HomeMy WebLinkAbout2466 UNICORNIO ST; ; CBR2018-1888; Permit(_ City of
Carlsbad
Print Date: 09/24/2019
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
II Dwelling Units:
Bedrooms:
Project Title:
2466 Unicornio St
BLDG-Residential
2152600400
$226,075.01
Residential Permit
Work Class: Alteration
Lot II:
Reference II:
Construction Type:
Bathrooms:
Orig. Plan Check II:
Plan Check 11:
Status:
Applied:
Issued:
Permit
Finaled:
Inspector:
Final
Inspection:
Description: CUTHBERT: 4185 SF REMODEL / 179 SF DECK/ 143 SF STORAGE ON FRONT BALCONY/
Applicant: Owner: Contractor:
Permit No: CBR2018-1888
Closed -Finaled
08/03/2018
11/26/2018
CRenf
9/24/2019 1:52:19PM
ARLEN ROPER COOWNER CUTHBERT EDWARD RAND
SUSAN G
GULICK CONTRACTING INC
1443 Panorama Ridge Rd
Oceanside, CA 92056-2202
760-522-3997
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
2466 Unicornio St
CARLSBAD, CA 92009
ELECTRICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL
MECHANICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL
PLUMBING BLDG RESIDENTIAL NEW/ADDITION/REMODEL
SB1473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-RESIDENTIAL
Total Fees: $2,212.52 Total Payments To Date: $2,212.52
1314 Alta Vista Dr
Vista, CA 92084-5640
858-220-0305
Balance Due:
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
$0.00
1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 f www.carlsbadca.gov
$1,076.85
$756.28
$66.00
$92.00
$182.00
$10.00
$29.39
ITHE FOLL°tN~ APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: □ PLANNING □ ENGINEERING
" • p-Building Permit Application {__ Cicy of 1635 Faraday Ave., Carlsbad, CA 92008
Carlsb
-:i,d Ph: 760-602-2719 Fax: 760-602-8558
U email: building@cartsbadca.gov
www .cartsbadca.gov
□BUILDING □FIRE 0 HAZMA T/APCD
Plan Check No.C6
Est. Value
Plan Ck. Deposit
Date
JOB ADDRESS 2466 Unicornio St -92009
APN
215 -260 -04 00
CT/PROJECT# PHASE# # OF UNITS # BEDROOMS # BATHROOMS TENANT BUSINESS NAME CONSTTI. 1YPE OCC. GROUP
5 R3
DESCRIPTION OF WORK: Include Square Feet of Affected Area(s)
Remodel inside the entire house -no new SF -but is 4185 SF remodel
New kitchen , new bathrooms, etc.
Portion of front balcony being enclosed as UNCONDITIONED storage at 143 SF
Also 179 SF portion of back patio roof being converted to a deck (already OK by Chris Sexton)
EXISTING USE
res
PROPOSED USE
res
GARAGE (SF) PATIOS (SF)
660 420
DECKS (SF) FIREPLACE
179 YES(a#. (E) No[]
AIR CONDITIONING
YES 0No □
FIRE SPRINKLERS
YES0 N00
APPLICANT NAME Arlen Roper PROPERTY OWNER NAME Sue & Ted Cuthbert
1443 Panorama Ridge Rd
ADDRESS 930 Via Mil Cumbres #22
CITY Oceanside
STATE ZIP
ca 92056 CITY Solana Beach STATE ca ZIP 92075
PHONE 760 522 3996
FAX
N/A
PHONE 858 361 3240
FAX
EMAIL EMAIL arlenroper@gmail.com ted.cuthbert@colliers.com
DESIGN PROFESSIONAL
ADDRESS
CITY STATE ZIP
PHONE
EMAIL
STATE UC.#
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to constru . alter, improve, demolish or repair any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law (Chapter 9. commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a
civil penalty of not more than five hundred dollars {$500)).
Workers' Compensation Declaration: / hereby affirm under penalty of perjury one of /he following dedarations:
.fltu.ave and wlll maintain a certificate of consent to self-Insure for workers' compensation as provided by Section 3700 of the Labor Code, for the perfonnance of the work for which this permit is issued.
~ have and will maintain work rs' compensation, as reQuired bv Section 700 of the Labor Code, for the performance of the work for which this permit Is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co. ~ I Policy No. l L? 0 0 0 I CJ 13') l8 ( Expiration Dale f I • I 3 -I ':\
This section need not be completed ff the permit is for one hundred dollars ($100) or less. • 0 Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
Calffomia. WARNING: Failure to secure workers' compensation coverage Is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (& 100,000), In
addition to the cost of compensation, da es as provided fo • Section 3706 of the Labor code, interest and attorney's fees •
..@S' CONTRACTOR SIGNATURE □AGENT DATE // -"2-"' -/ /7
I hereby affirm that I am exempt from Contractor's License Law for the following reason: 0 I, as owner of the property or my employees with wages as their sole compensation. will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
□
□
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-ouider will have the burden of proving that he did not build or improve for the purpose of sale).
I, as owner of the property, am exdusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Prolessions Code: The Contractor's License Law does not apply lo an owner of
property who builds or improves thereon, and contracts for such projectS with contractor(s) licensed pursuant to the Contractor's License Law).
I am exempt under Section ____ Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials tor construction oi the proposed property Improvement. Oves 0 No
2. I (have/ have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (indude name address/ phone / contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name / address/ phone / contractors· license number):
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name / address/ phone/ type of work):
..@S' PROPERTY OWNER SIGNATURE DATE
Is 4e applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account 1>£1? □ Yes □ No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? □ Yes □ No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? □ Yes □ No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AJR POLLUTION CONTROL DISTRICT.
of the wor1< this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Address
I certify that I haYe read the application and slate that the aboYe lnfunnation Is correct and that the lnfonnation on the plans is accurate. I agree to comply with all City ordinances and Slate laws relating to building conslruCtion.
I hereby au1horize represenfalive of the City of Carlsbad to enter upon the above mentioned property for ilspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CllY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANYWAY ACCRUE AGAINST SAD CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA perm~ is required for excavations over 5'0' deep and demolful or construction of slruc1ures over 3 skllies i1 heighl
EXPIRATION: Every perm~ issued by the Building Official lJ1der the • • of this Code shan expie by lrni1ation and become nul and voo ~ the buikling or WDl1< authorized by such pemit is not corrrnenced withi1
180 days from the date of such pemit or Wthe buidilg orwcrt by such peimil is suspended or abandoned at anytime aflerthe worl( is conmenced fora period of 180 days (Section 106.4.4 Uniloon Bui«lilg Code).
~APPUCANT'SSIGNATURE DATE ;.-"f ·l/3
Permit Type BLDG-Residential Apphcati1>n Date: 08/03/2018
Work Cl..-1ss Alteration ls,;ue Date: 11/26/2018
St,itU5. Closed -Finaled Expiration Date· 11/26/2019
IVR Number: 12978
--------
Scheduled Actual
Date Start Date
0912412019 09/2412019
September 24, 2019
Inspection Type Inspection No.
BLDG-Final
Inspection
105183-2019
Chcckltst Item
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
Inspection Status
Passed
COMMENTS
Owner;
Subdivision
Address
Primary Inspector
Chris Renfro
COOWNER CUTHBERT EDWARD
RAND SUSAN G
LA COST A MEADOWS #1
2466 Unicornio St
Carlsbad, CA 92009-5320
Reinspection
----
Passed
Yes
Yes
Yes
Yes
Yes
Complete
Complete
Page 3 of 3
Perr•ut Type BLDG-Residential Application Date: 08/03/2018 Owner: COOWNER CUTHBERT EDWARD
RAND SUSAN G
Work Class· Alteration Issue DatP.· 11/26/2018 S ubdiv is1on. LA COSTA MEADOWS #1
Status. Closed -Finaled Expiration Date· 11/26/2019 Address: 2466 Unicornio St
Carlsbad, CA 92009-5320
IVR Number: 12978
Scheduled Actual
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector Re inspection Complete
----
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
BLDG-14 No
Frame-Steel-Bolting-Welding
(Decks}
BLDG-24 Rough-Topout No
BLDG-34 Rough Electrical No
BLDG-44 No
Rough-Ducts-Dampers
04/17/2019 04/17/2019 BLDG-84 Rough 089216-2019 Passed Chris Renfro Complete
Combo(14,24,34,44}
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
04/23/2019 04/23/2019 BLDG-81 089724-2019 Passed Chris Renfro Complete
Underground
Combo(11, 12,21 ,31)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-11 Foundation-Ftg-P1ers Yes
(Rebar)
BLDG-12 Steel-Bond Beam Yes
BLDG-21 Yes
Underground-Underfloor
Plumbing
BLDG-31 Yes
Underground-Conduit Wiring
04/29/2019 04/29/2019 BLDG-17 Interior 090237-2019 Partial Pass Chris Renfro Reinspection Incomplete
Lath/Drywall
Checklist Item COMMENTS Passed
BLDG-Building Deficiency See card for areas inspected Yes
05/09/2019 05/09/2019 BLDG-18 Exterior 091487-2019 Partial Pass Chris Renfro Reinspoction Incomplete
Lath/Drywall
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
05/30/2019 05/30/2019 BLDG-17 Interior 093207-2019 Passed Chris Renfro Complete
Lath/Drywall
Checklist Item COMMENTS Passed
BLDG-Building Deficiency See card for areas inspected Yes
September 24, 2019 Page 2 of 3
Permit Type BLDG-Residential Application Date. 08/03/2018 Owner: COOWNER CUTHBERT EDWARD
RAND SUSAN G
Work Class. Alteration Issue Date 11/26/2018 Subdivision LA COSTA MEADOWS #1
Status. Closed -Finaled Expiration Date: 11/26/2019 Address. 2466 Unicornio St
Carlsbad, CA 92009-5320
IVR Number. 12978
------
Scheduled Actual
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector Re inspection Complete
01/15/2019 01/15/2019 BLDG-21 081419-2019 Passed Chris Renfro Complete
Underground/Underf
loor Plumbing
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Inspected underground waste and water Yes
lines to kitchen island, two new showers
and water closet's,
01/17/2019 01/17/2019 BLDG-11 081523-2019 Passed Michael Collins Complete
Foundation/Ftg/Pier
s (Rebar)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Footing/steel ok Yes
03/26/2019 03/26/2019 BLDG-84 Rough 086949-2019 Failed Chris Renfro Relnspection Complete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Not ready. Exterior needs to be wrapped No
and watertight. Sheer inspection next. Need
special inspection on 4 inch nailing or less
on sheer panel.
BLDG-14 No
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout No
BLDG-34 Rough Electrical No
BLDG-44 No
Rough-Ducts-Dampers
03/28/2019 03/28/2019 BLDG-13 Shear 087201-2019 Passed Chris Renfro Complete
Panels/HD (ok to
wrap)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
04/15/2019 04/15/2019 BLDG-84 Rough 088845-2019 Passed Chris Renfro Complete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
04/16/2019 04/16/2019 BLDG-84 Rough 089067 -2019 Cancelled Chris Renfro Reinspection Complete
Combo(14,24,34,44)
September 24, 2019 Page 1 of 3
QAN HUFF INSPECTIONS
2064 Meadowlark Ranch Circle (858) 583-3959
San Marcos, CA 92078
CERTIFIED INSPECTOR'S DAILY REPORT
Ci
JOB NO.
COVERING WORK PERFORMED
WHICH REQUIRED APPROVAL BY
THE SPECIAL INSPECTOR OF
0 REINFORCED CONCRETE O STRUCT saun_~ ,.Q, 9f~Y-APPLIED FIREPROOFING
D PRE-STRESSED CONCRETE D EPO "t) ~l:Q.:.N...._ _____ _
JOB ADDRESS 2. 7" 6G
DESCRIBE MATERIAL
DETAILED REPORT
OF WORK INSPECTED
0/L
0 REINFORCED MASONRY ~WO
BUILDING PERMIT NUMBER
LOCATION OF WORK INSPECTEO, TEST SAMPLES TAKEN, WORK REJECTEO, JOB PROBLEMS, PROGRESS, REMARKS, ETC
INCLUDES INFORMATION ABOUT· AMOUNTS OF MATERIAL PLACED OR WORK PERFORMED. NUMBER, TYPE AND IOENT. NO'S OF TEST
SAMPLES TAKEN, STRUCT. CONNECTIONS (WELDS MOE, H.T. BOLTS TORQUED) CHECKED; ETC
'/J Ll 1 C
INSPECTOR (PRINT OR TYPE)
SIGNATURE:
DATE SIGNED: Vd !z/1
(
CERTIFICATION OF COMPLIANCE: to the best of our knowledge, all of the reported work, unless otherwise noted, sustantially complies with approved plans, specifications,
and applicable sections of the building codes. This report covers the locations of the work inspected only and does not constitute engineering pin Ion or project control.
DATE: 10/31/ 18
JURISDICTION: Carlsbad
✓. EsG1I
PLAN CHECK#.: CBR2018-1888 SET II
2..~ un,carn·\:o 'ut-
PROJEcT ADDRESS: 144:.l Panerama Ridge Road
PROJECT NAME: Remodel for the Cuthbert Residence
'.:J APPLICANT
□ JURIS.
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to :
Arlen Roper
EsGil staff did not advise the applicant that the plan check has been completed.
EsGil staff did adv7:·se the plicant that the plan check has been completed.
Person contacted: Al\, Telephone#: 760 522 3996; 760-522-3997
Date contacted: (by:~) Email: arlenroper@gmail.com
Mail Telephone
0 REMARKS:
By: Javier Snider
EsGil
Fax In Person
Enclosures:
10/25/18
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
DATE: 08/ 15/ 18
JURISDICTION: Carlsbad
EsG1I
PLAN CHECK#.: CBR2018-1888 SET: I
'24ulP Ur\,CDrf\,O PROJECT ADDRESS: 1443 Panerama RidgeRwtd
PROJECT NAME: Remodel for the Cuthbert Residence
□ APP LICANT
?JU RIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
1:8] The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
1:8] The applicant's copy of the check list has been sent to:
Arlen Roper
D EsGil staff did not advise the applicant that the plan check has been completed .
1:8] EsGil staff did advise the applicant that the plan check has been completed .
Person contacted:~l:t::N R0P'fR Telephone#: 7'60 522 ~998 -W~(\1\/6*
Datecontacted: gj,~l,JY (by~ Email: arlenroper@gmail.com 7£D-5ZZ-3qq7
E;Mail Fax In Person
REMA
By: Javier Snider
EsGil
08/06/18
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92 123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
Carlsbad CBR2018-1888
08/15/18
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK#.: CBR2018-1888 JURISDICTION: Carlsbad
PROJECT ADDRESS: 1443 Panorama Ridge Road
FLOOR AREA: Existing=4185sf
Enclosed Storage= 143sf
New Deck=l 79sf
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: 08/15/18
FOREWORD (PLEASE READ):
STORIES:
HEIGHT:
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 08/06/18
PLAN REVIEWER: Javier Snider
This plan review is limited to the technical requirements contained in the California version of
the International Residential Code, International Building Code, Uniform Plumbing Code,
Uniform Mechanical Code, National Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the disabled. This plan review is based on
regulations enforced by the Building Department. You may have other corrections based on
laws and ordinance by the Planning Department, Engineering Department, Fire Department or
other departments. Clearance from those departments may be required prior to the issuance of
a building permit.
Present California law mandates that construction comply with the 2016 edition of the California
Code of Regulations (Title 24), which adopts the following model codes: 2015 IRC, 2015 IBC,
2015 UPC, 2015 UMC and 2014 NEC .
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad CBR2018-1888
08/15/18
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad
PREPARED BY: Javier Snider
PLAN CHECK#.: CBR2018-1888
DATE: 08/15/18
BUILDING ADDRESS: 1443 Panorama Ridge Road
BUILDING OCCUPANCY: R-3
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
4185 46.51
143 36.98
179 20.03
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
1997 UBC Building Permit Fee •
1997 UBC Plan Check Fee 3
Type of Review: 0 Complete Review
□ Repetitive Fee ~ Repeats
Comments:
□ Other
0 Hourly
EsGII Fee
Reg.
Mod.
VALUE ($)
194,644
5,288
3,585
203,518
□ Structural Only
$601.11 1
Sheet 1 of 1
Carlsbad CBR2018-1888
08/15/18
PLANS
1. Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted
in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil and the Carlsbad Planning,
Engineering and Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad
Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the
City Planning, Engineering and Fire Departments until review by EsGil is complete.
2. All sheets of plans must be signed by the person responsible for their
preparation. (California Business and Professions Code).
3. Plans deviating from conventional wood frame construction shall have the
structural portions signed and sealed by the California state licensed engineer or
architect responsible for their preparation, along with structural calculations.
(California Business and Professions Code).
4. Note on sheet AS is not legible. Sheet E2 shows CO2, should read CO.
GENERAL RESIDENTIAL REQUIREMENTS
5. Sleeping rooms shall have a window or exterior door for emergency escape.
Section R310. See sheet A4, bedroom #4
a) Windows must have an openable area of at least 5.7 square feet, with the
minimum openable width 20" and the minimum openable height 24".
b) The bottom of the clear opening shall not exceed 44" above the floor.
Do not measure to the window sill. This generally applies to windows that
have a height of 3' or less. See the figure below to see the correct
method of measurement.
Carlsbad CBR2018-1888
08/15/18
c) Such openings shall open directly into a public way or a court that opens
to a public way (4-sided courts are prohibited).
d) If such openings occur at a patio, the patio may not be enclosed.
Appendix H, Section AH103.2.
e) The emergency door or window shall be openable from the inside to
provide a full, clear opening without the use of any keys or tools.
f) For egress openings at window wells, refer to Section R310.2 for
requirements.
EXITS, STAIRWAYS, AND RAILINGS
6. Guards (Section R312): It appears the interior guardrail is being altered and
a new rail is being installed as well, please comply with the following.
a) Shall be installed along open-sided walking surfaces that are located
more than 30" above the floor or grade below.
b) Shall have a height of 42" (may be 34" along the sides of stairs).
c) Openings between railings shall be less than 4". The triangular openings
formed by the riser, tread and bottom element of a guardrail at a stair
shall be less than 6".
d) Shall be detailed to show capability to resist a concentrated load of 200
pounds in any direction along the top rail. Table R301 .5.
7. Handrails (Section R311 .7.8):
Carlsbad CBR2018-1888
08/15/18
a) Shall be provided on at least one side of each stairway with four or more
risers.
b) Handrails and extensions shall be 34" to 38" above nosing of treads and
be continuous.
c) The handgrip portion of all handrails shall be not less than 1-¼ inches nor
more than 2 inches in cross-sectional dimension. See Section R311.7.8.3
for alternatives.
d) Handrails projecting from walls shall have at least 1-½ inches between
the wall and the handrail.
e) Ends of handrails shall be returned or shall have rounded terminations or
bends.
MECHANICAL
8. Show on the plans the location, type and size (Stu's) of all heating and cooling
appliances or systems.
PLUMBING
9. An instantaneous water heater is shown on the plans. Please include a gas pipe
sizing design (isometric or pipe layout) for all gas loads.
a) The gas pipe sizing for a tank type water heater shall be based upon a
minimum 199,000 Btu gas input rating. Energy Standards 150.0(n).
10. Show the shower stall can accommodate a 30" circle and has a minimum floor
area of 1,024 sq. in . CPC Section 408.6.
11. Provide a note on the plans: The control valves in showers, tub/showers,
bathtubs, and bidets must be pressure balanced or thermostatic mixing valves.
CPC Sections 408, 409, 410.
12. Specify on the plans: Water conserving fixtures : New water closets shall use no
more than 1.28 gallons of water per flush, kitchen faucets may not exceed 1.8
GPM, lavatories are limited to 1.2 GPM, and showerheads may not exceed 1.8
GPM of flow. CPC Sections 407, 408, 411, 412.
13. Specify on the plans whether the existing house was built before or after 1994.
For additions or improvements to a residence built before 1994, note on the
plans that existing "noncompliant" fixtures (toilets that use more than 1.6 gallons
of water per flush, urinals that use more than one gallon of water per flush,
showerheads that have a flow capacity of more than 2.5 gallons of water per
minute, and interior faucets that emit more than 2.2 gallons of water per minute)
shall be replaced. Certification of compliance shall be given to the building
inspector prior to final permit approval. California SB407.
Carlsbad CBR2018-1888
08/15/18
14. Include on the Title Sheet of the plans the following statement: "Compliance with
the documentation requirements of the 2016 Energy Efficiency Standards is
necessary for this project. Registered, signed, and dated copies of the
appropriate CF1 R, CF2R, and CF3R forms shall be made available at necessary
intervals for Building Inspector review. Final completed forms will be available for
the building owner."
15. Note or provide the following design requirements for gas water heaters installed
to serve individual dwelling units: ES 150.0(n)
a) Gas piping sizing based upon a minimum input of 200,000 btu/hr.
b) A condensate drain installed no higher than 2" above the base of the
heater that also allows for gravity drainage.
c) The "B" vent installed in a straight position from the room containing the
water heater to the roof termination. (For future possible sleeving for high
efficiency heater venting.)
d) A 120 volt receptacle accessible to the heater installed within 3'.
16. Instantaneous water heaters shall have isolation valves on both the cold and the
hot water piping leaving the water heater complete with hose bibs or other fittings
on each valve for flushing the water heater when the valves are closed. ES 110.3
17. All domestic hot water piping to have the following minimum insulation installed:
½" pipe (1/2" insulation);¾" pipe (1" insulation); 1" to 1-½" pipe (1-½"
insulation). CPC 609.11 & ES 150.0(j)
a) Additionally, the½" hot water pipe to the kitchen sink, and the cold water
pipe within 5' of the water heater both require 1" minimum insulation. ES
150.OG)
Residential Energy Lighting Requirements: ES 150.0(k)
18. In bathrooms, garages, laundry rooms, and utility rooms at least one luminaire
shall be controlled by a vacancy sensor.
19. Recessed can light fixtures shall be IC listed, air-tight labeled, and not be
equipped with a standard medium base screw shell lamp holder. ES 150.0(k)
20. SFD outdoor lighting fixtures that are attached to a building are required to be
high efficacy, be manually on/off switch controlled, and have both motion sensor
and photocell control. See ES 150.0(k) 3 for additional control options.
Residential ventilation requirements: ES 150.0(o)/ASHRAE 62.2
Carlsbad CBR2018-1888
08/15/18
21 . Kitchens require exhaust fans with a minimum 100 cfm ducted to the exterior.
Detail compliance by including a complying exhaust fan or a ducted range hood
to the exterior.
22. Bathrooms require exhaust fans (minimum 50 cfm) to be ducted to the exterior.
A bathroom is defined "as a room with a bathtub, shower, or spa or some similar
source of moisture".
STRUCTURAL
23. Increase in Forces Due to Irregularities for Seismic Design Categories D. For
structures assigned to Seismic Design Category D and having a horizontal
structural irregularity of Type 1a, 1b, 2, 3, or 4 in ASCE 7-10 Table 12.3-1 or a
vertical structural irregularity of Type 4 in Table 12.3-2, the design forces
determined from Section 12.8.1 shall be increased 25 percent for connections of
diaphragms to vertical elements and to collectors and for connections of
collectors to the vertical elements. Collectors and their connections also shall be
designed for these increased forces unless they are designed for the load
combinations with over strength factor of Section 12.4.3.2, in accordance with
ASCE Section 12.10.2.1. Please review and revise structural calculation and
coordinate with plans.
24. A full review of the structural calculations and S sheets will be conducted after
above is resolved .
ELECTRICAL
25. Show on the plan the amperage of the electrical service, the location of the
service panel and the location of any sub-panels. If the service is over 200
amperes, submit a single line diagram, panel schedules, and provide
service load calculations.
MISCELLANEOUS
26. To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
27. Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes □ No □
Carlsbad CBR2018-1888
08/15/18
28 . The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Javier Snider at EsGil. Thank you .