HomeMy WebLinkAbout5928 FARNSWORTH CT; ; US130098; Permit6/6/24, 2:07 PM US130098 Permit Data
City of Carlsbad.
Hazardous Installations
5928 FARNSWORTH
Job Address:
CT
Permit Type: HI
Parcel No: 2120701000
Lot #: 0
Reference No.:
Permit No: US130098
Status: APPROVED
Applied 6/3/2013
Approved: 6/3/2013
Issued: 6/3/2013
PC #: Inspector:
Project Title: CARLSBAD TECHNOLOGIES ANNUAL OPERATIONAL USE
PERMIT FOR HIGH PILE STORAGE RACKS
Applicant: Owner:
MCR FARNSWORTH L L C
1808 ASTON AVE #180
CARLSBAD CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
320 0 320 320
about:blank 1/1
THERE ARE NO
PLANS
ASSOCIATED. WITH
THIS PERMIT
Carlsbad Fire Department OTI P
Plan Review Requirements Category: HI, HPCSTOR
Date of Report: 06-03-2013 Reviewed by:
*44
Name: MCR FARNSWORTH I L C
Address: 1808 ASTON AVE #180
CARLSBAD CA
92008
Permit #: U5130098
Job Name: CARLSBAD TECHNOLOGIES
Job Address: 5928 FARNSWORTH CT CBAD
Please review carefully all comments attached.
Conditions:
CITY OF CARLSBAD FIRE DEPARTMENT - APPROVED:
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUANCE OF BUILDING PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTION AND REQUIRED TEST, NOTATIONS HEREON, CONDITIONS IN
CORRESPONDENCE AND CONFORMANCE WITH ALL APPLICABLE REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE THE VIOLATION OF ANY LAW.
At or prior to Final Fire and Building inspection an Emergency lighting facilities test shall be conducted by CFD
personnel during pre-dawn or dusk hours when ambient light is at 0.00 Lux or 0.0 Foot-candle.
This test shall be conducted to test the initial loss of power reading of illumination that is at least an average of 1
foot candle (11 lux) and a minimum of 0.1 foot-candle (1 lux) measured along the path of egress at the floor level.
And tested after 60-minutes to 0.6 fc (6 lux). Failure to provide sufficient lighting in egress aisles, corridors, exit
enclosures, exit passageways and stair enclosures is the AOR's responsibility. CFC Ch. 10, Sec. 1006.
Entry: 06/03/2013 By: GR Action: AP