HomeMy WebLinkAbout3446 VIA MERCATO; ; FA140100; Permit5/2/24, 3:56 PM FA140I00 Permit Data City of Carlsbad Fire Alarm Permit Permit No: FAI40I00 Job Address: 3446 VIA MERCATO Permit Type: FALARM Parcel No: 2230507200 Lot #: 0 Reference No.: Status: ISSUED Applied 7/11/2014 Approved: 7/21/2014 Issued: 7/21/2014 PC #: Inspector: Project Title: WELLS FARGO SPRINKLER MONITORING SYSTEM. FURNISH AND INSTALL A COMPLETE 24 VDC CLOSED CIRCUIT, MICROPROCESSOR BASED, ELECTRICALLY SUPERVISED, ANNUNICATED FIRE ALARM SYSTEM AS SPECIFIED IN THE PLANS. THE SYSTEM SHALL INCLUDE BUT NOT BE LIMITED TO ALL CONTROL PANELS, PWER SUPPLIES, SIGNAL INTIATING DEVICES, AUDIBLE AND VISUAL ALARM DEVICES, WIRE, AND ACCESSORIES REQUIRED TO PROVED A COMPLERE OPERATING SYSTEM. Applicant: STANDARD ELECTRONICS 9340 STEVENS RD SANTEE CA 619-596-9950 Owner: PROPERTY DEVELOPMENT CENTERS L L C C/O SAFEWAY INC 5918 STONERIDGE MALL RD PLEASANTON CA Fees ($) Add'I Fees ($) Total ($) Balance ($) 286 0 286 0 about:blank 1/1 Ph: (619) 596-9950 June 17, 2014 1 (619) 596-8850 Standard 9340 Stevens Road Santee, CA 92071 op C?. CIO LIC. #590876 BSISACO 4tACO1903 Electronics UL Installer #S3570-1 StandardFjectronics.us SUBMITTAL SHEET PROJECT: WELLS FARGO BANK - LA COSTA TOWN SQUARE 3446 Via mercato, Carlsbad, CA 92009 ARCHITECT: ELEC.ENGR: ELEC.CONTR: Viking Construction 1825 Ashton Avenue, Carlsbad, CA 92008 EQUIPMENT Fire Alarm Equipment ITEM QTY DESCRIPTION MODEL NO. DATA SHEET 1 2 12 Volt 7 AH Sealed Lead Acid Battery ES7-12 MK Battery 2 1 Sprinkler Monitoring Control Panel CSFM#:7165-1157:0123 XR100FC-R DMP LX Bus, Single Point Addressable Module CSFM#:7165- 1157:0124 711 DMP 4 1 Convential Photoelectric Smoke Detector CSFM#:7272- SLR-835-w DMP 5 1 6" Smoke Detector Base CSFM# 7272-0410:0132 N56-100W DMP 6 1 Cellular Dialer CSFM#:7165-1157:0123 463G Honeywell 7 1 Battery Harness (No Data Sheet) 318 DMP 8 .6K 4 Conductor, 22 AWG, Unshilded, Solid WG-1 103 1101 WCW 9 .4K 14 AWG THHN SOLID 14 AWG WCW I, Ph: (61.9) 596-9950 June 17, 2014 ""'96-8850 61 Fa,c 9)596-8850 9340 Stevens Road Standard, Santee, CA 92071 T C7, cio LIC. #590876 Electronics BSISAcO #AC01903 UI Installer StandardI1ectronjcs.us SUBMITTAL SHEET PROJECT: WELLS FARGO BANK - LA COSTA TOWN SQUARE 3446 Via mercato, Carlsbad, CA 92009 ARCHITECT: ELEC.ENGR: ELEC.CONTR: Viking Construction 1825 Ashton Avenue, Carlsbad, CA 92008 EQUIPMENT Fire Alarm Equipment ITEM QTY DESCRIPTION MODEL NO. DATA SHEET 1 2 12 Volt 7 AH Sealed Lead Acid Battery E57-12 MK Battery 2 1 Sprinkler Monitoring Control Panel CSFM#:7165-1157:0123 XRIOOFC-R DMP LX Bus, Single Point Addressable Module CSFM#:7 165- 1157:0124 711 DMP 4 1 Convential Photoelectric Smoke Detector CSFM#:7272- 0410:0107 SLR-835-W DMP 5 1 6' Smoke Detector Base CSFM# 7272-0410:0132 NS6-100W DMP 6 1 Cellular Dialer CSFM#:7165-1157:0123 463G Honeywell 7 1 Battery Harness (No Data Sheet) 318 DMP 8 .6K 4 Conductor, 22 AWG, Unshilded, Solid WG-1 103 1101 WCW 9 .4K 14 AWG THHN SOLID 14 AWG WCW Fl or F2 Terminal: 1.0 . 1 2 40210 20 ±150 2 41110 20 I— 20510)20 Discharge Time Aillibmw Battery W 31 South Sinclair Street • Anaheim, California 92806 Toll Free: 800-372-9253 • Fax: 714-937-0818 • E-mail: sales@mkbattery.com SPECIFICATIONS Nominal Voltage (V) 12V Nominal Capacity 20 hour rate 0.36A to 10.50V) 7.2Ah 10 hour rate 0.72A to 10.50V) 6.84Ah 5 hour rate (1.22A to 10.20V) 6.12Ah 1 C (7.2A to 9.60V) 3.24Ah 3C (21.6A to 9.60V) 2.52Ah Weight Approx. 5.39Lbs. (2.45kg) Internal Resistance (at 1KHz) 22 mg Maximum Discharge Current for 30 seconds: 144A Maximum Discharge Current for 5 seconds: 288A Operating Temperature Range Charge 0°C (32°F ) to 40°C (104°F) Discharge -15°C (5°F) to 50°C (122°F) Storage -15°C (5°F) to 40°C (104°F) harge Retention (shelf life) at 20°C (68°F) 1 month 92% 3 months 90% 6 months 80% Charging Methods at 20°C ( 68°F) Cycle Use: Charging Voltage 14.4 to 15.OV Maximum Charging Current: 2.16A Standby Use: Float Charging Voltage 13.50 to 13.80V Life expectancy: Cycle Use: 100% depth of discharge 200 cycles 80% depth of discharge 225 cycles 50% depth of discharge 500 cycles Standby Use: 3-5 years Case Material: ABS (Option : 94-H B & 94V-0 Flame Retardant Case Material) —* ($712 Maintenance-Free Rechargeable Sealed Lead-Acid Battery DIMENSIONS mm(inch) (FASTON TAB NO. 1871 (FABTaN TAO NO. 250) e G5±I(2.58.04) 151110.94*041 -==- II . r e - B Pb Discharge Time VS. Discharge Current (20°C) 12.0 11.0 10.0 0.0 -- SECURITY SIGNALING LISTED You Searth dmpatarms FDNY Ki : --------/ Fe your ca - and rtwork ctccrs Suitable for retail and residential installations On-board network & Plug-in Cellular Connection allows for MyAcceSSTM features MyAccess: Email and SMS remote user control Cost saving communication paths between the panel and Central Station Flash Updateabte: No more firmware chips to replace Provides up to 100 DMP 1100X or 1100XH Wireless devices Select Area. AlVPerimeter, or Home/Sleep/Away operation UL Listed for Burglary. Fire, Access Control DMPXR100 Series Command ProcessorTM Panels meet all your burglary. fire and access control applications needs. XC3 SRS 42- c2[ OCSSOTM SYSTEM FEATURES Eight individual reporting areas, with common areas 10.000 user codes with 99 profiles Up to eight supervised door access-points and/or keypads 12,000 event buffer 32 character names available for user, zone, area, profiles and Up to 100 output schedules to control relays and panel outputs group names Optional user authority to temporarily extend Shift schedules Fully supervised network and cellular communication Built-in phone line monitor Communications Diagnostics check network and cellular Multilingual menus available communication status, cell signal strength, and email status Built-in remote or on-site feature upgrade capability from the keypad Multi-Tenant Functions provides individualized protection and 1.5 Amps 12 VDC smoke and auxiliary output with OVC protection control for multiple areas within a single system Multiple on-board status LEDs Guest operation allows up to two separate protected systems Flexible system arming features, with Instant Arming option - XR100!SYSTEM FEATURES Up to 130 two-wire smoke detector or fire initiating zones On-board Ethernet ----....._----- i The XR100N has transitioned from dialer- focused communications to a true network and cellular communications approach by providing stronger, multi-layered panel communications that ensure a constant link between the panel and Central Station. Installers have the ability to create, configure and manage up to eight communication paths. The unique DMP Serial 3 format supports 16-character user, zone and area names to For commercial or multi-family residential The DMP MyAccess messaging features let installations. Multi-Tenant Operation enables users send commands via text messages thetransmissionofalarmsand alerts byarea to Cellular and Network equipped panels. account number instead of system account Residential and commercial users can now number enabling tenants and Central Stations remotely control their systems. Users can to identify specific zone events. Tenants arm or disarm their system, control outputs, can only silence alarms originating in their retrieve system status, and perform other protected area. functions. Each command received by the panel is acknowledged back to the user via return SMS Message. Program up to eight areas with a variety of nnfinn mu1inri indonn,4gnf 2rrninr, rh i.nrl decrease the central station response time Users are informed of alarm system activity r .... ... and limit dependence on automation literal and status— The panel transmits Email or area has a unique name and may have its own tables for message conversion, text messages regarding alarms, troubles, account number. and arming/disarming events. The GPRS/ Common areas automatically arm when the r - - SMS messages can be directed to as many last independent area is armed and disarm If a current primary communication path as three email addresses (up to 48 characters when the first independent area is disarmed. becomes unavailable, Adaptive Technology each) or cell phone numbers. Messaging can This is ideal for lobbies or areas where users directs the panel to make a seamless be configured via Remote LinkTM or from the need common access to specific areas. transition from one communication path to keypad. another within milliseconds, ensuring that [LC r no check-in or supervision messages are The Instant Arming option activates the missed. This allows a system to be fully systemwithoutthetypicaldelay,allowingthe supervised when the primary communication MyAccess messages are transmitted directly user to leave the premises with confidence path is unavailable, while minimizing between the panel and cell phone or browser that the area is protected. The Area Follower expensive cell traffic when all paths are with no external servers. Dealers can function can direct the devices in a lobby or good. The panel is constantly checking the offer these much-appreciated services to designated area not to trip until the system failed path to enable the panel to revert back their customers and realize the benefits of completes all entry and exit delays, allowing to the primary path when communication is additional recurring revenue, users to program the most convenient exit restored. path. I r / - L Providing end users with a way to reduce L.- Create, configure. and manage up to eight false alarms, both Cancel/VerifyTM and the The easily programmable communication paths between the panel and False Alarm Question features prompt end 900MHz frequency-hopping Central Station. Each path has its own panel users to validate whether an alarm has spread-spectrum DMP IlOOX communication programming parameters. occurred after entering their code. InaHome/ Series wireless system features two-way and can be identified as either primary or Sleep/Away or All/Perimeter system, the communication for superior operation. backup. This enables installers to configure a user can manually confirm a valid burglar supervision and battery life. Two-way reliable communication link. offering greater alarm and an alarm is then sent to the communication minimizes repetitive confidence that the panel will always be Central Station. signaling and helps to quickly identify connected to the Central Station. missing transmitters. Simple keypad access - r can be used to verify wireless device zones - Using the Home/Sleep/Away with Guest are in working order. The 1100X and 1100XH CC [C House operation, create up to two separate Wireless Receivers, as well as the 1100R The CellComRT Remote Digital Cellular systems (main and one guest). Keypads Wireless Repeater are authorized for wireless Communicator allows remote mounting up in each system can selectively arm the Commercial Burglary and Commercial Fire to 250 feet from the paneL perimeter, interior, or bedrooms for only their applications. Panel diagnostics can verify the connection protected areas. Main system users can add between the panel and the communicator, authorized users to all protected areas, but providing a fully supervised alarm guests can add users only for their protected The XR100 provides up to 142 zones, communication path over the GSM/GPRS 5'5tem, programmable for burglary. fire, and access network applications. The system contains eight burglary zones and two Class B 12 VDC powered zones. Up to 32 zones are available on 8 keypad addresses and up to 100 zones are available on the built-in LX-Bus. EcHEET ONE-MAN WALK TEST A special code is also available for installers to test the system. The One-Man Walk Test feature allows a single technician to check the panel response to burglary, fire, panic, and supervisory zones. OUTPUTS The XR100 provides up to 106 outputs that can be activated by zone or system events, by schedule, through the User Menu or when a card is presented. Output Groups allow multiple outputs to activate with a single event and/or can be assigned to a particular user profile. OUTPUT SCHEDULES Achieve maximum system flexibility with 100 programmable schedules that simplify planning and operations. Control any contact-activated device with schedules that automatically regulate relays and switched- ground outputs. DOOR STRIKE SCHEDULES WITH OVERRIDE Specific doors may use output schedules to unlock during certain times of the day or night, or the card reader can be completely disabled when desired. The schedule override feature keeps doors locked should the business open later or close earlier than scheduled. SHIFT SCHEDULES WITH HOLIDAYS Up to four independent Shift schedules are available for each of the eight areas. MULTI-LINGUAL DISPLAY OPTION XR1 00 Series systems may be programmed to display the User Menu and Status Display text in multiple Languages. REAL-TIME STATUS ENHANCES 3RD-PARTY INTEGRATION Alarm systems are increasingly being integrated with environmental control and home automation systems. With real-time status information from zones, doors, and other outputs. XR100 Series panels are readily integrated with these third-party control and automations systems. KEYPAD SHORTCUT KEYS Time-saving shortcut keys provide one- button access to system control, making frequently used functions like system arming, fast and simple. The shortcut keys enable users to arm, monitor zones, test, or reset the system and perform a variety of other functions faster and easier. Shortcut keys included are: All, Reset. Home. Chime. Perim. and Sleep. EIGHT INDEPENDENT ACCESS CONTROL DOORS Any access control reader with a Wiegand output can be connected to the XR1 00 Series panel. Attach card reader inputs to up to eight different locations. ACCESS CONTROL The XR100 system can restrict access for several reasons such as a schedule or armed area. The specific reason for access denial can be displayed on the keypad, stored in events, or sent to the central station, and to DMP Advanced Reporting software. Anti- passback feature also available. THINLINETM AND AQUALITETM KEYPADS The stylish and sleek 7000 Series keypads provide three 2-button Panic keys. AC power and Armed LEDs. 32-character display. backlit logo and keyboard plus an internal speaker. Aqualite/Thinline Keypad (Designer Series Cover) VALUABLE INDICATOR In a normal state, both the keypad and logo backlighting remain Blue on Aqualite keypads or Green on Thinline keypads. However, during an alarm state, the keypad and logo turn Red. The change in color allows persons on-site to instantly recognize an alarm condition. Red Backlighting for Alarm Conditions 7760 CLEAR TOUCH TM An attractive user interface featuring a glass touchscreen instead of traditional keys. The Blue touchscreen display turns Red for alarm conditions. Available in White. Black or Platinum, the 7760 adds elegance and style to any installation. - 7760 Clear TouchlM Keypad 9000 SERIES WIRELESS KEYPAD The 9060 and 9063 Wireless Keypads are fully functioning, supervised keypads that provide installation flexibility. These full-feature keypads include four 2-button panic keys and an internal speaker. The backlit keypad is easy to read, and both the keypad and logo turn Red in alarm conditions, providing a visual alert. Both Keypads have a 32-character display, and can be programmed with a 16-character home or business name. The 9063 keypad also includes a built-in proximity reader for codeless arming and disarming. _-9000 Wireless Keypad E;3YPAT 630F LCD Remote Fire Command 7000 Series ThinLine Keypads 7000A Series Aqualite Keypads 7100 Series Thinline Keypads 7760 Clear Touch Keypad 9060 Wireless Keypad 9063 Wireless Keypad w/ Prox Reader ePADTM Virtual Keypad EXPANSION MODULES 708 Bus Extender 710/710F Bus Splitter/Repeater 711 Single Zone Expansion 712-8 8-zone Expansion 714 4-zone Class-B Expansion 714-8 8-zone Class-B Expansion 714-16 16-zone Class-B Expansion 715 4-zone 2-wire smoke Expansion 715-8 8-zone 2-wire smoke Expansion 715-16 16-zone 2-wire smoke Expansion 716 Output Expansion. 4 Form C relays. 4 open collector outputs 717 Graphic Annunciator: 20 open collector outputs 725 4-zone Expansion, 24 VDC 736P Radionics Interface 739 X-10 Interface AUXILIARY MODULES 860 Relay Output Module 865 Style W/X Notification Circuit Module 866 Style W Notification Circuit Module 867 LX-Bus Notification Circuit Module 869 Style D Initiating Circuit Module 893A Dual Phone Line Module SMOKE/HEAT DETECTORS 521 B/BXT Addressable Smoke. Clean Me 521 LX/LXT Addressable Smoke/Heat CleanMe SLR-835B Conventional Smoke SLR-835BH Conventional Smoke/Heat CELLULAR COMMUNICATORS CellComRT Remote Digital Cellular Communicator INTRUSION DETECTORS SentrolGContacts and Sensors Optex PIRs Potter Contacts and Sensors lane Contacts and Water Sensors Virtually any other Intrusion Detectors ACCESS CONTROL .734 Wiegand Interface Module OP-08CB REX Motion Detector PB-2 Request-to-Exit Button Proximity Readers and Credentials DMP ProxPatch COMPUTER SOFTWARE Remote Link Upload/Download Programming Software System Link End-User Management Software Advanced Reporting Module Alarm Monitoring Module Command Center Module Account Groups Module Link Server Application Entré Access Control Software CENTRAL STATION RECEIVERS SCS-1 R Security Control Receiver SCS-105 Single-Line DMP Serial 3 Receiver Compatible with Central Station Receivers that accept Standard CID, DD. or DMP Serial 3 messaging Two?) DMP WIRELESS 1100X Receiver I100XH High Power Receiver 1100R Repeater 1101 Universal Transmitter. Internal and External Contacts 1102 Universal Transmitter, External Contact 1103 Universal Transmitter, External Contact• 1105 Universal Transmitter. Internal and External Contact DMP WIRELESS CONTINUED 1107 Micro Window Transmitter 1114 Four-Zone Expander 1116 Relay Output 1117 LED Annunciator 1118 Remote Indicator Light 1119 Door Sounder 1121 Pet Immune PIR Motion Detector 1125 PIR Motion Detector 1126C Ceiling Mount Curtain PIR 1126R 360 Ceiling Mount PIR 1126W Wide Angle Ceiling Mount PIR 1127C Wall Mount Curtain PIR 1127W Wall Mount Wide Angle PIR 1129 Glassbreak Detector 1131 Recessed Contact 1135 Siren 1139 Bill Trap 1142 Two-Button Hold-up Transmitter 1142BC Two-Button Belt Clip Hold-up Transmitter 1145-4 Four-Button Key Fob 1145-2 Two-Button Key Fob 1145-1 One-Button Key Fob 1161 Residential Smoke Detector 1162 Residential Smoke/Heat Detector 1165 Commercial Smoke Detector 1165H Commercial Smoke/Heat Detector 1165HS Commercial Smoke/Heat Detector with Sounder 1181 Post Indicator Valve (UL) 1182 OS & Y Valve Supervisory Switch (UL) ACCESSORIES 300 Four-wire Harness 303 Silence/Reset Push-Button 305 Plug-in Output Relay 306 Tamper Harness 307-S Screw-On Tamper Switch 3012 CLip-On Tamper Switch 335 Intrusion Siren 370 Lightning Suppressor 374 Surge Voltage Suppressor 399 Programming Harness 431 Output Harness 861 Power Distribution Module SYSTEM SPECIFICATIONS LISTINGS AND APPROVALS Primary Power (included) 16.5 VAC 50 VA transformer Refer to the XR1 00 Series Installation Guide (LT-0899. LT-0899CAN). XR1 00 Secondary Power 12 VDC Battery Series Programming Guide (LT-0896. LT-0896CAN) and specific compliance Models 365, 366, 367, 368 or 369 listings for installation and programming requirements necessary to meet a Output Rating particular approval. Bell 1.5 Amps at 12 VDC ANSI/SIA CP-01 -2010 False Alarm Reduction Smoke and Auxiliary 1.5 Amps at 12 VDC California State Fire Marshall (CSFM) Current Draw 1 80m FCC Part 15 and FCC Part 68 Enclosures: New York City (FDNY COA #6055) Material Cold-rolled steel Underwriters Laboratories (UL) Listed Model (Gray or Red) 17.5 W x 13.5 H x 3.5' D UL AA High Line Security Model 350AiGray) —.__.17.5" W x 13.5" H X 3.75" D Underwriters Laboratories Canada (ULC) Listed For;additionat-information. access www.dmp.com and select Compliance. 800441A282dmp.com Springfield. Missouri 65803-8877 Made in the USA '2500 North Partnership Boulevard N. CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL - FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7165-1157:0123 Page 1 of 2 CATEGORY: 7165 - FIRE ALARM CONTROL UNIT (COMMERCIAL) LISTEE: Digital Monitoring Products2500 N. Partnership Blvd, Springfield, MO 65803 Contact: Terry Shelton (417) 831-9362 Fax (417) 831-1325 Email: tshelton@dmp.com DESIGN: Models XRSOO, XR500N, XR500E, XRIOO XRIOON, XR500FC, XR500NFC, XRIOOFC, and XRIOONFC combination fire andjrgIary alarm control units. Local, remote station (PPU), proprietary (PPU), and cent!3.Sfation (PPU) services. Refer to listee's data sheet for additional detailed prodtescription and operational considerations. System components: XR500, XR500N, XRIOO XRIOON; Main Board XR500FC, XR500NFC, XRIOOFC, XRIOONFC; Main Board 349, 350, 350A, 352P, 352X; Enclosure 341; Battery Enclosure 630F, 690, 690F, 693, 790, 790F, 791, 793; Supervised LCD Keypads 7060, 7060A, 7063, 7063A, 7064, 7070, 7070A; LCD Keypads 7073, 7073A, 7074, 7760, 7160, 7160A; LCD Keypads 7163, 7163A, 7170, 7170A, 7173, 7173A; LCD Keypads 7560, 7560A, 7563, 7563A, 7570, 7570A, 7573, 7573A; LCD Keypads 325; Transformer Bracket 322, 327, 323; Transformer Adaptor 481, 462N, 462P, 462FM, 472; Interface Card 461; Interface Adaptor 714,714-8,714-16,715, 711, 711E; Zone Expanders 715-8, 715-16, 725; Zone Expanders Output Expander Annunciator Module 860; Relay Module 865, 866, 867; Indicating Modules 869; Initiating Module 893A; Dual Phone Line Module 733, 734; Wiegand Interface 73613; Interface Module 710, 710F; Bus Splitter 303; Reset/Silence Switch iCOM, iCOM-E; Internet Alarm Router IlOOX, I100XH; RF (Wireless) Receiver IlOOR; Wireless Repeater 1103; Wireless Transmitter *463C463G; Digital Cellular Communicator (may be used as the stand alone primary Rev. 10-22-12 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2013 Listing Expires June 30, 2014 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division Listing No. 7165-1157:0123 Page 2 of 2 communicator) RATING: 120 VAC, 0.5 A, 60 Hz primary, 12 VDC secondary INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as combination fire and burglary alarm control units for use with separately listed electrically compatible initiating and indicating devices. Refer to listee's Installation Instructions Manual for details. These control units can generate a distinctive three-pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition. This control unit meets the requirements of UL Standard 864, 9th Edition. NOTE: 1. The Fire Alarm Verification Feature (delay of fire alarm signal), the maximum Retard/Reset/Restart period shall not exceed 30 seconds. 2. Burglary and other non-fire functions were not examined. Rev. 10-22-12 gt This. listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2013 Listing Expires June 30, 2014 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division a cED Simple Expansion Solutions Expand your DMP Command Processorlm panel options with a wide array of expansion modules. Add supervised Class B burglary zones. Connect non-powered burglary or fire type devices for intrusion, glassbreak, and motion detection. Add 12 VDC zones for addressable 2-wire smoke detectors with 715 moduels. SINGLE AMD MULTIPLE P(MIN.7 ZONE EXPANSION MODULE FEATURES Provides Class B zones for burglary and fire Compatible with DMP Command Processor Panels that allow zone expansion Suitable for mounting near protection devices Connect devices using 4-wire bus Easily mount attractive cases on wall or 3-gang box Compatible with all panel zone types Easy connection to 4-wire keypad or LX.BuslM Proven design ensures stability and performance Data LED on zone expander indicates good panel communication Durable and attractive plastic or metal housing Low current draw Can be powered from panel or auxiliary power supply 7Z crr r_ rjçj-_ I .T JC.L USE ON THE DMP LX-BUSTm The modules can be used on the LX-Bus' of DMP Command Processorlm Panels. The modules connect to the 4-wire bus and use only one zone address. To assign an additional zone expander use the next available zone address. CONNECT TO KEYPAD BUS You can also use the modules as an addressed device on the keypad data bus of DMP Command Processor panels. Simply set the module to an available keypad address and connect the wiring to the appropriate screw terminals. SIMPLE ADDRESSING Address the 711, 714, 714-8, 714-16, 715, 715-8, 715-16, and 725 modules by setting two on-board rotary switches with a small screwdriver. The 712-8 uses slide dip switches. EASY INSTALLATION Zone Expansion Modules are mounted in a decorative plastic housing suitable for installing outside the panel enclosure, such as on walls or single gang boxes. After all wiring connections are made, the cover snaps on to form tight-fitting protection against incidental contact or tampering. 714-8, 714-16, 715-8, and 715-16 Zone Expanders are housed in a rugged, 20-gauge, cold-rolled steel enclosure. You may also mount the 708, 710, 710F, and 725 modules inside a DMP enclosure using the 3-hole configuration and the provided standoffs. The 712-8 only mounts using the 3-hole configuration and provided standoffs. ZONE PROGRAMMING Program the zone on the modules with any of the panel's available zone types for use in burglary applications including Arming type zones when used with keyswitches. The expansion zones are programmable for annunciation on DMP keypads connected to the panel. Each zone can also be individually programmed to report alarms, troubles, and restorals to remote DMP SCS-1 R Receivers. 708 BUS EXTENDER MODULES The 708 Bus Extender Modules allow you to increase the length of wire used to run an LX-Bus or keypad bus by a maximum of 4,000 feet, while providing immunity to noise on the wires. The 708 Bus Extenders are received from the factory as a pair of modules that connect between the panel and LX-Bus or keypad bus devices. Use the 708 Modules for applications that include running wire over long distances, through noisy environments, or where the bus is bundled with other wires, such as telephone company wire. The 708 Extender can be used on all DMP panels. 708 FEATURES Extends Keypad Bus or LX-Bus by 4000 feet with one pair of modules Connects to an auxiliary power supply for added power Uses existing wire: No need to run additional wire Allows twisted pair and/or shielded wire between the 708 modules 710171 OF BUS SPLITTER! REPEATER MODULES The 710 and 710F Bus Splitter/Repeater Modules allow you to expand the typical LX-Bus or Keypad bus installation both in the number of devices and the length of the wire used. Each 710/710F Module provides three bus connections each up to 2,500 feet. When using multiple modules, the total distance of all circuits can be an incredible 15,000 feet! hO As a splitter, the 710 provides superior mechanical wire connecting capability for up to three additional 12 VDC LX-Bus or keypad bus circuits. This makes the 710 module an excellent junction box when terminating multiple LX-Bus/keypad bus runs at one location. As a repeater, the 710 module can be installed at the end of an LX-Bus or keypad bus circuit to allow an additional circuit to be added, thus increasing the total wire length. 71 OF As well as providing all of the functions of the 710 listed above, the 710F also allows you to use the 725 Zone Expander to expand the number of 24 VDC zones. The 710F Bus Splitter/Repeater allows the connection of a 24 VDC power supply to the 725 to power smoke detectors and isolate the 24 Volt source from the panel. Therefore, the 710F must be used when using the 725 Zone Expander. 712-8 ZONE EXPANSION MODULE Expand your system at an affordable price! You can connect non-powered burglary devices to DMP Command Processor panels using the 712-8 Module. The 712-8 Module is compatible with many intrusion contacts, glassbreak detectors, motion detectors, and intrusion detectors. 712-8 FEATURES Eight grounded, addressable burglary zones Set jumper for LX-Bus or Keypad bus operation Compatible with all DMP Command Processor panels Expand systems by daisy chaining a second 712-8 Easily address using dip switches Snaps into panel enclosure using 3-hole pattern Separate zone 1K End-of-Line resistors included ___________ 7141715 ZONE EXPANDERS 714-8, 714-16, 715-8, AND 725 24 VDC EXPANSION The 714 contains four Class B burglary 71 5-16 DESCRIPTION MODULE zones and is suitable for use with burglary The expanders are housed in a Model The 725 provides four 24 VDC powered and fire devices that are normally opened 340 locking metal enclosure suitable zones that enable you to connect or normally closed. Individual zones are for mounting in a remote Location. 2-wire smoke detectors to the XR500 supervised with 1k Ohm EOL resistors and Each expander provides screw terminal Series, XR2500F, XR200, and XR200-485 can be programmed with any burglary or strips for zone inputs and data bus Command Processor Panels. As a result, fire zone type. connections, a two position jumper to the 725 provides you the, flexibility to The 715 contains four Class B powered zones and is suitable for use with 12 VDC, 2-wire smoke detectors and non-powered on the 715 are supervised with a 3.3k Ohm EOL resistor and can be programmed with any burglary or fire zone type. fire or burglary devices. Individual zones uesignte connection to tne KeypaG ous retront a L4 vott system witnout tne need or the LX-Bus, and an LED to indicate to run more wire or change to 12 Volt communication with the panel. Separate smoke detectors. zone End-of-Line resistors are included with each expander. OPTIONAL ACCESSORIES The standard wiring harness can be replaced with the optional 7181 Plug-in Screw Terminal. The enclosure can also accommodate the 7191 Terminal Boards for the 714 or the 7201 Terminal Boards for the 715, which pass through the wiring of the panel's LX-Bus. 1K EOL resistors are included with the 719T and 3.3K resistors are included with the 7201. 714/715 FEATURES Four protection zones on each module Comes with 12-conductor wire harness Optional 12-position screw terminal 714-81714-16 EXPANDERS The 714-8 Expander contains 8 Class B zones. The 714-16 Expander contains 16 Class B zones. Both are suitable for use with normally open or normally closed burglary and fire devices. Individual zones are supervised with a 1k Ohm EOL resistor and can'Eprocazjd as any zone type. 715-81715-16 EXPANDERS The 715-8 Expander contains 8 Class B powered zones. The 715-16 Expander contains 16 Class B powered zones. Both are suitable for use with 12 VDC 2-wire devices, such as smoke detectors or with non-powered fire or burglary devices. Individual zones are supervised with a 3.3k Ohm EOL resistor and can be programmed as any zone type. 714-8,714-16,715-8, AND 715-16 FEATURES 8 or 16 protection zones per expander Durable metal enclosure housing with lock and key Individual screw terminals accommodate 14 to 22 gauge wire for easy connection Suitable for mounting in a remote location 725 FEATURES Provides four 24 VDC zones Sensor reset performed through panel relay or 716 Output Expander Powered from 24 VDC power supply Supervised operation 24 Volt surge protection from 710F Provides ability to use 24 VDC 2-wire smoke detectors Easily mounted in 3-hole pattern ill DESCRIPTION The 711 Zone Expansion Module connects to the panel's 4-wire keypad bus or LX-Bus and are set to an address that determines the reporting zone number. The 711 provides one Class B zone for the connection of detection devices. 711 FEATURES Single-zone expander Rugged screw terminals accommodate 14 to 22 AWG Board fits in Radionics POPIT housing Easy rotary switch addressing Digital M.nitoring Product. r nrrcnJJ rr ZONE EXPANSION MODULE COMPARISON CHART Refer to the chart below for a comparison of the features for each DMP Zone Expansion Module. Module Address Number of Zones 3-HolePlastic Case Operating Voltage Compatible Panels 708 N/A N/A Yes Yes 12 VDC All DMP 12 VDC 710 N/A N/A Yes Yes 12 VDC 710F N/A N/A Yes Yes 712-8 DipSwitch 8 Yes No 12VDC XR500 Series, XR2500F XRSuper6, XR20, XR40, XR200, XRZOO-485 12VDC 711 Rotary 1 No Yes 12 VDC 714 Rotary 4 Class B No Yes 12VDC 714-8 Rotary 8ClassB No MetalEnclosure 12VDC 714-16 Rotary 16ClassB No MetalEnclosure 12VDC 715 Rotary 4ClassB No Yes 12VDC 715-8 Rotary 8ClassB No MetalEnclosure 12VDC 715-16 Rotary 16ClassB No MetalEnclosure 725 Rotary 424VDCClassB No Yes 24VDC XRSOO Series, XR2500F,XR200,XR200-485 7141715 SPECIFICATIONS Operating Voltage 8.8 to 15.0 VDC Operating Current 714 Average 7mA+ 1.6mA per zone Alarm 7mA + 2mA per zone 715 Average 7mA + 4mA per zone + 0.1 per 2-wire smoke Alarm 7mA + 58mA per shorted zone + 0.1 per 2-wire smoke + 30mA per smoke in alarm Dimensions 4.5" X 2.75" X 1.75" 714-89 714-16, 715-8, AND 715-16 SPECIFICATIONS Operating Voltage 8.8 to 15.0 VDC Operating Current 714-8/16 Average 20mA + 1.6mA per zone Alarm 20mA + 2mA per zone 715-8/16 Average 20mA + 4mA per zone + 0.1 per 2-wire smoke Alarm 20mA + 58mA per shorted zone + 0.1 per 2-wire smoke + 30mA per smoke in alarm Enclosure 20-Gauge cold-rolled steel Dimensions 12.5" W 11.5" H x 3.5" D 714-8/-16 Color Gray 715-8/-16 Color Red MODULE SPECIFICATIONS 708 SPECIFICATIONS Operating Voltage 8.8 to 15.0 VDC Operating Current 20mA Per Pair Dimensions 4.5" X 2.75" X 1.75" Maximum Distance 4,000 feet between the two 708 Modules 710171 OF SPECIFICATIONS Operating Voltage 8.8 to 15.0 VDC Operating Current 710 30mA 710F 40mA Dimensions 4.5" X 2.75" X 1.75" Distance 2,500 feet (one module), 15,000 feet maximum 711 SPECIFICATIONS Operating Voltage 8.8 to 15.0 VDC Operating Current Average 7mA + 1 .6mA per active zone Alarm 7mA + 2mA per zone in alarm Zone Voltage 5 VDC (1 .6mA across EOL) Dimensions 4.5" X 2.75" X 1.75" 712-8 SPECIFICATIONS i LISTINGS AND APPROVALS Operating Voltage 8.8 to 15.0 VDC i Refer to the appropriate panel programming and installation Current Draw 17mA + 1.6mA per active zone for specific compliance listings for installation and prograi 17mA + 2mA per zone in alarm I requirements necessary to meet a particular approval. Dimensions 4.5" H x 2.5" W 725 SPECIFICATIONS Operating Voltage 24 VDC Nominal Average Current 8mA + 4mA per active zone Alarm Current 8mA + 4mA per active zone + 30mA per smoke in alarm + 47mA per shorted device EOL Resistor Model 316 6.8k EOL Underwriters Laboratories (UL) Listed California State Fire Marshall (CSFM) New York City MEA accepted (711, 714, 715 only) For additional information, access www.dmp.com and select Compliance. 2500NorthPartnershipBoulevard Springfield, Missouri 65803-8877 IN CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL NFL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM b '1 LISTING SERVICE LISTING No. 7165-1157:0124 Page 1 of 2 CATEGORY: 7165- FIRE ALARM CONTROL UNIT (COMMERCIAL) LISTEE: Digital Monitoring Products2500 N. Partnership Blvd, Springfield, MO 65803 Contact: Terry Shelton (417) 831-9362 Fax (417) 831-1325 Email: tshelton@dmp.com DESIGN: Model XR2500F *combination fire and burglary alarm control unit. Local, remote station, proprietary, and central station services. Refer to listee's data sheet for additional detailed product description and operational considerations. System components: XR500; Main Board 322, *323, *327; Transformer Adaptor 725; Zone Expander Output Expander Annunciator Module 630, *630F, 690, 693, 790; Supervised LCD Keypad 791, 790F, 793; Supervised LCD Keypad 7060, 7060A, 7160, 7063; *LCD Keypads 7063A, 7163, 7070, 7070A; *LCD Keypads 7170, 7073, 7073A, 7173; LCD Keypads 866; Indicating Module 893A; Dual Phone Line Module 710F; Bus Splitter 481, 462N, 462P; *Interface Card *461; Interface Adaptor 714, 714-8, 714-16, 715, 711; Zone Expanders 715-8, 715-16, 725; Zone Expanders 860; *Relay Module 865, 867, 869; *Indicating Module 893A; *Dual Phone Line Module 733 734; *wiegand Interface 303; *ReseUSilence Switch 710; *BUS Splitter IlOOX: *RF (Wireless) Receiver 1101, 1102, 1103; *Wireless Transmitters RATING: 16 VAC S6VA INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. Rev. 04-24-08 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2013 Listing Expires June 30, 2014 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division Listing No. 7165-1157:0124 Page 2 of 2 MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as a fire alarm control unit for use with separately listed electrically and functionally compatible initiating and indicating devices. Intended for use with separately listed Models 521 LX and 521 LXT (CSFM Listing No. 7272-1157:106) 2-wire photoelectric type smoke detectors or Model SLRLX (CSFM Listing No. 7300-1157:122) 2-wire smoke detector base. Refer to listee's Installation Instruction Manual for details. This control unit does not generate a temporal pattern signal. if the distinctive three-pulse Temporal Pattern Fire Alarm Evacuation signal (for total evacuation) in accordance with NFPA 72, 2002 Edition is required the control unit must be used with appliances that can generate the temporal pattern signal. This control unit meets the requirements of UL-864, 8th Edition Standard. NOTE: For Fire Alarm Verification Feature (delay of fire alarm signal), the maximum Retard/Reset/Restart period shall not exceed 30 seconds. *Rev. 04-24-08 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct e.VG operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2013 Listing Expires June 30, 2014 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division L L (• LISTED Pvo©effecic Sm©ke Ond Smokelll-Øecicc Detectors The SLR Series are suited for commercial and residential applications. All-in-one units and separate base and head units make the SLR series a flexible smoke detection option. Unrivaled smoke detection performance backed by years of fire detection engineering expertise Units work in any application where photoelectric smoke or heat detectors are specified Automatic Sensitivity window verification meets NFPA 72 inspection, testing, and maintenance requirements Extremely low profile and clean, decorative Lines are suited for architecturally sensitive environments SLR SERIES PHOTOELECTRIC SMOKE DETECTORS - .,. .. !S6- B 00W BASE FEATURES Compatible with SLR-835 or SLR-835H detector heads Base and heads available in white PC/ABS blend 6" diameter base Optional trim ring 2-wire relay detector Ut-3 EJ'X 12 VDC or 24 VDC operating voltage Low profile - only 1.8" high with base For use with the N56-100W Base 135' F latching heat sensor 12 VDC or 24 VDC operating voltage Low profile - only 2.2" high with base Low profile - only 2.375" high • For use with the NS6-100W Base 135' F latching heat sensor EECO FEATURES Removable smoke chamber for cleaning or replacement Superior RF and transient voltage protection Two built-in Status/Sensitivity/Alarm LEDs Non-directional smoke chamber Tamper-resistant security locking feature Direct 2-wire unit with trim ring, no base needed Choose either 12 VDC or 24 VDC operating voltage Available in ivory Low profile - only 2" high L:ik Direct 2-wire unit with trim ring, no base needed Choose either 12 VDC or 24 VDC operating voltage Available in ivory C IF BUILT-IN STATUSJALARM LED SLR-835B ENGINEERING The SLR Series Detectors use two built-in, This direct-wire detector is a complete SPECIFICATIONS bi-color LEDs to indicate status. In a single unit that mounts in all areas The contractor shall furnish and install normal condition, the LEDs flash Green where photoelectric smoke detectors where indicated on the plans, DMP/ every three seconds. When the detector are required. Its compact size and stylish Hochiki Model SLR-835B Photoelectric recognizes that its sensitivity has drifted design fit in to any environment. Smoke Detectors or DMP/Hochiki Model outside the UL listed sensitivity window, SLR-835BH flkl....i.. .....I. the LEDs flash Red every three seconds. A single unit direct-wire photoelectric When the detector senses smoke and heat smoke detector that mounts in all goes into alarm, the status LEDs latch on areas where both smoke and heat fire Red. The LEDs stay on until the detector detection is required. Rated to detect is reset. heat from fires at 135° F or higher. The ADVANCED SMOKE CHAMBER heat detector is self-restoring and makes TECHNOLOGY testing quick and easy. The smoke chamber in the SLR Series NS6- 100W BASE Detectors consist of a pulsing LED light source and a silicon photo diode receiving A six-inch base unit for use with the element. During normal operation, the SLR-835 photoelectric smoke detector head or SLR-835H photoelectric smoke receiving element receives no light from the light source and remins..in a normal heat detector head. An optional trim condition. In the event of a ti°°°sngi ring can be installed as required. particles enter the smoke chamber and SLR-835 HEAD cause light from the LED light source to Connected to the NS6-100W base, this reflect into the receiving element. The detector provides quality photoelectric received light is processed by the detector smoke detection in any environment. circuitry and indicated as an alarm to the Suitable for business, public areas, and Fire Alarm Control Panel (FACP). homes. SUPERIOR HEAT DETECTION SLR-835H HEAD The SLR-835H and SLR-835BH add heat Using the NS6-100W base this unit not only detection capabilities to the smoke provides photoelectric smoke detection detection features. The wide range but adds heat sensitivity for even more chamber allow these photoelectric heat security. This self-restoring heat detector smoke detectors to quickly respond can detect fires radiating 135° F or higher. to both smoldering ember or flaming Place the SLR-835H in all areas where fires. Working together with the smoke both smoke and heat fire detection is detection capabilities, when a fire required. reaches 135° F the latching heat sensor immediately sets off the alarm. SLR SERIES SPECIFICATIONS LISTINGS AND APPROVALS Average Standby Current 38mA ave. @ 12 VDC Underwriters Laboratory (UL) Listed 55mA ave. @ 24 VDC California State Fire Marshal (CSFM) Alarm Current 150mA max. For additional information, access www.dmp.com and select Compliance! Alarm Trip Current 6mA minimum Operating Voltage PANEL COMPATIBILITY Nominal 12 VDC or 24 VDC SLR835B/SLR-835BH Working 8.0 to 35.0 VDC XR500 Series Command Processor Panel - Requires 725 Module Ambient Temperature 32°F to 120°F XR2500F Addressable Fire Alarm Control Panel - Requires 725 Module SLR-835B1SLR-8358H XR100 Series Command Processor Panel - Requires 725 Module 835BH Heat Sensor 135° F XR5 Fire Commandlm Panel Compatibility Identifier HD-6 XRSuper6, XRZO, or XR40 Command Processor Panel SLR-8 3 SISLR-8 3 SH HEADS XRZOO or XR200-485 Command Processor Panel 835H Heat Sensor 135° F NS6-100W with SLR-835 Head or SLR-835H Head Compatibility Identifier HD-3 XR500 Series Command Processor Panel XR2500F Addressable Fire Alarm Control Panel XR100 Series Command Processor Panel XRZOO or XR200-485 Command Processorlm Panel INTRUSION - FIRE - ACCESS - NETWORKS 2500 North Partnership Boulevard Digital MnitorkigProduct; Made in the USA Springfield, Missouri 65803-8877 .L.CUJJ r,uuwic..0 II.., flL IIIUI\ Detector mounted on a DMP/Hochiki Model N56-100W base. The detector heads shall be listed compatible with UL listed fire alarm panels. The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED shall latch at full brilliance. The detector may be reset by actuating the fire alarm control panel reset switch. The detector shall have a sensitivity window verification feature. The vandal resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field-selectable. It shall be possible to perform a functional test of the detector without the need to generate smoke. The method shall simulate the effects of products of combustion in the chamber to ensure testing of detector circuits. Voltage and RF transient suppression techniques shall be employed to minimize false alarm potential. CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7272-0410:0107 Page 1 of I CATEGORY: 7272 - SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC LISTEE: Hochiki America Corporation7051 Village Drive, Ste. 100, Buena Park, CA 90621-2268 Contact: Michael Urn (714) 670-3248 Fax (714) 522-2268 Email: murn@hochiki.com Models SLG-12, SLG-24, SLG-24FH, SLG-24F, SLK-12, SLK-24ZLK-24FH, SLK-24FB, DESIGN: SLK-24FL, SLK-24FLB, SLK-835, SLK-835H, SLR-835, SLR-835W, SLR-835B-2, SLR-835B-4, SLR-835B-2W, SLR-835B-4W, SLR-24, SLR-24H, SLR-24V, *SLR..24VN SLR-835H, SLR-835HW, SLR-835BH-2, SLR-835BH-2W, SLR-835BH-4, SLR-835BH-4W photoelectric type smoke detectors. Unit with suffix -H or -FH employs a supplemental heat sensor. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 12 VDC and 24 VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model designation, electrical rating and UL label. APPROVAL: Listed as photoelectric smoke detectors for use with separately listed compatible fire alarm control units when used in conjunction with listee's listed bases (CSFM Listing No. 7300-0410:132). Models with supplemental heat sensor are not approved for use in lieu of required heat detectors. NOTE: Formerly 7257-0410:107 *Rev 2-14-2003 IPI This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2013 Listing Expires June 30, 2014 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division mom, I 14aca4III - c'31ecträc Smoke and Smolze/Heat Detecears The SLR Series are suited for commercial and residential applications. All-in-one units and separate base and head units make the SLR series a flexible smoke detection option. Unrivaled smoke detection performance backed by years of fire detection engineering expertise Units work in any application where photoelectric smoke or heat detectors are specified Automatic Sensitivity window verification meets NFPA72 inspection, testing, and maintenance requirements Extremely low profile and clean, decorative lines are suited for architecturally sensitive environments SLR SERIES PHOTOELECTRIC SMOKE DETECTORS DETECTOR FEATURES Removable smoke chamber for cleaning or replacement Superior RF and transient voltage protection Two built-in Status/Sensitivity/Alarm LEDs Non-directional smoke chamber Tamper-resistant security Locking feature L3B Direct 2-wire unit with trim ring, no base needed Choose either 12 VDC or 24 VDC operating voltage Available in ivory Low profile - only 2" high SLR-8358H Direct 2-wire unit with trim ring, no base needed Choose either 12 VDC or 24 VDC operating voltage Available in ivory Low profile -.:only 2.375" high 135° F .latchingheat-sensor M56-Mr: BASE FEATVJRES Compatible with SLR-835 or SLR-835H detector heads Base and heads available in white PC/ABS blend 6" diameter base Optional trim ring 2-wire relay detector SL4U 12 VDC or 24 VDC operating voltage Low profile - only 1.8" high with base For use with the NS6-100W Base &L-R-83SH REAL' 135 F latching heat sensor 12 VDC or 24 VDC operating voltage Low profile - only 2.2" high with base For use with the N56-IOOW Base J~. SLR SERIES SPECIFICATIONS Average Standby Current 38mA ave. @ 12 VDC 55mA ave. @ 24 VDC Alarm Current 150mA max. Alarm Trip Current 6mA minimum Operating Voltage Nominal 12 VDC or 24 VDC Working 8.0 to 35.0 VDC Ambient Temperature 32°F to 120°F SLR-83 5BISLR-83 SBH 835BH Heat Sensor 135° F Compatibility Identifier HD-6 SLR-83S/SLR-835H HEADS 835H Heat Sensor 135° F Compatibility Identifier HD-3 U IF _ BUILT-IN STATUS/ALARM LED SLR-835B ENGINEERING The SLR Series Detectors use two built-in, This direct-wire detector is a complete SPECIFICATIONS bi-color LEDs to indicate status. In a single unit that mounts in all areas The contractor shall furnish and install normal condition, the LEDs flash Green where photoelectric smoke detectors where indicated on the plans, DMP/ every three seconds. When the detector are-required. Its compact size and stylish Hochiki Model SLR-835B Photoelectric recognizes that its sensitivity has drifted design fit in to any environment. Smoke Detectors or DMP/Hochiki Model outside the UL listed sensitivity window, SLR-835BH SLR-835 Photoelectric/ Heat Smoke the LEDs flash Red every three seconds. When the detector senses smoke and A single unit direct-wire photoelectric Detector mounted on a DMP/Hochiki Model NS6-100W base. The detector heads goes into alarm, the status LEDs latch on heat smoke detector that mounts in all areas where both smoke and heat fire shall be Listed compatible with UL listed Red. The LEDs stay oNtiL the detector rlpferfinn is rpniiirpri Rated tn itrt fire alarm panels. is reset. heat from fires at 135° F or higher. The ADVANCED SMOKE CHAI4BER heat detector is self-restoring and makes TECHNOLOGY testing quick and easy. The smoke chamber in the SLR Series Ns64 00W BASE Detectors consist of a pulsing LED light A six-inch base unit for use with the source and a silicon photo diode receiving SLR-835 photoelectric smoke detector element. During normal operation, the head or SLR-835H photoelectric smoke receiving element receives no light from heat detector head. An optional trim the light source and remains in a normal ring can be installed as required. condition. In the event of a fire, smoke particles enter the smoke chamber and SLR-835 HEAD cause light from the LED light source to Connected to the NS6-100W base, this reflect into the receiving element. The detector provides quality photoelectric received light is processed by the detector smoke detection in any environment. circuitry and indicated as an alarm to the Suitable for business, public areas, and Fire Alarm Control Panel (FACP). homes. SUPERIOR HEAT DETECTION SLR-835H HEAD The SLR-835H and SLR-835BH add heat Using the N56-1 00W base this unit not only detection capabilities to the smoke provides photoelectric smoke detection detection features. The wide range but adds heat sensitivity for even more chamber allow these photoelectric heat security. This self-restoring heat detector smoke detectors to quickly respond can detect fires radiating 135° F or higher. to both smoldering ember or flaming Place the SLR-835H in all areas where fires. Working together with the smoke both smoke and heat fire detection is detection capabilities, when a fire required. reaches 135° F the latching heat sensor immediately sets off the alarm. The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED shall latch at full brilliance. The detector may be reset by actuating the fire alarm control panel reset switch. The detector shall have a sensitivity window verification feature. The vandal resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field-selectable. It shall be possible to perform a functional test of the detector without the need to generate smoke. The method shall simulate the effects of products of combustion in the chamber to ensure testing of detector circuits. Voltage and RF transient suppression techniques shall be employed to minimize false alarm potential. LISTINGS AND APPROVALS Underwriters Laboratory (UL) Listed California State Fire Marshal (CSFM) For additional information, access www.dmp.com and select Complia PANEL COMPATIBILITY SLR-835B/SLR-835BH XR500 Series Command Processor"' Panel - Requires 725 Module XR2500F Addressable Fire Alarm Control Panel - Requires 725 Module XR100 Series Command Processor Panel - Requires 725 Module XR5 Fire Command Panel XRSuper6, XR20, or XR40 Command Processor' Panel XR200 or XR200-485 Command Processor Panel NS6-100W with SLR-835 Head or SLR-835H Head XR500 Series Command Processor Panel XR2500F Addressable Fire Alarm Control Panel XR100 Series Command Processorm Panel XRZOO or XR200-485 Command Processor Panel 2500 North Partnership Boulevard Springfield, Missouri 65803-8877 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7300-0410:0132 Page 1 of 2 CATEGORY: 7300 - FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: Hochiki America Corporation 7051 Village Drive, Ste. 100, Buena Park, CA 90621-2268 Contact: Michael Urn (714) 670-3248 Fax (714) 522-2268 Email: mum@hochiki.com DESIGN: Detector bases (2 and 4-wire). Unit is intended for use with a separately listed compatible detector head. Refer to listees data sheet for detailed product description and operational considerations. Models listed below. HA-4W HA-4W1 HA-4WX HA-2 HA-SL HA-SR HA-SLR I-IA-RA2 I-IA-NRA2 HA-1-12R HA-2R HA-22R HA-1-2 HA-1-2A HA-L2R HA-1-22 HA-1-22A HA-1-22F HA-1-22R HA-1-22S HA-LA2 HA-LRA HA-LRA2 HA-LNA2 HA-LNRA2 HS-2 HS-21- HS-20 HS-21 HS-21L HS-21D HS-22 HS-22L HS-22D HS-100 HS-200D HS-220 HS-220L HS-220D NS-221 HS-221L HS-221D HS-221X HS-221XL HS-221XD HS-224 HS-224L HS-224D HS-225 HS-225L HS-225D HS-2RB HS-21 RB HS-220RB HS-221 RB HS-224RB HS-2RB4 HSB-2 HSB-2N HSB-12-1 HSB-12-IN HSB-12-4 HSB-12-4N RSB-21 HSB-21N HSB-100 HSB-200 RSB-200N HSB-220 HSB-220N HSB-221 l-ISB-221N HSB-2215 HSB-224 HSB-224N HSB-225 HSB-225N HSC-4R HSC-21L HSC-220L HSC-220R HSC-221L HSC-221R HSC-224RA HSC-224L HSC-224R HSC-225L HSB-DCP-6 HSB-NSA-6 YBA-M2 YBA-M21 YBA-M22 YBA-M220 YBA-M221 YBA-M224 YBA-M225 YBA-M 100 YBA-MAP YBA-R3 YBA-RL/4 YBA-RL/4-1 YBA-RU4-2 YBA-RL/4-RA YBC-RLII2 YBC-RLJI2-1 Rev 01-12-12 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2013 Listing Expires June 30, 2014 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division Listing No. 7300-0410:0132 • Page 2of2 YBC-RL/12-2 YBC-RL/12-4 YBC-RL/4-RA YBC-RLI2NC YBC-RLI2NBE YBJ-RLI2ND YBN-RI2NA YBN-NSA-4 NS4-100 NS4-220 NS4-221 NS4-224 NS6-100 NS6-220 NS6-221 NS6-224 *FFO4BASE *FFO613ASE *FFOSBASE Models may or may not come with suffix -W. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as bases for use with listee's separately listed compatible smoke and heat detectors. Refer to heat or smoke detector listings for compatibility. Models HA-2R, HA-SLR, HA-LRA2 and HSC Series w/ suffix R are also suitable for releasing device service. Model YBA-R3 is intended for use with thermostat detector only. NOTE: Formerly 7300-0410:100, 106, 115, 124, 125, 126, 130, 131 & 133 *Rev O1_12.12 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2013 Listing Expires June 30, 2014 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division 463G Digital Cellular Communicator Description The 463G Digital Cellular Communicator provides a fully supervised alarm communication path over the GPRS network. The 463G is installed in the panel J6 Interface Card connection or a 461 Interface Adaptor card and powered by the panel so no additional enclosure, power supply or battery back-up is needed. What is Included The 463G includes the following: One Model 463G One Model 380-400 SIM Card (463G only, 463G NOSIM requires SIM card to be provided from alternate carrier) One Model 381-2 18-inch Coax cable with SMA connector One Model 300 4-Wire LX-Bus harness One Model 383 Rubber Duck Antenna One Ferrite Core Compatibility The 463G is compatible with the XR100IXR500 Series panels using software Version 202 or higher. For ULC listed applications, use software Version 203C or higher. TiwfIIIiasii Cmifimi4i. LU UU U V Ground Yourself Before Handling the Panel! To discharge static, touch any grounded metal, such as the enclosure, before touching the panel. Remove All Power From the Panel! Remove all AC and Battery power from the panel before installing or connecting any modules, cards, or wires to the panel. Installing the 463G Align the 463G card 50 pin connector with the J6 connector and press the card onto the connector while applying even pressure to both sides of the board. See Figure 1. Connecting the Antenna Position one of the supplied washers onto the SMA connector and push the threaded end through an enclosure knockout. Position the second washer onto the threaded end extending through the knockout and secure the nut. Attach the included Rubber Duck Antenna to the SMA connector. See Figure 1. As an alternative, the antenna coax can be connected directly to the 463G SMA connector when the coax enters the enclosure via conduit. Nut Antenna Washers \öConnector SMA Conneor 0IXR500 anel 465G erface Card —i.[ Interface ector Card Coax Cable from 463G Le,d slMcard.f_I Zone Expansion SMA Harness Connector -Connector D _________ to ___________ Ut-Bu __________________ Modules I®I®I®I®I®IV Red—Auxiliary Power 54 25 26 27 25 Yellow—Data In Green—Data Out Black—Ground Figure 1: Install and connect the 463G and Antenna Connecting Panel Power Before re-applying AC power, attach the included ferrite core inside the enclosure Connect to AC around the AC wires connected to terminals 1 and 2 as shown in Figure 2. Ensure transformer the wire is wrapped around the ferrite core (passes through the core twice) before ( closing and snapping the two halves of the core together. Then, reconnect all AC and k. Battery power to the panel. Connectto Note: For the XR100FC/XR500FC panels, attach the ferrite core to the top of the aneermInels pre-formed loop on the AC Wires. LXBusTM Expansion Capability F 2 Ferrite C The 463G card also provides a 4-wire LX-Bus' for the addition of any combination Figure - em e ore of 100 protection zones and 100 relay outputs. Insert the harness connector into the 4-pin LX-Bus header on the bottom of the 463G Interface Card. Note: Do not use shielded wire when using the LX-Bus. Do not connect the wires from the 463G to panel terminals or the panel J22 header. Programming/Activation Cellular Service is required before using the 463G for signal transmission. In Remote Link panel communication programming, select CELL as one of the Communication paths and program the IP Address of the receiver. The 463G comes with a SIM card ready for activation with SecureCom Wireless, L.L.C. More information is available at www.securecomwireless.com or refer to the Remote Link Guide (LT-0565). Or, use a SIM card ~Mm provided by the GPRS carrier of your choice. If you are activating the unit with an alternate carrier, order Model 463G NOSIM. Diagnostics The XR100/XR500 Series panels provide a Diagnostics function to test the Communication integrity and Cellular Signal strength of the 463G. To use Diagnostics, reset the panel, enter the Diagnostics code 2313 (DIAG), and press COMMAND. Communication Status Select COMM STATUS from the Diagnostics menu. The XR100/XR500 Series panels test the 463G for the following items: 463G Installed • SIM Card Installed • SIM Card Registered /Active • Communication Path Integrity 463G Operating • Cellular Tower Detected • APN (Access Point Name) Correct • Signal Strength -XX dBm Cellular Signal ISIGNAL: 1111111 Select CELL SIGNAL from the Diagnostics menu. The XR100/XR500 Series panels test and indicates the strength of the signal using a bar display. One bar indicating a weak signal. Seven bars indicating a strong signal. The Xs represent the numerical value of the cell signal strength in -dBm. Wiring Specifications for LX-Bus When planning an LX-Bus installation, keep in mind the following specifications: DMP recommends using 18 or 22-gauge unshielded wire for all keypad and LX-Bus circuits. Do Not use twisted pair or shielded wire for LX-Bus and keypad bus data circuits. To maintain auxiliary power integrity when using 22-gauge wire do not exceed 500 feet. When using 18-gauge wire do not exceed 1,000 feet. Install an additional power supply to increase the wire length or add devices. Maximum distance for any one circuit (length of wire) is 2,500 feet regardless of the wire gauge. This distance can be in the form of one long wire run or multiple branches with all wiring totaling no more than 2,500 feet. As wire distance from the panel increases, DC voltage on the wire decreases. Maximum number of devices per 2,500 feet circuit is 40. Note: Each panel allows a specific number of supervised keypads. Add additional keypads in the unsupervised mode. Refer to the panel installation guide for specific number of supervised keypads allowed. Maximum voltage drop between the panel (or auxiliary power supply) and any device is 2.0 VDC. If the voltage at any device is Less than the required level, add an auxiliary power supply at the end of the circuit. When voltage is too low, the devices cannot operate properly. For additional information refer to the LX-Bus/Keypad Bus Wiring Application Note (LT-2031). FCC Information This device complies with Part 15 of the FCC Rules. Affix the included FCC label to the exterior of the panel enclosure in plain sight. Operation is subject to the following two conditions: This device may not cause harmful interference, and this device must accept any interference received, including interference that may cause undesired operation. Changes or modifications made by the user and not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. NOTE: This equipment has been tested and found to comply with the Limits for a class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation: If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: - Reorient or relocate the receiving antenna. - Increase the separation between the equipment and receiver. - Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/TV technician for help. Specifications Listings and Approvals Primary Power 12 VDC from panel FCC Part 15B and CISPR 22 Current Draw FCC ID: MIVGSM0308 Standby 22mA Industry Canada ID: 4160A-GSM0308 Alarm 45mA PTCRB Certified Ordering Information New York City (FDNY COA #6055) New York City (FDNY COA #6145) 463G Cellular Communicator Underwriters Laboratories (UL) Listed 463GCAN Canadian Cellular Communicator ANSI/UL 365 Police Station Connect Burglar Alarm Systems 463G NOSIM Cellular Communicator w/o SIM Card ANSI/UL 1023 Household Burglar Alarm System Units Accessories ANSI/UL 1076 Proprietary Burglar Alarm Units E Systems 380-400 Level 400 SIM Card (1 supplied with 463G) ANSI/UL 1610 Central Station Burglar Alarm Units 381-2 18 Coax cable with SMA connector ANSI/UL 864 Fire Protective Signaling, 9th Edition 381-12 iT Coax Extension ANSI/UL 985 Household Fire Warning System Units Underwriters Laboratories Canada (ULC) Listed 381-25 25 Coax Extension ULC Subject-C1023 Household Burglar 383 Rubber Duck Antenna ULC/0RD-C1076 Proprietary Burglar 386 Wall Mount Antenna Bracket ULC S304 Central Station Burglar ULC S545 Household Fire 2500 North Partnership Boulevard ® Springfield, Missouri 65803-8877 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7165-1157:0123 Page 1 of 2 CATEGORY: 7165- FIRE ALARM CONTROL UNIT (COMMERCIAL) LISTEE: Digital Monitoring Products2500 N. Partnership Blvd, Springfield, MO 65803 Contact: Terry Shelton (417) 831-9362 Fax (417) 831-1325 Email: tshelton@dmp.com DESIGN: Models XR500, XR500N, XR500E, XRIOO XR100N, XR500FC, XR500NFC, XRIOOFC, and XRIOONFC combination fire and burglary alarm control units. Local, remote station (PPU), proprietary (PPU), and central station (PPU) services. Refer to listee's data sheet for additional detailed product description and operational considerations. System components: XR500, XR500N, XR100 XR100N; Main Board XR500FC, XR500NFC, XRIOOFC, XRIOONFC; Main Board 349, 350, 350A, 352P, 352X; Enclosure 341; Battery Enclosure 630F, 690, 690F, 693, 790, 790F, 791, 793; Supervised LCD Keypads 7060, 7060A, 7063, 7063A, 7064, 7070, 7070A; LCD Keypads 7073, 7073A, 7074, 7760, 7160, 7160A; LCD Keypads 7163, 7163A, 7170, 7170A, 7173, 7173A; LCD Keypads 7560, 7560A, 7563, 7563A, 7570, 7570A, 7573, 7573A; LCD Keypads 325; Transformer Bracket 322, 327, 323; Transformer Adaptor 481, 462N, 462P, 462FM, 472; Interface Card 461; Interface Adaptor 714, 714-8, 714-16, 715, 711, 711E; Zone Expanders 715-8, 715-16, 725; Zone Expanders Output Expander Annunciator Module 860; Relay Module 865, 866, 867; Indicating Modules 869; Initiating Module 893A; Dual Phone Line Module 733, 734; Wiegand Interface 736P; Interface Module 710, 710F; Bus Splitter 303; Reset/Silence Switch iCOM, iCOM-E; Internet Alarm Router IlOOX, I100XH; RF (Wireless) Receiver 1100R; Wireless Repeat -' 1103; WireleJaRsMiIer *463c463GThigitaI Cellular Communicator (may be used as the stand alone primary Rev. 10-22-12 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed SJ the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct QV operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2013 Listing Expires June 30, 2014 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division Listing No. 7165-1157:0123 Page 2 of 2 communicator) RATING: 120 VAC, 0.5 A. 60 Hz primary, 12 VDC secondary INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as combination fire and burglary alarm control units for use with separately listed electrically compatible initiating and indicating devices. Refer to listee's Installation Instructions Manual for details. These control units can generate a distinctive three-pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72,2002 Edition. This control unit meets the requirements of UL Standard 864, 9th Edition. NOTE: 1. The Fire Alarm Verification Feature (delay of fire alarm signal), the maximum Retard/Reset/Restart period shall not exceed 30 seconds. 2. Burglary and other non-fire functions were not examined. *Rev. 10-22-12 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listees data sheet, installation instructions and/or other Date Issued: July 01, 2013 Listing Expires June 30, 2014 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division UL Listed and Rated Type CMR or FPLR Multi-Conductor Non-Shielded Non-Plenum Cable P/N WG-1103 11OWG Conductor Non-Shielded Non-Plenum [riptiori - - 22 AWG4 Conductor Solid Bare Copper Non-Shielded Non-Plenum, UL C(UL) - CMR0r FPLR UL - Conductor Description - 22 Solid - - - - - -Insulation PVC.00B"Norn. Color Code - Black/Red/Yellow/Green - - - - - )acket - PVC .018' - - - - Marking - - A B C D E 0 12 3 4 5 6 7 8 9 22 AWG ULC(UL)CMROR FPLR UL75CROHS MADE IN THE USA 1Overall Diameter .138" Nom. - ;condudorDcR 16.5011m5/Mft. - -- -- Capacitance - 12pF/Ft.Nom. - - - - Impedance 100 Ohms/Mft. Temperature & Voltage Rating - 0 Cto 75C/300 Volt - Cable Weight - 14Lbs/Mft. - - - Agencies Approvals: NEC Article 800, 760; UL C(UL) CMR or FPLR UL, RoHS Compliant, Made in the USA SmartWireTM Building Wire THHN, THWN-2, 190 Nylon, 1WN75 (cUl) Thermoplastic Insulated, Nylon Sheathed Heat, Moisture, Oil & Gasoline Resistant 600 Volt Copper Product Description: Windy City Wire Type THHN or THWN-2 conductors are primarily used in conduit as branch circuits in commercial or industrial applications, as specified by the National Electrical Code. Type THHN or THWN-2 are available as stranded in sizes 14 AWG - 10 AWG, and as solid in sizes 14 - 10 AWG. The conductors are soft-annealed, stranded or solid copper and are insulated with a tough, heat and moisture resistant polyvinyl chloride (PVC), over which a nylon (polyamide) jacket is applied. Specifications: Windy City Wire Type THHN or THWN-2 meets applicable ASTM specifications, UL Standard 83, UL Standard 758, and UL Standard 1063. The conductors are Gasoline and Oil Resistant II, and have a voltage rating to 600 volts. All THHN is UL and cUL Listed. CSFM# 7161-1727:0100 AWG Conductor PVC Size Nzi. Stands Thickness Insulation Nylon (Mils) Thickness Jacket (Mils) Nominal 0.D. (Mils) Ampacity 90 C THHN/THWN-2 1.. Approx. Net Weight Per MFT F. r r. tl. Windy 0— City 'Afire standard stocking 1,000 (both ways). Other put size, 1 000' RockPock ups available upon ----------------------------- Boxes, with request. Ascending/Descending Sequential Foot Markers (Ui.) LISTED c(U9 US LISTED MADE IN THE USA.