HomeMy WebLinkAbout421 TAMARACK AVE; ; AS110046; Permit6/20/24, 8:51 AM AS110046 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address: 421 TAMARACK AV
Permit Type: SPRINK
Parcel No: 2060420200
Lot #: 0
Reference No.:
Permit No: AS110046
Status: ISSUED
Applied 3/23/2011
Approved: 3/23/2011
Issued: 3/23/2011
PC #: Inspector:
Project Title: URBINO RESIDENCE RESIDENTIAL FIRE SPRINKLER SYSTEM
Applicant:
MILLENNIUM FIRE PROTECTION
SUITE.F
101 COPPERWOOD WY
OCEANSIDE, CA
760-722-2722
Owner:
ALDERSON REVOCABLE TRUST 05-29-02
1122 COUNTRYW000 LN
VISTA CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
260 0 260 0
about:blank 1/1
MILLENNIUM FIRE PROTECTION CORP.
Urbino Residence
Overhead Fire Sprinkler
Material Submittal
MILLENNIUM FIRE PROTECTION C
101 COPPERW000 WAY, SUITE H
OCEANSIDE, CA 92058
760-722-2722
Job Name : Urbino Residence
Drawing : FP-1
Location : 421 Tamarack Ave.
Remote Area : I
Contract : 11-006
Data File :11-006 UrbinoResid.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
MILLENNIUM FIRE PROTECTION CRP Page 1
Urbino Residence Date 03/16/11
HYDRAULIC CALCULATIONS
for
Project name: Urbino Residence.
Location: 421 Tamarack Ave.
Drawing no: FP-1
Date: 3/16/11
Design
Remote area number: 1
Remote area location: Master Bed Room
Occupancy classification: NFPA 13D
Density: .05 - Gpm/SqFt
Area of application: 375 - SqFt
Coverage per sprinkler: 400 - SqFt
Type of sprinklers calculated: 4.9K SSP Concealer
No. of sprinklers calculated: 2
In-rack demand: n/a - GPM
Hose streams: 5- GPM
Total water required (including hose streams): 63.4 - GPM @ 40.3 - Psi
Type of system: Tree
Volume of dry orpreaction system: n/a - Gal
Water supply information
Date: 3/15/11
Location: Hydrant at address
Source: Gauge Hydrant
Name of contractor: MILLENNIUM FIRE PROTECTION CRP
Address: 101 COPPERWOOD WAY, SUITE H, OCEANSIDE, CA 92058
Phone number: 760-722-2722
Name of designer: J. Van Kolken
Authority having jurisdiction: Carlsbad Fire Prevention
Notes: (Include peaking information or gridded systems here.)
MOST DEMANDING PRESSURE WAS CALCULATED IN THIS REPORT
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve (C)
MILLENNIUM FIRE PROTECTION CRP Page 2
Urbino Residence Date 03/16/11
City Water Supply: Demand: Cl - Static Pressure : 79.2 Dl - Elevation : 10.936
C2 - Residual Pressure: 59.2 D2 - System Flow : 40.303 C2 - Residual Flow : 100 D2 - System Pressure : 63.424
Hose (Demand) : 5 D3 - System Demand : 45.303
Safety Margin : 11.154
150
140
130
p120
R110
E10°
90 --
Cl 80
U70 02
R6°
E5° ____ V D3
-- ___ ____ ______
40
30 ,-
20 .7Z
10 DT
..... .. _____
10 20 30 40 50 60 70 80 90
FLOW (N 1.85)
C2
Computer Programs by Hydratec inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
MILLENNIUM FIRE PROTECTION CRP Page 3
Urbino Residence Date 03/16/11
Fitting Legend
Abbrev. Name Y2 % 1 1% 1% 2 --2Y2 3 3Y2 4 5 6 -8 10 12 14 16 18 20 24
Blvt Ball Vic 728 Thrd 0 0 0.5 1 1.7 0.5 0 0 0 0 0 0 0 0 0 0 0 0 0 0
E NFPAI39O'StandardElbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
F NFPA 13 45'Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
S NFPA13Swing Check Valve 4 5 5 7 9 11 14 16 19 22 27 32 45 55 65 76 87 98 109 130
T NFPAI39O' Flow thruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *• The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
MILLENNIUM FIRE PROTECTION CRP Page 4
Urbino Residence Date 03/16/11
Node
No
Elevation K-Fact
___________-____
Pt
Actual
Pn Flow Density
Actual
Area Press
Req.
01 21.25 4.9 16.7 na 20.02 0.05 400 16.7
03 21.25 4.9 17.13 na 20.28 0.05 400 16.7
02 21.75 18.08 na
04 21.75 18.54 na
05 21.75 27.24 na
TR 20.0 28.98 na
BR 1.0 38.68 na
UG -4.0 41.28 na
MTR -4.0 50.33 na
SRC -4.0 63.42 na 5.0
The maximum velocity is 13.58 and it occurs in the pipe between nodes MTR and SRC
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-williams - 2007
MILLENNIUM FIRE PROTECTION CRP Page 5
Urbino Residence Date 03/16111
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe Notes ******
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
01 21.250 4.90 20.02 1 iT 9.563 10.000 150 16.700
to 1E 3.825 13.387 -0.217
02 21.750 20.02 1.101 0.0 23.387 0.0682 1.595 Vel = 6.75
0.0
02 20.02 18.078 K Factor = 4.71
03 21.250 4.90 20.28 1 IT 9.563 10.000 150 17.127
to 1 3.825 13.387 -0.217
04 21.750 20.28 1.101 0.0 23.387 0.0698 1.633 Vel = 6.83
0.0
04 20.28 18.543 K Factor = 4.71
02 21.750
to
04 21.750
04 21.750
to
05 21.750
05 21.750
to
TR 20
TR 20
to
BR I
BR 1
to
UG -4
UG -4
to
MTR -4
MTR -4
to
SRC -4
SRC
20.02 1.25 2E 9.523 12.000 150 18.078
0.0 9.523 0.0
20.02 1.394 0.0 21.523 0.0216 0.465 VeI= 4.21
20.28 1.25 IT 9.523 81.750 150 18.543
4E 19.046 28.570 0.0
40.3 1.394 0.0 110.320 0.0788 8.697 Vel = 8.47
0.0 1.5 2E 11.656 12.500 150 27.240
0.0 11.656 0.758
40.3 1.598 0.0 24.156 0.0405 0.979 Vel = 6.45
0.0 1.5 lBlvt 2.477 20.750 150 28.977
Is 13.113 15.590 8.229
40.3 1.598 0.0 36.340 0.0405 1.473 Vel = 6.45
0.0 1.5 1 5.828 5.000 150 38.679
0.0 5.828 2.166
40.3 1.598 0.0 10.828 0.0405 0.438 Vel = 6.45
0.0 1.5 3E 17.484200.000 150 41.283
2F 5.828 23.312 0.0
40.3 1.598 0.0 223.312 0.0405 9.052 Vel = 6.45
0.0 1 IBM 0.956 22.000 150 50.335
1 9.563 10.519 5.000 * Fixed loss = 5
40.3 1.101 0.0 32.519 0.2487 8.089 Vel = 13.58
5.00 Qa= 5.00
45.30 63.424 K Factor= 5.69
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
tqCo Fire Suppression
& Building Products
Technical Services 800-381-93121 +1-401-781-8220
www.tyco-fire.com
,a
rapid response
HOME FIRE SPRINKLER SYSTEM
Series LFII Residential Sprinklers
49 K-Factor Domed-Plate Concealed Pendent
Wet Pipe and Dry Pipe Systems
General
Description
The TYCO RAPID RESPONSE
Series LFII Residential Domed-Plate
Concealed Pendent 4.9 K-Factor
Sprinklers (TY2234) are decorative, fast
response, frangible bulb sprinklers de-
signed for use in residential occupan-
cies such as homes, apartments, dor-
mitories, and hotels.
The Cover Plate/Retainer Assembly
conceals the sprinkler operating
components above the ceiling. The
domed profile of the cover plate pro-
vides aesthetically appealing sprin-
kler design with lower flow rates than
can be achieved by lower profile cover
plates. The separable two-piece de-
sign of the Cover Plate and Support
Cup Assemblies allows installation of
the sprinklers and pressure testing of
the fire protection system prior to the
installation of the ceiling or application
of a finish coating.
Also, the separable "push-on and
thread-off" two-piece design of the
Sprinkler provides for 1/2 inch (12,7
mm) of vertical adjustment.
The Series LFll Residential Sprinklers
(1Y2234) are intended for use in the fol-
lowing scenarios:
wet and dry pipe residential sprinkler
systems for one- and two-family
dwellings and mobile homes per
NFPA 13D
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and
installation of sprinkler systems and
components. Improper handling and
installation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fall to
operate in a fire situation or cause it
to operate prematurely.
Page 1 of 6
wet and dry pipe residential sprinkler
systems for residential occupancies
up to and including four stories in
height per NFPA 13R
wet and dry pipe sprinkler systems
for the residential portions of any oc-
cupancy per NFPA 13
Historically residential sprinklers,
based on their Listing, have been
limited to wet pipe sprinkler systems
to assure speed of water delivery for
a given prescribed design area (num-
ber of design sprinklers). The Series
LFII Residential Domed-Plate Con-
cealed Pendent Sprinklers (TY2234)
Listing now offers the laboratory ap-
proved option of designing dry pipe
residential sprinkler systems.
Through extensive testing, it has been
determined that the number of design
sprinklers (hydraulic design area) for the
Series LFII Residential Domed-Plate
Concealed Pendent Sprinklers need
not be increased over the number of
design sprinklers (hydraulic design
area) as specified for wet pipe sprin-
kler systems, as is customary for den-
sity/area sprinkler systems designed
per NFPA 13.
Consequently, the Series LFII
Residential Domed-Plate Concealed
Pendent Sprinklers offer the features of
non-water filled pipe in addition to not
having to increase the number of de-
sign sprinklers (hydraulic design area)
for systems designed to NFPA 13,13D,
or 13R. Non-water filled pipe will permit
options for areas sensitive to freezing.
These Residential Sprinklers have a
4.9 (70,6) K-Factor that provides the
required residential flow rates at re-
duced pressures, enabling smaller pipe
sizes and water supply requirements.
The Series LFII Residential Domed-
Plate Concealed Pendent Sprinklers
(TY2234) have been designed with
heat sensitivity and water distribu-
tion characteristics proven to help in
the control of residential fires and to
improve the chance for occupants to
escape or be evacuated.
SEPTEMBER 2010
The Series LFII Residential Domed-
Plate Concealed Pendent Sprinklers
(TY2234) are shipped with a Dispos-
able Protective Cap. The Protective
Cap is temporarily removed for instal-
lation, and it must be replaced to pro-
tect the sprinkler while the ceiling is
being installed or finished. The tip of the
Protective Cap can also be used to
mark the center of the ceiling hole into
plaster board or ceiling tiles by gently
pushing the ceiling product against the
Protective Cap. When ceiling install-
ation is complete, the Protective Cap
must be removed and the Cover Plate
Assembly installed. The Protective Cap
must be removed to ensure proper
performance of the sprinklers.
NOTICE
The Series LFII Residential Domed-
Plate Concealed Pendent Sprinklers
(TY2234) described herein must be
installed and maintained in compli-
ance with this document and the ap-
plicable standards of the National
Fire Protection Association, in addition
to the standards of any authorities hav-
ing jurisdiction. Failure to do so may im-
pair the performance of these devices.
Owners are responsible for maintaining
their fire protection system and devices
in proper operating condition. The in-
stalling contractor or sprinkler manu-
facturer should be contacted with any
questions.
TFP45O
TFP45O
Page 2 of 6
WET PIPE SYSTEM
Minimum Flow and Residual Pressure
For Horizontal Ceiling For Sloped Ceiling For Sloped Ceiling
Maximum
Coverage Maximum
Spacing Areat°1 Ft. (Maximum 2-Inch Rise (Greater than 2-Inch Rise up (Greater than 4-Inch Rise up
Ft. x Ft. (m) for 12-Inch Run) to Maximum 4-Inch Rise to Maximum 8-Inch Rise
(m x m) for 12-Inch Run) for 12-Inch Run)
155°F (68°C) 155°F (68°C) 155°F (68°C)
12 x 12 12 13 GPM (49,2 LPM) 13 GPM (49,2 LPM) 19 GPM (71,9 LPM) (3,7 x 3,7) (3,7) 7.0 psi (0,48 bar) 7.0 psi (0,48 bar) 15.0 psi (1,03 bar)
14 x 14 14 13 GPM (49,2 LPM) 13 GPM (49,2 LPM) 19 GPM (71,9 LPM)
(4,3 x 4,3) (4,3) 7.0 psi (0,48 bar) 7.0 psi (0,48 bar) 15.0 psi (1,03 bar)
16 x 16 16 13 GPM (49,2 LPM) 13 GPM (49,2 LPM) 19 GPM (71,9 LPM) (4,9 x 4,9) (4,9) 7.0 psi (0,48 bar) 7.0 psi (0,48 bar) 15.0 psi (1,03 bar)
18 x 18 18 17 GPM (64,3 LPM) 17 GPM (64,3 LPM) 19 GPM (71,9 LPM)
(5,5 x 5,5) (5,5) 12.0 psi (0,83 bar) 12.0 psi (0,83 bar) 15.0 psi (1,03 bar)
20 x 20 20 20 GPM (75,7 LPM) 21 GPM (79,5 LPM) 24 GPM (90,8 LPM) (6,1 x 6,1) (6,1) 16.7 psi (1,15 bar) 18.4 psi (1,27 bar) 24.0 psi (1,65 bar)
For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest
coverage area for which hydraulic design criteria are stated.
The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual
pressures are calculated using the nominal K-Factor. Refer to Hydraulic Design under the Design Criteria Section.
TABLE A
SERIES LFII RESIDENTIAL DOMED-PLATE CONCEALED PENDENT SPRINKLERS (TY2234)
NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA
WET PIPE SYSTEMS
DRY PIPE SYSTEM
Minimum Flow N and Residual Pressure
Maximum Maximum
Coverage Area °1 Spacing For Horizontal Ceiling
Ft. x Ft. Ft. (Maximum 2-Inch Rise for 12-Inch Run)
(mxm) (m)
155°F (71°C)
12 x 12 12 13 GPM (49,2 LPM)
(3,7 x 3,7) (3,7) 7.0 psi (0,48 bar)
14 x 14 14 14 GPM (53,0 LPM) (4,3 x 4,3) (4,3) 8.2 psi (0,57 bar)
16x16 16 15 GPM (56,BLPM)
(4,9 x 4,9) (4,9) 9.4 psi (0,65 bar)
18 x 18 18 20 GPM (75,7 LPM)
(5,5 x 5,5) (5,5)
-
16.7 psi (1,15 bar)
20 x 20 20 22 GPM (83,3 LPM) (6,1 x 6,1) (6,1) 20.2 psi (1,39 bar)
For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest
coverage area for which hydraulic design criteria are stated.
The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual
pressures are calculated using the nominal K-Factor. Refer to Hydraulic Design under the Design Criteria section.
TABLE B
SERIES LFII RESIDENTIAL DOMED-PLATE CONCEALED SPRINKLERS (TY2234)
NFPA 13D HYDRAULIC DESIGN CRITERIA
DRY PIPE SYSTEMS
TFP45O
Page 3 of 6
Model/Sprinkler
Identification
Number (SIN)
TY2234
Technical
Data
Approvals
UL Listed for use with wet pipe and
dry pipe systems
C-UL Listed for use only with
wet pipe systems
NYC Approved under MEA 44-03-E
The Series LFII Residential Domed-
Plate Concealed Pendent Sprinklers
are only listed with the Series LFII
Residential Domed-Plate Concealed
Pendent Cover Plates having a factory
applied finish.
For details on these approvals, refer to
the Design Criteria section.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=4.9 GPM/psil/2 (70,6 LPM/barl/2)
Temperature Rating
155°F (68°C) Sprinkler with
139°F (59°C) Cover Plate
Vertical Adjustment
1/2 inch (12,7 mm)
Finishes
Refer to Ordering Procedure section.
Physical Characteristics
Frame ....................Brass
Button...................Bronze
Sealing Assembly.........Beryllium
Nickel w/ Teflon*
Bulb (3 mm) ................Glass
Compression Screw.........Brass
Deflector.................Copper
Button
Ejection Spring......Stainless Steel
Support Cup................Steel
Cover Plate................Brass
Retainer ..................Brass
Cover Plate
Ejection Spring......Stainless Steel
"Registered trademark of Dupont
Operation
When exposed to heat from a fire, the
Cover Plate, which is normally soldered
to the Support Cup at three points, falls
away to expose the Sprinkler Assembly.
The glass bulb contains a fluid that ex-
pands when exposed to heat. When the
rated temperature is reached, the fluid
expands sufficiently to shatter the glass
bulb allowing the sprinkler to activate
and flow water.
Design
Criteria
The RAPID RESPONSE Series LFII
Residential Domed-Plate Concealed
Pendent 4.9 K-Factor Sprinklers
(TY2234) are UL and C-UL Listed for
installation in accordance with the fol-
lowing criteria.
Note: When conditions exist that are
outside the scope of the provided cri-
teria, refer to the Residential Sprinkler
Design Guide TFP490 for the manu-
facturer's recommendations that may
be acceptable to the authority having
jurisdiction.
System Types
Per the UL Listing, wet pipe and dry
pipe systems may be utilized. Per the
C-UL Listing, only wet pipe systems
may be utilized.
For dry systems, corrosion-resistant or
internally galvanized pipe shall be uti-
lized with the sprinklers described in
this data sheet.
For dry systems not using CPVC, pen-
dent sprinklers shall be installed on re-
turn bends, where the sprinklers, return
bends, and branch line piping (that is,
potential areas for trapped water) are in
areas at or above 40°F (40C).
Refer to technical data sheet TFP485
about the use of Residential Sprinklers
in residential dry pipe systems.
When corrosion-resistant or internally
galvanized pipe and fittings with a po-
table water supply is utilized, return
bends need not be installed. However,
any portion of the piping that has the
potential to trap water must be main-
tained at or above 40°F (4°C) unless
provision to drain such areas is provid-
ed and maintained dry.
Water Delivery
When using the Series LFII Residential
Pendent Sprinklers (TY2234) in dry
pipe sprinkler systems, the require-
ments for "Dry System Water Delivery"
per Section 8.3.4.3 of the 2010 edition
of NFPA 130 apply. For a residential
hazard, in no case shall the time of wa-
ter delivery exceed 15 seconds for the
most remote operating sprinkler.
Hydraulic Design
(NFPA 13D and 13R)
The minimum required sprinkler flow
rate for systems designed to NFPA 130
or NFPA 13R are given in Tables A and
B as a function of temperature rating
and the maximum allowable coverage
areas. The sprinkler flow rate is the min-
imum required discharge from each of
the total number of "design sprinklers"
as specified in NFPA 13D or NFPA 13R.
NOTICE
The number of "design sprinklers"
specified in NFPA 13D and 13R for wet
pipe systems is to be applied when de-
signing dry pipe systems. There is no
need to increase the design area, as is
the case for density/area systems, in
accordance with U.S. Patent 7,712,543.
Hydraulic Design
(NFPA 13)
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is to be the greater of the following:
The flow rates given in Tables A and
B for NFPA 130 and 13R as a func-
tion of temperature rating and the
maximum allowable coverage area.
A minimum discharge of 0.1 GPM/
sq. ft. over the "design area" com-
prised of the four most hydraulically
demanding sprinklers for the actual
coverage areas being protected by
the four sprinklers.
The number of "design sprinklers"
specified in NFPA 13D and 13R for wet
pipe systems is to be applied when de-
signing dry pipe systems. There is no
need to increase the design area, as is
the case for density/area systems, in
accordance with U.S. Patent 7,712,543.
The Series LFII Residential Domed-Plate
Concealed Pendent Sprinklers must
not be used in applications where the
air pressure above the ceiling is greater
than that below. Down drafts through
the Support Cup could delay sprinkler
operation in a fire situation.
Obstruction To Water Distribution
Sprinklers are to be located in ac-
cordance with the obstruction rules
defined by NFPA 13 for residential
sprinklers.
Operational Sensitivity
The sprinklers are to be installed rela-
tive to the ceiling mounting surface as
shown in Figure 2.
TFP45O
Page 4 of 6
Sprinkler Spacing
The minimum spacing between
sprinklers is 8 feet (2,4 m). The maxi-
mum spacing between sprin-
klers cannot exceed the length
of the coverage area (Table A)
being hydraulically calculated; maxi-
mum 12 feet for a 12 ft. x 12 ft. cover-
age area, or 20 feet for a 20 ft. x 20 ft.
coverage area).
Installation
The RAPID RESPONSE Series LFll
Residential Domed-Plate Concealed
Pendent 4.9 K-Factor Sprinklers
(TY2234) must be installed in accor-
dance with the following instructions:
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm).
Obtain a leak-tight 1/2 inch NPT
sprinkler joint by applying a minimum-
to-maximum torque of 7 to 14 ft. lbs.
(9,5 to 19,0 Nm). Higher levels of torque
can distort the sprinkler Inlet with con-
sequent leakage or impairment of the
sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in an Escutcheon
Plate by under- or over-tightening the
Sprinkler. Re-adjust the position of the
sprinkler fitting to suit.
Install the pendent sprinkler in only
the pendent position with the cen-
terline of the sprinkler perpendicu-
lar to the mounting surface.
Remove the Protective Cap.
Lf.III.I
Do not remove the Sprinkler Strap
(Figure 1) until the sprinkler system
is to be placed in service.
With pipe-thread sealant applied
to the pipe threads, and using the
W-Type 7 Wrench shown in Figure
2, install and tighten the Sprinkler/
Support Cup Assembly into the fit-
ting. The W-Type 7 Wrench will ac-
cept a 1/2 inch ratchet drive.
Replace the Protective Cap by push-
ing it upwards until it bottoms out
against the Support Cup. The
Protective Cap helps prevent dam-
age to the Deflector and Arms dur-
ing ceiling installation and/or during
application of the finish coating of
the ceiling. It may also be used to
locate the center of the clearance
hole by gently pushing the ceiling
material against the center point of
the Cap.
NOTICE
As long as the Sprinkler Strap (Fig-
ure 1) or the Protective Cap (Figure
3) remains in place, the system is
considered to be "Out Of Service".
After the ceiling has been com-
pleted with the 2-1/2 inch (63 mm)
diameter clearance hole and in
preparation for installing the Cover
Plate/Retainer Assembly, remove
and discard the Protective Cap and
the Sprinkler Strap.
Note: Refer to Technical Data Sheet
TFP700 regarding instructions for
the removal of the Sprinkler Strap.
Push the Cover Plate/Retainer
Assembly into the Support Cup, and
as necessary, make the final adjust-
ment of the Cover Plate with respect
to the ceiling by turning the Cover
Plate/Retainer Assembly clockwise
until its flange just comes in contact
with the ceiling.
If it becomes necessary to remove
the Cover Plate, it can be removed
by unscrewing in a counter-clockwise
direction.
If the Cover Plate/Retainer Assembly
cannot be engaged with the Support
Cup or the Cover Plate/Retainer
Assembly cannot be engaged suf-
ficiently to contact the ceiling, the
Sprinkler Fitting must be repositioned.
Care and
Maintenance
The RAPID RESPONSE Series LFIl
Residential Domed-Plate Concealed
Pendent 4.9 K-Factor Sprinklers
(TY2234) must be maintained and ser-
viced in accordance with the following
instructions:
NOTICE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, obtain permission to shut
down the affected fire protection sys-
tems from the proper authorities and
notify all personnel who may he affect-
ed by this action.
Absence of the outer piece of an es-
cutcheon, which is used to cover a
clearance hole, can delay sprinkler op-
eration in a fire situation.
Owners must assure that the sprinklers
are not used for hanging of any objects
and that the sprinklers are only cleaned
by means of gently dusting with a feath-
er, duster; otherwise, non-operation in
the event of a fire or inadvertent opera-
tion may result.
Exercise care to avoid damage to sprin-
klers before, during, and after installa-
tion. Never paint, plate, coat, or oth-
erwise alter automatic sprinklers after
they leave the factory.
Replace sprinklers that:
were modified or over-heated.
were damaged by dropping, striking,
wrench twisting, wrench slippage, or
the like.
are leaking or exhibiting visible signs
of corrosion.
were exposed to corrosive products
of combustion but have not operated,
if you cannot easily remove combus-
tion by-products with a cloth.
have a cracked Bulb or have lost
liquid from the Bulb. Refer to the
Installation section in this data sheet.
For the Cover Plate/Retainer Assembly,
the following items apply:
When properly installed, a nominal
3/32 inch (2,4 mm) air gap exists
between the lip of the Cover and
the ceiling, as shown in Figure 3.
This air gap is necessary for proper
sprinkler operation. The air gap al-
lows heat flow from a fire to pass
below and above the Cover, helping
to assure appropriate release of the
Cover in a fire situation. If repaint-
ing the ceiling after installation is re-
quired, exercise care to ensure that
new paint does not seal off any of
the air gap.
Do not pull the Cover relative to the
Retainer. Separation may result.
Never repaint factory-painted Cov-
ers. When necessary, replace Cov-
ers with factory-painted units.
Responsibility lies with the owner for
the inspection, testing, and mainte-
nance of their fire protection system
and devices in compliance with this
document, as well as with the appli-
cable standards of the National Fire
Protection Association (for example,
NFPA 25), in addition to the standards
of any authorities having jurisdiction.
Contact the installing contractor or
sprinkler manufacturer regarding any
questions.
Automatic sprinkler systems are recom-
mended to be inspected, tested, and
maintained by a qualified Inspection
Service in accordance with local re-
quirernents and/or national codes.
TFP45O
Page 5 of 6
SEALING
ASSEMBLY
WRENCH
FLATS
DISPOSABLE IL
SPRINKLER
STRAP (SEE
INSTALLATION I
SECTION)
DEFLECTOR
THREAD INTO I
SUPPORT
UNTIL MOU
SURFACI
FLUSH
CEILIN
, FRAME
/ / (1/2' NPT)
,
'S
/ BUTTON , /
SUPPORT
I I I CUP WITH
I ROLL FORMED
I I I THREADS
11&7----LCOMPRESSION
BULB
I
SPRINKLER/SUPPORT CUP SCREW
ASSEMBLY I
I RETAINER 'a- WITH THREAD
01 101 TABS
ii EJECTION II SPRING
WRENCH
RECESS
f.
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 2
W-TYPE 7
SPRINKLER WRENCH
OVER
LATE
SOLDE
TABS (
COVER PLATE/RETAINER
ASSEMBLY
FIGURE 1
RAPID RESPONSE SERIES LFII RESIDENTIAL
CONCEALED PENDENT SPRINKLERS (TY2234)
(Shown with Disposable Sprinkler Strap)
2-1/2 DIA. SPRINKLER- (63,5 mm) 1/2° (12,7 mm) FACE OF SUPPORT CUP
1/2° \ THREADED SPRINKLER \ ASSEMBLY \
NPT ADJUSTMENT FITTING
COVER / PLATE
3/32 GAP 1-3/16°±1/47
DISPOSABLE
RETAINER
- (30,2 mm
±6,4 mm)
MOUNTING
_
SURFACE
COVER- SPRINKLER- 15/16' 1/4(6,4 mm) OPERATED rRETAINER SUPPORT CUP I (23,8 mm 3/4' (19,1 mm) SPRINKLER
ASSEMBLY ASSEMBLY
3-5/16 DIA. (84,1 mm) TIP PROTECTIVE CAP
FIGURE 3
RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLERS (TV2234)
INSTALLATION DIMENSIONS / DISPOSABLE PROTECTIVE CAP
TFP45O
Page 6 of 6
Limited
Warranty
Products manufactured by Tyco Fire
Suppression & Building Products
(TFSBP) are warranted solely to the
original Buyer for ten (10) years against
defects in material and workmanship
when paid for and properly installed
and maintained under normal use and
service. This warranty will expire ten
(10) years from date of shipment by
TFSBP. No warranty is given for prod-
ucts or components manufactured by
companies not affiliated by ownership
with TFSBP or for products and com-
ponents which have been subject to
misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards
of the National Fire Protection
Association, and/or the standards of
any authorities having jurisdiction.
Materials found by TFSBP to be defec-
tive shall be either repaired or replaced,
at TFSBP's sole option. TFSBP neither
assumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. TFSBP shall not be
responsible for sprinkler system design
errors or inaccurate or incomplete in-
formation supplied by Buyer or Buyer's
representatives.
In no event shall TFSBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFSBP
was informed about the possibility of
such damages, and in no event shall
TFSBP's liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, express
or implied, including warranties of mer-
chantability and fitness for a narticular
purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on fail-
ure of or defect in products, materials
or components, whether the claim is
made in contract, tort, strict liability or
any other legal theory.
This warranty will apply to the full
extent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and
Part Number (P/N).
Sprinkler Assembly
Series LFII Residential Domed-Plate
Concealed Pendent Sprinkler (1Y2234),
K=4.9, without Cover Plate Assembly,
P/N 51-873-1-155.
Cover Plate Assembly
Cover Plate Assembly having a (speci-
fy) finish for the Series LFll Residential
Domed-Plate Concealed Pendent
Sprinkler (TY2234), K=4.9, and P/N
(below).
Chrome .................... PIN 56-873-9-135
Signal white (a) (RAL 9003) ................ PIN 56-873-4-135
Pure White (b) (RAL 9010) ................ PIN 56-873-3-135
Custom ...................P/N 56-873-X-135
Previously known as Bright White.
Eastern Hemisphere sales only.
Sprinkler Wrench
Specify W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001,
Copyright 0 2008-2010 Tyco Fire Suppression & Building Products. All rights reserved.
tqC0 Fire Suppression
& Building Products
Technical Services 800-381-93121+1-401-781-8220
www.tyco-fire.com
Series TY-FRB — 28,42,56, and 80 K-Factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The TYCO Series TY-FRB, 2.8, 4.2, 5.6,
and 8.0 K-factor, Upright and Pendent
Sprinklers described in this data sheet
are quick response, standard coverage,
decorative 3 mm glass bulb-type spray
sprinklers designed for use in light or
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
ping malls.
The recessed version of the Series TV-
FRB Pendent Sprinkler, where applica-
ble, is intended for use in areas with a
finished ceiling. This recessed pendent
sprinkler uses one of the following,
A two-piece Style 10 (1/2 inch NPT)
or Style 40 (3/4 inch NPT) Recessed
Escutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a
A two-piece Style 20 (1/2 inch NPT)
or Style 30 (3/4 inch NPT) Recessed
Escutcheon with 1/4 inch (6,4 mm) of
recessed adjustment or up to 1/2 inch
(12,7 mm) of total adjustment from the
flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and
installation of sprinkler systems and
components. Improper handling and
installation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fall to
operate in a fire situation or cause it
to operate prematurely.
Page 1 of 10
Corrosion-resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be obtained
when exposed to corrosive atmo-
spheres. Although corrosion-resistant
coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently,
it is recommended that the end user
be consulted with respect to the suit-
ability of these coatings for any given
corrosive environment. The effects of
ambient temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level of the Series TV-
FRB Pendent Sprinklers is detailed
in Technical Data Sheet TFP356, and
Sprinkler Guards are detailed in Tech-
nical Data Sheet TFP780.
NOTICE
The Series TY-FRB Concealed Pendent
Sprinklers described herein must be
installed and maintained in compliance
with this document and with the appli-
cable standards of the National Fire
Protection Association, in addition to
the standards of any authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
Owners are responsible for maintaining
their fire protection system and devices
in proper operating condition. The
installing contractor or sprinkler manu-
facturer should be contacted with any
questions.
JULY 2010
Model/Sprinkler
Identification
Number (SIN)
TY1131: Upright 2.8K, 1/2- NPT
TY1231: Pendent 2.8K, 1/2 NPT
TY2131: Upright 4.2K, 1/2' NPT
TY2231: Pendent 4.2K, 1/2- NPT
TY3131: Upright 5.6K, 1/2 NPT
TY3231: Pendent 5.6K, lIZ NPT
TV4131: Upright 8.0K, 3/4 NPT
1Y4231: Pendent 8.0K, 3/4' NPT
TY4831: Upright* 8.0K, lIZ NPT
TY4931: Pendent* 8.0K, lIZ NPT
Ftern Hemisphere Sales Only
TFPI7I
SSU *
DEFLECTOR
P1 fm
3/4° NPT
TFPI7I
Page 3 of 10
7/16 (11,1 mm) ESCUTCHEON
ssu * NOMINAL PLATE SEATING
DEFLECTOR NPT MAKE-IN 1/2 SURFACE
6*
5T12-3116"
7/16
(11,1 mm) I NOMINAL (55,6 mm)
1
MAKE-IN
2,6 mm)
FLATS
(38,1mm)
1-1/2"
WRENCH
1/2 NPT SSP DEFLECTOR *
CROSS SECTION UPRIGHT PENDENT
STYLE 100r20
RECESSED
ESCUTCHEON
27/8* (73,0 mm) DIA.
RECESSED PENDENT
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector Assembly * Temperature rating is indicated on deflector or adjaceni to
2 - Button 5 - Compression orifice seat on frame. Screw
FIGURE 3
QUICK RESPONSE SERIES TV-FRB UPRIGHT (TY3131) AND PENDENT (TV3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
1/2 (12,7 mm) ESCUTCHEON
NOMINAL PLATE SEATING
MAKE-IN 3/411 SURFACE
W
I
I
NPT
/ 2-5!'16.
(58,7 mm)
1-9/16
(39,7 mm)
SSP DEFLECTOR*
STYLE 30 or 40
RECESSED
ESCUTCHEON
2-7/8 (73,0 mm) DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector Temperature rating is indicated on deflector or adjacent to
2 - Button
Assembly5
- Compression orifice seat on frame. Screw
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TV4131) AND PENDENT (TY4231) SPRINKLERS
ao K-FACTOR, 314 INCH NPT
TFPI7I
Page 4 of 10
7/16 (11,1 mm)
SSU NOMINAL DEFLECTOR MAKE-IN 1/2
NPT
5 Ii 7/16' A I\ (11,1 mm) 2-1/4'
---11 Pi I NOMINAL 7,2 mm)
2
MAKE-IN
-3/16' 1-9/16'
WRENCH (39,7 mm)
FLATS
SSP*-..
CROSS 1/211 NPT DEFLECTOR
SECTION UPRIGHT PENDENT
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector Assembly * Temperature rating is indicated on deflector or adjacent to
2 - Button 5 - Compression orifice seat on frame. Screw
FIGURE 5
QUICK RESPONSE SERIES TV-FRB UPRIGHT (TY4831) AND PENDENT 'TV4931) SPRINKLERS
8.0 K-FACTOR, 1/2 INCH NPT
Technical
Data
Approvals
UL and C-UL Listed
FM, LPCB, and NYC Approved
Refer to Table A and B for complete
approval information including
corrosion-resistant status.
Maximum Working Pressure
Refer to Table C.
Discharge Coefficient
K=2.8 GPM/psi'/2 (40,3 LPM/bar112)
K=4.2 GPM/psi112 (60,5 LPM/barl'2)
K=5.6 GPM/psi112 (80,6 LPM/barl/2)
K=8.0 GPM/ps11/2 (115,2 LPM/bar1/2)
Temperature Rating
Refer to Table A and B.
Finishes
Sprinkler: Refer to Table A and B.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated.
Physical Characteristics
Frame ...................Bronze
Button .............. brass/Copper
Sealing Assembly.........Beryllium
Nickel w/Teflont
Bulb ......................Glass
Compression Screw........Bronze
Deflector...........Copper/Bronze
Bushing (K=2.8) ...........Bronze
t Registered Trademark of Dupont
Operation
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB Pendent
and Upright Sprinklers are intended
for fire protection systems designed in
accordance with the standard installa-
tion rules recognized by the applicable
Listing or Approval agency (such as, UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based on
the requirements of FM's Loss Preven-
tion Data Sheets). Only the Style 10,
20, 30, or 40 Recessed Escutcheon, as
applicable, is to be used for recessed
pendent installations.
Installation
The TYCO Series TY-FRB Sprinklers
must be installed in accordance with
the following instructions.
NOTICE
Do not install any bulb-type sprinkler if
the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bub-
ble should be present. The diameter
of the air bubble is approximately 1/16
inch (1,6 mm) for the 1351F/570C and
3/32 inch (2,4 mm) for the 2860F/1410C
temperature ratings.
Obtain a leak-tight 1/2 inch NPTsprin-
kier joint by applying a minimum to
maximum torque of 7 to 14 ft.lbs. (9,5
to 19,0 Nm). Higher levels of torque
can distort the sprinkler Inlet with con-
sequent leakage or impairment of the
sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Escutch-
eon Plate by under- or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
The Series TY-FRB Pendent and
Upright Sprinklers must be installed
in accordance with the following
instructions.
Install Pendent sprinklers in the
pendent position. Install upright
sprinklers in the upright position.
With pipe-thread sealant applied to
the pipe threads, hand-tighten the
sprinkler into the sprinkler fitting.
Tighten the sprinkler into the sprin-
kler fitting using only the W-Type 6
Sprinkler Wrench (Figure 14). With
reference to Figures 1 through
5, apply the W-Type 6 Sprinkler
Wrench to the sprinkler wrench
flats.
TFPI7I
Page 6 of 10
SPRINKLER FINISH (See Note 8)
K
FACTOR TYPE TEMPERATURE BULB LIQUID
COLOR NATURAL
BRASS
I CHROME
PLATED
I WHITE***
POLYESTER LEAD
COATED
5.6
1/2" NPT
PENDENT
(TY3231)
and
UPRIGHT
(TY3131)
135°F/57°C Orange
1, 2, 3,4, 5, 6, 7
Blue
1, 2, 3, 5
155°F/68°C Red
I 175°F/79°C Yellow
200°F/93°C Green
286F/141°C
RECESSED
PENDENT (TY3231)*
Figure 10
135°F/57C Orange
1, 2, 4, 5 N/A
155°F/68°C Red
175°F/79C Yellow
200°F/93°C Green
286F/141°C Blue
RECESSED
PENDENT (TY3231)**
Figure 11
135°F/57C Orange
1, 2, 3, 4, 5
Blue
N/A
155°F/68°C Red
175°F/79C Yellow
200F/93°C Green
286F/141°C
8.0
3/4" NPT
PENDENT (TY4231)
and
UPRIGHT
(TY4131)
135°F/57°C Orange
1, 2,3, 4,5,6,7
Blue
1,2, 5
155F/68°C Red
175F/79°C Yellow
200°F/93°C Green
286°F/141°C
RECESSED
PENDENT (TY4231)*
Figure 12
135F/57°C Orange
1, 2, 5
Blue
N/A
155°17/68°13 Red
175°F/79°C Yellow
200°F/93°C Green
286°F/141°C
RECESSED
PENDENT (TY4231)**
Figure 13
135F/57C Orange
1, 2, 3, 5
Blue
N/A
155°F/68°C Red
175F/79°C Yellow
200°F/93°C Green
286F/141°C
8.0
112" NPT
PENDENT
(TY4931)
and
UPRIGHT
(TY4831)
135°F/57°C Orange
1, 2, 4, 5, 6 1, 2, 5
155°F/68°C Red
175F/79°C Yellow
200F/93C Green
286°F/141°C Blue
NOTES:
Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. However, LPCB does not rate the thermal sensitivity of recessed sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details, contact Tyco Fire Suppression & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax
31-53-428-3377.)
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed
as Corrosion-Resistant Sprinklers. Where Lead-Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS FOR
5.6 AND 8.0 K-FACTOR SPRINKLERS
TFPI7I
Page 7 of 10
SPRINKLER FINISH
K TYPE NATURAL I CHROME I WHITE LEAD FACTOR BRASS I PLATED POLYESTER COATED
PENDENT (TY1231)
and
2.8
UPRIGHT (TY1131)
1/2" NPT 75 PSI (12,1 BAR) N/A
RECESSED
PENDENT (TY1231)
PENDENT (TY2231)
and
4.2 UPRIGHT (TY2131)
1/2" NPT 175 PSI (12,1 BAR) N/A
RECESSED
PENDENT (TY2231)
PENDENT (TY3231) 175 PSI
5.6
and
UPRIGHT (TY3131) 250 PSI (17,2 BAR) (12,1 BAR)
1/2" NPT OR 175 PSI (12,1 BAR)
RECESSED (SEE NOTE 1)
PENDENT (TY3231) N/A
PENDENT (TY4231) 175 PSI
8.0
and
UPRIGHT (TY4131) (12,1 BAR)
3/4" NPT 175 PSI (12,1 BAR)
RECESSED N/A PENDENT (TY4231)
8.0 PENDENT (1Y4931) 175 PSI 1/2" NPT and
UPRIGHT (TY4831) 175 PSI (12,1 BAR) (12,1 BAR)
NOTES: 1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in Canada (C-UL); and, the Approval by the City of New York.
The Series TY-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
After installing the Style 10, 20, 30,
or 40 Mounting Plate, as applica-
ble, over the sprinkler threads and
with pipe-thread sealant applied to
the pipe threads, hand-tighten the
sprinkler into the sprinkler fitting.
Tighten the sprinkler into the sprin-
kler fitting using only the W-Type 7
Recessed Sprinkler Wrench (Fig-
ure 15). With reference to Figures 1
to 4, apply the W-Type 7 Recessed
Sprinkler Wrench to the sprinkler
wrench flats.
After ceiling installation and finish-
ing, slide on the Style 10, 20, 30, or
40 Closure over the Series TY-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
TABLE C
MAXIMUM WORKING PRESSURE
Care and
Maintenance
The TYCO Series TY-FRB must be
maintained and serviced in accordance
with the following instructions.
(.1t1II
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
Exercise care to avoid damage to
sprinklers before, during, and after
installation. Never paint, plate, coat,
or otherwise alter automatic sprinklers
after they leave the factory.
Replace sprinklers that:
were modified or over-heated.
were damaged by dropping, striking,
wrench twisting, wrench slippage, or
the like.
are leaking or exhibiting visible signs
of corrosion.
were exposed to corrosive products
of combustion but have not oper-
ated, if you cannot easily remove
combustion by-products with a cloth.
have a cracked bulb or have lost liq-
uid from the bulb. Refer to the Instal-
lation section in this data sheet.
TFPI7I
Page 8 of 10
2-7/8 DIA. -
5/8±1/4 (73,0 mm) 3/4° (19,1 mm)
(15,9*6,4 mm) 2-1/4 DIA. 1/4(6,4 mm) I
FACE OF (57,2 MOUNTING
SPRINKLER PLATE
FITTING
&L/
3,2 mm)
-i
MOUNTING
SURFACE
,,
,/''
CLOSURE SERIES 1-5/16" (33,3 mm)
TY-FRB 13/16" (20.6 mm)
FIGURE 6
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
5/8±1/4
2-7/8" DIA.
(73,0 mm) 3/4"(19,1 mm)
(15,9±6,4 mm) 2-1/4" DIA. 1/4° (6,4 mm) I
(57,2 mm) I I FACE OF MOUNTING
SPRINKLER PLATE I
FITTING
I - - (3,2 mm)
MOUNTING f
SURFACE
CLOSURE SERIES 1-1/4" (31,8 mm) I TY-FRB 3/4" (19,1 mm)
FIGURE 8
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
- 2-7/8' DIA.
(73,0 mm) 1/2±1/8" 1/2" (12,7 mm)
r (12,7±3,2 mm) 2-1/4" DIA. 1/4(6,4 mm) I
?-
•/,.!_J- I FACE OF
T
(57,2 mm) I I MOUNTING
SPRINKLER PLATE
I
FITTING
I_ 1/8"
/
(3,2 mm) I
MOUNTING / SURFACE//f
f CLOSURE SERIES (33,3 mm)
TY-FRB 1-1/16" (27,0 nm)
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
2-7/8° DIA. - 1/2±1/8" (73,0 mm) 1/2" (12,7 mm) r (12,7±3,2 mm) 2-1/4" DIA. 1/4"(6,4 mm) I
FACE OF (57,2 mm)
MOUNTING
;- I SPRINKLER PLATE I FITTING
1/8°
(3,2 mm)
t \ /
MOUNTING /
SURFACE/ SERIES
1-1/4" (31,13 mm) CLOSURE TY-FRB 1° (25,4 mm)
FIGURE 9
SERIES TV-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
Initial and frequent visual inspections of
random samples are recommended for
corrosion-resistant sprinklers to verify
the integrity of the corrosion-resistant
material of construction. Thereafter,
annual inspections per NFPA 25 should
suffice.
Inspections of corrosion-resistant
sprinklers are recommended at close
range, instead of from the floor level
per NFPA. Inspection at close range
can better determine the exact sprin-
kler condition and the long-term integ-
rity of the corrosion-resistant material,
which can be affected by the corrosive
conditions present.
Responsibility lies with the owner for
the inspection, testing, and mainte-
nance of their fire protection system
and devices in compliance with this
document, as well as with the appli-
cable standards of the National Fire
Protection Association (for example,
NFPA 25), in addition to the standards
of any other authorities having jurisdic-
tion. Contact the installing contractor or
sprinkler manufacturer regarding any
questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Care must be exercised to avoid dam-
age to the sprinklers -before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be
replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Initial and frequent visual inspections of
random samples are recommended for
corrosion-resistant sprinklers to verify
the integrity of the corrosion-resistant
material of construction. Thereafter,
annual inspections per NFPA 25 should
suffice.
2-7/8 DIA.
(73,0 mm) 3/4 (19,1 mm)
2-1/4' DIA.
(57,2 mm)
1/4 (6,4 mm)
MOUNTING
DI AT
5/8±1/4'
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
TFPI7I
Page 9 of 10
2-7/8° DIA.
(73,0 mm) 3/4' (19,1 mm)
2-1/4° DIA. 1/4 (6,4 mm) I I (57,2 mm) ;i;-1 MOUNTING I
DI±T I
2-7/8 DIA.
(73,0 mm) 1/2 (12,7 mm)
2-1/4' DIA.
(57,2 mm)
' 1/4 (6,4 mm) I I
Ti MOUNTING I
- DIAT I
5/8±1/4°
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
1/2±1/8'
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
MOUNTING
SURFACE
I SERIES CLOSURE
1/8°
(3,2 mm) I
1-1/4"(31,8 mm)
3/4"(19,1 mm)
T__\__ MOUNTING
SURFACE
CLOSURE SERIES 1-1/4° (31,8 mm)
1' (25,4 mm)
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH P110-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16' (33,3 mm)1
TY-FRB 13/16' (20,6 mm)
FIGURE 12
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8' DIA.
1/2±1/8' (73,0 mm) 1/2' (12,7 mm)
r (12,7±3,2 mm) 2-1/4' DIA. 1/4° (6,4 mm)
FACE OF
(57,2 mm)
MOUNTING I SPRINKLER I PLATE
2- 1/8' I FITTING
(3,2mm)
I MOUNTING
SURFACE/
CLOSURE SERIES 1-5/16' (33,3 mm)
1YFRB 1-1/16 (27,0 mm)
FIGURE 13
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
Inspections of corrosion-resistant
sprinklers are recommended at close
range, instead of from the floor level
per NFPA. Inspection at close range
can better determine the exact sprin-
kler condition and the long-term integ-
rity of the corrosion-resistant material,
which can be affected by the corrosive
conditions present.
WRENCH RECESS
(END 'A' USED FOR
1/2 NPT MODELS)
WRENCH RECESS
(END "B' USED FOR
3/4' NPT MODELS)
FIGURE 14
W-TYPE 6 SPRINKLER
WRENCH
WRENCH
RECESS
t.
PUSH WRENCH IN TO
ENSURE ENGAGEMENT WITH
SPRINKLER WRENCHING AREA
FIGURE 15
W-TYPE 7 RECESSED
SPRINKLER WRENCH
TFPI7I
Page 10 of 10
P/N 57- XXX- X- XXX
I L
MODEL/SIN
330 2.8K UPRIGHT (1/2"NPT) TY1131
331 2.8K PENDENT (1/2"NPT) TY1231
340 4.2K UPRIGHT (1/2°NPT) TY2131
341 4.2K PENDENT (1/2°NPT) TY2231
370 5.6K UPRIGHT (1/2°NPT) TY3131
371 5.61K PENDENT (1/2"NPT) TY3231
390 8.0K UPRIGHT (3/4"NPT) TY4131
391 8.0K PENDENT (3/4"NPT) TY4231
360 8.0K UPRIGHT (1/2"NPT) TY4831°
361 8.0K PENDENT (1/2°NPT) TY49311*
SPRINKLER TEMPERATURE
L FINISH RATINGS
1 1 NATURAL BRASS 135 135°F (57°C)
4 I WHITE POLYESTER I I 155 1 155°F (68°C)
3 WHITE (RAL901O)° 175 175°F (79°C)
9 1 CHROME PLATED 200 200°F (93°C)
7 I LEAD COATED I I 286 1 286-F (141-C)
° Eastern Hemisphere sales only.
TABLED
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire
Suppression & Building Products
(TFSBP) are warranted solely to the
original Buyer for ten (10) years against
defects in material and workmanship
when paid for and properly installed
and maintained under normal use and
service. This warranty will expire ten
(10) years from date of shipment by
TFSBP. No warranty is given for prod-
ucts or components manufactured by
companies not affiliated by ownership
with TFSBP or for products and com-
ponents which have been subject to
misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in
accordance with applicable Standards
of the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by TFSBP to be defective
shall be either repaired or replaced, at
TFSBP's sole option. TFSBP neither
assumes, nor authorizes any person
to assume for it, any other obligation in
connection with the sale of products or
parts of products. TFSBP shall not be
responsible for sprinkler system design
errors or inaccurate or incomplete infor-
mation supplied by Buyer or Buyer's
representatives.
In no event shall TFSBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFSBP
was informed about the possibility of
such damages, and in no event shall
TFSBP's liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, express
or implied, including warranties of mer-
chantability and fitness for a particular
Duroose.
This limited warranty sets forth the
exclusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim is
made in contract, tort, strict liability or
any other legal theory.
This warranty will apply to the full
extent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and Part
Number (P/N).
Sprinkler Assemblies with NOT
Thread Connections
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table 0).
Recessed Escutcheon:
Specify: Style (10, 20, 30, or 40)
Recessed Escutcheon with (specify*) finish, P/N (specify*).
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001.
Refer to Technical Data Sheet TFP770.
Copyright 0 2007-2010 Tyco Fire Suppression & Building Products. All rights reserved.
Fig. 22 - Hanger for CPVC Plastic Pipe
Single Fastener Strap Type
Size Range - 3/4" thru 2' CPVC pipe
Material - Pre-Galvanized Steel
Function - Intended to perform as a hanger to support CPVC piping used
in automatic fire sprinkler systems. The product acts as a hanger when tab
is upward and the fastener screw is in the horizontal position. Figure 22 can
be installed on the top of a beam, but in this situation acts as a guide to
the piping which is supported by the beam itself. It is not intended to sup-
port CPVC pipe from under a flat horizontal surface, such as a ceiling. For
this type of installation, use the TOLCO® Fig. 23, Double Fastener Strap for
CPVC Piping. Fig. 22, when inverted, with the hanger tab downward, can
function as a restrainer to prevent the upward movement of the sprinkler
head during activation.
Approvals - Underwriters' Laboratories Listed in the USA (UL) and Canada
(cUL) to support fire sprinkler piping. May be installed in wood using
fasteners supplied with product, or into minimum 20 gauge steel using (1)
1/4' x 1" tek type screw. Meets and exceeds the requirements of NFPA 13,
13R and 13D.
Features - Fig. 22 incorporates features which protect the pipe and ease installation. The flared edge design pro-
tects CPVC pipe from any rough surface. It is easily attached to the building structure using the special UL Listed
hex head self threading screw furnished with the product, this is the minimum size fastener acceptable. It is rec-
ommended that rechargeable electric drills fitted with a hex socket attachment to be used as installation tools. No
impact tools (such as a hammer) are allowed. Damage has been know to result from installations using impact type
tools. No pre-drilling of a pilot hole in wood is required.
Finish - Pre-Galvanized
Order By - Figure number and CPVC pipe size.
Dimensions • Weights
CPVC Max. Hanger Fastener Hex Approx. Pipe Size A B C Spacing (Ft.) Head Size Wt./1100
3/4 27A 1/16 1/16 51h 5/16 9
1 211A6 1A8 1W16 6 5/16 9
11/4 31A6 1/8 13/16 61h 5/16 11
1½ 3/i6 13/4 1A6 7 5/16 12
2 33/4 21/8 1A6 8 5/16 - 15
D OFFICMANUFACTURIPIG FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
Fig. 23 - Hanger for CPVC Plastic Pipe
Double Fastener Strap Type rom
Size Range - 3/4" thru 3" CPVC pipe
Material - Pre-Galvanized Steel
Function - Intended to perform as a hanger/restrainer to support
CPVC piping used in automatic fire sprinkler systems. Fig. 23 can
be installed on the top, bottom or side of a beam. The Fig. 23 also
functions as a restrainer to prevent the upward movement of the
sprinkler head during activation.
Approvals - Underwriters' Laboratories Listed in the USA (UL)
and Canada (cUL) to support fire sprinkler piping. May be installed
in wood using fasteners supplied with product, or into minimum 20
gauge steel using (2) 1/4" x 1" tek type screw. Meets and exceeds
the requirements of NFPA 13, 13R and 13D.
Features - Fig. 23 incorporates features which protect the pipe
and ease installation. The flared edge design protects the CPVC
pipe from any rough surface. It also incorporates snap restrainers
allowing easier and faster installation. Easily attaches to the building
structure using the two UL Listed hex head self threading screws*
furnished with the product. It is recommended that rechargeable
electric drills fitted with a hex socket attachment be used as instal-
lation tools. No impact tools (such as a hammer) are allowed.
Damage has been known
to result from installations using impact type tools.
No pre-drilling of a pilot hole in wood is required.
Finish - Pre-Galvanized
Order By - Figure number and pipe size
* Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
Dimensions • Weights
cpvc Max. Hanger Fastener Hex Approx. Pipe Size A B C Spacing (Ft.) Head Size Wt./1100
3/4 314 1A6 1A* 51h 5/16 9
1 334 111A6 1/16 6 5/16 9
11/4 4/16 2%2 1A6 61h 5/16 11
1½ 4A6 2/32 13A6 7 5/16 12
2 474 2/16 1A6 8 5/16 15
21/2 10/32 211/16 1/16 9 5/16 22
3 117/8 3 1/16 10 5/16 25
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
Fig. 28
"Stand-Off" Hanger & Restrainer for CPVC Plastic Pipe C® US LISTED
Size Range - 3/4" through 2"
Material - Carbon Steel, Pre-Galvanized
Function - Designed to be used as a hanger and restrainer for CPVC piping where
the "stand-off" design will ease installation by eliminating the need for wood blocking
Features /
Flared edge design protects CPVC pipe from any rough or abrasive surfaces \ , Unique twist and lock design holds pipe firmly in place and allows retrofit type . B
of installation
The Stand Off design eliminates the need for wood block extension C
Can be installed on horizontal or vertical piping regardless of mounting "......-'
surface orientation.
Attaches easily to wood structure with two hex head self-threading screws
furnished with product.
Installs easily using rechargeable electrical driver with 5/16" extension socket
eliminating impact tool damage to pipe.
Attaches easily to steel, minimum 18 gauge with (2) 1/4" x 1" tek type self drilling
tapping screws.
U.L. Listed as a hanger and a restrainer for fire sprinkler piping.
Approvals - Underwriters' Laboratory Listed in the USA (UL) and Canada (cUL) to
support automatic fire sprinkler systems. May be installed into wood using fasteners
supplied with product, or into minimum 18 gauge steel using (2) 1/4" x 1" tek type screws.
Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28 satisfies the UL
vertical restraint requirement where needed. UL Listed as a hanger and vertical restraint
when installed on 3/8" composite wood material. Use two Fig. 27B Speed Nuts when
used as a hanger and restraint. Use one Fig. 27B Speed Nut on the upper installed
screw when used as a hanger only.
Order by - Figure number and pipe size.
PATENT # 10446292
FIG79 (I) REOUIRED .....FIQ.2Th
HIGH WE (2) REOUID
OFHGER
JjJ Dimensions • Weights
HANGER APPLICATION HANGER& RESTRAINT Pipe Approx.
F*20
APPLICATION A B Size Wt.
3/4 31/3 2 3½ 180
4, 1 36 2A6 31h .210
.J1 ( 11/4 3% 2% 31/2 .225
Ij 1½ 4 21h 3½ .310
F8-----..I i 2 . 41h 211/16 3/8 .340
I FI26 FIG2E
.....FOID - ._ ................... ..........._.. ................ -. [i_TIJIiIIJiIIIJ
OFFICMANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879. PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
Fig. 200 - "Trimline" Adjustable Band Hanger C@US LISTED Fig. 200R (Import) - "Trimline" Adjustable Band Hanger
w/Retainer Ring
Size Range - 1/2 thru 8" pipe
Material - Carbon Steel, Mil. Galvanized to G90
specifications
Function - For fire sprinkler and other general piping
purposes. Knurled swivel nut design permits hanger
adjustment after installation.
Features -
(1/2' thru 2") Flared edges ease installation for
all pipe types and protect CPVC plastic pipe
from abrasion. Captured design keeps adjusting
nut from separating with hanger. Hanger is eas-
ily installed around pipe.
(21h" thru 8") Spring tension on nut holds it
securely in hanger before installation. Adjusting
nut is easily removed.
Approvals - Underwriters' Laboratories listed
(1/2" thru 8') in the USA (UL) and Canada (cUL)
for steel and CPVC plastic pipe and Factory Mutual
Engineering Approved (3/4' thru 8"). Conforms to
Federal Specifications WW-H-1 71 E, Type 10 and
Manufacturers Standardization Society SP-69, Type
10.
Maximum Temperature - 650°F
Finish - Mil. Galvanized. Stainless Steel materials will
be supplied with (2) hex nuts in place of a knurl nub.
Order By - Figure number and pipe size
Note - Figure 200R (import) with retainer ring and
non-captured knurl nut.
Dimensions • Weights
Pipe Rod Size Max. Rec. Approx.
Size Inch Metric A B Load Lbs. WtJ100
1/2 3/8 8mm or 10mm 31/a 25/8 - 400 11
3/4 3/8 8mm or 10mm 31/s 21h 400 11
1 3/8 8mm or 10mm 33/8 2% 400 12
11/4 3/8 8mm or 10mm 33/4 2/e 400 13
11/2 3/8 8mm or 10mm 37/8 2/s 400 14
2 3/8 8mm or 10mm 41/2 3 400 15
21h. 3/8 10mm 55A 41A 600 27
3 3/8 10mm 57/s 4 600 29
31/2 3/8 10mm 7% 51/ 600 34
4 3/8 10mm 73A 5 1000 35
5 1/2 12mm 91/8 61/4 1250 66
6 1/2 12mm 101/8 6Y4 1250 73
8 1/2 12mm 131/8 83/4 1250 136
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • F(: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
C®US US1tD Fig. 25 - Surge Restrainer
Size Range - One size fits 3/4" thru 2" pipe.
Material - Pre-Galvanized Steel .- • '..: •.. -
Function - Designed to be used in conjunction with TOLCO® Band Hangers to
restrict the upward movement of piping as it occurs during sprinkler head
activation or earthquake type activity. The surge restrainer is easily and efficient-
ly installed by snapping into a locking position on the band hanger. This product
is intended to satisfy the requirements as indicated in the National Fire Protection
Association NFPA 13, 2007 edition, 9.2.3.4.4.1 and 9.2.3.4.4.4 Can be used to
restrain either steel pipe or CPVC plastic Pipe.
Approvals - Underwriters' Laboratories Listed qnly when used with TOLCO
band hangers Fig. 2, 2NFPA and 200, in the USA (UL) and
Canada (cUL).
Finish - Pre-Galvanized
Order By - Figure number and TOLCO band hanger, size from 3/4"
thru 2".
Patent #5,344,108
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 'PH: 951.737.5599 • FM: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
Fig. 980 - Universal Swivel Sway Brace Attachment CUS LISTED
Size Range One size fits bracing pipe 1" thru 2', TOLCO 12 gauge channel, and all
structural steel up to 1/4" thick.
Material - Carbon Steel
Function - Multi-functional attachment to structure or
braced pipe fitting.
Features - This product's design incorporates a concen-
tric attachment opening which is critical to the performance
of structural seismic connections. NFPA 13 (2002) Figure
9.3.5.9.1 indicates clearly that fastener table load values are
based only on concentric loading. Mounts to any surface
angle. Break off bolt head assures verification of proper
installation.
Installation - The Fig.980 is the structural or transitional
attachment component of a longitudinal or lateral sway
brace assembly. It is intended to be combined with the
"bracing pipe" and TOLCO "braced pipe" attachment, Fig.
1000, 1001, 2002, 4L, 4A or 4B to form a complete bracing
assembly. NFPA 13 and/or OSHPD guidelines should be
followed.
ed
rn
To Install - Place the Fig. 980 onto the "bracing pipe'. Tighten the set bolt until set bolt head breaks off.
Attachment can pivot for adjustment to proper brace angle.
Approvals - Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). Approved by Factory Mutual
Engineering (FM). Included in our Seismic Restraints Catalog approved by the State of California Office
of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information
relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines.
Note - The Fig. 980 Swivel Attachment and the Fig. 1001, Fig. 1000, Fig. 2001 or Fig. 4A Pipe Clamp make up a
sway brace system of UL Listed attachments and bracing materials which satisfies the requirements of Underwriters'
Laboratories and the National Fire Protection Association (NFPA)
Finish Plain
Note - Available in Electro-Galvanized finish.
Order By - Figure number and finish.
PATENT #6,273,372
Dimensions • Weights
Max. Design **Max. Design
A B H* Load Lbs. Load Lbs. Approx.
wtjloo (cULus) (FM)
51/4 1/8 17/32 2765 2800 132
Available with hole sizes to accommodate up to 3/4' fastener. Consult factory.
** Load shown is allowable with brace installed, between 30° - 90°. No reduction of load based on
brace angle is required.
Lateral Brace
TOLCO® brand bracing components are desgined to be compatible ONLY with other TOLCO® brand bracing components, resulting in a Listed
seismic bracing assembly. DISCLAIMER - NIBCO does NOT warrant against the failure of TOLCO® brand bracing components, in the instance
that such TOLCO® brand bracing components are used in combination with products, parts or systems which are not manufactured or sold under
the TOLCO® brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect, incidental or consequential damages of any
kind, including but not limited to loss of business or profit, where non-TOLCO brand bracing components have been, or are used.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
Longitudinal Brace
Fig. 4L CUS LISTED
Longitudinal In-Line' Sway. Brace Attachment
Size Range - 21/2" through 8" IPS.
Material - Carbon Steel
Function - For bracing pipe against sway and seismic disturbance.
Approvals - Underwriter's Laboratories Listed in the USA (UL) and
Canada (cUL) 21/2" - 8". Approved by Factory Mutual Engineering (FM),
21/2" - 8" pipe.
Installation Instructions - The Fig. 4L is the "braced pipe" attachment
component of a longitudinal sway brace assembly. It is intended to be
combined with the "bracing pipe" and TOLCO structural attachment
component to form a complete bracing assembly. NFPA 13 and/or
OSHPD guidelines should be followed.
To Install - Place the Fig. 4L over the pipe to be braced and tighten
bolts. Then engage "bracing pipe" into jaw opening and tighten set bolt
until hex head snaps off. Jaw attachment can pivot for adjustment to
proper brace angle.
Finish - Plain
Note - Available in Electro-Galvanized and HOG finish.
Order By - Figure number, pipe size and finish.
.............
...
4-Way Riser Brace
(Plan view)
Dimensions • Weights
Bolt Max. Rec. *Max Rec. Approx. Sizes A C D Size Load Lbs. Load Lbs. wt./100 (cULus) (FM)
21h 6/16 21/2 2/4 1/2 2015 3000 253
3 7 23/4 31/16 1/2 2015 1550 268
4 81h 3% 311,1,6 1/2 2015 1550 348
5 93/4 37/8 43A 1/2 2015 1450 380
6 11 1h 5 51/8 1/2 2015 1450 640
8 131/4 611A6 61/8 1/2 2015 1450 728
* Load shown is allowable with brace installed, between 30° - 90°. No reduction of load
based on brace angle is required.
FM approved when used with 1 , 11/4", 11/2 or 2° Sch. 40 brace pipe.
TOLCO® brand bracing components are designed to be compatible ONLY with other TOLCO® brand bracing components, resulting in a Listed seismic
bracing assembly. DISCLAIMER - NIBCO does NOT warrant against the failure of TOLCO® brand bracing components, in the instance that such
TOLCO® brand bracing components are used in combination with products, parts or systems which are not manufactured or sold under
the TOLCO® brand. NIBCO shall NOT be liable under any circumstance for any direct or indirect, incidental or consequential damages of any kind,
including but not limited to loss of business or profit, where non-TOLCO brand bracing components have been, or are used.
OFFICE/MANUFACTURING FACILITY • 1315 SAMPSON AVE. • CORONA, CA 82878 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
wwwtoko.com
KG-505-W-8
Grooved
KT-505W
300 lb. WWP Bronze Ball Valves
Fire Protection Valve • Threaded or Grooved Body Style • Full Port Design 1 - 2' •
Standard Port Design 21/2' • Accepts Internal Supervisory Switche
300 PSI/20.7 Bar Non-Shock Cold Water
CONFORMS TO MSS SP-1 10 • FM APPROVED .
UL LISTED FOR INDOOR AND OUTDOOR SERVICE.
CALIFORNIA STATE FIRE MARSHAL LISTING NO. 7770-1243:103
APPROVED BY NEW YORK CITY M.E.A. 218-04-E WITH
APPROPRIATE NYC INDICATOR.
MATERIAL LIST
PART SPECIFICATION
Body Bronze ASTM B 584 Alloy C84400
Ball chrome Plated Brass ASTM B 124 Alloy C37700
Seat Ring carbon-filled [FE
Thrust Washer Reinforced TFE
ncificon
Resista
Stem Bronze ASTM B 371 Alloy C69430
Stem 0-Ring Nitrile
Retaining Washer Brass
Retaining Ring Steel
Ground Wire Screw Steel
505-8 Act Assy. Brass
Body End Bronze ASTM B 584 Alloy C84400
Mounting Screw Steel
Lock Washer Steel
Handle Pin Brass
Hand Wheel Steel/plastisol coated (11/4" 21/2")
Brass Tee Handle (1 I
Indicator Flag Painted Steel
Body Gasket Elastomer
lB. Lead Screw 0-Ring Nitrile
Thrust Washer Anti-friction Polymer
Cover Gasket Neoprene
Flag Seal 0-Ring Nitrile
Tamper-Proof Screw Stainless Steel
Pipe Plug (-4 units) Stainless Steel (Not shown)
Refer to page 41 for details for TS-2M Switch Kit.
DIMENSIONS-WEIGHTS-QUANTITIES
Size
In. mm.
Threaded
In. mm.
A
Grooved
In. mm.
Threaded
In. mm.
Dimensions
B
Grooved C D
In. mm. In. mm. In. mm.
E
In. mm.
F
In. mm.
6
In. mm.
Weight
Cvt Threaded Grooved Box Master
Value Lbs. Kg. Lbs. Kg. Wy. Ctn. Wy,
1 25 3.33 85 - - 1.66 42 - - 2.11 54 3.81 97 2.31 59 6.14 1561.75 44 57 6.1 2.77 - - 1 10
1114 32 4.18 106 - - 2.09 53 - - 2.46 624.21 107 2.72 69 6.33 161 3.50 89 103 7.1 3.23 - - 1 8
1½ 40 4.70 119 - - 2.35 60 - - 2.95 74 4.46113 2.97 75 6.33 161 3.50 89 143 8.1 3.68 - - 1 4
2 50 5.15 131 6.71 170 2.57 65 3.36 85 3.69 94 4.67 119 3.18 81 6.33 181 3.50 89 245 10.7 4.86 9.7 4.40 1 4
21h 65 5.65 144 7.28 185 2.92 74 3.64 93 3.75 95 4.67 119 3.18 81 6.33 161 3.50 89 183 13.0 5.91 12.6 5.73 1 4
t Note: Cv is defined as the flow in GPM that a valve will carry with a pressure drop of 1.0 psi when the media is water at 600 F.
AOV!D
II NIBCO INC WOAI D HEADQUARTERS • 1516 MIODLEBUFtY ST. • EIKHART. IN 46516-4740 • USA • PH: 1.600.234.0227
TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.336.4226 • INTERNATIONAL OFFICE PH +1.574.295.3327 • F,(: 4 1.574.295.3455
www.tibco.com
PART SPECIFICATION
Body Bronze ASTM B 584 Alloy C84400
- . Stem Stainless Steel ASTM A 582 Alloy C30300
Spring 316 Stainless Steel
Disc Holder Stainless Steel Type 301
Disc Water, Oil or Gas (8una-N) Steam (PTFE) (Y)
Seat Screw Stainless Steel ASTM A 276 Alloy S43000
Body End Bronze ASTM 8 584 Alloy C84400
1-480
Threaded
S-480
Solder
B__
Class 125 Bronze Ring Check® Valves incification
Inline Lift Type • Resilient Discs • Spring Actuated flSIStart>'
125 P51/8.6 Bar Saturated Steam (PTFE Disc)
250 PSI/17.2 Bar Non-Shock Cold Working Pressure
CONFORMS TO MSS SP-80
MATERIAL LIST
T-480-Y (PTFE Disc)
NPTxNPT
DIMENSIONS -WEIGHTS -QUANTITIES
Size
In. mm. In.
A
mm.
Dimensions
B
In. mm. In.
C
mm.
T-480
In. mm.
S-480 Master
Lbs. Kg. Ctn. Oty.
3/ 10 2.00 51 1.38 35 1.44 37 0.41 0.19 0.44 0.20 100
1/2 15 2.06 52 1.38 35 1.19 30 0.36 0.16 0.40 0.18 100
3/4 20 2.25 57 1.63 41 1.31 33 0.48 0.22 0.52 0.24 100
1 25 2.63 67 2.00 51 1.50 38 0.77 0.35 0.85 0.39 50
11/4 32 2.94 75 2.38 60 1.69 43 1.14 0.51 1.28 0.58 30
11/2 40 3.31 84 2.75 70 2.00 51 1.63 0.74 1.75 0.79 30
2 50 3.69 94 3.38 86 2.31 59 2.27 1.03 2.70 1.23 10
Ordering: The 1.480 and S480 both have standard Buna-N Discs.
Also available with PTFE (Y) Discs; specify 1-480-V or S-480-V.
W' Wu 2' require ½ pound pressure to open.
S-480-Y (PIFE Disc)
CxC
NIBCO check valves maybe installed in both horizontal and
For detailed Operating Pressure, refer to Pressure Temperature Chart on page 111. vertical lines with upward flow or in any intermediate position.
Warning - Do Not Use For Reciprocating Air Compressor Service.
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLE8URY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227
TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
The AGF Manufacturing Inc. Model 1000 TESTMIDRAIN®
provides both the test function and the express drain
function for a wet fire sprinkler system.
The Model 1000 complies with the requirements of
NFPA-13, NFPA-13R, and NFPA-13D.
The Model 1000 TESTANDRAIN® is a compact single
handle ball valve which includes a tamper resistant test
orifice and integral tamper resistant sight glasses, and is
300 PSI rated.
Available in a full range of sizes from 34" to 2" NPT and
BSPT, with all specifiable orifice sizes /e" (2.8K), 7Ae" (4.2K),
½" (5.6K), 17/32" (8.0K), We" (11.2K, ELO), 34" (14.0K, ESFR),
and K25 as required by NFPA 13, 2007 Edition (see reverse).
The orifice size is noted on the indicator plate and the valve
features a tapped and plugged port for system access.
A locking kit is available and can be ordered with the valve
to provide vandal resistance or prevent unintentional alarm
activation.
Repair kits including (1) adapter gasket, (1) ball, (2) valve
seats, (1) stem packing, and (1) stem washer are available
for all TESTAtIDRAIN® valves. Valve and orifice size must
be specified when ordering.
MODEL 1000 - FRONT VIEW, VERTICAL INSTALLATION
FROM BRANCH
SYSTEM ACCESS PORT
STREET
T EL STREET _.II1][III] TO DRAIN OR PIPE
TO DRAIN
RIGHT HAND/STRAIGHT INSTALLATION
TESTANDF.AIN is a registered trademark of AGF Manufacturing Inc. DS1000 10/09
DIMENSIONS
Orifice Size Available: 3/°, /16°, ½", 17/32°, ELO (5/8 )*, ESFR (3/4 )*, & K25**
TO DRAIN
MATERIALS
Handle: Steel
Stem: Rod Brass
Ball: C.R Brass
Body: Bronze
Valve Seat: Impregnated Teflon®
Indicator Plate: Steel
Handle Stop: Steel
APPROVALS
UL and ULC Listed (EX4019)
FM Approved
NYC-BSA No. 720-87-SM
MODEL 1000 - PLAN VIEW FRONT VIEW - HORIZONTAL INSTALL
SIZE A B C D E F C H
3/4" 51A6" 1½" 23/16 35A" 33/8" 113/16 4A6" 63/8"
(128 mm) (37.5 mm) (57 mm) (93 mm) (86 mm) (46 mm) (1117 mm) (162.5 mm)
1½" 26" 35A" 33/8" 113/16" 49A6 63/8"
(128 mm) (37.5 mm) 1 (57 mm) (93 mm) (86 mm) (46 mm) (117mm) (162.5 mm)
11/4" 57/16" 111A6" 29/16" 41/4" 35/16" 115A6" 59/16" 51/2"
(163 mm) (43 mm) (65 mm) (108mm) (83 mm) (51 mm) (141 mm) (1192 mm)
1Y2" 67A6" 113A6" 3¼" 51/16" 37/8"2%"81/4" 107/8"
(1163 mm) (45 mm) (81.5 mm) (127 mm) (99 MM) (67 mm) (207 mm) (274 mm)
2" 6/16" 113A6" 31/4" 51/16" 37/8" 2%" 81/4" 107/8"
(163 mm) (45 mm) (81.5 mm) (127 mm) (99 mm) (67 mm) (207 mm) (274 mm)
* Available on 11/4" to 2" size units only
** Available on 11/2" and 20 size units only
THE MODEL 1000 PROVIDES ALL OF THE FOLLOWING..
From the 2007 Edition of NFPA 13
Chapter 8.16.2.4.1* Provisions shall be made to properly drain all parts of the system.
Chapter 8.16.2.4.2 Drain connections, interior sectional or floor control valve(s) - shall be provided with a drain
& 8.16.2.4.3 connection having a minimum size as shown in Table 8.16.2.4.2.
Chapter 8.16.2.4.4 Drains shall discharge outside or to a drain capable of handling the flow of the drain.
Chapter A.8.17.4.2 (Wet Pipe System) test connection is permitted to terminate into a drain capable of accepting full
flow.., using an approved sight test connection containing a smooth bore corrosion-resistant orifice
giving a flow equivalent to one sprinkler...
Chapter 8.17.4.2.2 The test connection valve shall be readily accessible.
Chapter 8.17.4.2.4 shall be permitted to be installed in any location.., downstream of the waterflow alarm.
Chapter 8.17.4.3.1 (Dry Pipe System) a trip test connection not less than 1" in diameter, terminating in a smooth bore
corrosion-resistant orifice, to provide a flow equivalent to one sprinkler...
Chapter 8.17.4.3.2 The trip test connection.., with a shutoff valve and plug not less than 1", at least one of which shall
be brass.
USA Patent # 4741361 and Other Patents Pending
AGF Manufacturing Inc. Job Name:___________________________ 100 Quaker Lane, Malvern, PA 19355
Phone: 610-240-4900 Architect:
Fax: 610-240-4906
www.testandrain.com
Contractor:
Engineer:
(E)POTTER VANE TYPE WATERFLOW
The Symbol of Protection ALARM SWITCH - SMALL PIPE
Stock No. 1111100
U.S. Patent No. 3921989, Canadian Patent No. 1009680
Other Patents Pending
Install VS-SP VS-SP in systems that are not subject to variable water
pressure. Failure to do so will result in false alarms.
AcAUTION
This device is not intended for applications in explosive
environments.
The Model VS-SP is a vane type waterfiow switch for use on wet
sprinkler systems. These devices may be used as sectional flow
indicators on large sprinkler systems and on smaller sprinkler systems
such as mobile homes and residential dwellings.
The VS-SP does not have a retard to prevent false alarms due to water
surges. Therefore it should NOT be used on systems with variable water
pressure supplies except in the case of elevator recall.
Installation
These devices may be mounted in horizontal or vertical pipe. On
horizontal pipe they should be installed on the top side of the pipe
where they will he accessible. The units should not be installed within
6" (15cm) of a valve, drain or fitting which changes the direction of the
water flow. Select the propr paddle for the pipe size and type of TEE
used. See Fig. I for instruc:ions on how to change the paddle.
The unit has a I' NPT bushing for threading into a non- corrosive TEE.
UL, ULC, CSFM and NYBSA Listed, CE Marked
Service Pressure: Up to 250 PSI (17,2 BAR)
Minimum Flow Rate for Alarm: 10 GPM (38 LPM)
Maximum Surge: 18 FPS (5,5 m/s)
Enclosure: Die-cast, red enamel finish
Cover held in place with tamper resistant screws
Contacts: One set of SPOT (Form C), standard
Second set optional, see below:
IS Amps at 1251250VAC
0.5 Amps at 125 VDC
0.25 Amps at 250VDC
2.5 Amps at 30 VDC resistive
Conduit Entrance: One opening for 1/2" conduit
Usage: Listed plastic, copper and schedule 40iron pipe
For pipe sizes - I" (251nm), 1-114" (32mm), 1-1/2' (38mm).
and 2" (50mm)
Note: 12 paddles are furnished with each unit, one for each
pipe size of threaded and sweat TEE, one for 1" C PVC, one
for I" CPVC (Central), one for 1" Nibco threaded tee, and one
for 1-1/2" threaded (Japan).
Environmental Specifications:
Suitable for indoor or outdoor use with factory installed
gasket and die-cast housing.
NEMA4/1P55 rated enclosure -use with appropriate conduit fitting.
Temperature range: 40°F to 120°F (4,5°C to 49°C)
Service Use:
Automatic Sprinkler NF PA-13 3
One or two family dwelling 4PA-131)
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
Optional: Extra Contacts Switch Kit, Stock No. 0090013
(Extra Contacts Switch is Field Installed)
Cover Tamper Switch Kit, Stock No. 5420220
See Fig. 2 for proper TEE size, type and installation. Use no more than
three wraps of teflon tape as thread lubricant. Screw the device into the
TEE fitting as shown in Fig. 2. Care must be taken to properly orient
the device for the direction of waterfiow.
The vane must not rub the inside of the TEE or bind in any way. The
stem should move freely when operated by hand.
Testing
Check the operation of the unit by opening the inspector's test valve at
the end of the sprinkler line, or the drain and test connection if a test
valve is not provided.
If there are no provisions for testing the operation of the flow detection
device on the system, application of the VS—SP is not recommended
or advisable.
Potter Electric Signal Compa iy, 1.1C -2081 Craig Road, St. Louis. MO, 63146-4161 • Phone: 800-325-3936/Canada888-882-1 833• www.pouersignal.com
PRINTED IN USA MFG. #5400769 - REV \' PAGE I OF 2
5/08
S.
(E,)POTTER
The Symbol of Protection
VS-SP
VANE TYPE WATERFLOW
ALARM SWITCH - SMALL PIPE
Fig. I Fig. 2
OPTIONAL SECOND
SWITCH AVAILABLE
I H __ H IF REQUIRED. FLOW
0 SWITCH KIT I I I I I ''-
APPROX. I STK 110090013 0 MOUNTSO I I I
ARROWON
BUSHING
POINTS IN
DIRECTION
0 OF WATER DEITH
DIRECTION OF
FLOW
WATER FLOW I' NPT
THREADED
FITTING ON
- -
ALL SIZES Screw the device into the tee fitting as shown. Care must be taken to
RUN OF
properly orient the device for the direction of waterfiow. On sat
tees, no threaded bushings, inserts, or adapters are permitted, unless THE TEE Important: .. MAY BE they comply with the dimensions listed in the chart below.
There are 12 paddles furnished THREADED Important -The depth to the inside bottom of the tee should have the with each unit. Due for each size of OR SVEAT following dimensions: threaded, sweat or plastic TEE as TYPE described in Fig. 2. These paddles
have raised lettering that shows
the pipe size and type of TEE
that they are to he used with. The DIRECTION t use more than three wraps ot'teflon tape. proper paddle must be used. The OF WATER Do u paddle must be properly attached FLOW (see drawing) and the screw that
holds the paddle must be securely
Lightened.
Switch information I Typical Control Panel Connections Switch Terminal Connections Clamping Plate Terminal
TOP OF SWITCH
JEIL
SWITCH ACTION COM
I
N.C.
non
N.C.
LOCAL BELL/HORN CONNECTION
N.O.
- N.C. BELL POWER OR
HORN
DWG. #769—I
END—OF—LINE RESISTOR TYPE P i
o=
N.C.N.1 _
COM-
OPEN CIRCUIT TYPE
TO
-7
PANEL
CLOSED CIRCUIT TYPE
N.O.
COM.,,,
TO 7NC. PANEL
OWC
CAUTION
An uninsulated section of a single conductor should
not be looped around the terminal and serve as two
separate connections. The wire must be severed, thereby
providing supervision of the connection in the event that
the wire becomes dislodged from under the terminal.
Due to the possibility of unintended discharges caused by pressure
Surges, trapped air, or short retard tunes. waterfiow switches that
are monitoring wet pipe sprinkler Systems should not be used as
the sole initiating device to discharge AFFF, deluge, or chemical
suppression systems.
Note: The Model VS-SP has one SPDT switch. An optional second
switch is available if required. For example, one switch would connect
to an annunciator panel, and the optional switch could be used to operate
a local bell. Order Switch Kit No. 0090013.
Testing
The frequency of inspection and testing for the Model VS-SP and its
associated protective monitoring system should be in accordance with
applicable NFPA Codes and Standards and/or the authority having
jurisdiction (manufacturer recommends quarterly or more frequently).
PRINTED IN USA MFG. 95400769 - REV V PAGE 2 OF 2
5108
<2>
(E)POTTER BELLS
The Symbol of Protection PBA-AC & MBA-DC
These vibrating type bells are designed for use as fire, burglar or general
signaling devices. They have low power consumption and high decibel
ratings. The unit mounts on a standard 4" (10 square electrical box
for indoor use or on a model BilK-i weatherproof backbox or BBX-i
deep weatherproof backbox for outdoor applications. Weatherproof
backbox model BBK-1, Stock No. 1500001.
UL, ULC, and FM Approved
Sizes Available: 6" (150mm). 8" (200mm) and 10' (250mm)
Voltages Available: 24VAC
I2OVAC
I2VDC (10.2 to 15.6) Polarized
24VDC (20.4 to 31.2) Polarized
Service Use: Fire Alarm
General Signaling
Burglar Alarm
Environment: Indoor or outdoor use (See Note I)
-40° to 150°F (40° to 66°C)
(Outdoor use requires weatherproof backbox.)
Termination: AC Bells - 4 No. 18 AWG stranded wires
DC Bells - Terminal strip
Finish: Red powder coating
Optional: Model BBK- I weatherproof backbox
Model BBX-1 deep weatherproof backbox
Notes:
Minimum dB ratings are calculated from integrated sound pressure
measurements made at Underwriters Laboratories as specified in UL
Standard 464. UL temperature range is -30° to 150°F (-34° to 66°C).
Typical dB ratings are calculated from measurements made with a
conventional sound level meter and are indicative of output levels in
an actual installation.
ULC only applies to MBA DC bells.
Size inches
(mm)
Voltage Model
Number
Stock
Number
Current
(Max.)
Typical dB at
10 ft. (3m) (2)
Minimum dB at
10 ft. (3m) (1)
6(150) 12VDC MBA126 1750070 .12A 85 76
8(200) 12VDC MBA128 1750080 .12A 90 77
10(250) 12VDC MBA1210 1750060 .12A 92 78
6(150) 24VDC MBA246 1750100 .06A 87 77
8(200) 24VDC MBA248 1750110 .06A 91 79
10(250) 24VDC MBA2410 1750090 .06A 94 80
6(150) 24VAC PBA246 1806024* .17A 91 78
8 (200) 24VAC PBA248 1808024* .17A 94 77
10(250) 24VAC PBA2410 1810024* .17A 94 78
6(150) I20VAC PBAI206 1806120* .05A 92 83
8(200) 120 VAC PBA 1208 1808120* .05A 99 84
10(250) 120VAC PBA12010 1810120* .05A 99 86
All DC bells are polarized and have built-in transient protection.
* Does not have ULC listing.
in outdoor or wet installations, bell must be mounted with
weatherproof backbox. BilK-I or BBX-l. Standard electrical boxes
will not provide a weatherproof enclosure. If the bell and/or assembly
is exposed to moisture, it may fail or create an electrical hazard.
Potter Electric Signal Company, LLC •2081 Craig Road, St. Louis, MO, 631464161 • Phone: 800-325-3936/Canada 888-882-1833• www.pottersignal.com
PRINTED IN USA MFG. #5400776 - REV PAGE 1 OF 2
5/08
Weatherproof Backbox Dimensions Inches (mm)
Fig. 2
Box has one threaded 1/2 conduit entrance
p(8 /u c3/4
(141.: ....._.,._..,
(86) - IS
4114"
(1(181
I>VGU 770.2
®POTTER BELLS
The Symbol of Protection PBA-AC & MBA-DC
Bells Dimensions Inches (mm)
Fig. I
SWIll 716.1
Wiring (rear view)
Fig. 3
A.C. BELLS
WIIrrIi (IN) WIllIE (01fF)
C6L
FROM CONTROL
PANELOR
PRECEDING HELL
HLAC6IIN)
CArnON:
WHEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SHOWN.
NOTES:
I. WhEN USINOAC BELLS.TEIhMINAIE EACH EXIRA WIRE SEPARATELYAF'IER LAST BELL.
2• uRIS-OF-LINE RESIStOR IS NOT REQUIRED ONAC HELLS.
0Wrn776-3
Installation
The bell shall be installed in accordance with NFPA 13, 72, or
local AHJ. The top of the device shall be no less than 90' AFF and
not less than 6" below the ceiling.
Remove the gong.
Connect wiring (see Fig. 3).
Mount bell mechanism to backbox (bell mechanism must be
mounted with the striker pointing down).
Reinstall the gong (be sure that the gong positioning pin, in the
mechanism housing, is in the hole in the gong).
Test all bells for proper operation and observe that they can
be heard where required (bells must be heard in all areas as
designated by the authority having jurisdiction).
mø r,
-
Failure to install striker down will pruvent bell from operating-
PRINTED IN USA MPG. #5400776 - REV Y PAGE 2 OF 2