HomeMy WebLinkAbout2036 CORTE DEL NOGAL; ; AS100139; Permit5/9/24, 9:03 AM AS100139 Permit Data
City of Carlsbad
Sprinkler Permit
2036 CORTE DEL
Job Address:
NOGAL
Permit Type: SPRINK
Parcel No: 2130612900
Lot #: 0
Permit No: AS100139
Status: ISSUED
Applied 11/3/2010
Approved: 11/3/2010
Reference No.: Issued: 11/3/2010
PC #: Inspector:
Project Title: CRW T.I. FIRE SPRINKLER PLAN CHECK & INSPECTIONS
Applicant:
AZTEC FIRE & SAFETY
8107 COMMERCIAL ST
LA MESA, CA
Owner:
RU INVESTMENTS L L C
C/O MICHAEL BELLO
2350 SE BRISTOL ST
NEWPORT BEACH CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
130 0 130 0
about:blank Ill
Vertical Sidewall Conventional
Bulletin 014 Rev. D
Model Fl FR Series
Quick Response
Standard Spray
Horizontal Sidewall Recessed
Pendent/F1/F2
Upright Pendent
CD C
CD
0
CD <
Le
ReIiabk
Model Fl FR 56 Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
Model Fl FR 56 Recessed Sprinkler Types
Standard Pendent/F1/F2/FP
Horizontal Sidewall
Model Fl FR 56 Concealed Sprinkler Types
Standard Pendent
Listing & Approvals
Underwriters Laboratories Inc. and Certified for
Canada (cULus).
Factory Mutual Approvals (FM)
Loss Prevention Council (LPCB, UK)
VdS Schadenverhutung GmbH
UL Listing Category
Sprinklers, Automatic & Open (VNlV)
Quick Response Sprinkler
Product Description
Reliable Models F1FR, Series Sprinklers are quick re-
sponse sprinklers which combine the durability of a stan-
dard sprinkler with the attractive low profile of a decorative
sprinkler.
The Models F1FR Series Recessed automatic sprinklers
utilize a 3.0 mm frangible glass bulb. These sprinklers have
demonstrated response times in laboratory tests which
are five to ten times faster than standard response sprin-
klers. This quick response enables the Model F1FR Series
sprinklers to apply water to a fire much faster than standard
sprinklers of the same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely manu-
factured glass capsule. This glass bulb is specially con-
structed to provide fast thermal response.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid
expands, forcing the bubble smaller and smaller as the liq-
uid pressure increases. Continued heating forces the liquid
to push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
Recessed
Horizontal Sidewall
Application
Quick response sprinklers are used in fixed fire protèc-
tion systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflec-
tor style and sprinkler type are in accordance with the lat-
est published standards of the National Fire Protection As-
sociation or the approving Authority Having Jurisdiction.
Quick response sprinklers are intended for installation as
specified in NFPA 13. Quick response sprinklers and stan-
dard response sprinklers should not be intermixed.
v r ).
:.•
Recessed
Pendent/FP
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model Fl FR Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread
Size
Nominal K Factor Sprinkler
Height
Approval
Organization
Sprinkler Identification Number
(SIN)
US Metric Upright j Pendent
Standard-Upright (SSU) and pendent Deflectors Marked to Indicate Position
½' (15mm) ½" NPT(RY2) 5.6 1 80 2.25" (57mm) 1 1, 2. 3. 4 RA142501 RA 1414 (X2)
Conventional-Install in Upright or Pendent Position
15mm) ½" NPT(RY2) 5.6 1 80 1 57mm 1 3.4 RA1475
' cULus listed corrosion resistant (Polyester coated) sprinkler.
(21 Polyester coated FM approved sprinkler.
t.4
Upright Pendent Conventional
Model Fl FR 56 Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model GFR2 Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread
Size
K Factor Sprinkler
Height
Sprinkler Identification Number
(SIN) US Metric
1/2" (15mm) ½" NPT(R½) 5.6 80 2.25" (57mm) RA1414
Refer to escutcheon data table for approvals and dimensions.
1• I
Model F1FR 56/F1 or F2
2 5/8 014 (66.7mm) —.
HOLE IN CEILING
2 5/I6 DL4 (58.7mm) -
CUP
IX ;12 REDUCER
I I
\ I /
CEILING
FACE OF F,mNG
To FAC E OF CEILING IMENSION
0)
ADJUSTMENT
011r,"2
(I) REFER TO FP ESCUTCHEON DATA TABLE FOR APPROVALS AND DIMENSIONS.
Model F1FR 56/FP
2.
Vertical Sidewall
Model Fl FR Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
Nominal Nominal K Factor Sprinkler Approval Sprinkler
US I
I Metric Orifice Thread Size Height Organizations Identification
Numbers (SIN)
1/2" (15mm) ½" NPT(R1/2) 5.6 8.0 2.25" (57mm) 1:2.3.4
RA1485 15mm ½" NPT(R1/2) 5.6 8.0 2.25" (57mm) 4()
"ILPC Approval is for pendent position only.
Sprinkler Type Deflector to Ceiling Distance
(Min. - Max.)
Upright 4" (102mm) - 12" (305mm)
Pendent 4" (102mm) - 12" (305mm)
Model Fl FR Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW
Installation Wrench: Model D Sprinkler Wrench
Installation Data: Horizontal Sidewall
Nominal K Factor Sprinkler Approval Organizations Sprinkler
_________________ Height and Type of Approval Nominal Orifice Thread Size Identification
US I Metric Light Hazard Ordinary O I Numbers (SIN) Hazard
½" (15mm) ½" NPT (R1/2) 5.6 80 2.63" (67mm) 1,2 1 RA1435
FACE OF FITTING -
To FACE OF CEILING
DIMENSION I 1/4" MIN.
[31.8mm) I -2 1/4" HOLE DL4. 4" 6"
CEILING TO
[57.2mm] [3 2mm] [101.6mm-152.4mm]
1" X 1/2" REDUCER DEFLECTOR
- 1 15116" D14
(49.2m 27/32" DIA.
[72.2mm)
I W771 lt,~N~Y TURN COLLAR
TIGHT AGAINST SPRINKLER
WRENCH BOSS,
o,JFGoJ
ADJUSTMENT
(1) REFER TO ESCUTCHEON DATA TABLE FOR APPROVALS AND DIMENSIONS.
Horizontal Sidewall
3.
Model Fl FR Quick Response Concealed Pendent Sprinklers
Installation Wrench: Model RC1 Sprinkler Wrench
Technical Data:
Nominal
Orifice
"K" Factor Thread
Size Model
Temp. Rating Max.
Ambient
Temp
Bulb
Color Approvals
Sprinkler
Identification
Number(SIN) US Metric Sprinkler Cover
/2' (15mm) 5.6 80 112" NPT F1FR 1350F/570C 1350F/570C 100°F/38°C Orange 12 2 RA1414
1/2" (15mm) 5.6 80 ½' NPT I F1FR I 155°F/68°C 1350F/57CC 1000F/38CC I Red 1 1. 2, 411 RA1414
5.6 80 112" NPT F1FR 1750F/790C 1650F/740C 100°F/38°C Yellow 1.2 RA1414
5.6 80 ½' NPT F1FR 200°F/930C 1 1650F/740C 100°F/380C Green 1, 2 RA1414
For VdS only = 155CF/680C Norbulb and 1/2 [12.7mm] adjustment.
/1' ,LJUS1FIT
Figure 1
Installation Aid
A protective cap is included for use during installation.
Important: The F1FR 56 Sprinkler with Model CCP cover
plate is not an FM Approved combination.
Installation
Quick response sprinklers are intended for installation
as specified in NFPA 13. Quick response sprinklers and
standard response sprinklers should not be intermixed.
The Model F1FR 56 Recessed Quick Response Sprin-
klers are to be installed as shown. The Model Fl or F2 Es-
cutcheons illustrated are the only recessed escutcheons
to be used with the Model F1FR 56 Sprinklers. The use
of any other recessed escutcheon will void all approvals
and negate all warranties.
When installing Model F1FR 56 Sprinklers, use the
Model D Sprinkler Wrench. Use the Model GFR2 Wrench
for installing Fl FR 56 Recessed Pendent Sprinklers. Any
other type of wrench may damage these sprinklers.
NOTE: A leak tight ½" NPT (R1/2) sprinkler joint can
be obtained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m).
Do not tighten sprinklers over maximum recommended
torque. It may cause leakage or impairment of the sprin-
klers.
The Model Fl FR 56/ CCP Concealed Sprinkler uses the
½" orifice, ½" NPT (R1/2), 135°F (57°C), 155°F (681C),
175°F (79°C) or 200°F (93°C) Model F1FR 56 Pendent
Figure 2
Sprinkler with a threaded Model CCP cup which is fac-
tory attached to the sprinkler. The assembly is complet-
ed by the installation of the attractive, low profile, 135°F
(57°C) or 165°F (74°C) rated Model CCP push on cover
plate assembly. The cover plate and sprinkler cup as-
semblies are joined using a cover plate skirt with flexible
tabs for threaded engagement. A choice of two cover
plate assemblies provide either ½" (13mm) or /16" (8mm)
of cover adjustment.
Do not install these sprinklers in ceiling which have
positive pressure in the space above.
After a 2 /8" (67mm) diameter hole is cut in the ceil-
ing, the sprinkler is easily installed with the Model RC1
Wrench. A Teflon* based thread sealant should be
applied to the sprinkler threads only. The Model RC1
Wrench is then used to engage the sprinkler wrenching
surfaces and to install the sprinkler in the fitting. When
inserting or removing the wrench from the sprinkler/cup
assembly, care should be taken to prevent damage to
the sprinkler. DO NOT WRENCH ON ANY OTHER PART
OF THE SPRINKLER. The cover plate is then pushed
onto the cup. Final adjustment is made by hand turning
the cover plate until the skirt flange makes full contact
with the ceiling. Cover plate removal requires turning in
the counter clockwise direction.
After installation, inspect all sprinklers to ensure that
there is a gap between the cover plate and ceiling and
that the four cup slots are open and free from any air flow
impediment to the space above.
Concealed cover plate/cup assemblies are listed only
for use with specific sprinklers. The use of any other con-
cealed cover plate/cup assembly with the Model F1FR
56 Pendent Sprinkler or the use of the Model CCP Con-
cealed cover plate assembly on any sprinkler with which
it is not specifically listed my prevent good fire protection
and will void all guarantees, warranties, listings and ap-
provals.
Glass bulb sprinklers have orange bulb protectors to
minimize bulb damage during shipping, handling and
installation. REMOVE THIS PROTECTION AT THE TIME
THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR
FIRE PROTECTION. Removal of the protectors before this
time may leave the bulb vulnerable to damage. RASCO
wrenches are designed to install sprinklers when covers
are in place. REMOVE PROTECTORS BY UNDOING THE
CLASP BY HAND. DO NOT USE TOOLS TO REMOVE
THE PROTECTORS.
Temperature Ratings
Classification
Sprinkler
Temperature Max. Ambient
Temp. Bulb Color
0 OF
Ordinary 57 135 100°F (38°C) Orange
Ordinary 68 155 100°F (38°C) Red
Intermediate 79 175 150°F (66°C) Yellow
Intermediate 93 200 150°F (66°C) Green
High " 1 141 1 286 1 225°F (107°C) I Blue
Not available for recessed sprinklers.
I Escutcheon Data (1)
Escutcheon "A" Faceof Fitting to
Model Approvals Adjustment INmension Ceiling or Wall
Fl 1.3,4 Max Recess 1W (38.1mm) /E' -
Mn Recess 3/4" (19.lrmi) (5rrirn - 24rwn)
F2 1,2.3 ,4 Max Recess 1 ./' (3B.1 MM) 3/-.67- lb
Min Recess 1" (25rrrn) (5mm - 17rmi)
J) Push wv 1 4 Max Recessed /16 (llrrrn) 172 (38.1rrin)
Thread-off Min Recessed I Is (24rr1n) 1' (254am)
SIN: RA1435 - cULus and FM permts use with Fl or F2 escutcheons for light
hazard only.
Maintenance
The Models Fl FR 56 and Fl FR 56 Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or
gentle vacuuming. Remove any sprinkler which has
been painted (other than factory applied) or damaged
in any way. A stock of spare sprinklers should be main-
tained to allow quick replacement of damaged or oper-
ated sprinklers. Prior to installation, sprinklers should be
maintained in the original cartons and packaging to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non-operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Recessed Pendent
Vertical Sidewall
Horizontal Sidewall
Recessed Horizontal sidewall
Concealed pendent
Finishes (1)
Standard Finishes
Sprinkler Escutcheon Cover plate
Bronze Brass
Chrome Plated Chrome Chrome
White Polyester Plated White
Coated ON White Painted
SpeciP Application Finishes
Sprinkler Escutcheon Cover plate
Bright Brass ' Bright Brass Bright Brass
Black Plated Black Plated Satin
Black Paint (2) Black Paint Oft White
Oft White (2) Off White Black Paint
Satin Chrome Satin Chrome Black Plated
(" Other finishes and colors are available on special order.
Consult the factory for details.
(2) cULus Listed only.
131 200OF(93°C) maximum.
,41 cULus listed "corrosion resistance" applies to SIN Numbers
RA1425 (Upright) and RA1414 (Pendent) in standard black or white.
' FM Approvals finish as Polyester coated" applies to SIN Number
RA1414 (Pendent) in standard black or white.
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
Orifice Size
Deflector Type
Temperature Rating
Sprinkler Finish
Escutcheon Type
Escutcheon Finish (where applicable)
Cover plate Model
Cover plate Thread size
Cover plate Temperature
Cover plate Adjustment
Cover plate Finish
Note: When Model F1FR 56 Recessed sprinklers are ordered, the
sprinklers and escutcheons are packaged separately.
5.
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
IeIiabk ®Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A 02/10 PIN 9999970300
Reliable...For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
Automatic sprinklers
Flush automatic sprinklers
Recessed automatic sprinklers
Concealed automatic sprinklers
Adjustable automatic sprinklers
Dry automatic sprinklers
Intermediate level sprinklers
Open sprinklers
Spray nozzles
Alarm valves
Retarding chambers
Dry pipe valves
Accelerators for dry pipe valves
Mechanical sprinkler alarms
Electrical sprinkler alarm switches
Water flow detectors
Deluge valves
Detector check valves
Check valves
Electrical system
Sprinkler emergency cabinets
Sprinkler wrenches
Sprinkler escutcheons and guards
Inspectors test connections
Sight drains
Ball drips and drum drips
Control valve seals
Air maintenance devices
Air compressors
Pressure gauges ldentification signs
Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years. and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
As i (5-b i sl
Fig. 25 - Surge Restrainer c®usLISTED
Size Range - One size fits 3/4" thru 2" pipe.
Material - Pre-Galvanized Steel
Function - Designed to be used in conjunction with TOLCO® Band Hangers to
restrict the upward movement of piping as it occurs during sprinkler head
activation or earthquake type activity. The surge restrainer is easily and efficient-
ly installed by snapping into a locking position on the band hanger. This product
is intended to satisfy the requirements as indicated in the National Fire Protection
Association (NFPA 13, 1999 Edition), 6-2.3.3, 6-2.3.4 and A-6i-2.3.3 Can be
used to restrain either steel pipe or CPVC plastic Pipe.
Approvals - Underwriters' Laboratories Listed pall when used with TOLCO
band hangers Fig. 2, 2NFPA and 200, in the USA (UL) and
Canada (cUL).
Finish - Pre-Galvanized
Order By - Figure number and TOLCO band hanger, size from 3/4"
thru 2".
Patent #5,344,108
1
It ;
1/
<•
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE • CORONA. CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
v.iww.tnkn.,nm
Fig. 200 - "Trimline" Adjustable Band Hanger C® 115 LISTED
Size Range - 1/2" thru 8" pipe
Material - Carbon Steel, Mu. Galvanized to G90
specifications
Function - For fire sprinkler and other general piping
purposes. Knurled swivel nut design permits hanger
adjustment after installation.
Features -
(1/2" thru 2") Flared edges ease installation for
all pipe types and protect CPVC plastic pipe from
abrasion. Captured design keeps adjusting nut
from separating with hanger. Hanger is easily
installed around pipe.
(21/2" thru 8") Spring tension on nut holds it
securely in hanger before installation. Adjusting
nut is easily removed.
Approvals - Underwriters' Laboratories listed (1/2"
thru 8") in the USA (UL) and Canada (cUL) for steel
and CPVC plastic pipe and Factory Mutual Engineering
Approved (3/4" thru 8"). Conforms to Federal
Specifications WW-H-1 71 E, Type 10 and Manufacturers
Standardization Society SP-69, Type 10.
Maximum Temperature - 650°F
Finish - Mil. Galvanized. For Stainless Steel materi-
als, order TOLCOTM Fig. 200WON.
Order By - Figure number and pipe size
Dimensions • Weights
Pipe Rod Size Max. Rec. Approx.
Size Inch Metric A B Load Lbs. WtJ100
1/2 3/8 8mm or 10mm 31/8 2/8 400 11
3/4 3/8 8mm or 10mm 31A 21h 400 11
1 3/8 8mm or 10mm 33A 25A 400 12
11/4 3/8 8mm or 10mm 3W4 2/8 400 13
1½ 3/8 8mm or 10mm. 3/8 2/8 400 14
2 3/8 8mm or 10mm 41h 3 400 15
21h 3/8 10mm 55A 41/8 600 27
3 3/8 10mm 5/8 4 600 29
3½ 3/8 10mm 73A 51/4 600 34
4 3/8 10mm 7% 5 1000 35
5 1/2 12mm 91/8 61/4 1250 66
6 1/2 12mm 101/8 6V4 1250 73
8 1/2 12mm 131/8 8V4 1250 136
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
I CUSTOMER SERVICE • 800.786.5266
wwwtnIcn.,nm
114' 8002957 GST 100 1/4 x1"
114' 8003957 GST 200 1/4 x 2"
1/4' 8004957 GST 300 1/4 x 3"
3/8" 8006957 GST .75 1/4 x 314'
318" 8007957 GST 10 114 x1'
3/8" 8008957 GST 20 114 x 2"
4. 3/8' 8068925 GST 20-SS 114 x 2"
4. 3/8" 8009925 GST 25-380 3/8 x 2-112"
4. '? 318' 8010957 GST 30 114 a 3'-
318" 8069925 GST 30-SS 1/4 a 3'
3/8" 8011925 GST 40 1/4x4'
3/8" 8012925 GST 60 1/4x6'
1/2" 8013925 GST2 1/4x2"
'c.. 210 (7/16" OSB)
670 (3/4' Ply) -
1760 (Fir)
2060 (Fir)
564 (314" Ply)
210 (7116" OSB) 300 670 (3/4" Ply)
1760 (Fir) 850
1760 (Fir) 850
2113 (Fir) 1500
2060 (Fir) 1500
2060 (Fir)
2180 (Fir)
2230 (Fir)
1760 (Fir)
25 125
25 125
25 125
25 125
25 125
-
1475 25 125
25 125
25 125
1475 25 125 #14 Black
25 125 Nut Driver
Part #8113910
25 125
25 125 -
41 25 125
I AsiG-bi-sot
Product Features
'No pre-drilling required.
'Quick to install using the Sammy
Nut Driver with an 18V cordless
drill/driver.
Saves time from traditional
methods.
Reduces installation cost.
"Made in the U.S.A.
iii
1/2'
e01423
8015925,
GST 2.5-380 318 x 2-1/2
GST3 1/4x2'
zuj (Fir)
2275 (Fir) 25 125
1/2" 8016925 GST4 1/4x4" 2180 (Fir) 25 125
1/7 - 8017925 GST6 114 a 6" 2230 (Fir) 25 125 #14 SW Red
Nut Driver
Part # 8114910
IS.A.MMY . - -
Jam
:• .
b
3/8" 8139957 SII-GST20 114x2' 1257 (Fir) 1050 1475 25 125 125
O &-" 3/8' 8141957 SH-GST30 114x3 1720 (Fir) 1500 1475 25 125 1 #14 Black
Nut Driver 4 SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into Part #8113910
contact with the material you are installing into, continue drilling unlit nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations.
For the most up to date information, visit www.sammysuperscrew.com 4 \ (IS
_USA MADC IN
Note: When installing SWDR. follow the above instructions, then add retainer nut
and torque to 20 foot lbs. for maximum pullout in purlin steel.
Not less than 7 nominal width (1.112) up to 3-117 pipe: not less than
3'(2-1;21 nominal width 4'9 5 pipe
4
Minimum 2-117 from bottom for
/ ' ( . branch tines. M:nimurn 3 horn
1/ 1 / bottom for main lines. Exception: This 1! // / requirement shall not apply to2or
/ 1 thicker naing strips resting on top of I / steel beams,
/
- —
Product Features
No pre-drilling required.
:41 Quick to install using the Sammy
Nut Driver with an 18V cordless
drill/driver.
Saves time from traditional
methods.
Reduces installation cost.
Made in the U.S.A.
ComposiITruss
Co c_ed
ft -. . 'QMWM 0020M
- 1/4' 8018957 SWG 100 1/4 xi" 622 (Fir) 25 125
1/4' 8019957 SWG 200 1l4x 2" 1725 (Fir) 25 125
3/& 8020957 SWG 10 114 xr 622 (Fir) 300 25 125
4
I
3/8' 8021957 SWG 20 114 2' 1725 (Fir) 1050 25 125
3/8" 8073925 SWG 20-SS 1/4 x 2' 1725 (Fir) 850 25 125
#14 SW Red 318" 8022925 SWG 25.380 318 x 2.1/2' 2249 (Fir) 1500 25 125
Nut Driver L 3/8' 8023925 SWG 30 114 x 3" 1884 (Fir) 25 125
Part #8114910
INSTALLATION STEPS -U PM INTO WOOD & STEEL: IINSTALTION STEPS -Lj INTO WOOD & STEEL
Insert the appropriate nut driver into a 3/8"or 1/2" portable drill. 1. Insert the appropriate nut driver into a 3/8 or 1/2p0r1ab1e drill.
Insert the SAMMYS into the #14 (black) nut driver (p/n 8113910). Drill 2. Insert the SAMMYS into the #I4SW (red) nut driver (p/n 8114910). With drill
should be in a vertical position. unit in a horizontal position and at a right angle to the structural member,
begin installation.
Push the face of the nut driver tight to the member. When the
nut driver spins freely on the SAMMYS. stop drill and remove. 3. When the nut driver spins free on the SAMMYS. stop the drill and
remove.
The SAMMYS is now ready to receive 114",3/8 1/2" or metric
all thread rod, bolt stock. (The 1/2' requires the #14S W red nut driver) 4. The unit is now ready to receive 1/4 3l8ormetric all thread rod or
bolt stock.
Note: When installing DSTR, follow the above instructions.
then add retainer nut and torque to 20 foot lbs. for maximum
pullout in putlin steel.
2 MK ~ I I 119wInw,
SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the Overcomes into
contact with the material you are installing into, continue drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations.
CIoE CtoE -
I
C to E
I
CluE
t.
NOMINAL
SIZE
IN.
I END
to
END
IN....
IAPPR OX.I
WEIGHT
EACH
Lbs.•:
11/4 3.75 2.0
1 1/2 3.75 2.2
2 3.75 3.0
21/2 3.75 5.0
3 4.25 7.1
4 5.00 11.9
5 5.25 17.1
6 6.50 27.5
8 7.75 47.0
10 9.00 68.0
12 10.00 107.0
JiL
GROOVED FITTINGS!
MECHANICAL TEES 0 * <~>
LISTED LISTED APPROVED
For fire protection services request submittal GRS 1.3
?,R®PIPEPRODUCTS
Ni N2 N3 N4
GxMPT GxB GxG GxH
ADAPTER NIPPLES
NOMINAL
SIZE
IN.
I END
to
END
IN.
WEIGHT
EACH
Lbs.
1 3.00 0.40
1114 4.00 0.80
1 1/2 4.00 0.90
2 4.00 1.20
21/2 4.00 1.90
3 4.00 2.50
4 6.00 5.50
5 6.00 7.40
6 6.00 9.50
8 6.00 14.20
10 8.00 27.00
12 8.00 33.00
SW = Segmentaly welded steel
(d) = Ductile iron
Model MT-3 & MT-9 Mechanical tee serves the same function as MT-1 & MT-8 but
uses a steel electro plated u-bolt to save space and for easier installation in
tight places. It is ideal for direct connections with sprinkler heads and drop nipples.
HOUSING: Ductile iron ASTM A536 grade 65-45-12.
COATING: Zinc electroplated
U - BOLT: Carbon steel SAE grade 2, zinc plated.
NUT: Carbon steel ASTM A194, zinc plated.
GASKET: EPDM (-30 ... F to + 230.. .F)
THREADS: MT-3 NPT per ANSI/ASME BI.20.1
MT-9 British standard parallel (BSP) per BS21
NOMINAL SIZE IN.
MAX. WORKING
P.5.1.1
HOtE SIZE IN.
MT-9
aim 'ZSIONS.InC',--- APPROX. WEIGHT EACH Lbs A I C 0 K
1 114. 112 300 1.19 2.14 1.64 3.50 1.21 2.25 0.03
1 114. 314 300 1.19 2.14 1.64 3.50 1.21 2.25 0.87
1114. 1 300 1.19 2.27 1.61 3.50 1.21 2.25 1.06
1 112. 112 300 j 1.19 2.26 1.76 3.50 1.33 2.25 0.83
1 112.314 300 1.19 2.26 1.76 3.50 1.33 2.25 0.87
1112 x 1 300 1.19 2.39 1.73 3.50 1.33 2.25 1.06
2. 112 300 1.19 2.51 2.01 3.75 1.56 2.25 0.87
2. 314 300 1.19 2.51 2.01 3.75 1.56 2.25 0.94
2.1 300 1.19 2.64 1.98 3.75 1.56 2.25 1.09
2 112. 112 300 1.19 2.76 2.26 4.25 1.81 2.25 0.89
2 112. 314 300 1.19 2.76 2.28 4.25 1.81 2.25 0.98
2112. 1 300 1.19 2.88 2.22 4.25 1.81 2.25 1.14
3 O.D.x112 300 1.19 2.82 2.32 4.25 1.88 2.25 0.89
3 0.0.014 300 1.19 2.82 2.32 4.25 1.88 2.25 0.98
3 O.D. s1 300 1.19 2.95 1 2.29 4.25 1.88 2.25 1.14
Page 12
MECHANICAL TEES
STAR®PIPEPRODUCTS
LISTED LISTED APPROVED
For fire protection services request submittal GRS 1.3
Mechanical branch connections for reducing branch outlets without welding. The MT-1 is a bolted saddle type fitting with NPT female
threaded outlets. Design assures superior sealing, full pipe support, excellent stability and easy installation
iTHREADED MECHANICAL BRANCH111
NOMINAL
SIZE
IN.
1ULorFMMAX.1
WORKING
P.S.I./
HOLE
DIA.
+i25/-0.0 IN.
' NUTS/BOLTS
(INCH)
QTY. SIZE
' DIMENSIONS.Inch/r.m APPROX.-
WEIGHT
EACH
Lbs.
A B C 0 E
2x1 300 1.50 2 318x2 2.62 1.58 4.62 2:47 1.96 1.70
20114 300 1.75 2 318x2 2:62 1.58 4.62 2.47 1.94 1.70
20 1/2 300 1.75 2 318x2 2.62 1.58 4.62 2.86 1.94 1.70
2 112x1 300 1.50 2 112x2 314 3.12 1.83 5.56 3.38 2.46 3.60
2112x1114 300 200 2 112x23/4 312 183 556 338 244 360
2 112x1 112 300 2.00 2 112x2 3/4 3.12 1.83 5.56 3.38 2.44 3.60
3x1 300 1.50 2 112x2 3/4 3.44 2.15 6.25 3.91 2.78 3.80
3x1 1/4 300 2.00 2 1/2x2 314 3.44 2.15 625 3.91 2.76 3.80
3x1 1/2 300 2.00 2 1/2x2 3/4 3.44 2.15 6.25 3.91 2.76 3.80
3x2 300 2.50 2 1/2x2 3/4 3.44 2.15 6.25 3:91 2.74 4.40
3 1/2x2 300 2.50 2 1/2x2 314 3.88 2.46 6.62 3.92 3.18 4.60
4x1 300 1.50 2 1/2x2 3/4 4.00 2.65 7.25 3.83 3.34 4.60
4x1 1/4 300 2.00 2 1/2x2 3/4 4.00 2.65 7.25 3.83 3.32 4.60
4x1 1/2 300 2.00 2 1/2x2 3/4 4.00 2.65 7.25 3:83 3.32 4.60
4x2 300 2.50 2 112x2 3/4 4.00 2.65 7.25 4.52 3.30 4.80
4x2 1/2 300 2.75 2 1/2x2 3/4 4.00 2.65 7.25 4.52 3.07 5.40
5x1 1/2 300 2.00 2 5/8x4 4.75 3.18 8.30 3.83 4.07 6.93
5x2 300 2.50 2 5/8x4 4.75 3.18 8.30 3.83 4.05 7.48
5x2 1/2 300 2.75 2 5/8x4 4.75 3.18 8.30 3.83 3.82 7.61
6x1 1/2 300 2.00 2 5/8x4 5.12 3.71 9.38 3.86 4.44 7.50
6x2 300 2.50 2 5/8x4 5.12 3.71 9.38 4.42 4.42 8.00
6x2 1/2 300 2.75 2 5/8x4 5.12 3.71 9.38 4.42 4.19 8.00
8x2 300 2.50 2 3/4x4 1/4 6.25 4.83 12.32 4.48 5.55 11.60
All sizes may be used as mechanical crosses.
Threads are NPT per ANSI/ASME B1.20.1
* Contact Star Pipe Products for actual listings on specific pipes
Page 13
MECHANICAL TEES
IPDL1TS
LISTED LISTED APPROVED
For fire protection services request submittal GRS 1.3
Mechanical branch connections for reducing branch outlets without welding. The MT-2 is a bolted saddle type fitting with
grooved outlets. Design assures superior sealing, full pipe support, excellent stability and easy installation
- C - C - -0-
j 4GROOVED M ECHA NICAL BRANCH TE
NOMINAL
SIZE
IN.
' UL0rFMMAX.
WORKING
P.S.I./
' HOLE
DIA.
+.125/-0.0
IN.
' NUTS/BOLTS
(INCH)
QTY. SIZE
' DIMENSIONS-Inch/ APPROX.
WEIGHT
EACH
Lbs.
A B C D
3 O.D.xl 1/4 300 2.00 2 1/2x2 3/4 3.18 1.89 5.69 3.38 3.60
3 0.D.x1 1/2 300 2.00 2 112x2 3/4 3.18 1.89 5.69 3.38 3.60
3x1 1/2 300 2.00 2 112x2 3/4 3.44 2.15 6.25 3.91 3.80
3x2 300 2.50 2 1!2x2 3/4 3.44 2:15 6.25 3.91 4.40
4x1 1/2 300 2.00 2 112x2 3/4 4.00 2.64 7.25 3.83 4.60
4x2 300 2.50 2 1/2x2 3/4 4.00 2.65 7.25 4.52 4.80
4x2 112 300 2.75 2 1I2x2 3/ 4.00 2.65 7.25 4.52 5.40
4x3 O.D. 300 2.75 2 112x2 3/4 4.00 2.65 7.25 4.52 7.60
4x3 300 3.50 2 1/2x3 1/4 4.13 2.65 7.25 5.12 7.60
5x2 300 2.50 2 5/8x4 4.75 3.18 8.30 4.52 7.19
5x2 1/2 300 2.75 2 5/8x4 4.75 3.18 8.30 4.52 7.19
5x3 300 3.50 2 5/80 5.00 3.18 8.30 5.12 7.90
6x1 1/2 300 2.00 2 5/8x4 5.12 3.71 9.38 3.86 7.50
6x2 300 2.50 2 5/8x4 5.12 3.71 9.38 4.42 8.00
6x2 1/2 300 2:75 2 5/8x4 5.12 3.71 9.38 4.42 8.00
6x3 O.D. 300 2.75 2 5/8x4 5.12 3.71 9.38 4.42 9.70
6x3 300 3.50 2 5/8x4 5.25 3.71 9.38 5.62 9.70
6x4 300 4.50 2 5/8x4 5.38 3.71 9.38 6.50 13.60
6.5 O.D.x1 1/2 300 2.00 2 5/8x4 5.12 3.65 9.25 3.86 7.50
6.5 O.D.x2 300 2.50 2 5/8x4 5.12 3.65 9.25 4.42 8.00
6.5 O.D.x3 O.D. 300 2.75 2 5/8x4 5.12 3.65 9.25 4.42 8.00
6.5 O.D.x3 300 3.50 2 5/8x4 5.25 3.65 9.25 5.62 9.70
6.5 O.D.x4 300 4.50 2 5/8x4 5.38 3.65 9.38 6.50 13.60
8x2 1/2 300 2.75 2 3!4x4 1(4 6.25 4.83 12.32 4.48 11.60
8x3 300 3.50 2 3/4x4 1/4 6.50 4.83 12.32 5.68 12.60
8x4 300 4.50 2 3/4x4 1/4 6.38 4.83 12.32 6.59 15.30
All sizes may be used as mechanical crosses.
Outlet branch is machined per standard cut groove specification
* Contact Star Pipe Products for actual listings on specific pipes
Page 14
MECHANICAL TEES
STAR®PIPEPRODUCTS
là <S>
LISTED LISTED APPROVED
For fire protection services request submittal GRS 1.3
Mechanical branch connections for reducing
branch outlets without welding. The MT-8 is a
bolted saddle type filling with BSP female
threaded outlets. Design assures superior
sealing, full pipe support, excellent stability and
easy installation.
a!
C7~~W4
t 1-111771
I M T -8 *1 a THREADED MECHANICAL BRAN T EE
I NOMINAL IULorFMMAX.I HOLE NUTS/BOLTS ' DIMENSIONS -Inch/urn 1APPROX. I
SIZE WORKING DIA. (INCH) I WEIGHT IN. P.S.I./ +.25/-0.0 QT Y. SIZE A B C D E EACH
IN.. Lbs..,.
2x1 300 1.50 2 318x2 2.62 1.58 4.62 2.47 1.96 1.70
2x1 1/4 300 1.75 2 3/8x2 262 1.58 4.62 247 1.94 1.70
2x1 1/2 300 1.75 2 3/8x2 2.62 1.58 462 2.86 1.94 1.70
3ODx1 300 150 2 1/2x23!4 318 189 569 338 246 360
3 O.D.xl 1/4 300 2:00 2 1!2x2 3/4 3.18 1.89 5.69 3.38 244 3.60
3 O.D.x1l 1/2 300 2.00 2 1/2x2 3/4 3.18 1.89 5.69 3.38 2.44 3.60
• ..: .
3x1 300 1.50 2 112x2 3/4 3.44 2.15 6.25 3;91 2.78 3.80
3x1 1/4 300 2.00 2 1/2x2 3/4 3.44 2.15 6.25 3.91 2.76 3;80
3x1 1/2 300 2.00 2 1/2x2 3/4 3.44 2.15 6.25 3.91 2:76 3.80
3x2 390 2.50 2 1/2x2 3/4 3.44 2.15 6.25 3:1 274 4.40
4x1 300 1.50 2 1/2x2 3/4 4.00 2:65 7.25 3:83 3.34 4.60
4x1 1/4 300 2.00 2 1/2x2 3/4 4.00 2.65 7.25 3:83 3.32 4.60
4x1 1/2 300 2.00 2 1/2x2 3/4 4.00 2.65 7.25 3.83 3.32 4.60
4x2 300 2.50 2 1/2x2 3/4 4.00 2.65 7.25 4.52 3.30 4.80
4x3 O.D. 300 2.75 2 1/2x2 3/4 4.00 2.65 7.25 4.52 3.07 5.40
6 O.D.x 11/2 300 2.00 2 5/8x4 5.06 3.65 9.25 3:86 4ç2 7.50
6 O.D.x 2 300 2.50 2 5/8x4 5.06 3.65 9.25 4.42 4.32 8.00
6 O.D.x3 O.D. 570-t 2.75 2 5/8x4 5.12 3.65 9.25 4.42 4.19 8.00
All Sizes may be used as mechanical crosses.
Threads are British standard paralled jointing per BS 21.
* Contact Star Pipe Products for actual listings on specific pipes
Page 15
I I I I a 'M I I Fffj I I
:)
-
- -- -.. %•,- s--- -
—I.
-
'-,
- v--- .-
-
t
-
[&
Sched. em10@/Sc%ed i e- I )®
Fully Listed and FM Approved Sprinkler Pipe
When you specify Schedule-10/Schedule-40 sprinkler pipe you get a UL listed and FM approved product. Although these
products do not require separate approvals, Schedule-1O/Schedule-40 gives you the extra quality assurance you demand.
Our Sch-10 (lY"- 8") pipe and Sch-40 (1"- 2V.,") pipe have passed the same thorough lab testing as our other listed pipe
products. and receive periodic mill inspections from both UL and FM agents to ensure consistent quality.
Schedule-10/Schedule-40 product can be
"hot-dip" galvanized to meet FM
requirements for dry systems in
accordance with the zinc coating
specifications of ASTM A-123.
Our advanced formula mill coating of-
fers a clean, durable surface. It is also
paint-ready for custom color applications
without special preparation.
The internal surface of all black Allied
Tube & Conduit Fire Sprinkler pipe
products up to 4.5000" in diameter is
coated with our new Antibacterial For-
mula, "ABF". In scientific laboratory
test, ABS proved to have superior resis-
tance to microbial colonization of pipe
walls, thereby delaying or possibly pre-
venting the onset of Microbiologically
Influenced corrosion (MIC) when the
First Sprinkler System is first installed.
Meets "Buy American" requirement
and is available through distributors in
the USA, Canada and Mexico.
f ' 0 Specificationsi
NPS Nominal I.D. WI. WI. (1120 Filled) PcW WI/Lift (21') WI/Lift (24') Wt/lift (25)
In. mm In; mm Lbs/Fl; Kg/rn Lbs/Fl: Kg/rn Lift Lbs: Kg Lbs; Kg Lbs; Kg
1.049 1.680 2.05 70 2.470 2,822 2.940
25 26.6 2.5 3.05 70 1,120 1,280 1,334
11/4" 1.380 2.270 2.93 51 2,431 2,778 2,894
32 35.1 4.36 4.36 51 1,103 1,260 1,313
1½' 1.610 2.720 3.61 44 2,513 2,872 2,992
40 40.9 4.0 5.37 44 1,140 1,303 1,357
2.067 3.650 5.13 30 2,300 2.628 2,738
50 52.5 5.4 7.63 30 1,043 1,192 1,242
2W 2.469 5.790 7.86 19 2,310 2,640 2,750
65 62.7 8.6 11.73 19 1,048 1,197 1,247
Sch-10 Specifications
NPS Nominal I.D. WI. WI. (1120 Filled) Pcs/ WI/Lift (21') WI/Lift (24') WI/Lift (25')
In; mm In; mm Lbs/Fl; Kg/rn Lbs/Fl; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1" 1.097 1.400 1.81 91 2,675 3,053 3,185
25 27.9 2.1 2.70 91 1,213 1,385 1,445
11/4" 1.442 1.810 2.52 61 2,319 2,664 2,760
32 36.6 2.7 3.75 61 1,052 1,208 1.252
1W 1.682 2.080 3.04 61 2,664 3,045 3,172
40 42.7 3.1 4.52 61 1,208 1,381 1,439
2' 2.157 2.640 4.22 37 2,051 2,344 2,442
50 54.8 3.9 6.28 37 930 1,063 1,108
21h" 2.635 3.530 5.89 30 2,224 2,542 2.648
65 66.9 5.3 8.77 30 1,009 1,153 1,201
3" 3.260 4.330 7.94 19 1,728 1,975 2.057
80 82.8 6.4 11.82 19 784 896 933
4.260 5.610 11.78 19 2,238 22558 2.665
90 108.2 8.3 17.53 19 1,015 1,160 1,209
5.295 7.77 17.33 10 1,632 1,865 1,943
125 134.5 11.56 25.80 10 740 846 881
6.357 9.290 23.03 10 1,951 2,230 2,322
150 161.5 13.8 34.27 10 885 1,012 1.053
8" 8.249 16.490 40.15 7 2,424 2,770 2.885
200 209.5 24.5 59.75 7 1,100 1,256 1,309
Schedule-I 0/Schedule-40 pipe are in
compliance with the following:
ASTM A-135, and NFPA 13. Both pipe
products have a working pressure rating
of 300 psi maximum and also meet the
stringent requirement for the following
tests:
NXIelded Outlets
Hydrostatic Pressure
Side \Va1l Rupture
Vibration Test
tLICQ/Flow Control ç:) allied
TUBE & CONDUIT
@ <S> @
Listed Approved Listed
16100 S. Lathrop• Harvey, IL 60426 Customer Service:
11350 Norcom Rd. • Philadelphia, PA 19154 (800) 882-5543
2525 N. 27th Ave. • Phoenix, AZ 85009 Fax 708-339-1806
S5-3