)vjrH1p Trim QflO Plhnw
Figure 35E :
_____________
A
_________
1/2 1.13 0.24
3/4 1.31 0.40
ITg5 0.64
1-1/41.750.95
-1/2 1.94 124
[2E-1/2
.25
].70
1.74
328
Ductile Iron Rediwine- 9fl0 Flhnw
Figure 35RE size A T WT
3/4x112 1.22 1.20 0.33
xl/2 1.36 1.26 0.44
x314 1.45 1.38 0.53
-1/4 x1/2 1.53 1.34 0.64
-1/4x314 1.631 1.45 075
-1/4x1 1.671 1.58 0.77
-1/2 x 112 1.75 1.1 0.90
-1/2x3/4 1.75 1.52 0.95
-1/2x1 Täö T T
-1/2x1-1/4 1.88 1.82 1.14
xl/2 1.97 1.60 1.35
x3/4 1.97 1.60 1.39
xl 2.02 1.73 1.58
xl-1/4 2.10 1.90 1.62
x 1-112 2.16 2.02 1.67
-1/2 x 1-1/2 1 2.51 2.16 2.32
2-1/2 x 2 1 2.60 2.39 3.01
ThwH1e Iron Brae Sp,fllninn
Figure 35U Size T Wgt
[L 111111 3/4
ti
1/2 TW 0.47
2.00 0.66
1
1-1/4
1-1/2 2.L ~j 2.03
3.151 2 -
1")iw441 Trnin Too
Figure 35T T -
._
I
1/2
F
T
t
1.50 0.85
4 1.75 1.30
1-1/2 1.941 1.63
1
2 T2512.631
2-1/2 2.7014.55
Thwflla Tmii rnitinturicr
Figure 35CP Size A .Y!
III
A III 1
1/2 1.38 0.18
3/4 .63 0.26
1 1.75 0.44
1-1/4 2 0.54
2.19 0.71 1
1-1/2
2 2.62 1.15
2-1/2 3.00 229
Ductile Iron ('an
Figure 35C Size A
4
A J[
Tl
1/2 0.87 0.15
3/4 0.97 0.22
1 1.16 0.33
1-1/4 1.28 0.54
1-1/2 1.33 0.68
2 1.45 0.96
2-1/2 1.70 1.80
Thwfile Trim ller Riihino
Figure 350B Size X WF
II JI
A
1x1/2 1.06 0.22
1x3/4 1.06 0.18
1-1/4 x 1 1.19 0.31
1-1/2x1 1.25 0.53
-1/2 x 1-1/4 125 0.35
2x1 Ti 0.75
2x1-1/4 1.38 0.69
2 x 1-1/2 1.38 0.62
Thii*ile Iron &c° Fllbnw
Figure 35F Size T W
-
4
/2 0.88 0.22
3/4 0.98 0.33
1.13 0.48
-1/4 1.29 0.73
1-1/2 1.44 0.931
2 1.69 1.55
2-1/2 I j.
Ductile Iron Beam Clamns
At
Figure 35SP -
Size A
3/8 0.75 0.31
1/2
Schedule;iiiiiiO'/Sch.edu1e.4O'
Fully Listed and FM Approved Sprinkler Pipe
When you specify Schedule-I0/Schedule-40 sprinkler pipe you get a UL listed and FM approved product. Although these
products do not require separate approvals Schedule-10/Schedule-40 gives you the extra quality assurance you demand.
Our Sch-10 (11/"- 8") pipe and Sch-40 (1'L 2") pipe have passed the same thorough lab testing as our other listed pipe
products, and receive periodic mill inspections from both UL and FM agents to ensure consistent quality.
Sch-40 Specifications
UPS Nominal I.D. 01. WI. (H20 Filled) PoW WVLIft (21') Wt1Uft (24') WUU (25')
In, mm In, mm 1.bs,fl Kghn Lbs.Ft; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1' 1.049 1.680 2.05 70 2,470 2,822 2,940
25 26.6 2.5 3.05 70 1,120 1,280. 1,334
1/i' 1.380 2.270 2.93 51 2,431 2,778 2,894
.32 35.1 4.36 4.36 51 1,103 1,260 1,313
1W 1.610 2.720 3.61 44 2,513 2,872 2,992
40 40.9 4.0 5.37 44 1,140 1,303 1,357
2" 2.067 3.650 5.13 30 2,300 2,628 2,738
50 52.5 5.4 7.63 30 1,043 1,192 1,242
216" 2.469 5.790 7.86 19 2,310 2,640 2,750
65 62.7 8.6 11.73 19 11048 1,197 1,247
Sch-10 Specifications
UPs Nominal I.D. WI WI. (H20 Filled) Pea/ WVLIII (21') WVIift (24') WIIUH (25')
In; mm In, mm Lhsft,Kghn Lbsft,Kg4n Lift Lbs;Kg Lbs;Kg Lbs;Kg
1.097 1.400 1.81 91 2,675 3,053 3,185
25 27.9 2.1 2.70 91 1,213 1,385 1,445 U. 1:442 1:810 ................61 2,319 2,664.........2;760
32 36.6 2.7 3.75 61 1,052 1,208 1,252
1W 1.682 2.080 3.04 61 2,664 3,045 . 3,172
40 42.7 . 3.1 4.52 61 1,208 1,381 1,439
2.157 2.640 4.22 37 2,051 2,344 2,442-
50 54.8 3.9 6.28 37 930 1,063 1,108
2W . 2.635 3.530 5.89 . 30 2,224 2,542 2,648
65 66.9 5.3 8.77 30 1,009 1,153 1,201
3.260 4.330 7.94 19 1,728 1,975 2,057
80 82.8 6.4 11.82 19 784 896 .933
4.260 5.610 11.78 19 2,238 2,558 2,665
90 108.2 8.3. 17.53 . 19 1,015 1,160 1,209
5 5.295 7.77 17.33 10 1,632 1,865 1,943
125 134.5 11.56 25.80 10 740 846 881
6' . 6.357 . 9.290 23.03 10 1,951 2.230 2,322
150 161.5 13.8 34.27 10 885 1,012 1,053
8' 8.249 16.490 40.15 7 2,424 2,770 2,885
200 . 209.5 24.5 59.75 . 7 1,100 1,256 1,309
Schedule-10/Schedule40 product can be
"hot-dip" galvanized to meet FM
requirements for dry systems in
accordance with the zinc coating
specifications of ASTM A-123.
Superior Coating
Our advanced formula mill coating of-
f'ers a clean, durable surface. It is also
paint-ready for custom color applications
without special preparation.
The internal surface of all black Allied
Tube & Conduit Fire Sprinkler pipe
products up to 4.5000" in diameter is
coated with our new Antibacterial For-
mula, 'ABF". In scientific laboratory
test, ABS proved to have superior resis-
tance to microbial colonization of pipe
walls,thereby delaying or possibly pre-
venting the onset of Microbiologically
Influenced corrosion (NEC) when the
First Sprinkler System is first installed.
American ITMade
Meets 'Buy American" requirement
and is available through distributors in
the USA, Canada and Mexico.
Schedule-10/Schedule-0 pipe are in
compliance with the following:
ASTMA-135,andNFPA 13. Both pipe
products have a working pressure rating
of 300 psi maximum and also meet the
stringent requirement for the following
tests:
Welded Outlets . . . () <€i> (.j) Hydrostatic Pressure
Side Wall .
. Listed Approved Listed
Vibration Test
tqco/aow Control () ciffiecJ 16100 S. Lathrop Harvey, IL 60426
11350 Norcom Rd.' Philadelphia, PA 19154
Customer Service:
(800) 882-5543
TUBE S CONDUIT . 2525 N. 27th Ave. ' Phoenix, AZ 85009 Fax 708-339-1806
S5-3
TOTC 10
Moon POflATeD
CORONA. CA • (909) 737.5599 15
FIG. 2 ADJUSTABLE RING HANGER
FIG. 2 NFPA ADJUSTABLE RING HANGER WITH REDUCED ROD SIZE
Size Range - 1/2 thru 6 inch pipe.
Material - Carbon Steel, Mu. Galvanized to C-gO
specification.
Function - For general piping purposes. Knurled
swivel nut design permits hanger adjustment after
installation. Spring tension on swivel nut holds it
securely in hanger before installation. Swivel nut
easily removed.
Approvals - Underwriter& Laboratories listed and
Factory Mutual Engineering approved. Conforms
to Federal Specification WW-H-171E, type 10, and
Manufacturers Standardization Society SP-69,
lype 10.
Maximum Temperature - 650°F
Finish - Mil. Galvanized and Stainless Steel.
Order By. - Figure number and pipe size.
f:?i
PIPE ROD STOCK MAX. APPROX. WEIGHT PER 100 REC. FIG. 2 SIZE SIZE A B C SIZE LOAD LSS. FIG. 2 NFPA
1/2 3/8 3-1/8 2-5/8 1-3/8 169ax1 400 17 17 /L01 1 3/8 3-3/8 2-5/8 11/8 16gax1 400 18 18
£114 $J/.4 L7/ .400
1-1/2 3/8 3-7/8 2.7/8 1 16gax1 400 21 21
- 2 J/4 400
2-1/2 1/2* 5-3/4 4-1/4 1.5/8 149ax1.3/16 600 41 40
a 4/iL _A i/& . iJ4LL'3 / ]. 6 600
3-1/2 1/2* 7-3/8 5-1/4 2-1/8 14gax1-3/16 600 52 50 L L .i000
5 5/8 9 6-1/8 2-1/4 129ax1J/4 1250 97 95
12g/ 1250 kic' 3I& nut Is used when NFPA rod sizing is requested.
"1/2" nut is used when NFPA rod sizing is requested,
Size Range - 1/4. thru 1-1/2 inch rod in 10,-0"
lengths.
Material - Carbon Steel
Maximum Temperature- 750°F
Finish - Plain, Electro-Galvanized, and Stainless
Steel.
Order By - Figure number, rod diameter, and
finish.
MAX. REC. LOAD LBS. APPROX.
ROD FOR SERVICE TEMPS WEIGHT
SIZE 650F 750F PER 100 FT.
1/4 240 215 12
1/2 1130- 1010 .53
Fhj
3/4 2710 2420 123
4960 4420 222
"I N1111 o
1-1/2 11630 10370 510
100
INCORPORATED
CORONA. CA • (909) 737-5599 53
FIG. 99
ALL THREAD ROD CUT TO LENGTH
Size Range - 3/8 thru 7/8 inch rod in 1 inch
increments.
Material - Carbon Steel
Maximum Temperature- 750°F
Finish - Plain, Electro-Galvanized, and Stainless
Steel.
Order By - Figure number, rod diameter, rod
length, and finish.
MAX. REC. LOAD LBS.
ROD FOR SERVICE TEMPS. SIZE 6507 750F
3/8 610 540
1/2 1130 1010
5/8 1810 1610
3/4 2710 2420
7/8 3770 3360
FIG. 100
ALL THREAD ROD FULL LENGTHS
SAMMYS® FOR WOOD
us I,. 1k,,.
No pre-drilling required.
Quick to install using the Sammy
Nut Dnver with an 18V cordless
drill/driver.
Saves time from traditional
methods.
Reduces installation costs.
Made in the U.S.A.
"
fwbulldex.)
i
#14 Black
Nut Driver
Part # 8113910
1"
#14 SW Red
Nut Driver
F'art#8114910
1/4" 8002957 GST 100 1/4 xl" 210 7/16"OSB)
1/4 8003957'GST-20 0 114x2 1760 (Fit)
1/4" 8004957 GST 300 1/4 x 3' 2060 (Fir)
3/8 8007957 (38110 114x V. 210 (7/18'OSB)
670
3/8' 8008957 GST 20 1/4 x 2' 1760 (Fir)
3/8' 8068925 GST2O.SS 1/4x2 1.760 (Fe)
3/8" 8009925 (38125.380 3/8x2-1/2' 2113 (Fir)
3/8 8010957 GST30 1140' 2060 (Fir)
3/8' 8069925 GST 3D-SS 1/4x3" 2060 (Fir)
W. 8011925 GST40 114x4 2180 (Fir)
112" 8013925 GST2 1/4x2 1760 (Fir)
1/2 8014925 GST 25380 3!8x2 1/2' 2113 (Fir)
1/2" 8015925 GST3 1/4x3' 2275 (Fir)
25 125
2g... 125
25 125
'300 14
850 1475 25 125
850 .. .: 12
1500 25 125
1500. .1475, 25.• .125.
25 125
25 125
25 125
• .• 25.E
25 125
ITII :'7
(LH MADE IN U.S.A
SECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each tine. When the face of the driver comes into
co-tact with the malarial you are installing into, continue drilling until nut driver spins tree. Installation is then complete. Warranty requires the use of the appropriate nut driver for Installations.
TO( ?R 1011~
I IICO R P0 RAVED
1.20 CORONA. CA- (909) 737-5599
FIG. 1000
"FAST CLAMP" SWAY BRACE ATTACHMENT
Size Range. - Pipe size to be braced: 1" through 8"
Sch. 10 and 40. Pipe size used for bracing: I" and
1-1/4" Sch. 40 IPS.
Material - Carbon Steel
Function - For bracing pipe against sway and
seismic disturbance. The pipe attachment com-
ponent of a sway brace system: Fig. 1000 is used
in conjunction with a Tolco 900 Series Fitting and
joined together with bracing pipe p?r NFPA p13*,
forming a complete sway brace assembly.
Features - Can be used to brace Schedules 10 and
40 IPS.
Field adjustable, making critical pre-engineering of
bracing pipe unnecessary.
Unique design requires no threading of bracing
pipe.
Can be used as 4-way riser brace.
Can be used as longitudinal brace.
All steel construction eliminates structural
deficiencies associated with casting type sway
brace fittings.
Comes individually packaged with illustrated
installation instructions - sizes are clearly marked.
Steel leaf spring insert provided, to assure installer
and inspector that necessary minimum torque
(5 lb/it) has been achieved.
Application Note - Fast Clamp reed not be field
assembled. Position Fast Clamp and tighten two
hex nuts until leaf spring flattens.
*Length of bracing pipe per National Fire
Protection Association, Pamphlet fl13, paragraph
A-3-10.3.5: 1" Schedule 40 hracig pipe maximum
7-2". 1.1/4" Schedule 40 bracing pipe maximum
9-2".
Approvals - Underwriters' Laboratories listed.
Note - Must be used with Tolco U.L. Listed 900
Series attachment.
Finish - Plain, Electro-Galvanized, HOG, and.
Fig. 980 - Universal Swivel Sway Brace Attachment
Size Range - One size fits bracing pipe 1 thru 2", TOLCO 12 gauge channel, and all structural
steel up to 114" thick.
Material - Carbon Steel
Function - Multi-functional attachment to structure or
braced pipe fitting.
Features -This product's design incorporates a concentric
attachment opening which is critical to the performance of
structural seismic connections. NFPA 13 (2002) Figure
9.3.5.91 indicates clearly that fastener table load values are
based only on concentric loading. Mounts to any surface
angle. Break off bolt head assures verification of proper installation.
CUS LISTED
Component of State of
California OSHPD Approved
Seismic Restraints System
Installation -The Fig.980 is the structural or transitional
attachment component of a longitudinal or lateral sway brace
assembly. It is intended to be combined with the "bracing
pipe" and TOLCO "braced pipe" attachment, Fig. 1000, 1001,
2002, 4L, 4A or 48 to form a complete bracing assembly.
NFPA 13 and/or OSHPD guidelines should be followed.
To Install - Place the Fig. 980 onto the "bracing pipe". Tighten the set bolt until set bolt head breaks off. Attachment
can pivot for adjustment to proper brace angle.
Approvals - Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). Included in our Seismic Restraints Catalog approved by the State of California Office
of Statewide Health Planning and Development (OSHPD. For additional load, spacing and placement information
relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines.
Note - The Fig. 980 Swivel Attachment and the Fig. 1001, Fig. 1000, Fig. 2001 or Fig. 4A Pipe Clamp make up a
sway brace system of UL Listed attachments and bracing materials which satisfies the requirements of Underwriters'
Laboratories and the National Fire Protection Association (NFPA)
Finish - Plain
Note Available in Electro-Galvanized finish.
Order By - Figure number and finish.
PATENT #6,273,372
-
Dimensions 'Weights
Max. Design Approx. /.•. 4i A B f ri Load Lbs. Wt1100
51/4 17/% 17/32 2765 132
* Available with hole sizes to accommodate up to C14' fastener. Consul factory.
Lateral Brace
TOLC07M brand bracing components are desgined to be compatible ONLY with other TOLCO"" brand bracing components, resulting in a Listed seismic bracing assembly. DISCLAIMER - NIBCO does NOT warrant against the failure of TOLCO"' brand bracing components, in the instance that such TOLCO'" brand bracing components are used in combination with products, parts or systems which are not manufactured o
r
s
o
l
d
u
n
d
e
r
the TOLCO"" brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit, where non-TOLCO brand bracing components have been, or are used.
OFRCE/MANUFACTURING FACILITY. 1375 SAMPSON AVE. • COROitA, CA 92179. Pit: 951.737.5599" FAX: 951.737.0331) CUSTOMER SERVICE. 500.716.5266 www.tolco.com
•••.
.:.. . .
cipë F o'/-D)~na F .`o v®
I gh Strength Steel Pipe-,
The original high-strength Iightwali sprinkler p
i
p
e
w
i
t
h
h
y
d
r
a
u
l
i
c
s
s
u
p
e
r
i
o
r
t
o
S
c
h
e
d
u
I
e
-
.10.
) ollIecJ
lUBE & CONDUIT
(IUUffi
IT-7, 73.177.171MIMI.ri
Product Nominal Wt/Ft Wt/Ft PCs/ WI/Lift Wt/Lift Wt/Lift
NPS I.D. H20 Filled Lift 21' 24' 25'
X 1" 1.191 0.830 1.31 91 1586 1812 1888
*25 30.3 1.2 1.95 91 719 822 856
1 1/4° 1.536 1.059 1,87 Si 1356 1550 1615
*32 39.0 1.6 2.78 61 615 703 733
x 11/9" 1.728 1.667 2.71 61 2135 2440 2542
*40 43.9 2.5 4.03 61 968 1107 1153
x2° 2.20.3 2.104 3.79 - 37 1634 1868 1946
*50 56.0 3.1 5.64 37 741 847 883
2 1/2° 2.703 2.564 5.10 30 1615 1846 1923
*65 68.7 3.8 7.59 30 733 837 872
x3" 3.314 3.387 7.18 19 1351 1544 1608
*0 84.2 5.0 10.69 19 613 700 729
x 4" 4.310 4.473 10.86 19 1784 2039 2124
*90 109.5 6.7 16.16 19 809 925 963
X.6" 6,403 7.714 21.70 10 1620 1851 192
*150 162.6 11.5 32.29 t0 735 840 875
SuperFlo/Dyna-Fiow pipe is
manufactured to meet- ASTM A-
795. Type E, Grade A and is in
compliance with NFPA-13 and
NFPA-14. All sizes of Dyna
Flow/Super Flo are UL Listed,
FM Approved and ULC Listed.
(@ 0 CS
Listed Approved Listed
Super Flo/Dyna-Flow is UL/ULC
Listed for use with roll grooved,
:P couplings, and welded.
joints, for wet, dry, preaccion and
deluge systems. Ic is FM Approved
for roll grooved, plain-end, and
welded joints for wet systems.
Refer to appropriate documentation
for up-to-date listing and approval
information. SuperFlo/Dyna-Plow
is now available "hot-dip"gal.vanized
and has been specifically approved
by FM for dry systems uses.
Super Flo/Dyna-Fiow pipe is the "original
high-strength Iightwall sprinkler pipe.
Super Flo/Dyna-Flow has outstanding
hydraulic capabilities and is recognized
as the most popular alternative to
Schedule-10 pipe. Lightweight, easy to
cut and easy to handle for installation.
Super Flo/Dyna-Flow is a valuable
addition to any fire protection system.
VA Superior Hydraulics
With an inside diameter of up to 11%
larger than Schedule-40 and up to 7%
larger than Schedule-10, SuperFlo/
Dyna-How pipe hydraulics are exceptional.
get I.D.s enable Super Flo/Dyna-Flow,
d related components, to be down-
sized within the system, thus increasing
the potential for job cost savings. For
complete Hazen-Williams charts, refer to
Super Fio/Dyna-Flow Hydraulic Data
Tables."
Coatings &Fabrication
Super Flo/Dyna-Flow products are coated
with an environmentally approved and
specially formulated modified-acrylic or
wateibased coating. This durable coating
is palatable. The black coating acts as
an exceUent primer and is resistant to
weathering and U.V. degradation from
outdoor storage.
Metallurgical properties provide excellent
'fabrication characteristics for end prep
finishes, welding and roll grooving. No
-sciai process or equipment are needed
fabrication and 'ints]iaiioii.
T
Lightweight and easy to install, .
resulting in inor, e.ftient use of
your freight and labor. dollars.
Provides stability needed to
comply with standard hanger
spacing (15 ft O.C.) per NFPA.
Available in Standard lengths
for your convenience, or can be
ordered in custom lengths
upon approval.
Fast cutting and .weid.ing,.as well
as easy roll grooving and end
preparation.
Available in Factory roll grooved
form for quicker shop turnaround.
Clean, durable mill coating
provides longer "shelf life" 'and,
acts as art c.xccllent primer for
custom paint applications.
16100 S. Lathrop 11350 Norcom Rd. 2525 N. 271h Ave. Customer Service:
Harvey, It 60426 Philadelphia, PA 19154 Phoenix. AZ 85009 1-800-797-6210
Fax 70.R-339-1806