HomeMy WebLinkAbout2382 FARADAY AVE; ; AS040108; Permit6/6/24, 2:08 PM AS040108 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address: 2382 FARADAY AV
Permit Type: SPRINK
Parcel No: 2120621700
Lot #: 0
Reference No.:
Permit No: AS040108
Status: ISSUED
Applied 7/19/2004
Approved: 8/12/2004
Issued: 8/12/2004
PC #: Inspector:
Project Title: BELLA D'ORA FIRE SPRINKLER PLAN CHECK & INSPECTIONS
Applicant:
PARAMOUNT FIRE SYSTEMS, INC.
P.O. BOX 713194
SANTEE, CA
619-562-6247
Owner:
PACIFIC CARLSBAD ONE L P
C/O JAMES T GIANULIS
3838 CAMINO DEL RIO N #300
SAN DIEGO CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
100 0 100 0
about:blank 1/1
tqGO /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
(ENTRAL
Customer Service/Sales:
Tel: (215) 362-0700 / (800) 523-6512
Fax: (215) 362-5385
Series TYFRB - 28, 42, 56, and 80 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage EIt1b4
General
Description
The Series TY-FRB, 2.8, 4.2, 5.6, and
8.0 K-factor, Upright and Pendent
Sprinklers described in this data sheet
are quick response - standard cover-
age, decorative 3 mm glass bulb type
spray sprinklers designed for use in
light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20(1/2 inch NPT) or Style 30(3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the fixed pipe
drops to the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TY-FRB Pendent Sprinklers are
detailed in Technical Data Sheet
1FP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the integrity of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
Model/Sprinkler
Identification
Numbers
TY1131 - Upright 2.8K, 1/2"NPT
TY1231 - Pendent 2.8K, 1/2"NPT
TY2131 - Upright 4.2K, 1/2"NPT
TY2231 - Pendent 4.2K, 1/2"NPT
TY3131 - Upright 5.6K, 1/2"NPT
TY3231 - Pendent 5.6K, 1/2"NPT
TY4131 - Upright 8.0K, 3/4"NPT
TY4231 - Pendent 8.0K, 3/4"NPT
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 2.8 GPM/psil/2 (40,3 LPM/bar1/2)
K = 4.2 GPM/psil/2 (60,5 LPM/bar1/2)
K = 5.6 GPM/psil'2 (80,6 LPM/barl/2)
K = 8.0 GPM/psi"2 (115,2 LPM/barll2)
Temperature Ratings
Refer to Table A and B
Finishes
Sprinkler: Refer to Table A and B
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
Frame ............Bronze
Button ........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflont
Bulb ..............Glass
Compression Screw .....Bronze
Deflector .......Copper/Bronze
Bushing (K=2.8) .......Bronze
4-
Page 1 of 8 APRIL, 2003 TFPI7I
SSP DEFLECTOR*
PENDENT
WRENCH
FLATS
2-7/8" (73,0 mm) DIA.
RECESSED PENDENT
SSU*
DEFLECTOR
6*1
7/16 . 5 I
(1111,11 mm) ____ : MAKE-IN
I 2-3/16" ,
$ (55,6 mm)
1/2NPT**
. 3
1
UPRIGHT CROSS SECTION
ESCUTCHEON 7/16(11,1 mm) STYLE 100r20
PLATE SEATING NOMINAL RECESSED
SURFACE NPT MAKE-IN ESCUTCHEON
2-3/16"
(55,6 mm) 1
SSP DEFLECTOR*
PENDENT
L
\kUJ WRENCH
-
FLATS
2-7/8" (73,0 mm) DIA.
RECESSED PENDENT
Page 2 of 8
ESCUTCHEON 7/16'(11,1 mm) STYLE 10 or 20
PLATE SEATING • ** NOMINAL RECESSED
SURFACE 1/2 MAKE-IN ESCUTCHEON KIOIr
TFPI7I
SSU* I
DEFLECTOR I
61
jJ-7
J
I
7/16" 51
(111 ,
NOMINAL
mm) I
MAKE-IN
I 2-3/16" '.' $ (55,6 mm)
1/2nNPT** t 7
UPRIGHT CROSS SECTION
1 - Frame 3-Sealing 4-Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. Screw **Pips thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TYII3I) AND PENDENT (TY1231) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
1 - Frame 3-Sealing 4-Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2- Button Assembly 5- Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K-FACTOR, 112 INCH NPT
6*
TFPI7I Page 3 of 8
ESCUTCHEON
PLATE SEATING
SURFACE
2-3/16"
(55,6mm) (J
7/16"(11.1 mm)
** NOMINAL
MAKE-IN NPT I
STYLE 10or20
RECESSED SSU* ESCUTCHEON DEFLECTOR
7/16" 1 Z 11,1mm)
MAKE-IN
WRENC ____(55,6 mm)
2-3/16"
NOMINAL
FLATS
1/2"NPT I SSP DEFLECTOR* h — 2-7/8" (73,0 mm) DIA.
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
- Frame 3- Sealing 4- Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2" (12,7 mm)
PLATE SEATING ** NOMINAL
SURFACE MAKE-IN NPT
2-16"
(58,7 mm)
1-9/16"
J
(39,7 mm)
SSP DEFLECTOR* L 2
STYLE 30 or 40
RECESSED
ESCUTCHEON SSU
c
DEFLECTOR
___________ 6*
5
_______ (12,7 mm) I I NOMINAL 4
__
MAKE-IN
WRENCH (57,2 mm) 3 FLATS
I_
-7/8" (73,0 mm) 01k --1 3/4" NPT ** I
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3- Sealing 4- Bulb 6- Deflector Temperature rating is indicated on deflector or adjacent to 2- Button Assembly 5- Compression orifice seat on frame. Screw Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Page 4 of 8 TFPI7I
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED
I WHITE*
IPOLYESTER
2.8
1/2"
PENDENT
(TY1231)
and
UPRIGHT
(TY1131)
135"F/57"C Orange
1,2,3,5 155°F/68"C Red
175"F179°C Yellow
200"F/93°C Green
286"F/141"C Blue
NPT 135°F/57°C Orange
1,2, 5
RECESSED
PENDENT
(TY2231)
Figure 5
155017/680C Red
175°17/790C Yellow
200°F/93°C Green
135°F/57°C Orange
RECESSED
PENDENT
(TY2231)
Figure 6
155"F/68°C Red
175"F179"C Yellow
200°F/93°C Green
4.2
1/2"
NPT
PENDENT
(TY2231)
and
UPRIGHT
(TY3131)
1 35"F/57"C Orange
1,2
155F/68°C Red
1750171790C Yellow
200F/93"C Green
286"F/141.0 Blue
1350F/57"C Orange
RECESSED
PENDENT
C1Y2231)*
FIgure 7
155°F/68"C Red
175"F179°C Yellow
200"F/93"C Green
1350F/57°C Orange
RECESSED
PENDENT
(TY2231)
Figure
155"F/68"C Red
175°F1790C Yellow
200"F/93"C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response
Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354-01-E.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
* Installed with Style 10(1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Re-
cessed Escutcheon, as applicable.
Installed with Style 20 (1/2" NPT) or Style 30(3/4" NPT) 1/2" Total Adjustment Re-
cessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to all colors (Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
Installation
The Series TY-FRB Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/570C to 3/32
inch (2,4 mm) for the 286°F/1410C
temperature ratings.
A leak tight 1/2 inch NPT sprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 13).
With reference to Figures 1, 2, 3, and
4, the W-Type 6 Sprinkler Wrench is to
be applied to the sprinkler wrench
flats.
The Series TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
TFPI7I Page 5 of 8
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED
I WHITE'
IPOLVESTER
LEAD
COATED
5.6
1/2"
PENDENT
(TY3231)
and
UPRIGHT
(TY3131)
1 35°F/57°C Orange
1,2,3,4,5,6 1,2,3,5
155017/680C Red
175017/790C Yellow
200°17193°C Green
286"F/141°C Blue
NPT 135°17/570C Orange
1,2,4,5 N/A
RECESSED
PENDENT
(TY3231)"
Figure 9
155"F/68"C Red
175°F179°C Yellow
2000F/930C Green
135°F/57°C Orange
1, 2, 3, 4,5 I 1,2,4,5 N/A
RECESSED
PENDENT
fY3231r
Figure 10
1550F/680C Red
1750F179"C Yellow
200"F/93°C Green
8.0
PENDENT
(TY4231)
and
UPRIGHT
(TY4131)
135"F/57°C Orange
1,2, 3, 4,5,6
1,2,5 1550F/680C Red
1750F179"C Yellow
200°F/930C Green
286°F/141°C Blue
NPT 1350F/570C Green
1,2,4,5 N/A
RECESSED
PENDENT
(TY4231)"
Figure 11
1550F/680C Orange
175°F179°C Red
200°171930C Yellow
1350F/57°C Orange
1,2,3,4,5 N/A
RECESSED
PENDENT
(TY4231)"
Figure 12
1550F/68"C Red
175"F/79°C Yellow
200"F/93°C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB) as Quick Response Sprinklers; however, the LPC does not rate the thermal
sensitivity of recessed sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. listings and approvals apply to all colors (Special Order).
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 14). With reference to Figure 1,
2, .3, and 4, the W-Type 7 Recessed
Sprinkler Wrench is to be applied to
the sprinkler wrench flats.
Step C. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 10, 20, 30, or
40 Closure over the Series TY-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
Page 6 of 8
2-7/8" DIA.
5/8±1/4"
(73,0 mm) 3/4"(119,11 mm)
(15,9±6.4 mm) 2-1/4" DIA. I 1/4" (6,4 mm)
FACE OF MOUNTING
SPRINKLER PLATE
FITTING
I 1/8"
(32 mm)
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16" (33,3 mm)
TY-FRB 13/16" (20,6 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
- 2-7/8" DIA.
(73,0 mm) I 3/4"(119,11 mm)
(15,9±6,4 mm)
.. 2-1/4" DIA. 1/4(6,4 mm) I
FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE FITTING
AAL/
MOUNTING
SURFACE/
SERIES 1-1/4"(31,8 mm) CLOSURE TY-FRB 3/4" (19,1 mm)
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
TFPI7I
2.7/8" DIA.
(73,0 mm) 1/2±1/8" 1/2'(12,7 mm) r (12,7±3,2 mm) 2-1/4" DIA. 1/4'(6,4 mm) I
PLATE I SPRINKLER
FACE OF
57,2
mm) MOUNTING
/ - (3,2 mm)
MOUNTING
4-
__
FITTING
CLOSURE (33,3mm)f
SURFACE ?q
1-1/16 (27,0 mm)
FIGURE 6
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
2-718"DIA.
(73,0 mm) 1/2±1/8" 1/2"(12,7mm) r (12,7±3,2 mm) 2.1/4" DIA. 1/4(6,4mm)
FACE OF (57,2 mm) MOUNTING I SPRINKLER PLATE
FITTING
I
MOUNTING
SURFACE
CLOSURE SERIES 1-1/4" (31,8 mm) I
TV-FRB 1"(25,4 mm)
FIGURE 8
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
Care and
Maintenance
The Series TY-FRB Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shutdown the
affected fire protection system must be
'Obtained from the proper authorities
and all personnel who maybe affected
by this action must be notified.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be Completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
TFPI7I
2-7/8" DIA. - (73,0 mm) 3/4(19.1 mm) ________
(15.9*6,4 mm) 2-1/4" DIA. I 1/4"(6,4 mm) I
FACE OF MOUNTING SPRINKLER PLATE FITTING
1/8"
(3,2 mm)
Vol
MOUNTING
SURFACE
SERIES 1-1/4"(31,8 mm) CLOSURE TVFRB 314"(19,1 mm)
FIGURE 9
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE $14 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8" DIA. -
(73,0 mm) I 3/4" (19,1 mm)
(15,9*6,4 mm) 2-1/4" DIA. 1/4" (6.4 mm) I
FACE OF (57,2 mm) MOUNTING I
/,i#
1/8' I SPRINKLER PLATE I
FITTING
__ - ___________ (3,2 mm)
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16" (333mm)f
TY-FRB 13116'(20.6 mm)
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
Page 7 of 8
2-7/8" DIA.
(73,0 mm) 1/2±1/8" 1/2"(12,7 mm) r (12,7±3,2 mm) _2-1/4-DIA. 1/4"(6,4 mm)
I SPRINKLER PLATE
FACE OF mm) MOUNTING
FITTING / _____ _______
1/B'
4
______ ____
SURFACE,,////'t
\
MOUNTING
SERIES 1-1/4" (31 .8 mm) CLOSURE TY.FRB 1. (25,4 mm)
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8' DIA.
1/2*1/8" (73.0 mm) 1/2"(12,7 mm)
(12,7±3,2 mm) 2-1/4" DIA. 1/4"(6,4 mm)
FACE OF (57,2 mm) MOUNTING
SPRINKLER ..- PLATE
FITTING - I / I 1/8'
I - _____________ I (,2 mm)
-
/
/ MOUNTING / SURFACE /
CLOSURE SERIES 1-5116'(33,3 mm)
TV. FRB 1-1/16' (27,0 mm)
FIGURE 12
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.
WRENCH RECESS
(END "A' USED FOR
1/2' NPT MODELS)
WRENCH RECESS
(END 'B' USED FOR
3/4' NPT MODELS)
FIGURE 13
W-TYPE 6 SPRINKLER
WRENCH
WRENCH
RECESS
PUSH WRENCH
INTO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 14
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Page 8 of 8 TFPI7I
P/N 57 - XXX - X - XXX I L
I MODEL/SIN
330 2.8K UPRIGHT (1/2'NPT) TY1131
331 2.81K PENDENT (1/2'NPT) TY1231
340 4.2K UPRIGHT (1/2'NPT) TY2131
341 4.2K PENDENT (1/2'NPT) TY2231
370 5.61K UPRIGHT (1/2'NPT) TY3131
371 5.6K PENDENT (1/2'NPT) TY3231
390 8.0K UPRIGHT (3/4"NPT) TY4131
391 8.0K PENDENT (3/4'NPT) TY4231
I I
L 135
SPRINKLER I
155
175
200
286 1
RATING
1
1 NATURAL BRASS 155°F/68°C
4 WHITE POLYESTER 1750F/7I10C
9 CHROME PLATED
1
200°F/93°C
7 LEAD COATED 286°F/147C
TABLE C
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPUED. INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
Ordering
Procedure
When placing an order, indicate the full
product name. Refer to the Price List
for complete listing of Part Numbers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table C).
Recessed Escutcheon:
Specify: Style (specify) Recessed Es-
cutcheon with (specify finish), P/N
(specify).
1/2 (15 mm) Style 10
Chrome Plated .........P/N 56-701-9-010
1/2' (15 mm)
Style 10
White Color
Coated ................P/N 56-701-4-010
1/2 (15 mm) Style 10
Brass Plated ...........P/N 56-701-2-010 1/2 (15 mm)
Style 20
Chrome Plated .........P/N 56-705-9-010
1/2" (15 mm)
Style 20
White Color
Coated ................P/N 56-705-4-010
1/2' (15 mm)
Style 20
Brass Plated ...........P/N 56-705-2-010
3/4" (20 mm)
Style 30
Chrome Plated .........P/N 56-705-9-011 3/4' (20 mm)
Style 30 White Color
Coated ................P/N 56-705-4-011
3/4" (20 mm)
Style 30
Brass Plated ...........P/N 56-705-2-011 3/4' (20 mm)
Style 40 Chrome Plated .........P/N 56-700-9-010
3/4" (20 mm)
Style 40 White Color
Coated................P/N 56-700-4-010
3/4" (20 mm)
Style 40 Brass Plated ...........P/N 56-700-2-010
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
L