HomeMy WebLinkAbout3440 VIA MERCATO; ; AS140217; Permit5/2/24, 3:54 PM AS140217 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address: 3440 VIA MERCATO
Permit Type: SPRINK
Parcel No: 2230507200
Lot #: 0
Reference No.:
Permit No: AS140217
Status: ISSUED
Applied 8/20/2014
Approved: 9/3/2014
Issued: 9/3/2014
PC #: Inspector:
Project Title: CHASE BANK NEW COMMERCIAL FIRE SPRINKLER INSTALLATION•
PER NFPA 13.
Applicant:
GUARDIAN FIRE PROTECTION
13941 E. IVANHOE ST
GILBERT, AZ
480-797-9133
Owner:
PROPERTY DEVELOPMENT CENTERS L L C
C/OSAFEWAY INC
5918 STONERIDGE MALL RD
PLEASANTON CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
202 0 202 0
about:blank Ill
Fire -Fire Sprinkler Hy
F Guardian Fire Protection Iopment, Inc.
CHASE BANK
Pagelj
I General Project Data Report
[General Data
Project Title:
Designed By:
Code Reference:
Client Name:
Address:
Company Name:
Company Address:
Phone:
Building Name:
Contact at Building:
Address Of Building:
CHASE BANK
RR
NFPA 13
GUARDIAN FIRE PROTECTION
361 E. IVANHOE ST
GUARDIAN FIRE DESIGN
1911W. SAWTOOTH WAY
480-797-0873
CHASE BANK
JODY ROBBINS
3440 VIA MERCATO
Project File Name:
Date:
Approving Agency:
Phone:
City, State Zip Code:
Representative:
City And State:
Building Owner:
Phone at Building:
City, State Zip Code:
1752-CHASE BANK - CARLSBAD
CA. .fiw
7/9/2014
AHJ
480-962-9393
GILBERT, AZ
RR
SAN TAN VALLEY, AZ
JP MORGAN CHASE BANK, N.A.
CARLSBAD, CA
LP!pJect Data - - - -
Description Of Hazard: LIGHT HAZARD Sprinkler System Type: Wet
Design Area Of Water Application: 1500 ft2 Maximum Area Per Sprinkler: 130 ft2
Default Sprinkler K-Factor: 5.60 K Default Pipe Material: DYNA-FLOW-10
Inside Hose Stream Allowance: 0.00 gpm Outside Hose Stream Allowance: 100.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm
Sprinkler Specifications
Make: VIKING Model: VK300
Size: 1/2 Temperature Rating: 200 F
Water Supply Test Data
Source Of Information: GUARDIAN FIRE PROT
Test Hydrant ID: Date Of Test: 6-22-14
Hydrant Elevation: 0 ft Static Pressure: (8280 psi
Test Flow Rate: 1453.00 gpm Test Residual Pressure: 72.80_ L psi LA Calculated System Flow Rate: 40147 gpm Calculated Inflow Residual Pressure: 53.91 psi
Available Residual Pressure At .
System Flow: psi
[Calculation Project Data
Calculation Mode: Demand
HMD Minimum Residual Pressure: 7.04 psi
Number Of Active Nodes: 27
Number Of Active Pipes: 26
Number Of Active Sprinklers: 17
AREA #1
Minimum Desired Flow Density: gpm/1t2
Number Of Inactive Pipes:
Number Of Inactiv.e..Sirink
These pl,tins hate hecn reviewed toi ippteun compliance
ill) the current applicable emides and iiid;irds in kirce
in the jurisdiction. The owner or 4.01111 ,1001, nu uiuliie
this I cviess in stippom of an application Cor a building
pLruiiim srnh the express tiitdriaiiding that this res less
in ni' was relic es the oss ncr or contractor or I heir
protessiiim;ai engineer or ai'chimect Ilir smile responsmhihi
for full compliance Willi said COtICS and standards.
including the building code or for any responsihillv for
deluciencies. errors. OlfllSSltSilS m, negligence in these
plans Whether or m'ot noted in this review.
Date: ft/i'
!ICoMlENl) APIR( )VAI.
11 khCslMlNl) AlIPW )VAI.. AS d ITFl)
e - Fire Sprinkler Hydraulics Calculation Program. . - :, Elite Softare Development, I
ardian Fire Protection CHASE BA
ert.AL85296 ... •... .,. Lha.S Pag
iFireSprinkler Input
INodeInPut Data
Area Group Sprinkler Pressure Node Elev (ft) Non-Sprinkler
Node Node Description Branch Dia KFactor (K) Estimate (psi) Branch Non- Flow (gpm)
No. Branch Description 'in' Branch Len. Branch Stnd Stnd Fittings Branch Sprk
Fittings (ft) KFactor (K)
l
1 Sprinkler ---- 5.60 10.05 18.00 0.00
0.000 0.0 ---- 0.0 0.00
2 Sprinkler ---- 5.60 10.24 18.00 0.00
0.000 0.0 ---- 0.0 0.00
3 Sprinkler ---- 5.60 11.07 18:00 0.00
0.000 0.0 ---- 0.0 0.00
4 Sprinkler ---- 5.60 12.60 18.00 0.00
-- ---- 0.000 0.0 ---- 0.0 0.00
5 Sprinkler ---- 5.60 7.04 18.00 0.00
0.000 0.0 ---- 0.0 - 0.00
6 Sprinkler ---- 5.60 7.23 18.00 . 0.00
----
0.000 0.0 ---- 0.0 0.00
1 Sprinkler ---- 5.60 7.81 18.00 0.00
0.000 0.0 ,---- 0.0 0.00
8 Sprinkler ---- 5.60 8.93 18.00 0.00
0.000 0.0 ---- 0.0 0.00
Sprinkler ---- 5.60 11.17 18.00 0.00
0.000 0.0 ---- 0.0 0.00
I
10 Sprinkler ---- 5.60 7.30 18.00 0.00
0.000 0.0 ---- 0.0 0.00
11 Sprinkler ---- 5.60 7.50 18.00 0.00
I . ---- 0.000 0.0 ---- 0.0 0.00
12 Sprinkler ---- 5.60 8.10 - 18.00 0.00
0.000 0.0 ---- 0.0 0.00
13 Sprinkler ---- 5.60 9.26 18.00 0.00
0.000 0.0 ---- 0.0 0.00
14 Sprinkler ---- 5.60 11.58 18.00 0.00
-. ---- 0.000 0.0 ---- 0.0 0.00
15 Sprinkler ---- 5.60 14.11 18.00 0.00
- ---- 0.000 0.0 ---- 0.0 0.0
16 Sprinkler ---- 5.60 14.37 18.00 0.00
- ---- 0.000 0.0 ---- 0.0 0.00_
17 Sprinkler ---- 5.60 15.47 18.00 0.00
0.000 0.0 ---- 0.0 0.00
18 No Discharge ---- N/A 18.86 15.00 0.00
---- 0.000 0.0 ---- 0.0 0.00
Fire - Fire Sprinkler Hydraulics Calculation Prógrám -
Guardian Fire Protection .
LGilbert, AL 85296
A
_L
- Elite Sftware Development, In
- .. CHASE BANK
Pagej
Fire Sprinkler Input Data - _1
.[Node Input Data (cont'd).
Area Group Node Node Description Branch Dia No. Branch Description in
/
Sprinkler
KFactor (K)
Branch Len.
(ft)
Pressure
Estimate (psi)
Branch Stnd
Fittings
Node Elev (ft)
Branch Non-
Stnd Fittings
(ft)
Non-Sprinkler
Flow (gpm)
Branch Sprk
KFactor(K)
19 No Discharge ----
0.000
N/A
0.0
11.18
----
18.00
0.0
0.00
0.00
20 No Discharge ---- N/A 19.00 15.00 0.00
0.000 0.0 ---:- 0.0 0.00
21 No Discharge ---- N/A 11.59 18.00 0.00
0.000 0.0 ---- 0.0 0.00
22 No Discharge ---- N/A 19.63 15.00 0.00
0.000 .0.0 0.0 0 .00
23 No Discharge ---- N/A 15.47 18.00 0.00
0.000 0.0 ---- 0.0 0.00
24 No Discharge ---- N/A 21.02 15.00 0.00
0.000 0.0 ---- P0.0 .0.00
25 No Discharge ---- N/A 30.92 15.00 0.00
0.000 0.0 ---- . 0.0 0.00
26 Non-Sprinkler . ---- N/A 46.79 0.00 100.00
0.000 0.0 ---- 0.0 0.00
27 No Discharge ---- N/A 53.91 0.00 0.00
0.000 0.0 ---- 0.0 0.00
Elite Software Developme4inc.1, i[fri:Fire Sprinkler Hydraulicè Calculation Program
I I Guardian Fire Proteàtion - . klt~~s - CHASE BANK I
[Gilbert, AL85296 "-,... Page4 I
PipeInput Data ' ..-.
CFactor Be End End Nominal T e Fitting Nominal Fitting Total
Node N d Pipe Description 0 e Diameter Groupat Length Length Length (gpm/inch-
(inch) (feet) (feet) (feet) psi)
1 2 DYNA-THREAD NT 1.250 0 8.10 0.00 8.10 120
2 3 DYNA-THREAD NT 1.250 0 9.40 0.00 9.40 120
3 4 DYNA-THREAD NT 1.250 0 8.00 0.00 8.00 120
5 6 DYNA-THREAD NT 1.250 0 11.10 0.00 11.10 120
6 7 DYNA-THREAD NT 1.250 0 9.00 0.00 9.00 120
7 8 DYNA-THREAD NT 1.250 0 8.10 0.00 8.10 120
8 19 DYNA-THREAD NT 1.250 0 9.10 0.00 9.10 120
9 19 DYNA-THREAD NT 1.250 0 0.11 0.00 0.11 120
10 11 .DYNA-THREADNT 1.250 - 0 11.10 0.00 11.10 120
11 12 DYNA-THREAD NT 1.250 0 9.00 0.00 9.00 120
12 13 DYNA-THREAD NT 1.250 0 8.10 0.00 8.10 120
13 21 DYNA-THREAD NT 1.250 0 9.10 0.00 9.10 120
14 21 DYNA-THREAD NT 1.250 0 0.11 0.00 0.11 120
15 16 DYNA-THREAD NT 1.250 0 8.10 0.00 8.10 120
16 23 DYNA-THREAD NT 1.250 0 9.10 0.00 9.10 120
17 23 DYNA-THREAD NT 1.250 0 0.11 0.00 0.11 120
4 18 DYNA-THREAD NT 1.250 0 El 4.60 9.93 14.53 120
19 20 DYNA-THREAD NT 1.250 0 2T 3.00 13.24 16.24 120
21 22 DYNA-THREAD NT 1.250 0 21 3.00 13.24 16.24 120
23 24 DYNA-THREAD NT 1.250 0 21 3.00 13.24 16.24 120
18 _20 DYNA-FLOW-10 2.500 0 9.60 0.00 9.60 120
20 22 DYNA-FLOW-10 2.500 0 11.00 0.00 11.00 120
22 24 DYNA-FLOW-10 2.500 0 11.00 0.00 11.00 120
24 25 DYNA-FLOW-10 2.500 0 E 41.00 9.33 50.33 120
25 26 DYNA-FLOW-10 2.500 0 BC 15.00 32.66 47.66 120
26 27 PVC C-900 PRESSURE 4.000 0 5ETG 276.00 21.00 297.00 150
[Fire - Fire Sprinkler Hydraulics CalculatiàriPrórim
, : ;'.•, .. Elite Software DeéIopnient, Inc. I Guardian Fire Protection l . CHASE BANK 00 LGiIbertAL85296. .•.. . ;.: .. '. .. . .. Pagj
Fire Sp` rinkleiOUtpüt Data..: .. .
OieraiINodeGroupiflgs.Oiitput.Data .. .. . .
Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm) -
1 2 0 -17.75 17.75 0.00. 0.00 10.05
2 1 0 17.75 17.92 0.00 0.00 10.24 0.00134
2 3 0 -35.67
3 2 0 35.67 18.63 0.00 0.00 11.07 0.00200
3_ 4 0 -54.30
4 3 0 54.30 19.88 0.00 0.00 . 12.60 0.00322
4 18 0 -74.17
.
5 6 0 -14.86 14.86 0.00 0.00 7.04 0.00137
6 5 0 14.86 15.06 0.00 0.00 7.23 0.00041
6 7 0 -29.92
7 6 0 29.92 - 15.65 0.00 0.00 7.81 0.00105
7 8 0 -45.56
8 7 0 45.56 16.73 0.00 0.00 8.93 0.00171
-- .8 19 0 -62.30
9 19 0 -18.72 18.72 0.00 0.00 11.17 0.00313
10 11 0 -15.13 15.14 0.00 0.00 7.30 0.00052
11- 10 0 15.13 15.34 0.00 0.00 7.50 0.00065
11 12 0 -30.48
12 11 0 . 30.48 15.94 0.00 0.00 8.10 0.00102
12 13 0 -46.41
13 12 0 46.41 .17.04 0.00 0.00 9.26 0.00177
13 21 0 -63.45
14 21 0 -19.05 19.06 0.00 0.00 11.58 0.00328
15 16 0 -21.03 21.03 0.00 0.00 14.11 0.00263
16 15 0 21.03 21.23 - 0.00 0.00 14.37 0.00291
16 23 0 -42.26
17 23. 0 -22.02 22.02 0.00 0.00 15.47 0.00403
18 . 4 0 74.17 0.00 0.00 0.00 18.86 0.00000
18 20 0 -74.17
19 8 0 62.30 0.00 0.00 0.00 11.18 -0.00001
19 9 0 18.72
19 20 0 -81.01
20 18 0 74.17 0.00 .0.00 0.00 19.00 0.00000
20 19 0 81.01
.20220 -155.19
Fire- Sprinkler Hydraulics Calculation Program - -. .. Elite Software Inc. Inc. Guardian Fire Protection
Azzo
CHASE BANK tGiIbert, AL_85296 - ' ' Page 6J
Fire Sprinkler Output Data 4
[..2yerall Nàde Groupings Output bata (cont'd) '
Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node 'Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)
21 14 0 19.05
21 22 0 -82.50
22 20 0 155.19 0.00 0.00 0.00 19.63 0.00000
22 21 0 82.50
--22 24 0 -237.69
23 16 0 42.26 0.00 0.00 0.00 15.47 0.00000
23 17 0 22.02
23 24 0 -64.28
24 22 0 237.69 0.00 0.00 0.00 21.02 0.00000
24 23 0 64.28
24 25 0 -301.97
25 24 0 301.97 0.00 0.00 0.00 30.92 0.00000
25 26 0 -301.97
26 25 0 301.97 0.00 100.00 0.00 46.79 -0.00012
26 27 0 -401.97
27 26 0 401.97 0.00 0.00 -401.97 53.91
F Fin- Fire Sprinkler Hydraulics Calculation Program
Guardian Fire Protection
LGilbert, AL 85296 . . -•
1 . Elite Software Dévelópment, Inc.]
CHASE BANK
Page 71
[Fire(Sprinkler Output Data -
fOverall PipeOutpUt Data ..
1'.,
...
Beg. Nodal Elevation Spk/Hose
End. KFactor Discharge
Node (K) (gpm)
Residual
Pressure
(psi)
Nom. Dia.
Inside Dia.
C-Value
q (gprn)
Velocity
(fps)
F. Lift
Fittings
Type-Grp
PieL:n.
Tot-Len
(ft)
PF-(psi)
PE-(psi)
PT-(psi)
1 5.60 18.00 17.75 10.05 1.25 17.75 0.02421 8.10 0.196
2 5.60 18.00 17.92 10.24 1.416 17.75 -----0.00 0.000
DYNA-THREAD NT 120 3.62 0 8.10 0.196
2 5.60 18.00 17.92 10.24 1.25 17.92 0.08809 9.40 0.828
3 5.60 18.00 18.63 11.07 1.416 35.67 -----0.00 0.000
DYNA-THREAD NT 120 7.27 0 9.40 0.828
3 5.60 18.00 18.63 11.07 1.25 18.63 0.19167 8.00 1.533
4 5.60 18.00 19.88 12.60 1.416 54.30 0.00 0.000
DYNA-THREAD NT 120 11.06 0 8.00 1.533
5 5.60 18.00 14.86 7.04 1.25 14.86 0.01743 11.10 0.193
6 5.60 18.00 15.06 7.23 1.416 14.86 0.00 0.000
DYNA-THREAD NT 120 3.03 0 11.10 0.193
6 5.60 18.00 15.06 7.23 1.25 15.06 0.06363 9.00 0.573
7 5.60 18.00 15.65. 7.81 1.416 29.92 0.00 0.000
DYNA-THREAD NT 120 6.10 0 9.00 0.573
7 5.60 18.00 15.65 7.81 1.25 15.65 0.13856 8.10 1.122
8 5.60 18.00 16.73 8.93 1.416 45.56 -----0.00 0.000
DYNA-THREAD NT 120 9.28 0 8.10 1.122
10 5.60 18.00 15.14 7.30 1.25 15.14 0.01803 11.10 0.200
11 5.60 18.00 15.34 7.50 1.416 15.13 -----0.00 0.000
DYNA-THREAD NT 120 3.08 0 11.10 0.200
11 5.60 18.00 15.34 7.50 1.25 15.34 0.06584 9.00 0.593
12 5.60 18.00 15.94 8.10 1.416 30.48 0.00 0.000
DYNA-THREAD NT . 120 6.21 0 9.00 0.593
12 5.60 18.00 15.94 8.10 1.25 - 15.94 0.14336 8.10 1.161
13 5.60 18.00 17.04 9.26 1.416 46.41 0.00 0.000
DYNA-THREAD NT . 120 9.46 0 8.10 1.161
15 5.60 18.00 21.03 14.11 1.25 21.03 0.03314 8.10 0.268
16 5.60 18.00 21.23 14.37 1.416 21.03 0.00 0.000
DYNA-THREAD NT 120 4.28 0 8.10 0.268
5.60 18.00 19.88 12.60 1.25 19.88 0.34136 4.60 4.960
18 0.00 15.00 0.00 18.86 1.416 74.17 ET 9.93 1.299
DYNA-THREAD NT 120 15.11 0 14.53 6.259
8 5.60 18.00 16.73 8.93 1.25 16.73 0.24715 9.10 2.249
19 0.00 18.00 0.00 11.18 1.416 62.30 0.00 0.000
DYNA-THREAD NT 120 12.69 0 9.10 2.249
9 5.60 18.00 18.72 11.17 1.25 18.72 . 0.02672 0.11 0.003
19 0.00 18.00 0.00 11.18 1.416 18.72 0.00 0.000
DYNA-THREAD NT 120 3.81 0 0.11 0.003
Fire Fire Sprinkler Hydraulics Calculation Program .. Elite Sàftware Development, Inc. 1 Guardian Fire Protection J CHASE BANK Gilbert, AL 85296 .. - Pagej
iFire SprinkièrOütpUtMai -
loverall Pipe Output bata
Beg. Nodal Spk/Hose Residual Elevation Discharge KFactor Pressure (feet) Inside Dia Fittings It Len PE-(psi)
Node (K) (gpm) (psi) C-Value Velocity
(fps) Type-Grp (ft) PT-(psi)
18 0.00 15.00 0.00 18.86 2.50 0.00 0.01465 9.60 0.141
20 0.00 15.00 0.00 19.00 2.703 74.17 -----0.00 0.000
DYNA-FLOW-10 120 4.15 0 9.60 0.141
19 0.00 18.00 0.00 11.18 1.25 0.00 0.40184 3.00 6.526
20 0.00 15.00 0.00 19.00 1.416 81.01 2T 13.24 1.299
DYNA-THREAD NT -12016.50 0.16.247.825
13 5.60 18.00 17.04 9.26 1.25 17.04 0.25568 9.10 2.327
21 0.00 18.00 0.00 11.59 1.416 63.45 0.00 0.000
DYNA-THREAD NT 120 12.93 0 9.10 2.327
14 5.60 18.00 19.06 11.58 1.25 19.06 0.02762 0.11 0.003
21 0.00 18.00 0.00 11.59 1.416 19.05 0.00 0.000
DYNA-THREAD NT 120 3.88 0 0.11 0.003
20 0.00 15.00 0.00 19.00 2.50 0.00 . 0.05740 11.00 0.631
22 0.00 15.00 0.00 19.63 2.703 155.19 0.00 0.000
DYNA-FLOW-10 120 8.68 0 11.00 0.631
21 0.00 18.00 0.00 11.59 1.25 0.00 0.41563 3.00 6.750
22 0.00 15.00 0.00 19.63 1.416 82.50 2T 13.24 1.299
DYNA-THREAD NT 120 16.81 0 16.24 8.049
16 5.60 18.00 21.23 14.37 1.25 21.23 0.12054 9.10 1.097
23 0.00 18.00 0.00 15.47 1.416 42.26 0.00 0.000
DYNA-THREAD NT 120 8.61 0 9.10 1.097
17 5.60 18.00 22.02 15.47 1.25 22.02 0.03609 0.11 0.004
23 0.00 18.00 0.00 15.47 1.416 22.02 0.00 0.000
DYNA-THREAD NT 120 4.49 0 0.11 0.004
22 0.00 15.00 0.00 19.63 2.50 0.00 0.12633 11.00 1.390
24 0.00 15.00 0.00 21.02 2.703 237.69 -----0.00 - 0.000
DYNA-FLOW-10 120 13.29 0 11.00 1.390
23 0.00 18.00 0.00 15.47 1.25 0.00 0.26191 3.00 4.253
24 0.00 15.00 0.00 21.02 1.416 64.28 2T 13.24 1.299
DYNA-THREAD NT 120 13.10 0 16.24 5.552
24 0.00 15.00 0.00 21.02 2.50 0.00 0.19671 41.00 9.901
25 0.00 15.00 0.00 30.92 2.703 301.97 E 9.33 0.000
DYNA-FLOW-10 120 16.88 0 50.33 9.901
25 0.00 15.00 0.00 30.92 2.50 0.00 0.19671 15.00 9.375
26 0.00 0.00 100.00 46.79 2.703 301.97 BC 32.66 6.495
DYNA-FLOW-10 120 16.88 0 47.66 15.870
26 0.00 0.00 100.00 46.79 4.00 0.00 0.02395 276.00 7.113
27 0.00 0.00 0.00 53.91 4.266 401.97 5ETG 21.00 0.000
PVC C-900 PRESSURE CLASS 150 9.02 0 297.00 7.113
Fire FliSprinkler Hydraulics Calculation Pràgram. - •-. . .. Elite Software DeeIóieñtlriè
Guardian Fire Protection CHASE BANK
- Gilbert, AL 85296 .. .. .'.-' * ... .........••-.. Page9,
Fire Sprinkler OutpUt Data 1
[Overall Sprinkler Output Data
Flowing Sprinkler Residual Area Group Sprinkler Elevation Pressure Flowing Area Flowing Sprinkler
(ft2) Density Discharge Sprinkler Code KFactor (K) Node No. (feet) (psi) (gpm/ft2) (gpm)
1 5.60 18.00 10.05 130.00 0.137 17.75
Sub Totals For Non-Group 130.00 0.137 17.75
2 5.60 18.00 10.24 130.00 0.138 17.92
Sub Totals For Non-Group 130.00 0.138 17.92
3 5.60 18.00 . 11.07 130.00 0.143 18.63
Sub Totals For Non-Group 130.00 0.143 18.63
4 5.60 18.00 12.60 130.00 0.153 19.88
Sub Totals For Non-Group 130.00 . 0.153 19.88
5 5.60 18.00 7.04 130.00 0.114 14.86
Sub Totals For Non-Group . 130.00 0.114 14.86
1 6 5.60 18.00 7.23 130.00 0.116 15.06
SubTotals For Non-Group - 130.00 0.116 15.06
7 5.60 18.00 7.81 130.00 0.120 15.65
Sub Totals For Non-Group 130.00 0.120 15.65
8 5.60 18.00 8.93 130.00 0.129 16.73
Sub Totals For Non-Group 130.00 0.129 16.73
9 5.60 18.00 11.17 130.00 .0.144 18.72
Sub Totals For Non-Group 130.00 . 0.144 . 18.72
10 5.60 18.00 7.30 130.00 0.116 15.14
Sub Totals For Non-Group . 130.00 0.116 15.14
11 5.60 18.00 7.50 130.00 0.118 15.34
Sub Totals For Non-Group 130.00 0.118 15.34
12 5.60 18.00 8.10 130.00 0.123 15.94
Sub Totals For Non-Group 130.00 0.123 15.94
13 5.60 18.00 9.26 130.00 0.131 17.04
Sub r Non-Group 130.00 0.131 17.04
14 5.60 18.00 11.58 130.00 0.147 19.06
Sub Totals For Non-Group 130.00 0.147 19.06
15 5.60 18.00 14.11 130.00 0.162 21.03
Sub Totals For Non-Group 130.00 0.162 21.03
16 5.60 18.00 14.37 130.00 0.163 21.23
Sub Totals For Non-Group 130.00 0.163 21.23
17 5.60 18.00 15.47 130.00 0.169 22.02
Sub Totals For Non-Group 130.00 0.169 22.02
Totals For All Groups 2210.00 0.137 302.00
Fir -Fire Srinkler Hydraulics Calculation Program Elite Software Development, incT Guardian Fire Protection' - , CHASE BANK Gilbert, AL 85296 ' Z3. Page 10
Fire Sprinkler Output Summary
[iiiuiucauy Most Demanding Sprinkler Node
HMD Sprinkler Node Number: 5
HMD Actual Residual Pressure: 7.04 psi
HMD Actual GPM: 14.86 gpm
[Sprinkler Summary
Sprinkler System Type: Wet
Specified Area Of Application: 1500.00 ft2
Minimum Desired Density: 0.100 gpm/ft2
Application Average Density: 0.201 gpm/ft2
Application Average Area Per Sprinkler: 88.24 ft2
Sprinkler Flow: 302.00 gpm
Average Sprinkler Flow: 17.76 gpm
I Flow Velocity And Imbalance Summary
Maximum Flow Velocity (In Pipe 25 - 26) 16.88 ft/sec
Maximum Velocity Pressure (In Pipe 25 -26) 1.92 psi
Allowable Maximum Nodal Pressure Imbalance: 0.0100 psi
Actual Maximum Nodal Pressure Imbalance: 0.0065 psi
Actual Average Nodal Pressure Imbalance: 0.0010 psi
Actual Maximum Nodal Flow Imbalance: 0.0040 gpm
Actual Average Nodal Flow Imbalance: 0.0012 gpm
tOverall Network Summary
Number Of Unique Pipe Sections: 26
Number Of Flowing Sprinklers: 17
Pipe System Water Volume: 241.78 gal
Sprinkler Flow: 302.00 gpm
Non-Sprinkler Flow: 100.00 gpm
Minimum Required Residual Pressure At System Inflow 53.91 psi Node:
Demand Flow At System Inflow Node: 401.97 gpm
Fire Fire Sprinkler Hydraulics Calculation Program • : :, ElitiSoftware Develóment lnc.1
Guardian Fire Protection CHASE BANK
Gilbert AL 85296: PagjjJ
-
'L1ydrauIid:Suppli/Deiiiand •.
100
90
80
70
60
50
40
30
20
10
0
73
2 4 6 8 10 12 14 16 18 20
Flowrate(xl 00) gpm
Supply Curve Data
Static Pressure: 82.8 psi
Test Residual Pressure: 72.8 psi
Test Flow Rate: 1453 gpm
Demand Curve Data
Calculated Residual Pressure: 53.91 psi
Calculated Flow Rate: 401.97 gpm
Excess Available Residual Pressure At Calculated Flow: 27.96 psi
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 7.79 psi
April 25, 2008 Sprinkler 51a
The Viking Corporation, 210 N Industrial Park Road, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
DESCRIPTION
Viking Microfase and MicrofastHP6 Quick Response Upright and Conventional
(Old Style) Sprinklers are small, thermosensitive, glass-bulb spray sprinklers
available in several different finishes, temperature ratings, and K-Factors to
meet design requirements. The special Polyester and TeflonO coatings
can be used in decorative applications where colors are desired. In addi-
tion, these coatings have been investigated for installation in corrosive atmos-
pheres and are cULus listed as corrosion resistant as indicated in the Approval
Chart. (Note: FM Global has no approval classification for Teflone and Polyester coat-
ings as corrosion resistant.)
LISTINGS AND APPROVALS
cULus Listed: Category VNlV
nyu Approved: i...uass 20,20
NYC Approved: Calendar Number 219-76-SA and MEA 89-92-E, Volume 16
ABS Certified: Certificate 04-H8407984B-PDA
VdS Approved: Certificate G4060054, G4060056, G4880046, G4930039, and G4980020
LPC Approved: Ref. No. 096e103, TE30401, and TE30872
CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40131, and
0786-CPD-40171
MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008
NOTE: Other International approval certificates are available upon request.
Refer to the Approval Chart on page 51d and Design Criteria on page 51e for cULus and FM approval requirements that must be
followed.
TECHNICAL DATA
Specifications:
Available since 1987.
Minimum Operating Pressure: 7 psi (0.5 bar)
Maximum Working Pressure: Sprinklers VK315 and VK340 are rated for
use with water working pressures ranging from the minimum 7 psi
(0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres-
sure (HP) sprinklers can be identified by locating "250" stamped on
the deflector. All other Part Nos. not mentioned above are rated to a
maximum 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Testing: U.S.A. Patent No. 4,831,870
Thread size: Refer to the Approval Chart
Nominal K-Factor: Refer to the Approval Chart
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: Refer to the Approval Chart
Viking Technical Data may be found on
The Viking Corporation's Web site at
http:llwww.vikinggroupinc.com.
The Web site may include a more recent
edition of this Technical Data Page.
Material Standards:
Frame Casting: Brass UNS-C84400
Deflector: Brass UNS-C23000 or Copper UNS-C19500 for Sprinklers 06661B and 12281. Copper UNS-C19500 for Sprinklers
06665B, 06764B, and 07060. Brass UNS-C26000 for all other Sprinklers.
Bushing (for Sprinklers 067196, 067176, and 12286): Brass UNS-C36000
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-ClI000 and Stainless Steel UNS-530400
For TeflonO Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-Teflon® Coated
Form No. F_080488 Replaces page 51a-e, dated March 7, 2008.
(Updated LPCB Approval on Sprinkler 14817.)
Sprinkler 51 b April 25, 2008
MICROFAST® AND
MicrofastHP® QUICK
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Road, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
For Polyester Coated Sprinklers: Belleville Spring-Exposed
Ordering Information: (Also refer to the current Viking price list.)
Order Microfast® and MicrofastHP® Quick Response Upright and Conventional sprinklers by first adding the appropriate suffix for
the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome-Enloy® = F, White Polyester = M-/W, Black Polyester = M-/B, and Black Teflon® = N
Temperature Suffix (°F/°C): 135°/68° = A, 155°I68° = B. 175°/79° = D, 200°I93° = E, and 286°/141° = G
For example, sprinkler VK300 with a 1/2" thread, Brass finish and a 155 ¶168 °C temperature rating = Part No. 06661 BAB
Available Finishes And Temperature Ratings:
Refer to Table 1
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.)
Sprinkler Wrenches:
Standard Wrench: Part No. 10896W/B (available since 2000)
Sprinkler Cabinets:
Six-head capacity: Part No. 01724A (available since 1971)
Twelve-head capacity: Part No. 01725A (available since 1971)
INSTALLATION
Refer to appropriate NFPA Installation Standards.
OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
AVAILABILITY
The Viking Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers are available through a network
of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking
Corporation.
GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
April 25, 2008 Sprinkler 51c
MICROFAST® AND
MicrofastHP® QUICK N IKJNG4 RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Road, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinklir Temperature : Sprinkler Nominal.. Maximum Ambient
Classification Temperature Rating1 Ceiling Temperature2 B lb C U o or
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue
Sprinkler Finishes: Brass, Chrome-Enloy®, White Polyester, Black Polyester, and Black Teflon®
Corrosion-Resistant Coatings4: White Polyester, Black Polyester, and Black Teflon® -
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on
pages 51d. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through
the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the
coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with
Polyester and Teflon® coatings.
Protective
Wrench Sprinkler
Flat Cap
Figure 1:
Standard Sprinkler Wrench 10896W/B
Sprinkler 51 d April 25, 2008
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
Chart
--bmperature Tk Ey Microfast and MicrofastHP Quick Response I
Upright and Conventional Sprinklers [1Xl- E.i::I;'.or.applicabIe)
Maximum 175 PSI (12 bar) WWP
Base Part Thread Size Nominal
I Overall Length Listings and Approvals'
Number' SIN K-Factor ______________ (Refer also to Design Criteria on page 51e.)
BSP U.S. I metric2 Inches I mm cULus4 I FM7 I NYC8 I VdS I LPCB I CE I 0
Upr ght-Standard Orifice
06661B I VK300 1 1/2' 1 15 mm 1 5.6 1 80.6 1 2-3/16 56 A2 I A3 A2 -- -- -- -
07060 1 VK345 I -- 15 mm 1 5.6 1 80.6 1 2-3/16 1 56 1 -- A3 I - A3 I A3 I B312 B3'4
Conventional -Standard Orifice
06766B I VK310 1 1/2" 115 mm I 5.6 I 80.6 1 2-3/16 L 56 I A3 I -- I A3 I -- I A3 I B312 I B31
Upright -Large Orifice ___________________ 06665B VK350 3/4" -- 8.0 115.2 2-5/16 59 A2 A3 A2 A3 A3 1B3'2 --
14817 1 VK350 I -- 20 mm 1 8.0 1 115.2 1 2-5/16 1 59 1 A2 I A3 I A2 I A3 I A3 IB3'2 -- 06764B VK350 1 1/2" 1 15 mm 1 8.0 1 115.2 1 2-5/16 1 59 1 A2 I -- A2 I A3 I -- -- --
__________ Conventional-Large On ice
067686 I VK354 1 3/4" 1 20 mm 1 8.0 I 115.2 2-5/16 1 59 1 -A2 --1 -- I A3 I -- I A3 I B312 I --
__________ Upright-SmallOrifice
06714R"~j VK325 1 1/2" 1 15 mm 1 2.8 1 40.3 1 2-3/16 56 A2 I Al I A2 I -- -- . -- --
06719B" I VK327 1 1/2" 1 15 mm 1 4.2 1 60.5 1 2-3/16 1 56 1 A2 I -- A2 I -- -- -- -- 06931 B" I VK327 I -- 10 mm 1 4.2 1 60.5 1 2-3/16 1 56 1 A3 I E113 --
Maximum 250 PSI (17 bar) WWP
Upr ght-Standard Orifice
Base Part Thread Size Nominal Overall Length Listings and Approvals3
k Number" SIN K-Factor _ (Refer also to Design Criteria on page 51e.
NPT BSP U.S. metric2 Inches I mm I 7ULus4 I FM I NYC9 I VdS I LPCB I CE 1 0 12281 VK315 1 1/2" 1 15 mm 5.6 1 80.6 2-3/16 1 56 1 A2 I -- A2 I -- -- -- --
Upright-Srnaii Orifice10
12286" I VK340 I 1/2" 115 mm I 2.8 I 40.3 I 2-3/16 56 I A2 I - I A2 I --
Approved Temperature Ratings -
A - 135 OF (57 °C), 155 OF (68 °C), 175 OF (79 -C).'200 OF (93 °C), - . Approved Finishes
and 286 OF (141°C) 1 - Brass and Chrome-Enloy®
B - 155 OF (68 °C), 175 OF (79 °C), 200 OF (93 °C), and 286 OF (141°C) 2 - Brass, Chrome-Enloy®, White Polyester56, Black Polyester56,
C - 135°F (57 °C), 155 OF (68 °C), 175 OF (79 °C), and 286 OF (141°C) and Black Teflon®5
D - 135 OF (57 °C), 155 OF (68 °C), and 175 OF (79 °C) 3 - Brass, Chrome-Enloy®, White Polyester56, and Black Polyester56
E- 155 OF (68 °C) I
Footnotes
'Base part number is shown. For complete part number, refer to Viking's current price schedule.
2 Metric K-factor measurement shown is when pressure. is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
5cULus Listed as corrosion resistant.
6 Other colors are available on request with the same Listings and Approvals as the standard colors.
For installation in accordance with the latest applicable FM Loss Prevention Data Sheets and Technical Advisory Bulletins.
6 Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219-76-SA.
9 Accepted for use, City of New York Department of Buildings, MEA 89-92-E, Vol. 16.
'°Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated
wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or
internally galvanized.
"The sprinkler orifice is bushed.
12 (( Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003.
CE Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD40131.
14 ®. MED Certified, Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008.
April 25, 2008 Sprinkler 51e
MICROFAST® AND
MicrofastHP® QUICK '1 I FJ I1Gj RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
The Viking Corporation, 210 N Industrial Park Road, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
DESIGN CRITERIA
(Also refer to the Approval Chart on page 51d
cULus Listing Requirements:
Microfast® and MicrofastHP5 Quick Response Upright and Conventional Sprinklers are cULus Listed as indicated in the Approval Chart for installation
in accordance with the latest edition of NFPA 13 for standard spray sprinklers, or old style (conventional) sprinklers.
Designed for use in Light and Ordinary Hazard occupancies (exception: small orifice sprinklers are limited to Light Hazard where allowed by
the installation standards being applied, with hydraulically calculated wet systems only).
The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed. For conventional sprinklers, refer
to the installation guidelines for old style (conventional) sprinklers.
FM Aoeroval Requirements:
For installation in accordance with the latest applicable FM Loss Prevention Data Sheets (including 2-8N) and Technical Advisory Bulletins. FM Global
Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not limited to: minimum water supply requirements,
hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
QRI-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
THIS PAGE
INTENTIONALLY
LEFT BLANK
Form No. F_080488 Replaces page 51a-e, dated March 7, 2008.
(Updated LPCB Approval on Sprinkler 14817.)
March 14, 2008 Sprinkler 41 a
MICROFAST® AND
MicrofastHP® QUICK 'J I IJ r,1GI RESPONSE PENDENT
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Road, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
DESCRIPTION
Viking Microfase and MicrofastHP5 Quick Response Pendent Sprinklers are small,
thermosensitive, glass-bulb spray sprinklers available in several different finishes and
temperature ratings and K-Factors to meet design requirements. The special Polyester
and TeflonO coatings can be used in decorative applications where colors are desired.
In addition, these coatings have been investigated for installation in corrosive at-
mospheres and are cULus listed as corrosion resistant as indicated in the Approval
Chart. (Note: FM Global has no approval classification for Teflone and Polyester coat-
ings as corrosion resistant.)
LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Class 2020
IJfl A _ .___I %_I___I_. fli. ._L. -- -- .1 SlA #%S •SS - S rin.. Rppruveu; auenur riumoer and MEA o-i-t, votume lb
ABS Certified: Certificate 04-H5407984C-PDA
VdS Approved: Certificate G4040095, G4040097, G4060056, G4060057, G4880045, G4930038, and G4980021
LPC Approved: Ref. No. 096e/03 and 096e/04
CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40130, and
0786-CPD-40170
MED Certified: Standard EN 12259-I, EC-certificate of conformity 0832-MED-1 003 and 0832-MED-1 008
NOTE: Other International approval certificates are available upon request.
Refer to the Approval Chart on page 41d and Design Criteria on page 41e for cULus and FM approval requirements that must be
followed.
3. TECHNICAL DATA
Specifications:
Available since 1987.
Minimum Operating Pressure: 7 psi (0.5 bar)
Maximum Working Pressure: Sprinklers 12282 and 12290 are rated for
use with water working pressures ranging from the minimum 7 psi
(0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres-
sure (HP) sprinklers can be identified by locating "250" stamped on
the deflector. All other Part Nos. not mentioned above are rated to a
maximum 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Testing: U.S.A. Patent No. 4,831,870
Thread size: Refer to the Approval Chart
Nominal K-Factor: Refer to the Approval Chart
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: Refer to the Approval Chart
Viking Technical Data may be found on
The Viking Corporation's Web site at
http:!Iwww.vikinggroupinc.com.
The Web site may include a more recent
edition of this Technical Data Page.
Material Standards:
Frame Casting: Brass UNS-C84400
Deflector: Phosphor Bronze UNS-051000 or Copper UNS-Cl9500 for Sprinklers 066626, 06666B, 06765B, and 12104. Copper
UNS-C 19500 for Sprinkler 12282. Brass UNS-C26000 for all other Sprinklers.
Bushing (for Sprinklers 06718B, 06720B, and 12290): Brass UNS-C36000
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-530400
Pip Cap Attachment: Brass UNS-C36000
Ejector Spring (for Sprinkler 12104): Stainless Steel
Form No. F_081296 Replaces page 41a-f, dated October 12, 2007. (Added LPCB Approval and updated CE
Approval for Sprinkler 0666613, Added Dry System note in approval chart for Small Orifice.)
Sprinkler 41 b March 14, 2008
MICROFAST® AND
MicrofastHP® QUICK 4J C7G* RESPONSE PENDENT
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Road, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
For Teflon® Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-Teflon® Coated
For Polyester Coated Sprinklers: Belleville Spring-Exposed
Ordering Information: (Also refer to the current Viking price list.)
Order Microfast® and MicrofastHP® Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler fin-
ish and then the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome-Enloy® = F, White Polyester = M-1\N, Black Polyester = M-/B, and Black Teflon® = N
Temperature Suffix (°F/°C): 135°/68° = A. 155°/68° = B, 175°/79' = D, 200°/93° = E, and 286°/141° = G
For example, sprinkler VK302 with a 1/2" thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 066628AB
Available Finishes And Temperature Ratings:
Refer to Table 1
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.)
Sprinkler Wrenches:
Standard Wrench: Part No. 10896W/B (available since 2000).
Wrench for coated and/or recessed sprinklers: Part No. 12144W/B** (available since 2003)
NOTE: RECESSED PENDENT SPRINKLERS WITH PROTECTIVE CAPS MUST USE WRENCH 12144W/B.
**A 1/2 ratchet is required (not available from Viking).
Sprinkler Cabinets:
Six-head capacity: Part No. 01724A (available since 1971)
Twelve-head capacity: Part No. 01725A (available since 1971)
INSTALLATION
Refer to appropriate NFPA Installation Standards.
OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
AVAILABILITY
The Viking Microfast® and MicrofastHP® Quick Response Pendent
Sprinklers are available through a network of domestic and
international distributors. See The Viking Corporation web site for
the closest distributor or contact The Viking Corporation.
GUARANTEE
For details of warranty, refer to Viking's current list price schedule
or contact Viking directly.
Wrench
Flats Protective
Sprinkler
Cap
10896
Figure 1:
Standard Sprinkler Wrench 10896W/B
- Sprinkler Wrench
12144W/Bww for
installing coated
and/or recessed
pendent sprinklers
with protective caps.
**A 1/2' ratchet is required
(not available from Viking).
Carefully slide the
wrench sideways
around the protective
cap, ensuring engage-
ment with the sprinkler
wrench flats.
-c_.--------------
-
Li ------Li
March 14, 2008 Sprinkler 41c
M[CROFkST® AND V4sJ I Fi(I MicrofastHP® QUICK
RESPONSE PENDENT
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Road, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature I SprinklerNominal Maximum Ambient
Classification.. Temperature atingi Ceiling Temperattire2 B lb Col UOF
Ordinary 135 'F (57 'C) 100 'F (38 'C) Orange
Ordinary 155 'F (68 'C) 100 'F (38 'C) Red
Intermediate 175 'F (79 'C) 150 'F (65 °C) Yellow
Intermediate 200 'F (93 'C) 150 'F (65 'C) Green
High 286 °F (141 'C) 225 'F (107 'C) Blue
Sprinkler Finishes: Brass, Chrome-Enloy®, White Polyester, Black Polyester, and Black Teflon®
Corrosion-Resistant Coatings4: White Polyester, Black Polyester, and Black Teflon®
Footnotes
The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on
pages 41d. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through
the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the
coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with
Polyester and Teflon® coatings.
Figure 2: Wrench 12144W/B for Coated and/or Recessed Pendent Sprinklers
Sprinkler 41d March 14, 2008
MICROFAST®AND
"J I F1G
MicrofastHP® QUICK
RESPONSE PENDENT
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Road, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcsvikingcorp.com
Approval Chart Temperature KEY
Finio Microfast' and MicrofastHP Quick Response Pendent Sprinklers
Maximum 175 PSI (12 bat) WWP
Sprinkler Thread Size Nominal Overall Listings and Approvals3
Base SIN K-Factor Length (Refer also to Design Criteria on page 41e.)
Part No." NPT BSP U.S. metric2 Inches mm rULus4J FM5 NYC° VdS LPCB I (E I
Standard Orifice
06662B VK302 1/2 115 mm 5.6 80.6 2-1/4' 58 1 AiX, B1Y I A3X, 133Y AiX, B1Y A3 A3X, 133Y C3X, E3Y13 C3X, E3Y15
Large Orifice
06666B VK352 3/4' 20 mm 80 115.2 2-3/8" 60 A1X,BiY A2x, 132Y AIX, B1Y -- A3X C3' --
12104 VK352 3/4" 20 mm 80 115.2 2-1/4" 58 -- -- -- 03 -- -- --
06765B VK352 1/2" 15 mm 80 115.2 2-3/8" 60 AiX, B1Y - AiX, B1Y A3 -- -- --
Small Orifice9
067181310 VK329 1/2" 15 mm 28 40.3 2-3/16" 56 AiX, B1Y A2X AiX, B1Y -- -- -- --
06720B'° VK331 1/2" 15 mm 42 60.5 2-1/4" 58 AiX, B1Y -- AiX, B1Y -- -- - --
069328 VK331 -- 10 mm 4.2 60.5 2-3/8" 60 -- -- -- A3 -- G2' --
Maximum 250 PSI (17 bar) WWP
Standard Orifice
Sprinkler Thread Size Nominal Overall Listings and Approvals3
Base SIN -
K-Factor Length (Refer also to Design Criteria onpage 41e.)
Part No' NPT BSP U.S. metric2 Inches mm cULus4 FM NYC" VdS LPCB
12282 VK317 1/2" 15 mm 5.6 80.6 2-1/4" 58 AiX, BIY - AiX - -- -- --
Maximum 250 PSI (17 bar) WWP
Small 6rifice9
1229010 1 VK342 1/2" 115 mm 1 2.8 F40.3 2-3/16" 56 1 AIX, BIY I Aix --
Approved Temperature Ratings Approved Escutcheons
A- 135 OF (57 "C), 155 OF (68 "C), 175 OF (79 "C) 200 OF (93 "C), Approved Finishes X - Standard surface-mounted escutcheon or and 286 OF
B - 135 OF (57"d) 155 (68 °C) 175 "F (79 "C) and 200 "F (93 °C) 1 - Brass, Chrome-Enloy®, White Poly- the Viking Microfast® Model F-i Adjustable
C - 155 OF (68 °C), 175 OF (79 "C), 200 OF (93 °C), and 286 OF ester78, Black Polyester78, and Black Escutcheon 12
(141 "C) Teflon®7 V - Standard surface-mounted escutcheon or
D - 135 OF (57 "C), 155 OF (68 "C), 175 OF (79 "C), and 286 OF 2 . Brass and Chrome-Enloy® the Viking Microfast® Model F-i Adjustable
(141 "C) 3- Brass, Chrome-Enloy®, White PoIyester8, Escutcheon12 or recessed with the Viking
,, F (79 :'F (141 and Black Polyester8 Micromatic® Model E-1 or E-2 Recessed
G - 155 OF (68 "C) I Escutcheon
Footnotes
1 Base part number is shown. For complete part number, refer to Viking's current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
FM Approved for use only in wet-pipe sprinkler systems (or preaction systems qualifying as wet systems) for protection of occupancies described in the Factory
Mutual Engineering and Research Loss Prevention Data Sheets and Technical Advisory Bulletins.
6 Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219-76-SA.
cULus Listed as corrosion resistant. ° Other colors are available on request with the same Listings and Approvals as the standard colors.
Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized.
'°The sprinkler orifice is bushed. "Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 16.
12The Viking Microfast° Model F-i Adjustable Escutcheon is considered a surface-mounted escutcheon because it does not allow the fusible element of the
sj,rinkler to be recessed behind the face of the wall or ceiling. 13 (K Certified, Standard EN 12259-1, EC 0832-CPD-2001 0832-CPD-2003. -certificate of conformity and 14 C.E Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-401 30 and 0786-CPD-401 70. '5 G MED Certified, Standard EN 12259-1, EC-certificate of conformity 0832-MED-1 003 and 0832-MED-1 008.
March 14, 2008 Sprinkler 41e
MICROFAST® AND
MicrofastHP® QUICK
II(II1GI
l:ll[u.7M.. RESPONSE PENDENT
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
DESIGN CRITERIA
(Also refer. to the Approval Charton page 41d)
cULus Listing Requirements:
Microfast! and MicrofastHP5 Quick Response Pendent Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with
the latest edition of NFPA 13 for standard spray sprinklers.
Designed for use in Light and Ordinary Hazard occupancies (exception: small onfice sprinklers are limited to Light Hazard where allowed by
the installation standards being applied, with hydraulically calculated wet systems only).
The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
FM AnrovaI Requirements:
For installation in accordance with the latest applicable FM Loss Prevention Data Sheets (including 2-8N) and Technical Advisory Bulletins. FM Global
Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not limited to: minimum water supply requirements,
hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
QRI-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
Ceiling Opening Size:
2-5/16' (58,7 mm) minimum
2-1/2' (63.5 mm) maximum 2-1/8'
(54 mm)
1/2'
NPT
(15 mm)
_
I
1-5/8' W (58 mm)
(41 mm)
Pendent Sprinkler
06662B (VK302)
1-3/4'
(44.5 mm)
InstoJ.Lecl with a
standard 1/8' surface-
mounted escutcheon.
t -J 11
2' 1-1/2" (38,1 mm)
(50.8 mm) Minimum
Maximum
Installed with a Microf'ast
Model F-i AdjustabLe Escutcheon
Figure 3: Sprinkler VK302 Dimensions with a Standard Escutcheon and the Model F-I Adjustable Escutcheon
Sprinkler 41f March 14, 2008
MICROFAST® AND
MicrofastHP® QUICK
RESPONSE PENDENT
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Road, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
I 2-1/8" I Ceiling Opening Size: I 2-1/8" I I a- Ia -i (54 ) 2-5/16' (58,7 mm) minimum I (54 mm) I
2-1/2" (63.5 mm) maximum
1-3/4" \ 1-1/8" (28.6 mm)
(44.5 mm) Minimum
Maximum Lj f
Installed with a Microma-tic
Model E-1 Recessed Escutcheon
\I JI )II1_1'8" (28.6 mm)
(50.8 mm) çJ Minimum
Maximum
Installed with a thread on
Model E-2 Recessed Escutcheon
Figure 4: Sprinkler VK302 Dimensions with the Model E-1 and E-2 Recessed Escutcheons
Form No. F 081296 Replaces page 41a-f, dated October 12, 2007. (Added LPCB Approval and updated CE
Approval for Sprinkler 0666613, Added Dry System note in approval chart for Small Orifice.)
NPS Nominal I.D. Wt. wt. (H20 Filled) CRR
In; mm In; mm lbs/Ft; kg/rn Lbs/Ft; kg/rn Unthreaded
1.191 0.830 1.31 2.41
25 30.3 1.2 1.95 -
1'/4 1.536 1.059 1.87 1.55
32 39.0 1.6 2.78 -
'1½" 1.728 1.667 2.71 3.44
40 43.9 2.5 4.03 -
2.2031 2.104 3.79 2.78
50 56.0 3.1 5.64 -
2½" 2.703, 2.564 5.10 1.60
65 68.7 3.8 7.59 -
3.314 3.387 7.18 1.48
75 84.2: 5.0 10.69 -
4.310 4.473 10.86 1.00
100 109.5 ' ' 6.7 16.16 -
11~9
C
0 "~~ APPROVED
cDDcO@ w
High Strength Steel Pipe
Exceptional hydraulics
Lightweight and easy to
install
Available factory roll
grooved
UL and cULlisted
FM approved
® The original high-strength
light wall sprinkler pipe
with superior hydraulics.
Dyna-Flow is the "original" high-strength
light wall sprinkler pipe. With outstanding
hydraulic capabilities, Dyna-Flow is
recognized as the most popular alternative
to Schedule- 10 pipe. Lightweight and easy
to cut, Dyna-Flow is a valuable addition to
any fire protection system.
With an inside diameter (ID) up to 11%
larger than Schedule-40 and up to 7%
larger than Schedule -10, Dyna-Flow
pipe hydraulics are exceptional.
Larger ID's enable Dyna-Flow and related
components to be down-sized within the
system, increasing the potential for job
cost savings. For complete Hazen Williams
charts, refer to "Dyna-Flow Hydraulic
Data Tables".
Dyna-Flow pipe has metallurgical
properties that provide excellent
fabrication characteristics for end prep
finishes, welding and roll grooving.
There are no special processes or
equipment needed for fabrication and
installation.
® Superior Coating
Dyna-Flow products are coated with an
environmentally approved and specially
formulated modified-acrylic or water-based
coating. This durable coating is paintable
and acts as an excellent primer while
resisting weather and UV degradation
from outdoor storage.
® American Made
Able to meet "Buy American" requirements,
and is available through distributors in the
USA, Canada, Mexico and Latin America.
Specifications & Approvals
Dyna-Flow pipe is manufactured to meet
ASIM A-795 Type E, Grade A and is in
compliance with NFPA-13 and NFPA-14.
All sizes of Dyna-Flow are UL and cUL
listed and FM approved.
Dyna-Flow is UL and cUl listed for use
with roll grooved, plain-end and welded
joints for wet, dry, pre-action and deluge
systems. It is FM approved for roll grooved,
plain end and welded joints for wet
systems. Dyna-Flow is available "hot-dip"
galvanized** and has been specifically
approved by FM for dry system uses.
Dyna-Flow complies with NFPA 13 and is
rated at 300 psi working pressure.
** must be ordered in 10 bundle increments
II Customer Service (800) 882-5543 Fax: (800)659-7730 www.alliedtube-sprinkler.com CIe 16100 S Lathrop Ave. • 11350 Norcom Rd. • 2525 N 27th Ave. 600 Dean Sievers Place
TUBE & CONDUIT' Harvey, IL 60426 Philadelphia, PA 19154 Phoenix, AZ 85009 Morrisville, PA 19067
CRR CRR
11.39 1.00
9.50 1.00
9.14 1.00
8.41 1.00
Widely accepted substitute
for Schedule 40 NPS Nominal I.D. Wt. Wt. (H20 Filled)
Standard hanger spacing mm
-.
In, mm Lbs/Ft; kglm Lbs/Ftjq.
1.330 1.75
UL and cUL listed 25 27.4. .0 2:O.
1¼" 1.408 1.870 2.54 FM approved 32 . 35.8 .•. - 28. 3
lW 1.639 290 3.22
3.4
2" 2.104 3.050 4.57
® Combining the safety and
longevity of Sch-40 with
quality and hydraulic
advantages.
Dyna-Thread" pipe is the full line Schedule
40 replacement with the same CRR of
Schedule 40, 1.00, providing Dyna-Thread
with the same life expectancy as Sch-40.
With outstanding hydraulic capabilities,
Dyna-Thread is a more widely accepted
product substitution than lightwall
threadable pipe when Sch-40 is specified.
Dyna-Thread's inside diameter is up to
3.6% larger than Sch-40 and provides
improved hydraulics. When used in
combination with Dyna-Flow pipe, down
sizing of pipe and related components
often occurs, thereby reducing costs.
The consistent quality of steel used to
make Dyna-Thread facilitates smooth
threading and lower maintenance costs.
Increased strength and lighter weight
allows Dyna-Thread to reduce installation
fatigue and makes it ideal for retro-fit
applications.
® Superior Coating
Dyna-Thread products are coated with an
environmentally approved and specially
formulated modified-acrylic or water-based
coating. This durable coating is paintable
and acts as an excellent primer while
resisting weather and UV degradation
from outdoor storage.
® American Made
Able to meet "Buy American"
requirements, and is available through
distributors in the USA, Canada, Mexico
and Latin America.
® Specifications & Approvals
Dyna-Thread pipe is manufactured to
meet ASIM A-135, Type E Grade A, is in
compliance with NFPA-13 and all sizes are
rated at 300 psi working pressure. Dyna-
10 CIO
<~~>
APPROVO
Thread is UL and cUL listed for wet, dry
deluge and pre-action sprinkler systems
and FM approved for use in wet systems.
Dyna-Thread can be hot dip galvanized**
to meet FM requirements for use in dry
systems. Dyna-Thread is approved for all
threaded couplings and welded outlets
and is suitable for all roll-grooved and
plain end fittings.
- ** must be ordered in 10 bundle increments
PO
0
Customer Service (800) 882-5543 Fax (800) 659 7730 www alliedtubi
16100 S lathrop Ave 11350 Norcom Rd • 2525 N 27th Ave 600 Dean
TUBE & CONDUIT Harvey 1160426 Philadelphia PA 191S'i Phoenix AZ 8500° MorrisvillE
Description
The 6" and 10" Alarm Bells provide an audible notification of a
sprinkler system event. Can be used to signal flow with in the
sprinkler system or tampering with a monitored valves. Each bell
is complete and provides 4 wire connectivity for "through" wiring
to additional devices*. UL Listed.
Specifications
Size: 6", 10"
Power: 120VAC
(4 conductor)
Finish: Red
Installation
Install according to the installa-
tion instructions provided with
each bell. Installation of the
alarm bell should be performed
by a qualified electrician only.
Improper installation may
cause electrical shock,
damage or failure of one or
more connected devices.
MAKE SURE SOURCE
POWER HAS BEEN DISCON-
NECTED AND "LOCKED
OUT" PRIOR TO INSTALLA-
TION AND CONNECTION OF
THE ALARM BELL TO ANY
DEVICE.
Additional Accessories:
ABS Back Box
Wire Bell Cage
02009 Fire Protection Products, Inc (FPPI)
Fire Protection Products, Inc
13. F!.,, -1.
6241 Yarrow Dr., Suite A, Carlsbad, CA 92011-1541
t ,, I For questions: 1 800 344-1822• 1 800 344-3775 fax • www.fppi.com
SYSTEM
SENSOR
WFD Series
Waterfiow Detector
System Sensor's WFD series is compatible
with schedule 10 through 40 steel pipe, sizes
2 "through 8 and can be mounted in a vertical
or horizontal position.
Features Robust Construction. The WFD series consists of a rugged,
NEMA 4 rated enclosure. Desi;ned for both indoor and outdoor
Two-inch conduit openings in new WFD30-2 models use, the WFD series operates across a wide temperature range, from
UL listed models are NEMA 4 rated 320F to 120 F.
Sealed retard mechanism immune to dust and other contaminants
Visual switch activation
Field replaceable retard mechanism and SPDT switches
Rugged, dual SPDT switches enclosed in a durable terminal block
Accommodates up to 12 AWG wire
Designed for both indoor/outdoor use
100 percent synchronization activates both alarm panel and
local bell
Tamper resistant cover screws
Agency Listings
@ @ A MEA <~>
LISTED approved
C5169
AMRDKD
5739 77704209.140 167.93.0 1W9f,2M
Reliable Performance. UL lsted models are equipped with
tamper resistant cove, screws to prevent unauthorized entry. Inside,
two sets of SPDT (Fcrm C) synchronized switches are enclosed in a
durable terminal bloc< to assure reliable performance.
False Alarm Immunity. The WFD series incorporates a mechanical
retard feature, which minimizes the risk of false alarm due to
pressure surges or air t -apped in the sprinkler system. In addition,
the mechanical retard's unique sealed design is immune to dust and
other contaminants.
Simplified Operation. The WFD series is designed to simplify
installation. Two conduit oper.ings permit easy attachment to the
local alarm system. The retard mechanism and dual SPDT switches
are field-replaceable.
Delay Adjustment Dial Overall Dimensions, Installed
'p°. NOTE: Retard Gets n,°y exceed 90 sectruls.
Adjust and we* thol 1m0 dm not ,,c,ed 90Ic,tds.
Pt"
Pinhic vane
Waterfiow Detector
Vane-type waterfiow detectors shall be installed on system piping as designated on the drawing and/or as specified herein. Detectors shall mount on any
clear pipe span of the appropriate nominal size, either a vertical upflow or horizontal run, at least & from any fittings which may change water direction,
flow rate, or pipe diameter or no closer than 24 from a valve or drain. Detectors shall have a sensitivity in the range of 4 to 10 gallons per minute and a
static pressure rating of 450 psi' for 2'- & pipes. The detector shall respond to waterfiow in the specified direction after a preset time delay which is field
adjustable.The delay mechanism shall be a sealed mechanical pneumatic unit with visual indication of actuation. The actuation mechanism shall include
a polyethylene vane inserted through a hole in the pipe and connected by a mechanical linkage to the delay mechanism. Outputs shall consist of dual
SPDT switches (Form C contacts). Two conduit entrances for standard fittings of commonly used electrical conduit shall be provided on the detectors.
A grounding provision is provided. Unless noted, enclosures shall be NEMA 4 listed by Underwriters Laboratories Inc. All detectors shall be listed by
Underwriters Laboratories Inc. for indoor or outdoor use.
IFi7IHTiUi.iii J, --77 4 -
Static Pressure Rating 450 PSI' Operating Temperature Range 32°F to 120°F (0°C to 49°C)
Maximum Surge 18 Feet Per Second (FPS) Enclosure Rating' NEMA4 - suitable for indoor/outdoor use
Triggering Threshold 4-10 GPM Cover Tamper Switch Standard with ULC models, optional for UL
Bandwidth (Flow Rate) models, part no. 546-7000
Conduit Entrances Two openings for Wconduit. Service Use Automatic Sprinkler: NFPA-13
One open, one knock-out type One or Two Family Dwelling: NFPA 13D
Residential Occupancies up to 4 Stories: NFPA 13R
National Fire Alarm Code: NFPA-72
Contact Ratings Two sets of SPDT (Form C) U.S. Patent Numbers 3,845,259
10.0A,1/2 HP@ 125/250 VAC 4,782,333
2.5A@6/12/24V0C - 5,213,205
Compatible Pipe Steel water pipe, schedule 10 through 40 Warranty 3 Years
WFDE Field Wiring Diagram
'' i?°" CaNTATRA11NsB atod4L&.l,on,,,w, lay.c l0ps — 24V0C I 25McPS
WD see
TVWAFM
bar
Were
UL Model ULC Model Pipe Size Hole Size Shipping Weight
WFD20 WFD20A 2 1 V4 4.2 lbs.
WFD25 WFD25A '21h- 1W 4.3 lbs.
WFD30-2 WFD30-2A 3 2 4.5 lbs.
WFD35 WFD35A 31/2- 1Y4 4.7 lbs.
WFD40 WFD40A 4 2 5.2 lbs.
WFDSO WFD50A 5 2 6.3 lbs.
WFD60' WFD60A 2 6.8 lbs.
WFD80' WFD80A 2 7.5 lbs.
Accessories
A3008-00 Retard mechanism
A77-01-02 Terminal block
546-7000 Tamper proof switch kit
WFDW Tamper proof wrench for cover
WFDN4 Gasket kit
'Maximum pressure rating 400 psi as approved by Factory Mutual.
SYSTEM 3825 Ohio Avenue. St. Charles, IL 60174 '
Z-4 SEIISOR! Phone: 800-SENSOR2. Fax: 630-377-6495
Pradw tochange4t t,ne,ce,hot etenz,.kn
AOS.019O-Ol1.3107.9676
INSTALLATION AND MAINTENANCE INSTRUCTIONS
WFD Vane-type Waterfiow
Detectors
SYSTEM
$ SENSOR
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systernsensor.com
Specifications
Contact Ratings:
Triggering Threshold Bandwidth (Flow Rate):
Static Pressure Rating:
Dimensions, Installed:
Operating Temperature Range:
Compatible Pipe:
Shipping Weight:
Enclosure Rating:
U. S. Patent Numbers:
10 A @ 125/250 VAC '; 2.5 A @ 24 VDC
4 to 10 gpm
See models listed below.
3.5"H x 3.0"W x 6.7"D
32°F to 120°F (0°C to 49°C)
Steel water pipe, schedule 10 through 40.
4 to 7 lb., according to size:
NEMA Type 4, as tested by Underwriters Laboratories, Inc.
(IP56)
3,845,259; 4,782,333; 5,213,205
Important
Please Read Carefully And Save
This instruction manual contains important information
about the installation and operation of waterfiow detectors.
Purchasers who install waterfiow detectors for use by oth-
ers must leave this manual or a copy of it with the user.
Read all instructions carefully before beginning. Follow
only those instructions that apply to the model you are
installing.
ACAUTION I
Use vane-type waterfiow detectors in wet-pipe systems
only. Do NOT use them in dry pipe, deluge, or preaction
systems. The sudden inrush of water in such systems may
break the vane or damage the mechanism.
Do not use in potentially explosive atmospheres. Do not
allow unused wires to remain exposed.
*Maximum Pressure Rating 400 psi8 as approved by
Factory Mutual Research.
I AcAulloNi
Do NOT use any of the WFD models on copper pipe. The
clamping forces of the mounting bolts may collapse the
pipe sufficiently to prevent the detector from functioning
properly.
Do NOT install steel or iron pipe sections in copper piping
for mounting a waterfiow detector. Incompatibility between
the dissimilar metals causes bimetallic corrosion.
NFPA 25: Inspection,Testing and Maintenance ;f Sprinkler
Systems, Section 5.3.3.2
Other applicable NFPA standards, local codes, and the
requirements of the authority having jurisdiction
NOTE: Installation methods other than those listed in this
installation manual may prevent the device from reporting
the flow of water in the event the associated sprinkler sys-
tem is activated by a fire. System Sensor is not responsible
for devices that have been improperly installed, tested, or
maintained.
Mount the detector where there is adequate clearance
for installation and removal and a clear view of it for
inspections. See Figure 1 for mounting dimensions.
Locate the detector 6 to 7 ft. above the floor to protect
from accidental damage.
On horizontal runs, position the detector on the top or
side of the pipe. Do not mount it upside down because
condensation may collect in the housing and impair the
operation of the detector. For vertical flow applications,
mount the detector on pipe through which water flows
upward. Otherwise, the unit may not operate properly.
Mount the detector at least 6 inches from a fitting that
changes the direction of water flow and no less than 24
inches from a valve or drain.
I56-0459-016R
Installation Guidelines
Before installing any waterfiow alarm device, be thorough-
ly familiar with:
NFPA 72: National Fire Alarm Code
NFPA 13: Installation of cnrinitlpr Sustems o,-tinn 1 1 7
Principles Of Operation
Vane-type waterfiow detectors mount to water-filled pipes
in sprinkler systems. Waterfiow in the pipe deflects a vane,
which produces a switched output-usually after a speci-
fied delay. All waterfiow detectors have a pneumatically
controlled mechanical delay mechanism. Delays do NOT
accumulate; they reset if the flow of water stops before
the entire delay has elapsed. All switches actuate when
the water flow rate is 10 gallons per minute or greater, but
will not actuate if the flow rate is less than 4 gallons per
minute. This System Sensor installation manual covers
the following waterflow detectors for sprinkler/fire alarm
applications.
Pipe Max. Pressure
Model Pipe Size Schedule Rating (psig)
WFD20 2" 10 thru 40 450
WFD25 21/2" 10 thru 40 450
WFD30-2 3" 10 thru 40 450
WFD35 31/2" 10 thru 40 450
WFD40 4" 10 thru 40 450
WFDSO 5" 10 thru 40 450
WFDGO 6" 10 thru 40 450*
WFD80 8" 10 thru 40 450*
D770-01-00
5. Be sure the direction-of-flow arrow matches the direc- Figure 1.. Mounting dimensions;
tion of now in the pipe.
Mounting Instructions
Drain the pipe.
Cut a hole at the desired location. Center the hole in
the pipe, as shown in Figure 2, and be sure the hole is
perpendicular to the center of the pipe. Before drilling,
use a punch or scribe to mark the drill site to prevent the
bit from slipping. If the hole is off center, the vane will
bind against the inside wall of the pipe. Use a drill or
hole saw to cut a hole of the proper diameter. See Table
1 for hole size.
I AcAulloNi
When drilling the hole with a hole saw, make certain that
the center of the cut does not remain in the pipe.
Remove burrs and sharp edges from the hole. Clean and
remove all scale and foreign matter from the inside of the
pipe for one diameter on each side of the hole to ensure
free movement of the vane. Clean the outside of the pipe
to remove dirt, metal chips, and cutting lubricant.
Seat the gasket against the saddle and mount the detector
directly to the pipe. Carefully roll the vane opposite the
direction of flow and insert it through the hole. Seat the
saddle firmly against the pipe so that the locating boss
goes into the hole.
Install the U-bolt, tightening the nuts alternately to
ensure a uniform seal. See Table 2 for torque values.
Remove the metal cover with the tamper-proof wrench
provided. Move the actuator lever back and forth to
check for binding. If the vane binds, remove the detec-
tor and correct the cause before proceeding.
I AcAurloNi
Be sure the direction-of-flow arrow points in the right direc-
tion or else water flow will go unreported. See Figure 3.
Pre-Operation Testing
Fill the sprinkler system and check for leaks around the
waterfiow detector. If it leaks, first check for the proper
torque on the U-bolt nuts. If the leak persists, drain the
system and remove the detector (refer to Maintenance).
Check for dirt or foreign objects under the gasket, and
make sure that the pipe surface is not dented. Reinstall
the detector and check again for leaks. Do not proceed
until all leaks have been stopped.
Connect an ohmmeter or continuity tester across the
COM and B switch terminals. The ohmmeter should
indicate an open circuit.
Deflect the actuator lever and hold it until the pneumatic
delay shaft releases the switch buttons. The ohmmeter
or continuity tester should show a short circuit after the
delay has elapsed. If there is no delay, check the setting
of the delay adjustment dial.
'ipe
tic vane
Overall width pipe diameter + 7.6 cm (3)
Figure 2. Mounting hole location:
Wrong
T - I - i
L -~ IT
Right
-
Remove burrs from edge of hole. Clean Out scale
and foreign matter from inside wall of pipe. W01116.011
Table 1:
WFD MODEV HOLE SIZE
20, 25, 35
30-2, 40, 50, 60, 80 2"
Table 2:
WFD MODEL* TORQUE
20. 25, 35 30-35 ft.-lb.
30-2, 40, 50, 60, 80 55-60 ft-lb.
Wiring
FA-WARNING]
High Voltage. Electrocution Hazard. Do not handle live AC
wiring or work on a device to which AC power is applied.
Doing so may result in injury or death.
When utilizing switches at voltages greater than 74VDC
or 49VAC r.i means to provide all—pole disconnec-
tion must be incorporated in the fixed wiring, such as a
circuit breaker.
U-bolt flu
Pipe saddle
U-bolt
W0105-OO
D770-01 -00 2 156-0459-016R
Figure 3. Assembly diagram:
Tamper proof wrench
Z
er
Terminal block
! (Replacement P/N A77-01.02)
Delay mechanism (Replacement Electrical conduit entrance /N A3008-00) (22.2 mm dia.)
Mounting plate
U bolt nut
Pipe saddle
Plastic vane 'N
Roll paddle opposite
I I of flow arrow while inserting
Pipe
Saddle gasket
7U
Refer to Table 2
U bolt
Figure 4. WFD wiring:
NOTE: Common and B connections will
close when vane Is deflected. I.,..
when water is flowing. Dual switches
permit applications to be combined
on a single detector.
CONTACT RATINGS
t2SI2SOVAC IeAMPc
24 VDC 1 2.5 AMPS
Fire Alarm Control Panel
lljplcol Fire Alone Control Panel Connection
Two Waterfiow Detectors Shown
power worse
omPwith,atibtn I--9 i'
__• bell Break wire on shown for
Iconnection.
schematic o, DO NOT allow stripped wire
Typical Local Belt Connection IndIaidCel conch
W023400 in n, W,t.rltow' feeds to extend beyond
witch housing. DO NOT
Condition leep mireo.
All models have two SPDT switches. Switch contacts
COM and B are closed when water is flowing and open
when it is not. Connect the switches, as shown in Figure
4, depending on the application.
When connected to a listed sprinkler/fire alarm control
panel, the initiating circuit must be nonsilenceable.
A ground screw is provided with all waterflow detectors.
When grounding is required, clamp wire with screw in
hole located between conduit entrance holes. See Figure
5A, page 4.
If a second conduit entry is required, remove the
knockout plug using a flat blade screwdriver as shown
on Figure 513, page 4. Strike sharply with a hammer
to pierce the wall of the knockout plug. Move to an
adjacent wall section and repeat until the plug falls
out. Make sure that the waterflow detector is supported
adequately during this operation to avoid injury.
Mechanical Delay Adjustment
The pneumatic delay is preset at the factory to 30 seconds.
To adjust the setting, turn the adjustment dial clockwise to
increase the delay, counterclockwise to decrease it. The delay
is adjustable from 0 to 70 seconds. See Figure 6, page 4.
NOTE: Set the delay to the minimum required to prevent
false alarms from flow surges.
Periodically test time delay as required by Authority Having
Jurisdiction or code authority.
Maintenance
To prevent accidental water damage, control valves should
be shut tight and the system completely drained before
waterflow detectors are removed or replaced.
Inspect detectors in accordance with applicable NFPA
codes and standards and/or the authority having jurisdic-
tion for leaks and replace if a leak occurs. Test detectors at
least quarterly, as described under Operational Testing, to
ensure proper operation. Test more often if required by the
authority having jurisdiction.
Under normal conditions, System Sensor waterflow detec-
tors should provide years of trouble-free service. However,
if the delay mechanism or switch enclosure needs to be
replaced, follow these directions. To replace the delay
mechanism or switch enclosure, use a /I6" socket head
Operational Testing
Always notify a central station monitoring waterflow
alarms before repairing, maintaining, or testing waterflow
alarm devices.
waioi.Oi 1. Replace the cover and tighten the tamper proof screws
with the tamper proof wrench. Store the wrench in a
secure place.
2. Open the inspector's test valve and time how long it
takes for the detector to indicate a flow condition. The
detector should remain activated until the inspector's
test valve is closed. Air pockets in the sprinkler system
may increase the apparent delay.
D770-01 -00 3 156-0459-016R
screwdriver to remove the three screws that hold it in place.
Either mechanism can be easily replaced without removing
the detector from the pipe or draining the pipe. To replace
the delay mechanism, request Part No. A3008-00. For
switch enclosure, request Part No. A77-01-02. Do not repair
or replace any other waterflow detector components. If any
other part of the detector does not perform properly, replace
the entire detector. Installation methods other than those
listed in this installation manual may prevent the device
from reporting the flow of water in the event the associated
sprinkler system is activated by a fire. System Sensor is not
responsible for devices that have been improperly installed,
tested, or maintained.
To remove a detector:
Drain the pipe.
Turn off electrical power to the detector and disconnect
the wiring.
Loosen the nuts and remove the U-bolts.
Gently lift the saddle far enough to get your fingers
under it. Then, roll the vane so it will fit through the
hole while continuing to lift the waterflow detector
saddle.
Lift the detector clear of the pipe.
I ACAUTION I
If a vane breaks in a pipe, find and remove it. If it is not
removed, the vane may restrict the flow of water to all or
part of the sprinkler system.
Figure SA. Ground screw location:
GROUND F SCREW
/ (GREEN)
MOUN
-
1rPLATE Ll— I T7M
W0103-OO
Figure 511. Knockout nlu removal:
WOtt80I
Delay adjustment dial:
NOTE: Retard time may exceed 90 seconds. WOlt 2-01
Adjust and verify that time does not exceed 90 seconds.
Delay
adjustment
dial
Please refer to insert for the Limitations of Fire Alarm Systems
I àWARNING I
The Limitations of Waterfiow Alarm Devices
Waterfluw detectors may not work or operate properly if sprinkler piping being 3. Vane-type waterfiow detectors have a normal service life of tO-IS years. Hard
monitored is plugged with pipe scale, mud, stones or other foreign material, water systems, however, may substantially reduce waterflow detector service life.
Sprinkler systems should be checked regularly for such blocking material. fol- 4. Waterflow detectors are not a substitute for insurance. Building owners should
lowing the instructions in Chapter of NFPA Standard 13A. always insure properly and lives being protected by sprinkler systems.
Alarms generated by the activation of waterflow detectors may not be received 5. If valves controlling the water supply to a sprinkler system are closed, vane-type
by a central station if telephone or other communication lines to the detector are waterflow detectors will not work. All valves controlling a sprinkler water supply
out of service, disabled, or open, should be seated or locked in the normally open position. The normally open
position should be monitored by a sprinkler supervisory switch.
Three-Year Limited Warranty
System Sensor warrants its enclosed waterflow detector to be free from defects in Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunc.
materials and workmanship under normal use and service for a period of three lion and suspected cause of failure. The Company shall not be obligated to repair or
years from date of manufacture. System Sensor makes no other express warranty replace units which are found to be defective because of damage, unreasonable use,
for this waterflow detector. No agent, representative, dealer, or employee of the modifications, or alterations occurring alter the date of manufacture. In no case shalt
Company has the authority to increase or alter the obligations or limitations of this the Company be liable for any consequential or incidental damages for breach of this
Warranty. The Company's obligation of this Warranty shall be limited to the repair or or any other Warranty, expressed or implied whatsoever, even if the loss or damage
replacement of any part of the waterflow detector which is found to be defective in is caused by the Company's negligence or fault. Some states do not allow the exclu-
materials or workmanship under normal use and service during the three year period sion or limitation of incidental or consequential damages, so the above limitation or
commencing with the date of manufacture. After phoning System Sensor's toll free exclusion may not apply to you. This Warranty gives you specific legal rights, and you
number 800-SENSOR2 (736.7672) for a Return Authorization number, send defective may also have other rights which vary from state to state.
Units postage prepaid to: System Sensor, Returns Department, RA IS , 3825
D770-01-00 4 156-0459-016R
02005 System Sensor
Carlsbad Municipal Water District
Potable Water Discharge
Event Report
Date: 62244TL__
3440IVIATMERCAT0T
Location: CARLSBAD, CA 92009
7/
Reason for Discharge Event: FIRE SPRINKLER HYDRANT DISCHARD DATA
Type of Event: inivai
Dewatering Water Mains ( Jlr Estimated Discharge Flow: 4359 &?M
Note: Includes flow testing and flushing
Dewatering Reservoirs Start Time 800 AM
-
UnschoduledWater Discharge End Time 8:03 AM
Pre-Dechlorination Residual: 82
Ciear flow path of debris, surface
contaminants and/or hazardous Post-Dechlorination Residual: 82
materials. Do not remove native (less than 0.1 mg!L)
vegetation.
pH within limits of 6.0 and 9.0
_______
Erosion control, i.e.
sandbags, silt fencing, hay bales,
gravel bags, decreasing the velocity
ot discharge water. iLA-
Upon comletiorióf dewatering, ensure
that the flow path is tree of all
temporary erosion prevention materials.
Upon completion of dewatering, ensure
that any sediment oi silted areas are
cleared.
Water Sampling Performed by:
-
Comments:
Submitted by: Reviewd by:
(Name a Date) (Name a Date)
Flow Test Record
Test Hydrant 3440 VIA MERCATO
Location CARLSBAD, CA 92009
Hydrant ID No. Size main 8" PVC DR-1 8
Static ............. 92
Residual.........82
Pressure Drop 10 (PD! 1).....K factor for PD! 1 347
Flow: Hydrant(s)
Hydrant I location
Hydrant 2 location
Hydrant 3 location
Hydrant I Pitot 75 PSI GPM:1453 Size.of Orifice 2.5
Hydrant 2 Pitot PSI GPM: Size of Orifice_________
Hydrant 3 Pitot PSI GPM: Size of Orifice__________
Total:— 1453
(Qi)
CalcUlated test and flow, data - 0 x PD2 k =:.Q2
PDI*k
Static: ..................... 92
Desired Residual.......20
Pressure Drop (PD 2)72 K factor PD 2:10.07
1453 x 10.07 divided by 3.47 equals4216 GPM at 20 psi residual
Qi PD2k PD1k Q2
Comments:
Test conducted for:
CHASE BANK - LA COSTA & RANCHO SANTA FE STORE #17194
Conducted by:CHRIS GRIFFIN - GUARDIAN FIRE PROTECTION
Date:6-22-14 Time:8:00 AM