HomeMy WebLinkAbout3410 VIA MERCATO; ; AS140336; Permit4/15/24, 3:26 PM AS140336 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS140336
Status: ISSUED
Applied 12/24/2014
Approved: 1/7/2015
Issued: 1/7/2015
Job Address: 3410 VIA MERCATO
Permit Type: SPRINK
Parcel No:
Lot #: 0
Reference No.:
PC #: Inspector:
Project Title: PROJECT PIE TI FOR (N) PIE 2 RESTAURANT. TOTAL AREA
1910 SF. REMODEL OF EXISTING UNIMPROVED SPACE. TI
INCLUDING HT EBUILDING OF NEW DEMISING TENANT SPACE
NON-LOAD BEARING WALLS, NEW SINGLE OCCUPANCY
RESTROOMS, NEW ROOF MOUNTED HVAC WITH
ASSOCIATED DUCT WORK WITHIN THE SPACE, ASSOCIATED
PLUMBING AND ELECTRICAL, NEW CEILING GRID, TILE AND
LIGHT FIXTURES, PATCH, REPAIR NEW FINISHES.
Applicant: Owner:
PARAMOUNT FIRE SYSTEMS, INC.
P.O. BOX 713194
SANTEE, CA
619-562-6247
Fees ($) Add'l Fees ($) Total ($) Balance ($)
210 0 210 0
about:blank 1/1
TI TTT1
WE
FIRE DEPARTMEN AS1 40336 NTION DIVISION
FARADAY AVENUE
ILSBAD CA 92008
760-602-4665
I Constructtor I
-
Name of Project:_ rey. k?t
Address of job site:3t(O yt 1'4&CA-Th C4Suite#. 100 Building Permit No: CB
Contractor Informatiot. 't'(
Company Name cre_. y -fe.
Address 'Ô' uc City State CA Zip
Phone: 'I-571-P107 _Fax: Q -43
Contractor License Class and Number G-U Exp. Date: -ll.
Do you currently have a business license on file with the City of Carlsbad? Yes or No No: I - I 31 1
Name: i.vrc C-4.e.'-' Date:, -.
Submit plans and completed permit appIicatio25?' I"
CARLSBAD FIRE PREVENTION
1635 FARADAY AVENUE
CARLSBAD, CA 92008-7314
(760) 6024665
Fax: (760) 602-8561
firemailtcarlsbadca.gov
Office Hours are: M-Th 7:30 a.m. - 5:30 p.m. PSI
FRI 8:00a.m. - 5:00 p.m. PST
To Schedule an Inspection:
For inspections ONLY, please call (760) 602-4660, a minimum of two days in advance. Calls will be returned by the end of the next
business day. Inspection Hours are: 6:30 AM - 5:00 PM
Re-inspection fees and Hydrant Flow Test fees must be paid at the above address prior to receiving an inspection. Inspection
Personnel are prohibited by law from accepting payments in the field. All payments must be made at the address above.
Plan Check status Inquiries:•
Allow at least 10 business days for plan review comments and/or approval.
This office will contact you when the plans are approved / disapproved.
Please include a self-addressed stamped envelope for mail return of plans.
If after 10 business days you have not received a communication from our office, you may contact us at 760-602-4665, by FAX to 760-
602-8561 or e-mail us at: firemailcarlsbadca.gov
Revised 9/3/13
tqc, Eli Worldwide
Contacts
Series TY-FRB, 56 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers described in this data sheet
are quick response, standard coverage,
decorative 3 mm glass bulb-type spray
sprinklers designed for use in light or
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
ping malls.
The recessed version of the Series TV-
FRB Pendent Sprinkler, where applica-
ble, is intended for use in areas with a
finished ceiling. This recessed pendent
sprinkler uses one of the following:
A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 inch (15,9 mm) from
the flush pendent position.
A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 inch (12,7 mm) from
the flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Intermediate level versions of Series
TY-FRB Sprinklers are described in
Technical Data Sheet TFP357. Sprin-
kler guards and shields are described
in Technical Data Sheet TFP780.
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and
installation of sprinkler systems and
components. Improper handling and
installation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
Page 1 of 4
NOTICE
The TYCO Series TY-FRB Sprinklers
described herein must be installed and
maintained in compliance with this doc-
ument, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the stan-
dards of any other authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
Sprinkler
Identification
Number (SIN)
TV313 .......Upright 5.6K, 1/2NPT
TY323 ......Pendent 5.6K, 1/2NPT
Technical
Data
Approvals
UL and C-UL Listed
FM and VdS Approved
CE Certified
Maximum Working Pressure
175 psi (12.1 bar)
250 psi (17.2 bar)*
The maximum working pressure of 250 psi (17.2 bar) only applies to the listing by Un-
derwriters Laboratories, Inc. (UL).
Discharge Coefficient
K=5.6 GPM/psi112 (80,6 LPM/bar1I2
Temperature Rating
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
JANUARY 2013
Finishes
Sprinkler: Natural Brass, Chrome
Plated, Pure White (RAL 9010) and
Signal White (RAL 9003).
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
Frame ...................Bronze
Button..............Brass/Copper
Sealing Assembly.........Stainless
Steel w/TEFLON
Bulb ......................Glass
Compression Screw........Bronze
Deflector.................Bronze
AS140336
TFPI72
2
(50,8 mm)
WRENCH
FLATS
DEFLECTOR * I— 2-7/8" (73,0 mm) DIA.
PENDENT RECESSED PENDENT
TFPI72
Page 2 of 4
Components: * Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression
3 - Sealing Screw ESCUTCHEON PLATE 1/2 7/16 (11,1 mm)
Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN
CROSS SECTION UPRIGHT
FIGURE 1
SERIES TY-FRB UPRIGHT (TY313) AND PENDENT (TY323) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
I 7/16" I (11,1mm) I NOMINAL
MAKE-IN
2
(50,8 mm) I
1/2" NPT**
STYLE 15 or 20
RECESSED
ESCUTCHEON
/ WRENCH RECESS
/ (USE ONLY
6ii
- END
FIGURE 2
W- TYPE 6
SPRINKLER WRENCH
WRENCH
RECESS
t .
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 3
W- TYPE 7 RECESSED
SPRINKLER WRENCH
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules rec-
ognized by the applicable Listing or
Approval agency (such as, UL Listing
is based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM's Loss Prevention
Data Sheets). Only the Style 15 or Style
20 Recessed Escutcheon is to be used
for recessed pendent installations.
Installation
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb-type sprinkler if
the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bub-
ble should be present. The diameter
of the air bubble is approximately 1/16
inch (1,6 mm) for the 135°F (57°C) and
3/32 inch (2,4 mm) for the 286°F (141°C)
temperature ratings.
A leak-tight 1/2 inch NPT sprinkler joint
should be obtained by applying a min-
imum to maximum torque of 7 to 14
ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Escutch-
eon Plate by under- or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Upright and Pendent Sprinklers
The Series TY-FRB Upright and Pen-
dent Sprinklers must be installed
in accordance with the following
instructions.
Step 1. Install Pendent sprinklers in the
pendent position. Install upright sprin-
klers in the upright position.
Step 2. With, pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
TFPI72
Page 3 of 4
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Figure 2). With ref-
erence to Figure 1, apply the W-Type 6
Sprinkler Wrench to the wrench flats.
Torque sprinklers 7 to 14 ft.-lbs. (9,5 to
19,0 Nm).
Recessed Pendent Sprinklers
The Series TY-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. After installing the Style 15 or
Style 20 Mounting Plate over the sprin-
kler threads, and with pipe-thread
sealant applied to the pipe threads,
hand-tighten the sprinkler into the
sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque
sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0
Nm).
Step C. After ceiling installation and fin-
ishing, slide on the Style 15 or Style 20
Closure over the Series TY-FRB Sprin-
kler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
Care and
Maintenance
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be
replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section.)
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associa-
tion (e.g., NFPA 25), in addition to the
standards of any other authorities hav-
ing jurisdiction. Contact the installing
contractor or sprinkler manufacturer
regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
2-7/8° DIA.
(73,0 mm)
2-1/4" DIA.
FACE OF (57,2 mm)
SPRINKLER
FITTING 5/8" (15,9 mm)
FLUSH
3/8±5/16"
(9,5±7,9 mm) ,
MOUNLG \ . j I
SURFACE
(3,2 mm) 4
CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm)
TYFRB PLATE 3/4"(119,11 mm)
FIGURE 4
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
2-7/8" DIA. -
(73,0 mm)
FACE OF
SPRINKLER - 2-1/4" DIA.
FITTING (57,2 mm)
(7964)\ qo(3,2
1/2°(12,7mm)
FLUSH
MOUNTING ]
SURFACE/ mm)
CLOSURE SERIES MOUNTING 1-3/8 (34,9 mm)
TY-FRB PLATE 7/8° (22,2 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
RECESSED ESCUTCHEON
TFPI72
Page 4 of 4
P/N* 77 - XXX - X - XXX
SPRINKLER TEMPERATURE
FINISH RATINGS
SIN 1 NATURAL BRASS
370 5.6K UPRIGHT (1/2 NPT) TY313 4 SIGNAL WHITE (RAL 9003) 155 155-F (68-C)
371 5.6K PENDENT (1/2-NPT) 1Y323 3 PURE WHITE (RAL 9010)°° 175 175-F (79-C)
* Use suffix I" for ISO 7-1 connection; 9 CHROME PLATED for example. 77-370-4-175-I -
Eastern Hemisphere sales only
TABLE A
SERIES 7Y-FRB UPRIGHT AND PENDENT SPRINKLERS
- PART NUMBER SELECTION -
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Num-
ber (P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB (SIN), K=5.6,
(Upright or Pendent) Sprinkler Quick
Response, (specify) temperature rat-
ing, (specify) finish, P/N (Table A).
Recessed Escutcheon
Specify: Style 15 Recessed Escutcheon
with (specify*) finish, P/N (specify*)
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
Refer to Technical Data Sheet TFP770.
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
135 135°F(57°C)
200 200°F (93°C)
286 286°F (141°C)
GLOBAL HEADQUARTERS 11400 Pennbrook Parkway, Lansdale, PA 194461 Telephone +1-215-362-0700
Copyright 0 2013 Tyco Fire Products, LP. All rights reserved. two is trademark of The DuPont Corporation.