HomeMy WebLinkAbout2034 CORTE DEL NOGAL; ; AS040100; Permit5/9/24, 9:02 AM AS040100 Permit Data
City of Carlsbad
Sprinkler Permit
2034 CORTE DEL
Job Address:
NOGAL
Permit Type: SPRINK
Parcel No: 2130613100
Lot #: 0
PermitNo: AS040I00
Status: ISSUED
Applied 7/6/2004
Approved: 7/9/2004
Reference No.: Issued: 7/9/2004
PC #: Inspector:
Project Title: ASM AFFILIATES FIRE SPRINKLER PLAN CHECK &
INSPECTIONS
Applicant:
WESTERN STATES FIRE PROTECTION
SUITE 201
9550 CHESAPEAKE DR.
SAN DIEGO, CA
858-769-4900
Owner:
Fees ($) Add'I Fees ($) Total ($) Balance ($)
458 0 458 0
about:blank 1/1
4s vv AiIL,,ra'
U:N+ IfeLrd tL. t4b6AL..
Job Name TI BLDG2
Building
Location
System
Contract
Data File fplayout.WXI
F.M.".L~wq
A604-O L66
Fire Protection by Computer Design
WESTERN STATES FIRE PROTECTION
9550 Chesapeake Dr. #201
San Diego CA 92123
858 769 4900
FILE copy
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve (C)
WESTERN STATES FIRE PROTECTION Page
TIBLDG2 Date 063004
City Water Supply:
Cl - Static Pressure : 41.4 PSI
C2 - Residual Pressure: 40.9 PSI
C2 - Residual Flow : 218 GPM
150
140
P 120
R 110
E 100
S90
s80
U 70
R60
E 50
40
30
20
10
50 100 150 200 250 300 350 400 450
FLOW ( N" 1.85 )
-
Dl - Elevation : 5.847 PSI
D2 - System Flow : 169.84 GPM
D2 - System Pressure : 28.938 PSI
Hose(Adj City) : GPM
Hose ( Demand) : GPM
03 - System Demand : 169.84 GPM
Safety Margin : 12.147 PSI
-
-
- 130
-
Cl C2
D2
Computer Programs by Hydratec Inc. Route Ill Wndham N.H. USA 03087
Flow Diagram
WESTERN STATES FIRE PROTECTION Page 2 TIBLDG2 Date 063004
DOOI 4- 15.39 51
D002 4- 15.04 50
D003 i- 14.93 52
D004 4- 16.17 46
D005 . 15.16 53
D006 . 1513 49
D007 4- 14.82 54
D008 i- 15.91 47
D009 4- 16.73 48
D010 1539 51
D011 4- 15.17 55 4- 15.17 44
1 15.17 t 1.23
54 4- 14.82 44
t 1.23
53 4- 15.16 45
52 4- 14.93 45
51 4- 15.66 41
1. 11.23
50 15.04 42
49 4- 15.13 42
1 18.94
51 4- 15.13 43
48 4- 16.73 40
47 (- 15.9' 36
1 8.38
46 4- 16.17 37
? 1.23
3 -. 28.76 44 4- 1.23 45 4- 31.33 4
t 36.29
5 •-+ 26.88 41 -. 11.23 42 4- 18.94 43
T 63.17
7 i- 9.15 40 4- 25.87 8
T 54.02
9 4-25.8610
4- 34.07 6
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Flow Diagram
WESTERN STATES FIRE PROTECTION Page 3 TIBLDG2 Date 063004
9 - 25.86 10
1 - 7.53 3 36.29 5 i- 63.17 7 . 54.02 9 28.17 11 28.17 12
1 - 7.53 36 4- 8.38 37 4- 24.55 2 +- 24.55 4 i- 55.88 6 4- 89.95 8 i- 115.8210 i- 141.6812 .- 169.8413 4 169.84 TEST
Computer Programs by Hydratec Inc. Route 111 Wndham N.H. USA 03087
Fiftingi Summary
WESTERN STATES FIRE PROTECTION
TIBLDG2
Fitting Legend
Abbrev. Name
A Generic Alarm Va
B Generic Butterfly Valve
C Roll Groove Coupling
D Dry Pipe Valve
E 90' Standard Elbow
F 45' Elbow
G Gate Valve
H 45' Grvd-Vic Elbow
90' Grvd-Vic Elbow
J 90' Grvd-Vic Tee
K Detector Check Valve
L Long Turn Elbow
M Medium Turn Elbow
N PVC Standard Elbow
0 PVC Tee Branch
P PVC 45' Elbow
Q Flow Control Valve
R PVC Coupling/Run Tee
S Swing Check Valve
I 90' Flow thru Tee
U 45' Firelock Elbow
V 90' Firelock Elbow
W Wafer Check Valve
X 90' Firelock Tee
Y Mechanical Tee
Z Flow Switch
Page 4
Date 063004
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittingè Summary
WESTERN STATES FIRE PROTECTION Page 5
TIBLDG2 Date 063004
Unadjusted Fittings Table
1/2 3/4 - -- 1 11/4 11/2 2 21/2 3 31/2 4
A 7.7 21.5 17.0 B 7.0 10.0 12.0 C 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
D 9.5 17.0 28.0
E 2.0 2.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 10.0
F 1.0 1.0 1.0 1.0 2.0 2.0 3.0 3.0 3.0 4.0
G 1.0 1.0 1.0 1.0 2.0 H 1.0 1.5 2.0 2.0 3.0 3.0 3.5 3.5
I 2.0 3.0 4.0 3.5 6.0 5.0 8.0 7.0
J 4.5 6.0 8.0 8.5 10.8 13.0 17.0 16.0
K 14.0 14.0
L 1.0 1.0 2.0 2.0 2.0 3.0 4.0 5.0 5.0 6.0
M 2.0 2.0 3.0 3.0 4.0 5.0 6.0 6.0 8.0
N 7.0 7.0 7.0 8.0 9.0 11.0 12.0 13.0
0 3.0 3.0 5.0 6.0 8.0 10.0 12.0 15.0
P 1.0 1.0 1.0 2.0 2.0 2.0 3.0 4.0
Q 18.0 29.0 35.0
R 1.0 1.0 1.0 1.0 1.0 1.0 2.0 2.0
S 4.0 5.0 5.0 7.0 9.0 11.0 14.0 16.0 19.0 22.0
T 3.0 4.0 5.0 6.0 8.0 10.0 12.0 15.0 17.0 20.0
U 1.8 2.2 2.6 3.4
V 3.5 4.3 5.0 6.8 W 10.3
X 8.5 10.8 13.0 16.0
V 2.0 4.0 5.0 6.0 8.0 10.5 12.5 15.5 22.0
Z 2.0 2.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 10.0
5 6 8 10 12 14 16 18 20 24
17.0 27.0 29.0
9.0 10.0 12.0 19.0 21.0
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
47.0
12.0 14.0 18.0 22.0 27.0 35.0 40.0 45.0 50.0 61.0
5.0 7.0 9.0 11.0 13.0 17.0 19.0 21.0 24.0 28.0
2.0 3.0 4.0 5.0 6.0 7.0 8.0 10.0 11.0 13.0
4.5 5.0 6.5 8.5 10.0 18.0 20.0 23.0 25.0 30.0
8.5 10.0 13.0 17.0 20.0 23.0 25.0 33.0 36.0 40.0
21.0 25.0 33.0 41.0 50.0 65.0 78.0 88.0 98.0 120.0
36.0 55.0 45.0
8.0 9.0 13.0 16.0 18.0 24.0 27.0 30.0 34.0 40.0
10.0 12.0 16.0 19.0 22.0
33.0
27.0 32.0 45.0 55.0 65.0 76.0 87.0 98.0 109.0 130.0
25.0 30.0 35.0 50.0 60.0 71.0 81.0 91.0 101.0 121.0
4.2 5.0 5.0
8.5 10.0 13.0
13.1 31.8 35.8 27.4
21.0 25.0 33.0
12.0 14.0 18.0 22.0 27.0 35.0 40.0 45.0 50.0 61.0
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
WESTERN STATES FIRE PROTECTION Page 6
TIBLDG2 Date 063004
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Req.
D001 13.5 5.6 7.56 na 15.39 .1000 57.00 7.000
D002 13.5 5.6 7.21 na 15.04 .1000 80.00 7.000
0003 13.5 5.6 7.11 na 14.93 .1000 40.00 7.000
0004 13.5 5.6 8.34 na 16.17 .1000 129.00 7.000
D005 13.5 5.6 7.33 na 15.16 .1000 50.00 7.000
0006 13.5 5.6 7.3 na 15.13 .1000 147.00 7.000
0007 13.5 5.6 7.0 na 14.82 .1000 76.00 7.000
0008 13.5 5.6 8.07 na 15.91 .1000 127.00 7.000
D009 13.5 5.6 8.92 na 16.73 .1000 57.00 7.000
0010 13.5 5.6 7.56 na 15.39 .1000 30.00 7.000
Doll 13.5 5.6 7.34 na 15.17 .1000 48.00 7.000
55 10.0 9.4 na
54 10.0 9.04 na
53 10.0 9.39 na
52 10.0 9.16 na
51 10.0 9.64 na
50 10.0 9.27 na
49 10.0 9.36 na
48 10.0 11.09 na
47 10.0 10.19 na
46 10.0 10.47 na
3 13.5 9.62 na
44 13.5 8.44 na
45 13.5 8.44 na
5 13.5 9.74 na
41 13.5 8.7 na
42 13.5 8.58 na
43 13.5 8.91 na
7 13.5 10.1 na
40 13.5 10.24 na
9 13.5 10.36 na
1 13.5 9.61 na
11 13.5 10.4 na
36 13.5 9.51 na
37 13.5 9.63 na
2 13.5 13.19 na
4 13.5 13.25 na
6 13.5 13.54 na
8 13.5 14.22 na
10 13.5 15.3 na
12 13.5 16.88 na
13 13.5 23.08 na
TEST 0.0 28.94 na
The maximum velocity is 16.24 and it occurs in the pipe between nodes 12 and 13
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Standard
WESTERN STATES FIRE PROTECTION Page 7
TI BLDG2 Date 063004
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv Notes
Point Qt Pf/UL Eqv. Ln. Total Pf Pn
D001 15.39 1.080 2E 2.305 3.500 7.556 k Factor = 5.60
to 120 4.610 1.516
51 15.39 0.0695 8.110 0.564 Vet = 5.390
0.0
15.39 9.636 KFactor= 4.96
0002 15.04 1.080 2E 2.305 3.500 7.210 K Factor 5.60
to 120 4.610 1.516
50 15.04 0.0667 8.110 0.541 Vel = 5.267
0.0
15.04 9.267 K Factor = 4.94
0003 14.93 1.080 2E 2.305 3.500 7.112 K Factor =5.60
to 120 4.610 1.516
52 14.93 0.0657 8.110 0.533 Vel = 5.229
0.0
14.93 9:161 K Factor = 4.93
0004 16.17 1.080 2E 2.305 3.500 8.339 K Factor =5.60
to 120 4.610 1.516
46 16.17 0.0762 8.110 0.618 Vel = 5.663
0.0
16.17 10.473 K Factor= 5.00
D005 15.16 1.080 2E 2.305 3.500 7.329 K Factor =5.60
to 120 4.610 1.516
53 15.16 0.0677 8.110 0.549 Vel = 5.309
0.0
15.16 9.394 K Factor = 4.95
0006 15.13 1.080 2E 2.305 3.500 7.299 K Factor =5.60
to 120 4.610 1.516
49 15.13 0.0674 8.110 0.547 Vel = 5.299
0.0
15.13 9.362 KFactor= 4.94
0007 14.82 1.080 2E 2.305 3.500 7.000 K Factor = 5.60
to 120 4.610 1.516
54 14.82 0.0649 8.110 0.526 VeI= 5.190
0.0
14.82 9.042 K Factor = 4.93
0008 15.91 1.080 2E 2.305 3.500 8.074 K Factor 5.60
to 120 4.610 1.516
47 15.91 0.0740 8.110 0.600 Vel = 5.572
0.0
15.91 10.190 KFactor = 4.98
0009 16.73 1.080 2E 2.305 3.500 8.920 K Factor 5.60
to 120 4.610 1.516
48 16.73 0.0811 8.110 0.658 Vel = 5.859
0.0
16.73 11.094 KFactor= 5.02
D010 15.39 1.080 2E 2.305 3.500 7.556 K Factor =5.60
to 120 4.610 1.516
51 15.39 0.0695 8.110 0.564 Vel = 5.390
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Standard
WESTERN STATES FIRE PROTECTION Page 8
TIBLDG2 Date 063004
Hyd. Qa Dia. Filling Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv Notes
Point Qt Pf/UL Eqv. Ln. Total Pf Pn
0.0
15.39 9.636 K Factor = 4.96
D01 15.17 1.080 2E 2.305 3.500 7.339 K Factor =5.60
to 120 4.610 1.516
55 15.17 0.0677 8.110 0.549 Vel = 5.313
0.0
15.17 9.404 K Factor= 4.95
55 15.17 1.080 IT 5.762 2.370 9.404
to 120 5.762 -1.516
44 15.17 0.0678 8.132 0.551 VeI= 5.313
0.0
15.17 8.439 K Factor = 5.22
54 14.82 1.080 IT 5.762 8.330 9.042
to 120 5.762 -1.516
44 14.82 0.0649 14.092 0.914 VeI= 5.190
0.0
14.82 8.440 K Factor = 5.10
53 15.16 1.080 IT 5.762 2.580 9.393
to 120 5.762 -1.516
45 15.16 0.0676 8.342 0.564 VeI= 5.309
0.0
15.16 8.441 K Factor = 5.22
52 14.93 1.080 IT 5.762 6.330 9.162
to 120 5.762 -1.516
45 14.93 0.0657 12.092 0.795 Vel = 5.229
0.0
14.93 8.441 K Factor = 5.14
51 15.66 1.080 IT 5.762 2.370 9.636
to 120 5.762 -1.516
41 15.66 0.0718 8.132 0.584 Vel = 5.484
0.0
15.66 8.704 KFactor= 5.31
50 15.04 1.080 IT 5.762 6.620 9.267
to 120 5.762 -1.516
42 15.04 0.0666 12.382 0.825 Vel = 5.267
0.0
15.04 8.576 KFactor= 5.14
49 15.13 1.080 IT 5.762 5.080 9.361
to 120 5.762 -1.516
42 15.13 0.0674 10.842 0.731 Vel = 5.299
0.0
15.13 8.576 K Factor= 5.17
51 15.13 1.080 IT 5.762 6.000 9.636
to 120 5.762 -1.516
43 15.13 0.0674 11.762 0.793 VeI= 5.299
0.0
15.13 8.913 K Factor = 5.07
48 16.73 1.080 IT 5.762 2.370 11.094
to 120 5.762 -1.516
40 16.73 0.0812 8.132 0.660 Vel = 5.859
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Standard
WESTERN STATES FIRE PROTECTION Page 9
TIBLDG2 Date 063004
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes
Point Qt Pf/UL Eqv. Ln. Total Pf Pn
0.0
16.73 10.238 K Factor= 5.23
47 15.91 1.080 iT 5.762 5.540 10.190
to 120 5.762 -1.516
36 15.91 0.0740 11.302 0.836 Val = 5.572
0.0
15.91 9.510 KFactor= 5.16
46 16.17 1.080 iT 5.762 3.120 10.473
to 120 5.762 -1.516
37 16.17 0.0762 8.882 0.677 Vel = 5.663
0.0
16.17 9.634 K Factor = 5.21
3 -28.76 1.408 IT 6.617 12.750 9.616
to 120 6.617 0.0
44 -28.76 -0.0608 19.367 -1.177 Vel = 5.926
44 29.99 1.408 12.000 8.439
to 120 0.0 0.0
45 1.23 0.0002 12.000 0.002 Vel = 0.253
45 30.10 1.408 iT 6.617 61.000 8.441
to 120 6.617 0.0
4 31.33 0.0712 67.617 4.814 Vel = 6.456
0.0
31.33 13.255 K Factor= 8.61
5 -26.88 1.408 IT 6.617 12.750 9.743
to 120 6.617 0.0
41 -26.88 -0.0536 19.367 -1.039 Vel = 5.539
41 15.65 1.408 12.000 8.704
to 120 0.0 0.0
42 -11.23 -0.0107 12.000 -0.128 Vel= 2.314
42 30.17 1.408 12.000 8.576
to 120 0.0 0.0
43 18.94 0.0281 12.000 0.337 Vel = 3.903
43 15.13 1.408 IT 6.617 49.000 8.912
to 120 6.617 0.0
6 34.07 0.0831 55.617 4.624 Vel = 7.020
0.0
34.07 13.536 K Factor = 9.26
7 9.15 1.408 iT 6.617 12.750 10.096
to 120 6.617 0.0
40 9.15 0.0073 19.367 0.141 VeI= 1.885
40 16.72 1.408 IT 6.617 73.000 10.237
to 120 6.617 0.0
8 25.87 0.0500 79.617 3.978 Vel = 5.331
0.0
25.87 14.215 K Factor = 6.86
9 25.86 1.408 2T 6.617 85.750 10.361
to 120 13.233 0.0
10 25.86 0.0499 98.983 4.942 Vel= 5.329
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
final Calculations - Standard
WESTERN STATES FIRE PROTECTION Page 10
TIBLDG2 Date 063004
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes
Point Qt Pf/UL Eqv. Ln. Total Pf Pn
0.0
25.86 15.303 K Factor = 6.61
1 7.53 2.203 12.370 9.609
to 120 0.0 0.0
3 7.53 0.0006 12.370 0.007 Vet = 0.634
3 28.76 2.203 12.000 9.616
to 120 0.0 0.0
5 36.29 0.0106 12.000 0.127 Vet = 3.055
5 26.88 2.203 12.000 9.743
to 120 0.0 0.0
7 63.17 0.0294 12.000 0.353 VeI= 5.317
7 -9.15 2.203 12.000 10.096
to 120 0.0 0.0
9 54.02 0.0221 12.000 0.265 Vet = 4.547
9 -25.85 2.203 6.500 10.361
to 120 0.0 0.0
11 28.17 0.0066 6.500 0.043 VeI= 2.371
11 0.0 1.408 2E 3.308 90.830 10.404
to 120 2T 6.617 19.850 0.0
12 28.17 0.0585 110.680 6.473 Vet = 5.805
0.0
28.17 16.877 KFactor 6.86
1 -7.53 1.408 IT 6.617 12.750 9.609
to 120 6.617 0.0
36 -7.53 -0.0051 19.367 -0.099 Vet = 1.552
36 15.91 1.408 20.000 9.510
to 120 0.0 0.0
37 8.38 0.0062 20.000 0.124 Vet = 1.727
37 16.17 1.408 4E 3.308 58.620 9.634
to 120 IT 6.617 19.850 0.0
2 24.55 0.0453 78.470 3.558 Vet = 5.059
2 0.0 2.203 12.000 13.193
to 120 0.0 0.0
4 24.55 0.0052 12.000 0.062 Vet = 2.066
4 31.33 2.203 12.000 13.255
to 120 0.0 0.0
6 55.88 0.0235 12.000 0.282 Vet = 4.703
6 34.07 2.203 12.000 13.536
to 120 0.0 0.0
8 89.95 0.0567 12.000 0.680 Vet = 7.571
8 25.87 2.203 12.000 14.216
to 120 0.0 0.0
10 115.82 0.0904 12.000 1.085 Vel = 9.749
10 25.86 2.203 12.000 15.301
to 120 0.0 0.0
12 141.68 0.1312 12.000 1.575 Vel = 11.925
12 28.16 2.067 1 5.000 19.790 16.876
to 120 5.000 0.0
13 169.84 0.2503 24.790 6.206 Vet = 16.239
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Standard
WESTERN STATES FIRE PROTECTION Page 11
TIBLDG2 Date 063004
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv Notes
Point Qt Pf/UL Eqv. Ln. Total Pf Pn
13 0.0 4.026 1.000 23.082
to 120 0.0 5.847
TEST 169.84 0.0100 1.000 0.010 Vel = 4.280
.0
169.84 28.939 KFactor= 31.57
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
.AutoPbaking Summary
WESTERN STATES FIRE PROTECTION Page 12 TIBLDG2 Date 063004
Auto Peaking Summary - List of Pipes for Area Calculated
From
Left
Side
To Length From
Right
Side
To Length
37 2 48.620 1 36 22.750
40 8 63.000 3 44 22.750
43 6 39.000 5 41 22.750
45 4 51.000 7 40 22.750
37 2 58.620 1 36 12.750
40 8 73.000 3 44 12.750
43 6 49.000 5 41 12.750
45 4 61.000 7 40 12.750
Flow Pressure Pressure
Required Required Differential
Left 20.000 I 171.90 28.809 -0.147 Left 10.000 I 171.02 28.956 0.000 Area Calculated I 169.84 28.938 -0.018 Right 10.000 I 168.26 28.732 -0.224
Typical Distance Between Heads = 10.000
Split Point Used in Worst Area Peaked = 0007
Split Point Used in Area Calculated = D007
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Bulletin 136 Rev.L
iiabid Model Fl FR
Model Fl FR Recessed
Quick Response
Sprinklers
Model Fl FR Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
- HSW 1 Deflector
Model Fl FR Recessed Sprinkler Types
Recessed Pendent
Recessed Horizontal Sidewall
- HSW 1 Deflector
Upright Pendent
Listings & Approvals
Listed by Underwriters Laboratories, Inc. (UL)
Listed by Underwriters' Laboratories of Canada (ULC)
Certified by FM Approvals
Loss Prevention Council (LPC, UK) NYC BS&A No. 587-75-SA
Meets MIL-S-901C and MIL-STD 167-1
Verband der Schadenversicherer (VdS, Germany)
NYC MEA 258-93-E
UL Listing Category
Sprinklers, Automatic & Open
Quick Response Sprinkler
UL Guide Number
VNIV
Product Description
Reliable Models F1FR and F1FR Recessed Sprinklers are
quick response sprinklers which combine the durability of a
standard sprinkler with the attractive low profile of a decorative
sprinkler.
The Models Fl FR and Fl FR Recessed automatic sprinklers
utilize a 3.0 mm frangible glass bulb. These sprinklers have
demonstrated response times in laboratory tests which are five
to ten times faster than standard response sprinklers. This
quick response enables the Model Fl FR and Fl FR Recessed
sprinklers to apply water to a fire much faster than standard
sprinklers of the same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely manufac-
tured glass capsule. This glass bulb is specially constructed to
provide fast thermal response. The balance of parts are made
of brass, copper and beryllium nickel.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid ex-
pands, forcing the bubble smaller and smaller as the liquid
pressure increases. Continued heating forces the liquid to
push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
The temperature rating of the sprinkler is identified by the
color of the glass bulb.
Vertical Sidewall Conventional
Recessed Pendent
Application
Quick response sprinklers are used in fixed fire protec-
tion systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflector
style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection Asso-
ciation or the approving Authority Having Jurisdiction.
Quick response sprinklers are intended for installation as
specified in NFPA 13. Quick response sprinklers and stan-
dard response sprinklers should not be intermixed.
Horizontal Sidewall
HSW 1 Deflector
The Reliable Automatic Sprinkler Co., Inc. 525 North MacQuesten Parkway, Mount Vernon, New York 10552
Model Fl FR Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Sprinkler Type Standard-Upright (SSU) and Pendent (SSP)
Deflectors Marked to Indicate Position
K Factor Sprinkler
Height
Approval
Organization
Sprinkler Identification
Number (SIN) US Metric SSU SSp 72" (15mm) Standard Orifice with 72" NPT (AX] Thread 5.6 80 2.2' (56mm) 123,45,6,7 R3625 R3615
%" (20mm) Large Orifice with 72" NPT (R read 8.0 115 23" (58mm) 1.2,3,4,7,8 R3622 R3612
3(S" (17mm) Small Orifice with 7," NPT (AX) Thread 4.2 60 2.54" (65mm) 1,2,8 R3623 R3613 72" (10mm) Small Orifice with 7," NPT (AX) Thread 2.8 40 2.54" (65mm) 1,2,8 R3621 R3611
10mm Orifice XLH with F"Thread 4.2 60 56.1mm 41617 R3624 R3614
Conventional-Install in Upright or Pendent Position
4.2
5.6
I 8.0
60 80
115
56.1mm
56.1mm
58.4mm
-
4,6,7
4,7
R3674
R3675
R3672
lomm Orifice xLH with AXThread 15mm Standard Orifice with 7," NPT (RX) Thread 20mm Large Orifice with 3/4" NPT (R36) Thread
Upright Pendent Upright Conventional
Model Fl FR Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model RC1 Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread
Size
K Factor Sprinkler
Height
Approva01)
Organizations
Sprinkler Identification
Number (SIN) US Metric
72" (15mm) 7," NPT (RI/2) 5.6 80 2.2" (56mm) 1,2,3,4.5.7,8 R3615
(20mm) 72" NPT (R34) 8.0 115 2.3" (58mm) 1,2,3 R3612 x: (11mm) 7," NPT (RY2) 4.2 60 2.54"(65mm) 1,2,8 R3613
72" (10mm) 7,"NPT(RY2) 2.8 40 254" (65mm) 1,2,8 R3611
10mm 4.2 60 56.1mm 4,7 R3614 (1) Refer to escutcheon data table for approvals and dimensions.
2 1/4(67'.2mm) lZ D(
(46.2 75/16' 2m
I
VMLM I L fl
cEcN
nrw m(l)
03 ' r1 r°'
j I (3.2mm)
2 (27/32' DL'. ________ -. 72.2.n.n ) t32'l0
(7) REFER 70 EScu7ClffCN DITA I$ai M APPROVALS AND DIAN7S
2.
Model Fl FR Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
Nominal Orifice Thread Size K Factor
US I Metric Sprinkler Height Approval
Organizations
Sprinkler Identification
Number (SIN)
Y2" ½" NPT (R½) 5.6 80 2.2° (56mm) 1,2,3.6,8
R3685 15mm ½" NPT (R½) 5.6 80 2.2° (56mm) 4(1)
(1) LPC Approval is for Pendent position only.
I Orientation Deflector to Ceiling I
Dimension (Min. Max.)
I Upright 4° - 12" 002mm - 305mm) I I Pendent I 6" - 12° (152mm - 305mm) I
Vertical Sidewall
Model Fl FR Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread
Size
K Factor I Sprinkler
I Length
I Approval Organizations I and Type of Approval I Sprinkler I
Identification I I Number I (SIN) US I Metric I Light
Hazard
I Ordinary I Hazard
/2° (15mm) /2° NPT(R'h) 5.6 80 J 2.63" (67mm) I 1.2,3,5,8 1,2,5,8 R3635
NOTE: UL and ULC Listing permits use with Fl or F2 recessed escutcheon.
...
Horizontal Sidewall
3.
Installation
Quick response sprinklers are intended for installation
as specified in NFPA 13. Quick response sprinklers and
standard response sprinklers should not be intermixed.
The Model Fl FR Recessed Quick Response Sprinklers
are to be installed as shown. The Model Fl or F2 Escutch-
eons illustrated are the only recessed escutcheons to be
used with the Model Fl FR Sprinklers. The use of any other
recessed escutcheon will void all approvals and negate all
warranties.
When installing Model Fl FR Sprinklers, use the Model D
Sprinkler Wrench. When installing Model Fl FR Recessed
Sidewall Sprinklers, use the Model GFR1 Sprinkler
Wrench. Use the Model RCl Wrench for installing Fl FR
Recessed Pendent Sprinklers. Any other type of wrench
may damage these sprinklers.
Temperature Ratings
Classification
Sprinkler
Temperature Max. Ambient
Temp.
Bulb
Color 'c l
Ordinary 57 1 135 1F(38C) Orange Ordinary 68 I 155 110F(38"c) Red Intermediate 79 I 175 150-F(660C) Yellow
Intermediate 93 I 2W 150°F(66'C) Green
High (1) 141 286 225°F(107°c) Blue
Not available for recessed sprinklers.
Escutcheon Data
Escutcheon "A" FaceofFlthng
Modd Mxvvals Adiustrio toCdMVor
Fl 12,4 (19mm) (19mm) (5mm-24mm)
F2 1,23,4,5,7,8 1"
(13mm) (25mm) (5mm- 17mm)
F1' 1,2 Fully Recessed 7,, 16
Push (11mm)
1,2 Fully Retracted %" Thread-off
(24mm)
Maintenance
The Models Fl FR and Fl FR Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gen-
tle vacuuming. Remove any sprinkler which has been
painted (other than factory applied) or damaged in any
way. A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprin-
klers. Prior to installation, sprinklers should be maintained
in the original cartons and packaging until used to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non-operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Sidewall (Vertical, Horizontal HSW1)
Recessed Pendent
Recessed Horizontal Sidewall HSW1
Finishes (1) (2)
Standard Finishes
Sprinkler Escutcheon
Bronze Brass
Chrome Plated Chrome Plated (3)
White Polyester Coated White Painted (3)
Special Application Finishes
Sprinkler Escutcheon
Bright Brass Bright Brass
Black Plated Black Plated
Black Paint Black Paint
Off White Off White
Satin Chrome Satin Chrome
(') Other finishes and colors are available on special order.
Consult the factory for details.
FM Approvals is limited to bronze and brass, chrome or black
plated finishes only.
FP Push-on/Thread-off escutcheon
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
Orifice Size
Deflector Type
Temperature Rating
Sprinkler Finish
Escutcheon Type
Escutcheon Finish (where applicable)
Note: When Model F1FR Recessed sprinklers are
ordered, the sprinklers and escutcheons are packaged
separately.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputa-
ble sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc.
(800)431-1588 Sales Offices
(800)848-6051 Sales Fax
(914)668-3470 Corporate Offices
www.rellablespdnkler.com Internet Address
®Recycled
Paper
Revision lines indicate updated or new data
EG. Printed In U.S.A. 3103 P)N9999970027