Series TY-FRB - 2.8, 4.2, 5.6, and 8.0 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The Tyco® Series TY-FRB, 2.8, 4.2,
5.6, and 8.0 K-factor, Upright and Pen-
dent Sprinklers described in this data
sheet are quick response - standard
coverage, decorative 3 mm glass bulb
type spray sprinklers designed for use
in light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20 (1/2 inch NPT) or Style 30 (3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment pro-
vided by the Recessed Escutcheon re-
duces the accuracy to which the fixed
pipe drops to the sprinklers must be
cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the 'INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
tamed when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TY-FRB Pendent Sprinklers
are detailed in Technical Data Sheet
1FP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standaids of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TYII3I - Upright 2.81K, 1/2"NPT
TY1231 - Pendent 2.8K, 1/2"NPT
TY2131 - Upright 4.2K, 1/2"NPT
1Y2231 - Pendent 4.21K, 1/2"NPT
TY3131 - Upright 5.6K, 1/2"NPT
TY3231 - Pendent 5.6K, 1/2"NPT
TY4131 - Upright 8.0K, 3/4"NPT
TY4231 - Pendent 8.0K, 314"NPT
TY4831- Upright 8.0K, 1/2"NPT
TY4931- Pendent 8.0K, 1/29'NPT
Page 1 of 10 AUGUST, 2007 TFPI7I
7/16" (11,1 mm) STYLE 10 or 20
NOMINAL RECESSED
NPT MAKE-IN ESCUTCHEON SSU *
DEFLECTOR
6*
5
4
2
3
1
7/16"
11,1 mm)
'1OMINAL
MAKE-IN I 2-3/16"
(55,6 mm)
1/2" NPT
UPRIGHT
L .
VVRENC
2-7/8" (73,0 mm) DIA.
RECESSED PENDENT
SSP DEFLECTOR *
PENDENT
ESCUTCHEON
PLATE SEATING
SURFACE H \T
2-3/16"
(55,6 mm)
f
1-1/2"
(38,1 mm)
CROSS SECTION
Page 2 of 10 TFPI7I
1/2"
NPT
ESCUTCHEON
PLATE SEATING
SURFACE
2-1/4"
(57,2)
1-9/16"
(39,7 mm)
SSP DEFLECTOR *
7/16"(11,1 mm) STYLE 10 or 20
NOMINAL RECESSED
MAKE-IN ESCUTCHEON SSU
DEFLECTOR
7/16" 1
(11,1 mm) I
1
NOMINAL I
MAKE-IN
I 2-3/16"
WRENCH I (55,6 mm)
FLATS I
1/2" NPT
11'
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. Screw
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TYII3I) AND PENDENT(TY1231) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K-FACTOR, 112 INCH NPT
Page 3 of 10 TFPI7I
6*
RECESSED PENDENT CROSS SECTION PENDENT UPRIGHT
ESCUTCHEON
PLATE SEATING
SURFACE
F_
2J16" \
(55,6 mm)
1-1/2"
(38,1 mm)
SSP DEFLECTOR *
7/16" (11.1 mm) STYLE 10 or 20
NOMINAL RECESSED 1/2" MAKE-IN ESCUTCHEON
5j*
NPT i , DEFLECTOR
2-7/8' (73,0 mm) DIA. -"'-I 1/2" NPT
7/16"
11,1 mm)
1OMINAL
MAKE-IN
2-3/16"
(55,6 mm)
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
2-1/4"
(57,2 mm)
CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector
2 - Button Assembly 5 - Compression
Screw
* Temperature rating is indicated on deflector or adjacent to
orifice seat on frame.
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2(12,7 mm)
PLATE SEATING NOMINAL
SURFACE MAKE-IN NPT
2-5/16"
(58,7 mm) T1
1-9/16" I (39,7 mm)
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 314 INCH NPT
STYLE 30 or 40
RECESSED
ESCUTCHEON SSU*
DEFLECTOR
WRENCH
FLATS
SSP DEFLECTOR * I 2-7/8" (73,0 mm) DIA. 3/4" NPT
PENDENT RECESSED PENDENT UPRIGHT
Page 4 of 10 TFPI7I
7/16"(111,1 mm)
NOMINAL SSU
MAKE-IN DEFLECTOR
2-1/4"
(57,2 mm) I (1
WRENCH
FLATS
1/2'
NPT
S.-.--
DEFLECTOR
PENDENT
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector
2 - Button Assembly 5 - Compression
Screw
CROSS
UPRIGHT SECTION
* Temperature rating is indicated on deflector or adjacent to
orifice seat on frame.
FIGURE 5
QUICK RESPONSE SERIES TV-FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS
8.0 K-FACTOR, 1/2 INCH NPT
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A and B for complete
approval information including corro-
sion resistant status.)
Maximum Working Pressure
Refer to Table C.
Discharge Coefficient
K = 2.8 GPM/psi1/2 (40,3 LPM/barl'2)
K = 4.2 GPM/psi"2 (60,5 LPM/barl'2)
K = 5.6 GPM/psi"2 (80,6 LPM/barl'2)
K = 8.0 GPM/psi1l2 (115,2 LPM/barl'2)
Temperature Ratings
Refer to Table A and B
Finishes
Sprinkler: Refer to Table A and B.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated.
Physical Characteristics
Frame .............Bronze
Button .........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflont
Bulb ...............Glass
Compression Screw .....Bronze
Deflector .......Copper/Bronze
Bushing (K=2.8) .......Bronze
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
TFPI7I
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED
I WHIT E
IPOLYESTER
2.8
1I2
PENDENT
(TY1231)
and
UPRIGHT
(TYII3I)
135FI57C Orange
1,2,3,5
155°FI68C Red
175FI79°C Yellow
200F/93C Green
286°F/14?C Blue
NPT -
RECESSED
(TY1231)*
Figure 6
135F/57°C Orange
1,2, 5
PENDENT
155°F/68C Red
175°FI79C Yellow
200°F/93C Green
RECESSED
PENDENT
(rY1231)—
Figure 7
135°F/57°C Orange
155°F/68°C Red
175F/79°C Yellow
200°F/93°C Green
4.2
1/2"
NPT
PENDENT
(TY2231)
and
UPRIGHT
(1Y2131)
135F/57°C Orange
1,2 -
155°F/68C Red
175F/79°C Yellow
200F/93C Green
286°F1141°C Blue
RECESSED
(TY2231)*
Figure 8
135F/57°C Orange
PENDENT
155FI68*C Red
175°F/79C Yellow
200FI93C Green
135°FI57C Orange
RECESSED
PENDENT
(1Y2231)**
Figure 9
155F/68°C Red
175°F179°C Yellow
200F/93°C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Re-
sponse Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354-01-E.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment
Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
Page 5 of 10
Page 6 of 10 TFPI7I
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL I CHROME WHITE LEAD
LIQUID BRASS PLATED POLYESTER I COATED
135"F/57°C Orange
PENDENT
(TY3231)
and 1,2,3,4,5.6,7 1,2,3,5
155"F/68°C Red
175"F/79°C Yellow
UPRIGHT 200°F193"C Green
5.6 (TY3131)
286"F/141"C Blue 1/2"
NPT 135°F/57"C Orange
RECESSED
PENDENT
(1Y3231)* 1,2,4,5 N/A
155"F/68"C Red
175°F/79"C Yellow
Figure 10 200"F/93"C Green
135°F/57°C Orange
RECESSED
PENDENT
(TY3231)** 1, 2. 3,4, 5 N/A
155°F/68"C Red
1750F/79"C Yellow
Figure 11 200°F/93°C Green
135°F/57°C Orange
PENDENT
(TY4231)
and
UPRIGHT 1, 2, 3,4, 5, 6, 7
1,2,5
155°F/68"C Red
175°F179°C Yellow
200°F/93"C Green
8.0 (TY4131)
3/zr
NPT
286"F/141"CPReq
d
135°F/57°C
RECESSED155°F/68°CPENDENT
(TY4231)* 1,2,4,5 N/A 175"F/79"C
Figure 12 200°F/93°C Yellow
135"F/57"C Orange
RECESSED
PENDENT
(TY4231)** 1,2, 3, 4, 5 N/A
155°F/68"C Red
175°F/79°C Yellow
Figure 13 200"F/93"C Green
135"F/57"C Orange
8.0
1/2"
PENDENT
(TY4931)
and 1, 2, 4, 5, 6
1, 2, 5
155"F/68"C Red
175"F/79°C Yellow
200°F/93°C Green NPT UPRIGHT
(TY4831) 286°F/141"C Blue
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
TFPI7I Page 7 of 10
SPRINKLER FINISH
K TYPE NATURAL CHROME WHITE LEAD
BRASS PLATED POLYESTER
I
COATED
PENDENT (TY3231)
and
2.8 UPRIGHT (TY3131) 175 PSI (12.1 BAR) N/A
1/2" RECESSED PENDENT NPT (TY323)
PENDENT (TY4231)
and
4.2 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A
3/4" RECESSED PENDENT NPT (TY4231)
PENDENT (TY3231)
and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
5.6 UPRIGHT (TY3131) OR
1/2' 175 PSI (12,1 BAR) RECESSED PENDENT NPT (TY3231) (SEE NOTE 1) N/A
PENDENT (TY4231)
and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
8.0 UPRIGHT (TY4131)
RECESSED PENDENT NPT (TY4231) N/A
8.0 PENDENT(TY4931)
1/2" and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4831)
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C-UL); and , the Approval by the City of New York.
TABLE C, MAXIMUM WORKING PRESSURE
Installation
The Series TY-FRB Sprinklers must
be installed in accordance with the fol-
lowing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 1350F/570C to 3/32
inch (2,4 mm) for the 286°F/1410C
temperature ratings.
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 14).
With reference to Figures 1, 2, 3, 4,
and 5, the W-Type 6 Sprinkler Wrench
is to be applied to the sprinkler wrench
flats.
The Series TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 15). With reference to Figure 1,
2, 3, and 4, the W-Type 7 Recessed
2-7/8" DIA. - I (73.0 mm) I 1/2"(12,7 mm)
2-1/4" DIA. 1/4" (6.4 mm) I
(57,2 mm)
;-1 MOUNTING
Lm )
I
t
1-5/16" (33,3 mm)
1-1/16'(27,0 mm)
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
f \ -
MOUNTING
SURFACE
CLOSURE SERIES
TY-FRB
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
2-718" DIA.
I
(73.0 mm) 1/2" (12,7 mm)
2-1/4" DIA. 1/4"(6,4 mm)
(57,2 mm) MOUNTING
01 Arc
,
1/8"I
(3,2 mm) I
t $
1-1/4" (31,8 mm)
1" (25,4 mm)
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
I \ -
MOUNTING
SURFACE
CLOSUR ' SERIES
FIGURE 9
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
Page 8 of 10 TFPI7I
- 2-7/8' DIA.
5/8±1/4"
(73,0 mm) I (19,1 mm)
(15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) I
FACE OF MOUNTING SPRINKLER PLATE FITTING
(3,2 mm)
SURFACE
2
MOUNTING/
1-5/16 ' CLOSURE SERIES
TY-FRB 13/16" (20,6 mm)
FIGURE 6
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
2-7/8" DIA. I
(73,0 mm) j 3/4"(19,1 mm)
2-1/4" DIA. 1/4" (6,4 mm) I
(57,2 mm) 17-1 MOUNTING I 01 ArC
1/8' I
(3,2 mm)
MOUNTING
SURFACE
CLOSURE SERIES 1-1/4"( 1 .8 mm)
3/4"(19,1 mm)
FIGURE 8
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
Sprinkler Wrench is to be applied to
the sprinkler wrench flats.
Step C. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 10, 20, 30, or
40 Closure over the Series +Y-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
Care and
Maintenance
The Series TY-FRB Sprinklers must
be maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
The owner must assure that the sprin-
klers are not used for hanging of any
objects; otherwise, non-operation in
the event of a fire or inadvertent opera-
tion may result.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been corn-
TFPI7I
2-7/8 DIA. -
5/8±1/4" (73,0 mm) I 3/4" (19,1 mm)
(15,9±6,4mm) - 2-1/4"DIA. 1/4"(6,4mm)
FACE OF I MOUNTING i SPRINKLER PLATE I FITTING
(3,2 mm)
MOUNTING,,,/'
I
SURFACE
CLOSURE SERIES 1-1/4" (31,8 mm)
TY-FRB 314"(19,11 mm)
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8"DIA. I (73,0 mm) 3/4(19,1 mm)
2-1/4" DIA. 1/4" (6,4 mm) I
(57,2 mm) MOUNTING
rLJilt I
3,2 mm)
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16" (33,3 mm)1
TY-FRB 13/16" (20,6 mm)
FIGURE 12
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
Page 9 of 10
- 2-7/8" DIA.
1/2±1/8" I (73,0 mm) 1/2"(12,7 mm) r (12.7±3,2 mm) 2-1/4" DIA. 1/4"(6,4 mm) I
FACE OF I MOUNTING I SPRINKLER lei
(57 2mm)
I PLATE I FITTING
1/8"
t \
MOUNTING
SURFACE
SERIES 1-1/4" (31,8 mm) CLOSURE TVFRB 1"(25,4 mm)
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
- 2-7/8" DIA.
1/2±1/8" (73,0 mm) I 1/2"(12,7 mm)
(12.7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm) I
FACE OF (57,2 mm) MOUNTING I
_-
SPRINKLER PLATE
FITTING
I
f \ -
,t
.
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16"(33,3 mm)
TV-FRB 1-1/16" (27,0 mm)
FIGURE 13
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4" NPT MODELS)
FIGURE 14
W- TYPE 6 SPRINKLER
WRENCH
facturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 15
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Inspection Service in accordance with
local requirements and/or national
codes.
Page 10 of 10 TFPI7I
P/N 57-XXX-X-XXX
I MODEL/SIN I I RATING _L_ I SPRINKLER
330 2.8K UPRIGHT (1/2"NPT) TY1131 11 135 135F/57°C
331 2.8K PENDENT (1/2"NPT) TY1231 1 NATURAL BRASS 155 155°F/68C
340 4.21K UPRIGHT (1/2"NPT) TY2131 4 WHITE POLYESTER 175 175F/79C
341 4.2K PENDENT (1/2"NPT) TY2231 3 WHITE (RAL9010)* 200F/93C
370 5.6K UPRIGHT (1/2"NPT) TY3131 9 CHROME PLATED F286 28&F/14VC
371 5.6K PENDENT (1/2"NPT) TY3231 7 LEAD COATED
390 8.0K UPRIGHT (3/4°NPT) TY4131
391 8.0K PENDENT (3/4"NPT) TY4231 * Eastern Hemisphere sales only.
360 8.0K UPRIGHT (1/2"NPT) TY4831*
361 8.0K PENDENT (1/2"NPT) TY4931
TABLED
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
OT any ana ait otner warranties. ex-
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Refer to the Price
List for complete listing of Part Num-
bers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
PIN (specify from Table 0).
Recessed Escutcheon:
Specify: Style (10, 20, 30, or 40) Re-
cessed Escutcheon with (specify*) fin-
ish, P/N (specify*).
* Refer to Technical Data Sheet TFP770.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446