tqco /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
Series DS-1 - 56 K-factor
Dry Type Sprinklers
Standard Response, Standard Coverage
General
Description
The Tycoa Series DS-1, 5.6 K-factor,
Standard Response, Standard Cover-
age, Dry Type Sprinklers are decorative
5 mm glass bulb automatic sprinklers
designed for the following typical uses:
where pendent sprinklers are re-
quired on dry pipe systems that are
exposed to freezing temperatures
(e.g. sprinkler drops from unheated
portions of buildings)
where sprinklers and/or a portion
of the connecting piping may be
exposed to freezing temperatures
(e.g. sprinkler drops from wet sys-
tems into freezers, sprinkler sprigs
from wet systems into unheated
attics, or horizontal piping exten-
sions through a wall to protect an
unheated area of a building)
where sprinklers are used on sys-
tems that are seasonably drained
to avoid freezing (e.g. vacation re-
sort areas)
WARNINGS
The Series DS-1 Di',' Type Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of spnnkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the perfonnance of these
devices.
The owner is responsible for maintain-
ing their fire protection system and do-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
The Series DS-1 Dry Type Sprinklers
must only be installed in fittings that
meet the requirements of the Design
Criteria section.
Model/Sprinkler
Identification
Numbers
TY3255 - (Pendent)
TY3155 - (Upright)
TY3355 - (Horizontal Sidewall)
Technical
Data
Approvals
UL and C-UL Listed.
FM and NYC Approved.
(Refer to Table A)
Maximum Working Pressure
175 psi (12,1 bar)
Inlet Thread Connection
1 inch NPT (Standard Order)
ISO 7-Ri
Discharge Coefficient
K = 5.6 GPM/psi1'2
(80,6 LPM/bar19
Temperature Ratings
Refer to Table A
Finishes
Sprinkler: Natural Brass, Chrome
Plated, White Polyester
Escutcheon: White Coated or Chrome
Plated, Brass Plated
Physical Characteristics
Inlet.....................Copper
Plug ....................Copper
Yoke ..............Stainless Steel Casing . . . . Galvanized Carbon Steel
Insert ...................Bronze
Bulb Seat ..........Stainless Steel Bulb ......................Glass
Compression Screw ........Bronze
Deflector.................Bronze
Frame...................Bronze Guide Tube.........Stainless Steel
Water Tube.........Stainless Steel
Spring.............Stainless Steel Sealing Assembly ................
Beryllium Nickel w/Teflon*
Escutcheon ..........Carbon Steel
*Registered Trademark of DuPont
Patents
U.S.A. Patent No. 5,188,185
Page 1 of 8 JANUARY, 2008 TFP500
Page 2 of 8 TFP500
SPRINKLER FINISH
TY3255 Pendent TY3255 Pendent TY3355 Hor. SIdewall wl Standard wi Std. Escutcheon with top of Recessed Escutcheon (Ref. Fig. 5) Deflector-to-Colling
(Ref. Fig. 3) wl Deep Escutcheon distance of wl Wide Flange (Ref. Fig. 6) 4 to 12 inches
Recessed Escutcheon W/o Escutcheon (100 to 300 mm)
(Ref. Fig. 4) (Ref. Fig. 7) wl Std. Escutcheon
(Ref. Fig. 9)
wl Deep Escutcheon TY3155 Upright (Ref. Fig. 10) w/o Escutcheon w/o Escutcheon (Ref. Fig- 8) (Ref. Fig. 11)
Temperature Bulb Color Natural Chrome White Natural Chrome White Natural Chrome White Rating Code Brass Plated Polyester Brass Plated Polyester Brass Plated Polyester
135°F/57°C Orange 1.2.3.4 1,2.4 1,2,3.4 1.2,4 1.; 2.; 3", 4 1*. 2*, 4
1551F/680C Red 1.2.3.4 1.2,4 1.2,3.4 1.2.4 i.; 2.; 3". 4 1*, 2*. 4
175"F/79"C Yellow 1.2,3.4 1.2,4 1.2.3.4 1.2.4 i.; 2.; 3—,4 1*, 2*, 4
200"F/930C Green 1,2.3,4 1,2.4 1.2,3.4 1.2.4 1.; 2.; 3"'. 4 1*. 2*. 4
286°F/1410C Blue N/A 1.2.3.4 1,2.4 1.; 2',3*'. 4 1", 2*. 4
360"F/182"C Mauve N/A 1,2,3.4 1.2.4 i.; 2.; 4 1", 2*. 4
Notes:
Listed by Underwriters Laboratories, Inc (Maximum order length of 48 inches).
Listed by Underwriters Laboratories for use in Canada (Maximum order length of 48 inches).
Approved by Factory Mutual Research Corporation (Maximum order length of 48 inches)
Approved by the City of New York under MEA 352-01-E.
* Light and Ordinary Hazard Occupancies Only
Light Hazard Occupancies Only.
N/A- Not Available.
TABLE A
SERIES DS-I, STANDARD RESPONSE - STANDARD COVERAGE, DRY TYPE SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
PLUG WITH INLET
GASKETED SPRING
PLATE SEAL
- - YOKE
SPRING
_- CASING
U U
WATER
TUBE
- INSERT
GUIDE
TUBE BULB
SEAT 7
FRAME
5 m
BULB
VENT HOLE
- COMPRESSION
DEFLECTOR SCREW
FIGURE 1
SERIES DS-I, STANDARD RESPONSE
DRY TYPE SPRINKLERS ASSEMBLY
WRENCH
RECESS
WRENCH
FLAT PUSH WRENCH INTO
ENSURE ENGAGEMENT WITH
SPRINKLER WRENCH FLATS
FIGURE 2
W-TYPE 7 SPRINKLER WRENCH
TFP500 Page 3 of 8
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION) r --,
-- FACEOF
SPRINKLER
FITTING ATI1NG
-J
ORDER LENGTHS:
3-1/2' to 48'
8,9 to 1219,2 mm)
IN 1/4"(6.4 mm) 2-1/4" DIA.
INCREMENTS (57,2 mm)
FACE OF
CEILING rJA
(34,9±; mm) 1I0m!!J
FIGURE 3
TY3255 PENDENT
wi STANDARD RECESSED
ESCUTCHEON
SPRINKLER FITTING
(REFER TO DESIGN
CRIFERIASEC11ON) r
I---' --------
FACE OF
SPRINKLER
FITTING '---r
ij
ORDER LENGTHS:
3-1/2" to 48"
(88.9 to 1219.2 mm) 11
IN 1/4(8.4mm) 3" DIA.
INCREMENTS (76,2 mm)
FACE OF
CEILING
1-318 *1/8" 3-5/8" DIA.
(34,9 ± 3,2 mm) (92,1 mm)
FIGURE 4
TY3255 PENDENT
wi WIDE FLANGE RECESSED
ESCUTCHEON
SPRINKLER FITTING
(PH TO DESIGN
CRITERIA SECTION) r ------------
FACE OF
, H
SPRINKLER i_:
FITTING
J
ORDER LENGTHS: I 2-1/2" to 48" 1-3/4' DIA.
(63,5'to 1219,2 mm) (44.5 mm)
IN 1/4" (6.4 mm)
INCREMENTS
FACE OF
CEILING
I - tc
(76,2 mm)
FIGURE 5
TY3255 PENDENT wi STANDARD ESCUTCHEON
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION) r--
I-------I I FACE OF
SPRINKLER L.44 I I-i) FITTING
ORDER LENGTHS: 3-1/2" DIA.
1/2" to 46" (88.9 mm)
(12jto1168,4mm) 221/2- Dk
INCREMENTS l I
FACE OF
CEILING
4-1/4'±1/8
(108,0:t 3,2 mm)
FIGURE 6
TY3255 PENDENT
wi DEEP ESCUTCHEON
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FACE OF
SPRINKLER L] FITTING
I'
ORDER LENGTHS:
5 to 48'
(127.0 to 1219,2 mm)
IN 1/4" (6,4 mm)
INCREMENTS
MINIMUM
1-3/4 (44,5 mm)
DEFLECTOR
TO CEILING
FIGURE 7
TY3255 PENDENT
wlo ESCUTCHEON
TOP OF
DEFLECTOR
ORDER LENGTHS:
5 t048"
(127,0 to 1219,2 mm)
IN 1/4" (6,4 mm)
INCREMENTS
FACE OF
SPRINKLER
FITTING
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FIGURE 8
TY3155 UPRIGHT
w/o ESCUTCHEON
ORDER LENGTHS: FACE OF
1/2' to 45-314'(12,7 to 1162,1 mm) MOUNTING
IN 1/4'(6.4 mm) INCREMENTS SURFACE 4-13/16'* 1/8' '1 (122,2±3,2mm)
21/2'DIA. I FACE OF r:Z(63.5 mm
SPRINKLER FITTING
3-1/2" DIAL
1 (88,9 mm)
SPRINKLER FITTING
(REFER TO DESIGN CENTERLINE 5/16'
CRITERIA SECTION) OF WATERWAY (7.9 mm)
FIGURE 10
TY3355 HORIZONTAL SIDEWALL wi DEEP ESCUTCHEON
Page 4 of 8
ORDER LENGTHS:
2-1/2' to 48' (63,5 to 1219,2 mm)
IN 1/4' (6,4 mm) INCREMENTS 4±1/8 1 (101,6*3,2mm)
FACE OF FACE OF I 1-3/4' DIA.
-T- - SPRINKLER MOUNTING -i (44,5 mm)
J_L FITTING SURFACE
LIL__1J
/
T-J (76,2 mm)
SPRINKLER FITTING
C) (REFER TO DESIGN CENTERLINE 5116'
CRITERIA SECTION) OF WATERWAY (7,9 mm)
FIGURE 9
TY3355 HORIZONTAL SIDEWALL wi STANDARD ESCUTCHEON
TFPSOO
Operation
When the Series DS-1 is in service,
water is prevented from entering the
assembly by the Plug & Belleville Seal-
ing Assembly (Ref; Figure 1) in the Inlet
of the Sprinkler. The glass Bulb con-
tains a fluid that expands when ex-
posed to heat. When the rated tem-
perature is reached, the fluid expands
sufficiently to shatter the glass Bulb,
and the Bulb Seat is. released. The
compressed Spring is then able to ex-
pand and push the Water Tube as well
as the Guide Tube outward. This ac-
tion simultaneously pulls inward on the
Yoke, withdrawing the Plug & Belleville
Seal from the Inlet allowing the sprin-
kler to activate and flow water.
Design
Criteria
The Tyco9 Series DS-1 Sprinklers are
intended for use in fire sprinkler sys-
tems designed in accordance with the
standard installation rules recognized
by the applicable Listing or Approval
agency (e.g., UL Usting is based on
NFPA 13 requirements).
The 1 inch NPT Series DS-1 Sprin-
klers are to be installed in the 1 inch
NPT outlet or run of malleable or duc-
tile iron threaded tee fittings that meet
the dimensional requirements of ANSI
B16.3 (Class 150) or cast iron threaded
tee fittings that meet the dimension-
al requirements of ANSI B16.4 (Class
125). The Series DS-1 Sprinklers may
also be installed in the 1 inch NPT out-
let of a Grinnell Figure 730 Mechani-
cal Tee; however, the use of the Figure
730 for this arrangement is limited to
wet pipe systems.
Typically, the end sprinkler fitting on
a branch line is plugged as. shown in
Figures 3 through 11. The DS-1 Sprin-
klers cannot be installed into an elbow
fitting.
For wet pipe systems, the sprinkler
drop may be installed as shown in Fig-
ure 12. The configuration in Figure 12
may only be used where the sprinkler
fitting and water filled pipe above the
sprinkler fitting is not subject to freez-
ing and, where the length of the DS4
Sprinkler has the minimum exposure
length per Figure-14.
For wet pipe systems, the OS-i Sprin-
klers may also be installed, in the fol-
lowing Tycoe CPVC fittings: (P/N
80145)1" x 1" NPT FemaleAdapter or
(P/N 80249)1" x 1" x 1" NPT Sprinkler
Head Adapter Tee
For dry pipe systems, only use the
side outlet of maximum 2-1/2 inch size
ORDER LENGTHS:
I. 5-1/2' to 48"(139,7 to 1219,2 mm)
IN 1/4' (6,4 mm) INCREMENTS
FACE OF
I— SPRINKLER FITTING
MINIMUM
2-1/4"(57.2 itvn)
DEFLECTOR TO
MOUNTING
SURFACE
3.51 5/16'
SPRINKLER FITTING (7,9mm)
(REFER TO DESIGN CENTERLINE
CRITERIA SECTION) OF WATERWAY
FIGURE 11
TY3355 HORIZONTAL SIDEWALL w/o ESCUTCHEON
TFP500 Page 5 of 8
reducing tee's when locating the DS-
1 Sprinklers directly below the branch
line. Otherwise, use the configuration
shown in Figure 13 to assure complete
drainage of water from above the DS4
Sprinklers and the branch line.
NOTE
Do not install the Series DS-1 into any
other type fitting without first consult-
ing the Technical Services Depart-
ment. Failure to use the appropriate
fitting may result in: failure of the sprin-
kler to properly operate due to forma-
don of ice over the inlet Plug or bind-
ing of the inlet Plug; or, insufficient
engagement of the inlet pipe threads
with consequent leakage.
Branch, cross, and feedmain piping
connected to Dry Sprinklers and sub-
ject to freezing temperatures must be
pitched for drainage in accordance
with the minimum requirements of the
National Fire Protection Association
for dry pipe sprinkler systems.
When Dry Sprinklers are to be used
in wet pipe sprinkler systems protect-
ing areas subject to freezing tempera-
tures (e.g., sprinkler drops into freez-
ers), consideration must be given to
the appropriate length of the sprinkler
that will prevent freezing of the water in
the connecting pipes due to conduc-
tion. When the temperature surround-
ing the wet pipe sprinkler system is
maintained at a minimum temperature
of 40017/4°C, the following are the mini-
mum recommended lengths between
the face of the sprinkler fitting and the
outside surface of the protected area
(i.e., length exposed to minimum am-
bient of 40017/40C - Ref. Figure 14):
12 inches (300 mm) when the tem-
perature within the protected area
is -20°FI-290C
18 inches (450 mm) when the tem-
perature within the protected area
is -40°F/-400C
24 inches (600 mm) when the tem-
perature within the protected area
is -60°F/-510C
For protected area temperatures be-
tween those given above, the minimum
recommended length from the face of
the fitting to the outside of the protect-
ed area may be determined by interpo-
lating between the indicated values.
The 2007 edition of NFPA 13, Sec-
tion 8.4.10.2 requires that dry sprin-
klers connected to wet pipe sprinkler
systems protecting insulated freezer
structures have the clearance space
around the sprinkler barrel be sealed.
The use of the Model DSB-2 Dry
Sprinkler Boot described in Technical
Data Sheet TFP59I, and illustrated in
Figures 15 and 16, will meet the intent
of NFPA 13.
TO WET SIDE
SYSTEM OUTLET
PLUGGED
HEATED
AREA
- 1INCH
DSB-2 NPTTEE
INTENDED (SEE DESIGN
FOR FREEZER CRITERIA
STRUCTURES., SECTION)
FIGURE 12, SPRINKLER FITTING
IN HEATED AREA
RUN
OUTLET'
LUGGED
'F(SEEDESIGN
INCH
TTEE TO DRY SYSTEM CRITERIA
SECTION)
I I AREA I SUBJECT I DSB-2
I TO INTENDED
FOR FREEZER
FREEZING .S STRUCTURES
FIGURE 13, SPRINKLER FITTING
IN UNHEATED AREA
FACE OF
SPRINKLER -
FITTING
HEATED EXPOSURE
AREA LENGTH
(SEE DESIGN
DSB-2 CRITERIA
INTENDED SECTION)
FOR FREEZER
STRUCTURES ,
FIGURE 14, EXPOSURE LENGTH
STRAP TIES
(ENDS ON
OPPOSING
SIDES OF
BOOT)
DSB-2 BOOT
ADHESIVE
1-3/4' DIA.
(44.5 mm)
- CLEARANCE
HOLE
INSULATED
FREEZER
STRUCTURE
DS-1
SHOWN WITH
STANDARD
ESCUTCHEON
FIGURE 15
MODEL DSB-2 SPRINKLER
BOOT WITH PENDENT SERIES
DS-1 DRY SPRINKLER
1-314 01k
(44,5 mm)
CLEARANCE INSULATED HOLE FREEZER
ADHESIVE STRUCTURE
DSB-2
BOOT
STRAP TIES
(ENDS ON OS_i
OPPOSING SHOWN WITH
SIDES OF STANDARD
BOOT) ESCUTCHEON
FIGURE 16
MODEL DSB-2 SPRINKLER
BOOT WITH SIDEWALL SERIES
DS-1 DRY SPRINKLER
Page 6 of 8 TFP500
Installation
The Series DS4 Dry Type Sprinklers
must be installed in accordance with
the following instructions:
NOTES
The Series DS-1 must only be installed
in fittings that meet the requirements
of the Design Criteria section.
Refer to the Design Criteria section for
other important requirements regard-
ing piping design and sealing of the
clearance space around the Sprinkler
Casing.
Do not install any bulb type sprinkler if
the bulb is cracked or there is loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/57°C rating to
1/8 inch (3,2 mm) for the 360°F/1820C
rating.
A 1 inch NPT spnnkler joint should be
obtained with a minimum to maximum
torque of 20 to 30 ft. tbs. (26,8 to 40,2
Nm). Higher levels of torque may dis-
tort the sprinkler inlet with consequent
leakage or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in an Escutcheon
Plate by under- or over-tightening the
Sprinkler. Readjust the position of the
sprinkler fitting to suit
Step 1. Pendent sprinklers must be
installed only in the pendent position,
and upright sprinklers must be in-
stalled only in the upright position. The
deflector of a pendent or upright sprin-
kler is to be parallel to the ceiling.
Horizontal sidewall sprinklers are to be
installed in the horizontal position with
their centerline of waterway perpen-
dicular to the back wall and parallel to
the ceiling. The word "TOP" on the De-
flector is to face towards the ceiling.
Step 2. With pipe thread sealant ap-
plied to the inlet threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Wrench tighten the sprinkler by
wrenching on the Casing with a pipe
wrench whenever the casing is readily
accessible. Otherwise, use a W-Type 7
Sprinkler Wrench (Ref. Figure 2). The
wrench recess of the W-Type 7 is to be
applied to the sprinkler wrench flats
(Ref. Figure 2).
Step 4. After the ceiling/wall has been
installed/finished, slide on the outer-
piece of the Escutcheon until it comes
in contact with the ceiling/wall. Do not
lift the ceiling panel out of its normal
position.
In the case of the outer piece of the
Deep Escutcheon, hold the outer
piece in contact with the mounting
surface (ceiling), and then rotate the
inner piece approximately 1/4 turn with
respect to the outer piece, to hold the
Deep Escutcheon firmly together.
Care and
Maintenance
The Tycoe Series OS-i Dry Type Sprin-
klers must be maintained and ser-
viced in accordance with the following
instructions:
NOTES
Absence of the outer piece of an es-
cutcheon, which is used to cover a
clearance hole, may delay the time to
sprinkler operation in a fire situation.
Before closing a fire protection sys-
tem main control valve for mainte-
nance work on the fire protection sys-
tem that it controls, permission to shut
down the affected fire protection sys-
tems must be obtained from the prop-
er authorities and all personnel who
may be affected by this action must be
notified.
A Vent Hole is provided in the Bulb
Seat (Ref. Figure 1) to indicate if the
Dry Sprinkler is remaining dry. Evi-
dence of leakage from the Vent Hole is
an indication that there may be weep-
age past the Inlet seal and that the
sprinkler needs to be removed for de-
termining the cause of leakage (e.g. an
improper installation or an ice plug).
The fire protection system control
valve must be closed and the system
drained before removing the sprinkler.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be com-
pletely cleaned by wiping the sprin-
kler with a cloth or by brushing it with a
soft bristle brush.
Care must be exercised to avoid dam-
age - before, during, and after instal-
lation. Sprinklers damaged by drop-
ping, striking, wrench twist/slippage,
or the like, must be replaced. Also, re-
place any sprinkler that has a cracked
bulb or that has lost liquid from its bulb
(Ref. Installation Section).
The owner is responsible for the in-
spection, testing, and maintenance of
theirfire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associ-
ation (e.g., NFPA 25), in addition to the
standards of any other authorities hav-
ing jurisdiction. The installing contrac-
tor or sprinkler manufacturer should be
contacted relative to any questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualified Inspection Service in accor-
dance with local requirements and/or
national codes.
TFP500 Page 7 of 8
Limited
Warranty
Products manufactured by Tyco Fire
& Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years from
date of shipment by TFBP. No warran-
ty Is given for products or components
manufactured by companies not af-
filiated by ownership with TFBP or for
products and components which have
been subject to misuse, improper in-
stallation, corrosion, or which have not
been installed, maintained, modified or
repaired in accordance with applicable
Standards of the National Fire Protec-
tion Association, and/or the standards
of any other Authorities Having Juris-
diction. Materials found by TFBP to be
defective shall be either repaired or re-
placed, at TFBP's sole option. TFBP
neither assumes, nor authorizes any
person to assume for it, any other ob-
ligation in connection with the sale of
products or parts of products. TFBP
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
In no event shall TFBP be liable, in
contract, tort, Strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
The foreaolna warranty is made in lieu
press or implied. Including warranties
of merchantability and fitness for a
particular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
Dry Sprinklers:
Contact your local distributor for
availability, and please specify the
following:
1. Sprinkler.
Model/SIN.
Standard Response, Standard
Coverage, Dry Type Sprinkler
Deflector Style.
5.6 K-factor.
Order Length.
Dry Type Sprinklers are furnished
based upon Order Length as
measured per Figures 3 through
11, as applicable. After the mea-
surement is taken, round it to the
nearest 1/4 inch increment.
Inlet Connection (1 Inch NPT or ISO
7-Ri)
Temperature Rating.
Sprinkler Finish.
Escutcheon Style and Finish, as
applicable.
Part Number from Table B. (Part
numbers are for 1 inch NPT stan-
dard order sprinklers. Orders for all
other sprinkler assemblies must
be accompanied by a complete
description.)
2. W-Type 7 Sprinkler Wrench.
Refer to the Price List for complete
listing of Part Numbers.
Model DSB-2:
Specify: Model DSB-2 Dry Sprinkler Boot*, P/N 63-000-0-002.
* Includes one Boot, two Strap lies,
and 1/3 oz. of Adhesive (quantity of
adhesive is sufficient for installing one
Boot)
Page 8 of 8 TFP500
P/N 60- XXX- X- XXX
I I
SPRINKLER ESCUTCHEON I MODEL/SIN FINISH FINISH (2)
I I ORDER
LENGTH (1)
(EXAMPLES)
055 5.50"
082 8.25"
180 18.00"
187 18.75"
372 37.25"
480 48.00"
96 Pendent W/ Standard TY3255
Escutcheon (1" NPT) (Fig. 5)
93 Pendent w/ Deep TY3255
-
Escutcheon (1" NPT) (Fig. 6)
97 Pendent w/ Std. Recessed TV3255
Escutcheon (1" NPT) (Fig. 3)
92 Pendent w/o Escutcheon TY3255
-
(1"NPl) (Fig- 7)
94 Sidewall w/ Standard TY3355
Escutcheon (1" NPT) (Fig. 9)
53 Sidewall w/ Deep TY3355
-
Escutcheon (1" NPT) (Fig. 10)
54 Sidewall w/o TY3355
-
Escutcheon (1" NPT) (Fig. 11)
I 98
Upright w/o Escutcheon I 1V3155
(1"NPT) (Fig. 8)
1 NATURAL BRASS WHITE
4 WHITE POLYESTER WHITE
9 CHROME PLATED CHROME
0 CHROME PLATED WHITE
3 WHITE (RAL9O1O)4 WHITE (RAL9O1O)*
2 NATURAL BRASS BRASS PLATED
TEMPERATURE
RATING (3)
135F/57C
_L 155F/68C
175F/79C
200F/93C
_:.
286F/141C
5 360F/182C
NOTES
Dry Type Sprinklers are furnished based upon "Order Length"
as measured per Figures 3 through 11, as applicable, and for
each individual sprinkler where it is to be installed. After the
measurement is taken, round it to the nearest 1/4 inch increment.
Escutcheon Finish applies to sprinklers provided with
escutcheons.
286F/141C and 360/182C temperature ratings apply to
non-recessed sprinkler assemblies.
* Eastern Hemisphere sales only.
TABLE B
PART NUMBER SELECTION
SERIES DS-I, STANDARD RESPONSE, STANDARD COVERAGE, DRY TYPE SPRINKLERS
(Use Prefix "I" for ISO 7-RI Connection, e.g., 1-60-961-1-180)
0 2007-2008 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale Pennsylvania 19446
tqco /Fire & Building
I Products
Technical Services: Tel: (800) 361-9312/ Fax: (800) 791-5500
o9Oo
I L L U 114,
TM
N
We Cover All The Action
iU Li U Ji/L
ILLUSION1T' - 11,2 K-factor
Extra Large Orifice Concealed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The Tyco® ILLUSION", 11.2 Mac-
tor, Standard Coverage, Extra Large
Orifice Concealed Pendent Sprinklers
are decorative, fast response solder
type sprinklers featuring a flat cover
plate designed to conceal the sprin-
kler. When limited water pressure is
available and a higher applied water
density is necessary, the ILLUSION is
the best choice for architecturally sen-
sitive areas such as casinos, hotel lob-
bies, office buildings, churches, and
restaurants.
provide a measure of flexibility with
regard to which the length of fixed pipe
drops to the sprinklers must be cut.
The ILLUSION Sprinklers are shipped
with a Disposable Protective Cap. The
Protective Cap is temporarily removed
for installation, and it can be replaced
to help protect the sprinkler while the
ceiling is being installed or finished.
The tip of the Protective Cap can also
be used to mark the center of the ceil-
ing hole into plasterboard, ceiling tiles,
etc. by gently pushing the ceiling prod-
uct against the Protective Cap. When
the ceiling installation is complete, the
Protective Cap is removed and the
Cover Plate Assembly installed.
Each unit includes a Cover Plate As-
sembly that conceals the sprinkler op-
erating components above the ceiling.
The separable two-piece design of the
Cover Plate and Support Cup Assem-
blies allows installation of the sprin-
klers and pressure testing of the fire
protection system prior to installation
of a suspended ceiling or application
of the finish coating to a fixed ceiling.
They also permit removal of sus-
pended ceiling panels for access to
building service equipment without
having to first shut down the fire pro-
tection system and remove sprinklers.
Also, the separable two-piece design
of the Sprinkler provides for 3/4 inch
(19,1 mm) of vertical adjustment to
As an option, the ILLUSION Pendent
Sprinklers may be fitted with a silicone
Air and Dust Seal (Ref. Fig. 4). The Air
and Dust Seal is intended for sensitive
areas where it is desirable to stop air
and dust travel through the cover plate
from the area above the ceiling.
NOTICE
The ILLUSION Concealed Pendent
Sprinklers described herein must be
installed and maintained in compli-
ance with this document and with the
applicable standards of the National
Fire Protection Association, in addition
to the standards of any other authori-
ties ha ving junsdiction. Failure to do so
may impair the performance of these
devices.
Sprinkler
Identification
Number
TY5521
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the INSTALLER
WARNING that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
The owner is responsible for maintain-
ing their fire protection system and do-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Page 1 of 6 MAY, 2008 TFPIS4
Page 2 of S TFPIB4
Technical
Data
Approvals
UL and C-UL Listed.
(The listings apply only to the service
conditions indicated in the Design Cri-
teria section.)
Approvals for Air & Dust Seal
UL and C-UL Listed for use with the
ILLUSION (TY5521); however, use of
the Air & Dust Seal changes the sprin-
kler response rating from quick to
standard.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 11.2 GPM/psi112
(161,3 LPM/bar112)
Temperature Ratings
160°F/71*C Sprinkler!
139F!59C Plate 2120F!100eC Sprinkler!
165F/74C Plate
Adjustment
3/4 inch (19,1 mm)
Finishes
Cover Plate: Refer to Ordering Proce-
dure section.
BODY
(314 NPT) -
CAP
SADDLE -
SUPPORT
CUP WITH -
ROLL FORMED
THREADS
GUIDE
PIN
GUIDE PIN
HOUSING
DEFLECTOR -
THREAD INTO
SUPPORT CUP
UNTIL MOUNTING
SURFACE IS
FLUSH WITH
CEILING
SEALING
ASSEMBLY
SPRINKLER
WRENCHING
HEX
COMPRESSION
SCREW
LEVER
_ J I
II I SOLDER LINK I I I 7 ThI
I ELEMENT
I I I I
I I I I
I I I I I I DEFLECTOR
I --------... I (OPERATED
POSITION) I I
I SPRINKLER!SUPPORT CUP
ASSEMBLY I
I I
I I
RETAINER
WITH THREAD
DIMPLES
EJECTION
SPRING
Physical Characteristics
Body ...............Brass
Cap ..............Bronze
Saddle .............Brass
Sealing Assembly ..........
Beryllium Nickel wlleflon*
Solder Link Halves .......Nickel
Lever .............Bronze
Compression Screw ......Brass
Deflector .......Bronze/Brass
Guide Pin Housing ......Bronze
Guide Pins ......Stainless Steel
Support Cup ......Plated Steel
Cover Plate ...........Brass
Retainer ............Brass
Cover Plate Ejection Spring .....
...Stainless Steel
* DuPont registered trademark.
Patents
U.S.A. Patent No. 4,014,388.
SOLDER
TAB
Operation
When exposed to heat from a fire, the
Cover Plate, soldered to the Retainer
at three points, falls away to expose
the Sprinkler Assembly. At this point
the Deflector supported by the Guide
Pins drops down to its operational po-
sition.
When the rated temperature of the Sol-
der Link Element is reached, the Link
Element separates, allowing the sprin-
kler to activate and flow water.
COVER PLATEIRETAINER
ASSEMBLY
FIGURE 1
THE ILLUSION (TY5521)
CONCEALED PENDENT SPRINKLER ASSEMBLY
COVER
PLATE
TFPI84 Page 3 0t6
2-1/? DIA. SPRINKLER-
(63,5 mm) 314" (19.1 mm) FACE OF SUPPORT CUP
i" 7) THREADED SPRINKLER
;SPR
E
NPT
Y
PERATEDADJUSThIENT FITflNG
INKLER
COVER 2-1/8"*318" PLATE
- (54,0 mm RETAINER 3W GAP ±9,5 mm)
I COVER- SPRINKLER-
]
MOUNTING 3/8" (9,5 mm)
I RETAINER SUPPORT CUP • SURFACE I ASSEMBLY ASSEMBLY (4.8 mm)
3-3116"DIA. DISPOSABLE
\ 1-1/8" (28,6 mm)
- DEFLECTOR IN
(81,0 MM) TIP PROTECTIVE CAP OPERATED POSITION
FIGURE 2
THE ILLUSION PENDENT SPRINKLER INSTALLATION DIMENSIONS
Design
Criteria
The Tyco® ILLUSION (TY5521)
Concealed Pendent Sprinklers are UL
and C-UL Listed as quick response -
standard spray sprinklers for use in
accordance with the current NFPA
standard; however, in accordance with
its UL and C-UL Listing it cannot be
used for the protection of storage.
The ILLUSION Concealed Pendent
Sprinklers are only listed and ap-
proved with the ILLUSION Concealed
Cover Plates having a factory applied
finish.
The ILLUSION must not be used in
applications where the air pressure
above the ceiling is greater than
that below. Down drafts through the
Support Cup could delay sprinkler
operation in a fire situation.
Installation
The Tyco® ILLUSIONTm must be in-
stalled in accordance with the follow-
ing instructions;
NOT/CE
A 3/4 inch NPT sprinkler joint should
be obtained with a minimum to maxi-
mum torque of 10 to 20 ft.lbs. (13.4 to
26.8 Nm). Higher levels of torque may
distort the sprinkler inlet with conse-
quent leakage or impairment of the
sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in the Sprinkler
Assembly by under- or over-tightening
the Sprinkler/Support Cup Assembly.
Readjust the position of the sprinkler
fitting to suit.
Step 1. The sprinkler must only be
installed in the pendent position and
with the centerline of the sprinkler per-
pendicular to the mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 4. Wrench tighten the sprinkler
using only the W-Type 18 Sprinkler
Wrench (Ref. Figure 3). The W-Type
18 Sprinkler Wrench is to be applied to
the Sprinkler as shown in Figure 3.
Step S. Replace the Protective Cap
(Ref. Figure 2) by pushing it upwards
until it bottoms out against the Support
Cup. The Protective Cap helps prevent
or exhibiting visible signs of corrosion Care and must be replaced.
Page 4 of 6 TFPIS4
damage to the Deflector and Arms dur-
ing ceiling installation and/or during
application of the finish coating of the
ceiling. It may also be used to locate
the center of the clearance hole by
gently pushing the ceiling material
against the center point of the Protec-
tive Cap.
NOTICE
As long as the Protective Cap remains
in place, the system is considered to
be 'Out of Service".
Step 6. After the ceiling has been com-
pleted with the 2-1/2 inch (63,5 mm)
diameter clearance hole and in prepa-
ration for installing the Cover Plate As-
sembly, remove and discard the Pro-
tective Cap, and verify that the
Deflector moves up and down freely. If
the Sprinkler has been damaged and
the Deflector does not move up and
down freely, replace the entire Sprin-
kler assembly. Do not attempt to mod-
ify or repair a damaged sprinkler.
Step 7. When installing an Air and
Dust Seal, refer to Figure 4, otherwise
proceed to Step 8. To attach the Air
and Dust Seal, verify the angle of the
outside edge of the seal is oriented
according to Figure 4. Start the edge
of the Retainer in the grooved slot of
the Air and Dust Seal and continue
around the retainer until the entire Air
and Dust Seal is engaged.
Step 8. Screw on the Cover Plate/Re-
tainer Assembly until the Retainer -
Figure 2 (or Air and Dust Seal - Figure
4) makes contact with the ceiling. Do
not continue to screw on the Cover
Plate/Retainer Assembly such that it
lifts a ceiling panel out of its normal
position. If the Cover Plate/Retainer
Assembly cannot be engaged with the
Support Cup or the Cover Plate/Re-
tainer Assembly cannot be engaged
sufficiently to contact the ceiling, the
Sprinkler Fitting must be repositioned.
Maintenance
The Tyco® ILLUSIONTm must be
maintained and serviced in accord-
ance with the following instructions: =
Absence of the Cover Plate Assembly
may delay sprinkler operation in a fire
situation.
When properly installed, there is a
nominal 3/32 inch (2,4 mm) air gap
between the lip of the Cover Plate and
the ceiling, as shown in Figure 2. This
air gap is necessary for proper opera-
tion of the sprinkler by allowing heat
flow from a fire to pass below and
above the Cover Plate to help assure
appropriate release of the Cover Plate
in a fire situation, if the ceiling is to be
repainted after the installation of the
Sprinkler, care must be exercised to
ensure that the new paint does NOT
seal off any of the air gap.
Factory painted Cover Plates MUST
NOT be repainted. They should be re-
placed, if necessary, by factory
painted units. Non-factory applied
paint may adversely delay or prevent
sprinkler operation in the event of a
fire.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission toshut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Sprinklers that are found to be leaking
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied or over heated sprinklers must be
replaced.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
If a sprinkler must be removed, do not
reinstall it or a replacement without
reinstalling the Cover Plate Assembly.
if a Cover Plate Assembly becomes
dislodged during service, replace it im-
mediately.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by
a qualified Inspection Service in ac-
cordance with local requirements
and/or national codes.
TFPIB4 Page 5 of B
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted bylaw. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the full
product name. Contact your local dis-
tributor for availability.
Sprinkler Assembly:
Specify: TY5521, (specify temperature
rating) ILLUSION Pendent Sprinkler,
PIN (specify).
ISVFITVC 21F11OC
TY5521 50-711-1-160 50.711-1-212
Separately Ordered Cover Plate:
Specify: (specify temperature rating)
ILLUSION Cover Plate with (specify
finish), P/N (specify).
139F15YC(a) 185FR4C(b)
Brass .......56-892-1-135 56.892-1-185
Chrome .....56.892-9-135 58-892-9.165
Signal White (c)
(RAL 9003) . . 56.892-4-135 56-892-4-165
Grey White (d)
(RAL 9002) . . 56-892-0-135 56-892-0-165
Pure White (e)
(RN.. 9010) . . 58-892-3-135 56-892-3-165
Custom .....56-892-X-135 56-892-X-165
For use with 160'F!71C sprinklers.
For use with 212F1100C sprinklers.
(C) Previously known as Bright White.
Previously known as Standard White.
Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 18 Sprinkler Wrench,
P/N 56-000-1-265.
Air and Dust Seal:
Specify: Air and Dust Seal,
P/N 56-908-1-001.
Page 6 of 6 TFPI84
0 2008 TYCO FIRE Ri BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
allow easy tightening from
many angles, reducing
assembly effort. This sprin-
kler is available in various
temperature ratings (see
chart on page 2) and
finishes to meet many
design requirements.
The recessed pendent
should be utilized with a
Model V27 recessed
escutcheon which pro-
vides up to V4' (19 mm) of
adjustments.
Sprinkler Operation
The operating mechanism
is a frangible glass bulb
which contains a heat
responsive liquid. During a
fire, the ambient tempera-
ture rises causing the liquid
in the bulb to expand.
When the ambient temper-
ature reaches the rated
temperature of the sprin-
kler, the bulb shatters. As a
result, the waterway is
cleared of all sealing parts
and water is discharged
towards the deflector. The
deflector is designed to
distribute the water in a
pattern that is most effec-
tive in controlling the fire.
Coverage
For coverage area and
sprinkler placement, refer
to NFPA 13 standards.
/1'itauiïcr =k-5i.t:i j
V27, K5.6
Models V2709 and V2710
Standard Spray
Horizontal Sidewall and
Recessed Horizontal Sidewall
Standard and Quick Response
PRODUCT DESCRIPTION
These Model V27, standard
spray horizontal sidewall
sprinklers are designed for
_____ standard or recessed instal-
lation. The design provides
V2709 a crescent-shaped water
Standard V2710 discharge pattern for Instal- Horizontal Sidewall latlon along a wall or under
a beam or ceiling. The
design incorporates state-
of-the-art, heat responsive,
frangible glass bulb design
(standard or quick
response) for prompt, pre-
cise operation.
(
The the cast frame is more
streamlined and attractive
27o9
V2110 than traditional sand cast
frames. It Is cast with a
Recessed hex-shaped wrench boss to
Horizontal Sidewall
TECHNICAL SPECIFICATIONS
Models: V2709, V2710
Style: Horizontal Sidewall or
Recessed Horizontal Sidewall
Nominal Orifice Size:
½' (13 mm)
K-Factor: 5.6 Imp. (8.1 S.!.")
Nominal Thread Size:
WNPT(l5mm)
Max. Working Pressure:
175 psi (1200 kPa)
Factory Hydrostatic Test
100% @ 500 psi (3450 kPa)
Mm. Operating Pressure:
7psi (48 kPa)
Temperature Rating: See
chart on page 2.
MATERIAL
SPECIFICATIONS
Horizontal Deflector:
UNS C22000 Commercial bronze
Bulb: Glass with glycerin solu-
tion.
Bulb Nominal Diameter:
U Standard: 5.0 mm
U Quick Response: 3.0 mm
Load Screw: UNS C65 100 Low
Silicon bronze
Pip Cap: UNS C65 100 Low Sili-
con bronze
Seal: Teflon* tape
Spring: Beryllium nickel
Frame: Die cast brass 65-30
Lodgement Spring
UNS S30200 Stainless steel
ACCESSORIES
Installation Wrench:
U Open End: V27
U Recessed: V38-3
Finishes:
U Plain brass
U Chrome plated
U White painted"
U Flat black painted**
U Custom painted**
U Lead**
155, 200, 2865R Only:
U Wax'
U Wax over lead**
For cabinets and other accesso-
ries refer to separate sheet.
For K-Factor when pressure is mea-
sured in Bar, multiply S.I. units by
10.0.
Teflon is a rcgtstcrcd trademark of
Dupont Co.
UL Listed for corrosion resistanco in
all configurations.
VICTAULIC5 IS AN ISO 9001 CERTIFIED COMPANY
Vlctaulic Company of America Vlcvullc Comreny of Cand Vlctaulic Europo Vlctcullc America Lctlna Victaulic Anla Pacific
Phone: 1-800-PICK-VIC (1-800-142-5842) Phone: 416.675.5515 Phone:32-9-381 -1500 Phone: 610-559-3300 Phone: 65-6235-3035
Fax: 610-250-8817 Fax: 416-615-5565 Fax: 32-9-380-4438 Fax: 610-559-3608 Fax: 65-6235-0535
e-mail:pickvic@victaulic.com e-mail: viccanada@viclaulic.com e-mail: viceuro@viclaulic.be e-mail: vical@viclaulic.com e-mail: vicap@victaulic.com
2545 Rev.D 1111102 0 Registered Trademark of Victaullc 0 Copyright 2002 Mctaulic Primed in U.S.A.
APPROVALSILISTINGS
Nominal Approved Temperature Ratings °FIC t 91
K-Factor
Orifice Size Imperial Deflector
Model lnchesl:nm s.i.* Response Type UL FM@ ULC NYCIMEAI CSFM §
½ 5.6 135-360 135-360 135-360 135-360 135-360
V2709 13 8,1 Standard Horizontal Sidewall 182 57 182 57 182 57 182 SI 182
½ 5.6 Recessed HSW 135-200 135-200 135-200 135-200 135-200 V2709 13 8.1 Up Up to Adjustment 51 93 57 93 51 93 51 93 51 93
V2710 ½ 5.6 Quick Horizontal Sidewall 135-286 135-286 135-286
51 141
135-286 135-286
141 51 13 8.1 141 51 141 1 SI 141
½ 5.6 Recessed HSW 135-200 135-200 135-200
V2710 13 Quick UptowAdjustment 51 93 51 93 SI 93
135-200a
1193
51 93
½ 5.6 Recessed HSW 135-200 No 135-200 135-200
V2710 13 8.1 Quick upto~AdJusunt , U 93 51 93
Listings and approval as of pnnting. L2 All arc approved open, except for areas designated No. @ Ught Hazard only.
"For K-Factor when pressure is measured in Bar, multiply SI. units by 10.0.
t MEA #62-99-E. § CSFM #7690-0531:112
Temperature - °FIC
Sprinkler Victaulic Nominal Maximum Glass
Temperature Part Temperature Ambient Temp. Bulb
Classification Identification Rating Allowed Color
Ordinary A 135
51
100
33 Orange
Ordinary C 155
63
100
39 Red
Intermediate E 175 150
79 55 Yellow
Intermediate F 200
93
150
85 Green
High J 286
1.41
225 -
107 Blue
Extra Hight K 360 182
300
149 Mauve
- t M Open T No Bulb
* Standard response only.
All are approved open, except for areas designated "No.
- 150165 if wax coated.
RATINGS
All glass bulbs are rated for
temperatures from -67°F
(-55°C) to those shown in
adjacent table.
ORDERING INFORMATION
Please specify the following
when ordering: U Sprinkler Model Number
U Style
U Temperature Rating
K-Factor U Sprinkler Finish
U Thread Size U Escutcheon Finish
Quantity U Wrench Model Number
--
- Always read and understand installation, care, and maintenance instructions, supplied with each box of sprinklers, before proceeding with installation
of any sprinklers.
- Always wear safety glasses and foot protection.
- Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products. . 0 Installation rules, especially those governing obstruction, must be strictly followed.
Painting, plating, or any re-coating of sprinklers (other than that supplied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal injury andlor property damage.
The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the
current National Fire Protection Association pamphlet that describes care and maintenance of sprinkler systems. In addition, the authority having jurisdictiofi may have additional
maintenance, testing, and inspection requirements that must be followed.
If you need additional copies of this publication, or if you have any questions about the safe installation of this product, contact Victaulic World Headquarters, P.O. Box 31, Easton,
Pennsylvania 180444031, 610-559-3300.
-
40.11 -2
DIMENSIONS
3 (89 mm)
2W(57 mm) —
(32 mm)
(8 in ). 1111 mm)
Standard HSW-.V2709, V2710
(17 mm)
b
IN.
14
mm) (43 mm) (27mn
- Finished Ceiling
4- 12'(102T -305 mm) 4- 120
Per NFPA Per NFPA
—A. P2 MM) Zxs- (60 mm) T 2W in. ola Max' Hale
"- Finished Ceiling
-ft
2'(5lmm) 2W(60mm)
Mm. Hole Max. Hole
Finished Surface -' -4 4— Typical Wall
Finished Surface
- ._i L Typical Wall
MAXIMUM EXTENSION MAXIMUM RECESS
½" Adjustment
Recessed — V2709, V2710
(Dmw(rtgnollb scale)
124 mmt
(14 mm) 1iAe Ths
(58 mm) I (37 mm) (33 mm)
________ __________'-
Finished Ceiling Finished Ceiling
4-12'(102-305mm) 4-12'(102-305min) •1—
Per NFRk PerNEPA
L-0~rt
2' (51 mm) 2% (60 mm) 2' • 2' (51 mm) 20A"(60 mm)
Mm. Hole Max. Hole (75 mm) Mm. Hole Max. Hole
Finished Surface J L_ Typical Wall Finished
Surface
L Typical wall
MAXIMUM EXTENSION MAXIMUM RECESS
- -%" Adjustment
Recessed — V2709, V2710
(Thrnvuiq not to scale)
AVAILABLE WRENCHES
V38-3
Recessed
V21
Open End
No escutcheon / /
With escutcheon / -
40.11-3
URRUUURUUU
2'
0.6 m
4,
1.2 m
6'
1,8 et
8'
2,4 m
10'
3,0 m
12' 3,7 m
14'
4,3 m
16'
4,9 m
ipsi
48 kPa
15 psi
103 kPa
30 psi ------
207 kPa
DISTRIBUTION PATTERNS
MODELS V2709, V2710
1(5.6 STANDARD HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL
DISTRIBUTION PATTERNS - TRAJECTORY
10' Ea-q-
3,0 rn
8'
2.4 m
6' 1,8 m
4,
1,Zm
2'
0,6 m
0
UU•SRUlIU
NNEEMENEEMENE
MENEWENEEMENE
ENEEMENEEMMEN MONEEMENEEMME INEEMENEEMEMEN
2' 4' 6' 8' 10' 12' 14' 16' 18' 20' 22' 24' 26' 0,6m 1,2m 1,8m 2,4m 3,0m 3,7m 4,3m 4,9m 5,5m 6,11m 6,7m 7,3m 7,9m
ipsi
48 We
15 psi
103 kPa
30 psi -------
207 kPa
MODELS V2109, V2110
1(5.6 STANDARD HORIZONTAL SIDEWALL
DISTRIBUTION PATTERNS - PLAN VIEW
2' 4' 6' 8' 10' 12' 14' 16' 18' 20' 22' 24' 26' 28'
06 m 1.2 m 1.8 m 2.4 m 3.0m 3.7 m 4.3 m 4.9 m 5.5 m 6,1 m 6,7 m 7.3 m 7.9 m 8,5 m
NOTES: -
Data shown is approximate and can vary due to differences In Installation.
These graphs illustrate approximate trajectories, floor-wetting, and wall-wetting patterns for these specific Victaulic FireLock Automatic Sprinklers. They are
provided as information for guidance In avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation. Refer to
the appropriate NFPA National Fire Code or the Authority Having Jurisdiction for specific information regarding obstructions, spacing limitations and area of
coverage requirements. Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings. Approvals and War-
ranties.
WARRANTY Refer to the Warranty section
of the current Price List or
contact Victaulic for details.
This product shall be manufactured by Victaulic Company. Al products to be installed in accordance with current Victaulic installation/assembly instructions.
Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations.
40.11-4