HomeMy WebLinkAbout2525 EL CAMINO REAL; ; AS040069; Permit1/3/25, 3:30 PM
Job Address:
Permit Type:
Parcel No:
Lot#:
Reference No.:
PC#:
Project Title:
Applicant:
AS040069 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS040069
2525 EL CAMINO
Status: ISSUED
REAL
SPRINK Applied 5/17/2004
1563020900 Approved: 6/1/2004
0
Issued: 6/1/2004
Inspector:
LIDS, SPACE 149B FIRE SPRINKLER PLAN CHECK &
INSPECTIONS
Owner:
BRADSHAW ENGINEERING CORP PLAZA CAMINO REAL
8645 ARGENT ST
SANTEE CA
619-448-4300
about:blank
Fees($)
100
Add'I Fees ($)
0
C/O WESTFIELD CORP INC
11601 WILSHIRE BLVD
LOS ANGELES CA
Total($)
100
Balance($)
0
1/1
•
The Concealer®
A Concealed Sprinkler
With½" or 1½" Adjustment
Features
1. ½" Total adjustment provided by economical
standard inlet version.
2. 1½" Total adjustment provided by adjustable
inlet versions.
3. Adjustable inlet version available with either
1" NPT male or female threads eliminating
costly reducing coupling.
4. Simple sturdy cover attachment.
5. Smooth aesthetic ceiling profile.
6. As heat sensitive as an exposed sprinkler.
7. Available in white or other color painted or
brass, chrome, or black plated finishes.
8. Ordinary and intermediate temperature
ratings.
9. Multiple orifices for design flexibility.
1 O. Threaded cover does not require clips or
springs.
11. Listed by Underwriters Laboratories Inc.· and
Underwriters' Laboratories of Canada.
N.Y.C. BS&A No. 587-75-SA.
12. U.S. Patent No. 4,880,063.
Application
The Reliable Model G4
Concealer is the most versatile
concealed sprinkler available.
It provides the best form of fire
protection while offering an at-
tractive appearance and ½
inch of cover adjustment for
ease of installation. The ad-'--------~
justable 1" NPT inlet versions have one and _one half
inches of total adjustment and they also el1m1nate the
need for a reducing coupling. The small diamete_r cover
plate is easily and positively attached and blends into the
ceiling, concealing the most dependable fire protection
available, an automatic sprinkler system.
The Concealer® is designed for J:ISe where aesthetic
appearance is important. Offices, hospitals, motels and
restaurants are but a few of the applications where it can
be used. It is available in different orifice sizes allowing
Bulletin 121G Model G4
Concealed
Automatic
Sprinkler
Aso4oo&9 GJ
the designer to optimize system performance, thereby
achieving a most efficient installation.
The Concealer® can eliminate the need for precise
cutting of drop nipples. The threaded cover plate as-
sembly can be adjusted without tools so 1t mates accu-
rately with the ceiling. The fire protection system need
not be shut down to adjust or remove the cover plate as-
sembly.
Product Description
The Reliable Model G4 Concealer uses the proven
Model G fusible element in a standard style sprinkler
frame with a drop-down deflector. This assembly is re-
cessed into the ceiling and concealed by a flat cover
plate. The cover plate and_sprinkler cup assemblies are
attached using a strong threaded e.igagement. This
threaded engagement provides ½" of cover adjust-
ment. The cover plate is attached to the skirt using an or-
dinary temperature classification solder. This results in a
strong cover plate assembly with an ordinary tempera-
ture rating, and an intermediate temperature sprinkler
which can be installed in 150°F environments. When the
temperature at the ceiling rises, the solder holding the
cover plate fuses, allowing the release of this part and
thus exposing the sprinkler inside to the rising ambient
temperature.
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
•
The subsequent fusing of the sprinkler element opens the
waterway and causes the deflector to drop into position to
distribute the discharging water. Any secure engagement of
the threads between the cover plate and cup will assure that
the drop-down deflector is properly located below the ceil-
ing when a sprinkler operates.
Installation
Do not install The Concealer® in ceilings which have
positive pressure in the space above.
After a 2¾ inch diameter hole is cut in the ceiling, the
sprinkler is to be installed with the Model G4 Wrench. The
wrench has drive tangs which insert into cup slots. When
installing a sprinkler the wrench is first positioned into the
sprinkler/cup assembly until the wrench tangs engage
drive slots in the top of the cup (there are two sets of mat-
ing drive slots in the cup). The sprinkler is then tightened
into the pipe fitting. When inserting or removing the
Standard Temperatures
Classification Sprinkler Cover Plate Max.Celling
Temp.
Ordinary 135°F/57°C 135°F/57°C 100'F/38°C
Ordinary 165°F/74°C 135°F/57°C 100'F/38°C
Ordinary 165°F/74°C 165'F/74°C 100°F/38°C
Intermediate 212°F/100°C 165'F/74°C 150°F/66°C
Installation Data
"K" Factor
wrench from the sprinkler/cup as~embly care should
be taken to prevent damage to the sprinkler. DO NOT
WRENCH ON ANY OTHER PART OF THE SPRIN-
KLER/CUP ASSEMBLY • l •
The adjustable inlet versions are similar to the stan-
dard Model G4 except that an additional 1" of adjust-
ment is provided by means of a· telescoping inlet
section that threads in or out of a stationary coupling
reducer (either 1" male or 1" female) as shown in Fig-
ures 2 or 3. These sprinklers must be installed before
the ceiling is in place, by wrenching on only the cou-
pling reducer hex flats. After the ceiling has been in-
stalled with holes for the sprinkler, each telescoping
inlet section is to be adjusted with the G4 Wrench. Fi-
nal adjustment of each cover is made by hand turning
the cover in the clockwise direction until it is tight
against the ceiling.
Ordering Information
1. Sprinkler Model
2. Temperature Rating
3. Nominal Orifice
4. Cover Plate Finish
5. Inlet Type
Note: Unless otherwise
specified, the 165'F
sprinkler will be provided
with the 165'F cover.
Approval Organizations
1. Underwriters Laboratories. Inc.
2. N.Y.C. BS&A No. 587-75--SA
3. Underwriters' Laboratories of
Canada
Total Nominal Sprinkler Inlet Adjustment Orifice Thread Approvals
Note: Approvals are light and
ordinary hazard, except for small
orifice sprinklers which are limited
to light hazard occupancies. The
cup and skirt are fabricated from
plated steel and are intended for
interior non corrosive applications. us Metric
Non-Adjustable ½" ½" (15mm) 5.62 81.0
Non-Adjustable ½" 1/ie" 4.24 61.0
Non-Adjustable ½" ¾" 2.82 40.6
Adjustable 1½" ½" 5.53 79.7
Adjustable 1½" ¼a" 4.24 61.0
Adjustable 1½" ¾/' 2.72 39.2
½" NPT 1,2,3
YtNPT 1,2,3
;l,'NPT 1,2,3
1" NPT Male or Female 1,2,3
1" NPT Male or Female 1,2,3
1" NPT Male or Female 1,2,3
Installation Wrench
Model G4 Sprinkler Wrench
Cover Plate Finishes
• Bronze
, Bright Brass Plated
, Chrome Plated
• Black Plated
, White
Other colors and finishes
are available, consult
factory for details
'afP«T:J·
~:,-, =,i,,~"1/;;;Jj
v,~:,c• ----;,::)
Note: Paint or any other
coatings applied over the
factory finish will void all
approvals and warranties.
½" NPT Non-Adjustable Inlet
Figure 1
1" NPT Male-Adjustable Inlet
Figure 2
1" NPT Female-Adjustable Inlet
Figure 3
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standar~s of the National Fire Protection Association, Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 70" years, and are installed and serviced by the most highly qualified and
reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc.
Reliabld (800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 668-3470 Corporate Offices Revision lines indicate updated or new data.
www.reliablesprinkler.com Internet Address E.G. Printed in U.SA 4~ PIN 9999970014