HomeMy WebLinkAbout2470 FARADAY AVE; ; AS090046; Permit5/23/24,1:13 PM AS090046 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS090046
Job Address: 2470 FARADAY AV
Permit Type: SPRINK
Parcel No: 2090402800
Lot #: 0
Reference No.:
Status: ISSUED
Applied 5/14/2009
Approved: 5/14/2009
Issued: 5/14/2009
PC #: Inspector:
Project Title: BECKMAN COULTER T.I. FIRE SPRINKLER PLAN CHECK &
INSPECTIONS
Applicant:
WEST COAST FIRE PROTECTION
271 ROYMAR RD
SUITE F
OCEANSIDE, CA
(760)754-8472
Owner:
HAGAMAN FAMILY SURVIVORS 1990
TRUST 11-07-90
5320 SUNNY CREEK RD
CARLSBAD CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
130 0 130 0
about:blank 1/1
many angles, reducing
assembly effort. This sprin-
kler Is available in various
temperature ratings (see
chart on page 2) and fin-
ishes to meet many design
requirements.
The recessed pendent
should be utilized with a
Model V27 recessed
escutcheon which pro-
vides up to VV (19 mm) of
adjustments.
Sprinkler Operation
The operating mechanism
Is a frangible glass bulb
which contains a heat
responsive liquid. During a
fire, the ambient tempera-
ture rises causing the liquid
in the bulb to expand.
When the ambient temper-
ature reaches the rated
temperature of the sprin-
kler, the bulb shatters. As a
result, the waterway is
cleared of all sealing parts
and water is discharged
towards the deflector. The
deflector Is designed to dis-
tribute the water in a pat-
tern that is most effective
in controlling the fire.
Coverage
For coverage area and
sprinkler placement, refer
to NFPA 13 standards.
Zictsulicr V27, K5.6
Models V2703, V2704, V2707 and V2708
Standard Spray
Upright, Pendent and Recessed Pendent
Standard and Quick Response
PRODUCT DESCRIPTION
These Model V27 standard
spray sprinklers are
7 designed to produce a
4V2108
hemispherical spray pat-
tern for standard commer-
cial applications. They are
available with either stan-
Recessed dard or quick response
Pendent bulbs. The design incorpo- , () (I) <>
rates state-of-the-art, heat
responsive, frangible glass
SViaiii bulb design (standard or publicatIon 10.01 quick response) for prompt. V2707
V2708 precise operation.
The die cast frame Is more
streamlined and attractive
than traditional sand cast
Pendent frames. It Is cast with a
V270 hex-shaped wrench boss to
V2704 allow easy tightening from
Upright
TECHNICAL SPECIFICATIONS
Models: V2703, V2704, V2707.
V2708
Style: Pendent. Upright or
Recessed Pendent
Nominal Orifice Size:
½' (13 mm)
K-Factor: 5.6 Imp. (8.1 S.l.i
Nominal Thread Size:
½' NPT (15 mm)
Max. Working Pressure:
175 psi (1200 kPa)
Factory Hydrostatic Test:
100% @ 500 psi (3450 kPa)
Mm. Operating Pressure:
7psl (48 kPa)
Temperature Rating: See
chart on page 2.
MATERIAL
SPECIFICATIONS
Upright Deflector
Bronze per UNS C22000
Pendent Deflector.
Bronze per UNS C5 1000
Bulb: Glass with glycerin solu-
tion.
Bulb Nominal Diameter:
O Standard: 5,0 mm
O Quick Response: 3.0 mm
Load Screw: Bronze per UNS
C65100
Pip Cap: Bronze per UNS
C65100
Spring: Beryllium nickel
Seal: Teflon* tape
Frame: Die cast brass 65-30
Lodgement Spring:
Stainless steel per UNS S30200
ACCESSORIES
Installation Wrench:
O Open End: V27
0 Recessed: V38, V38-3
I] Socket: V27
Finishes:
Plain brass
O Chrome plated
White painted"
O Custom painted"
0 Lead
155, 200, 2865R Only -
0 Wax**
O Wax over lead**
For cabinets and other accesso-
ries refer to separate sheet.
NOTE: Weather resistant recessed
escutcheons available upon request.
" For K-Factor when pressure is mea-
sured in Bar, multiply S.I. units by
10.0. Teflon is a registered vademark of
Dupont Co.
UL Listed for corrosion resistance in
all configurations.
VICTAULIC5 IS AN ISO 9001 CERTIFIED COMPANY
Victaulic Company of America Victaulic Company of Canada Victaulic Europe Victaulic America Latina Victaulic Asia Pacific
Phone: 1-800-PICK-VlC (1-800-742-5842) Phone: 905-884-7444 Phone: 32-9-381-1500 Phone: 610-559-3300 Phone 65-6235-3035
Fax: 610-250-8817 Fax: 905-884-9774 Fax: 32-9-380-4438 Fax: 610-559-3608 Fax: 65-6235-0535
e-mail:pickvic@victaulic.com e-mail: viccanada@victaulic.com e-mail: viceuro@viclaulic.be e-mail: vical@victaulic.com e-mail: vicap@victaulic.com
2544 Rev.D 8103 5 Registered Trademark of Victaulic 0 Cop)llgrlt 20)3 Vetaulic Printed In U.S.A.
APPROVALSILISTINGS
Nominal Approved Temperature Ratings °FI°C (3
Orifice Size K-Factor
Inches Imperial Deflector
Model millimeters S.LA Response Type UL FM ULC NYCIMEAt CSFM §
½ 5.6 135-360 135-360 135-360 135-360 135-360 V2703 13 8.1 Standard Upright 57-182 57-182 57-182 57-182 51-182
½ 5.6 135-360 135-360 135-360 135-360 135-360 V2707 13 8,1 Standard Pendent 57-182 57-182 1 57-182 57-182 57-182
½ 5.6 Recessed Pendent 135-360 135-200 135-360 135 -360 135-360 V2707 13 8.1 Standard up to t4 Adjustment 57-182 57 -93 57 -182 57-182 57 -182
½ 5.6 135-286 135-286 135-286 135-286 135-286 V2704 13 8.1 Quick Upright 57-141 57-141 57-141 57-141 57-141
½ 5.6 135-286 135-286 135-286 135-286 135-286 V2708 13 811 Quick Pendent 57-141 57-141 57-141 1 57-141 1 57-141
½ 5.6 Recessed Pendent 135-200 135-200 135-200 135 -200 135-200 V2708 13 8.1 Quick UptowAdjustment 57-93 57-93 57-93 57-93 57-93
½ 5.6 Recessed Pendent 135-200 No 135-200 135-200 135-200
1 V2708 13 8.1 Quick UptoteAdjustmcrl 5793 5793
t Listings and approval as of printing. (3 All are approved open, except for areas designated 'No.
For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.
t MEA #62-99-E. § CSFM #7690-0531:112
RATINGS
All glass bulbs are rated for
temperatures from -67°F
(-55°C) up to those shown
In adjacent table.
Temperature - °FI°C
Nominal Maximum Sprinkler Victaulic Glass
Temperature Part Temperature Ambient Temp. Bulb
Classification Identification Rating Mowed Color
Ordinary A 135
57
100 38 Orange
Ordinary C 155 68
100
38 Red
Intermediate E 175 150 65 Yellow
Intermediate F 200 93
150
65 Green
High -
286
141
225 -
107 Blue
Extra High t K 360
182
300 149 Purple
- t M Open = NoBuib
t Standard response only.
All are approved open, except for areas designated 'No.
- 150/65 if wax coated.
ORDERING INFORMATION
Please specify the following
when ordering: 0 Sprinkler Model Number 0 K-Factor U Sprinkler Finish
U Style U Thread Size U Escutcheon Finish
o Temperature Rating U Quantity 0 Wrench Model Number
Always read and understand installation, care, and maintenance instructions, supplied with each box of sprinklers, before proceeding with installation
of any sprinklers.
Always wear safety glasses and foot protection.
Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products.
Installation rules, especially those governing obstruction, must be strictly followed.
W • Painting, plating, or any re-coating of sprinklers (other than that supplied by Victaulic) is not allowed.
Fatima to follow these instructions could result in serious personal injury arrdlor property damage.
The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the
current National Eke Protection Association pamphlet that describes care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may have additional
maintenance, testing, and inspection requirements that must be followed.
If you need additional copies of this publication, or if you have any questions about the safe installation of this product, contact Victailic World Headquarters, P.O. Box 31, Easton,
Pennsylvania 18044-0031, 610-559-3300.
40.10-2
DIMENSIONS
1W
2W (41 mm)
(60 mm)
17A€
(37 mm)
Standard Pendant - V2707, V2708 Standard Upright -V2703, V2704
Recesses - VZTUf, VL(U*
(Drawing not to scale)
2W (60 mm)
Max. 11010
2 (51 mm) r Mm. Hde -1
1W I (24 mm) 3'a (14f0m) Typicalceulng Tie
(33mm)
I F
FIfl hOdS CeJ24rnm)
(43mm)I MAXIMUM RECESS
(75 mm)
MAXIMUM EXTENSION
9140 Adjustment
Recessed - V2707, V2708
(Drawing not to scale)
AVAILABLE WRENCHES
V27
Socket
V38 orV38-3
Recessed
V27
Open End
V2701, V2708 Pendent / / /
V2707. V2708 Recessed Pendent /
V2703, V2704 Upright
40.10-3
DISTRIBUTION PATTERNS
MODELS V2707, V2708
K5.6 STANDARD PENDENT AND RECESSED PENDENT
DISTRIBUTION PATTERNS - TRAJECTORY
10' - I I I I I I I I I 3,0 m
8-
2,4 m
7psi
48 kPa
6'
1,8 m
15 psi
103 kPa
4'
1,2 m
30 psi -------
207 We
2'
0,6 m
0
0,6m 1.2m 1.8m 2,4m 3,0m 3,7m 4.3m
MODELS V2103, V2704
K5.6 STANDARD UPRIGHT DISTRIBUTION PATTERNS - TRAJECTORY i••iiva•••iiu
uai•ivauiuu•uu
uiiiuu•••uuiuiu
Data shown Is approximate and can vary due to differences in installation.
These graphs illustrate approximate trajectories, floor-wetting, and wan-wetting patterns for these specific Victaulic FireLock Automatic Sprinklers. They are
provided as information for guidance In avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for Installation. Refer to
the appropriate NFPA National Fire Code and the authority having jurisdiction for specific Information regarding obstructions, spacing limitations and area of
coverage requirements. Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings, Approvals and War-
ranties.
All patterns are symmetrical to the centerline of the waterway.
WARRANTY Refer to the Warranty section
of the current Price List or
contact Victaulic for details.
This product shall be manufactised by Victaulic company. Al products to be installed in accordance with cisrent victauliC installalionlassembly instructions.
Victaulic reserves the right to change product specifications, designs and standard equipment without mice and without incutring obligations.
40.10-4
10'
3,0 m
24
7psi
48 kPa
15 psi
103 kPa
30 psi
207 kPa
3'
0,6m 1.2m 1,8m 2.4m 3.0m 3,7m 4,3m 4,9m