Product Description
The Reliable Model G Automatic Sprinkler utilizes the
center strut solder in compression principle of
construction. The fusible alloy is captured in the
cylinder of the solder capsule by a stainless steel ball.
When the fusible alloy melts, the ball moves into the
cylinder allowing the cylinder to fall away from the
sprinkler. When this happens, the lever is released to
spring free from the sprinkler so that all of the operating
parts clear from the waterway allowing the deflector to
distribute the discharging water.
Except for the parts in the cylinder as mentioned
above, the sprinkler components are made from
copper based alloys for maximum corrosion
protection. Lead plated, wax coated or wax over lead
plated sprinklers are available for specially severe
environments. Chrome plated sprinklers are available
for decorative purposes.
All sprinklers are individually hydrostatically tested.
All sprinklers are identified as to their fusing point by
markings that appear on several of the operating parts
and by an identifying color that appears on the frame.
Sprinkler Types
Standard Upright -This deflector configuration is
normally used with exposed piping installations. Water
is distributed laterally and downward in a wide pattern
approximating a hemisphere which is completely and
I uniformly filled with water in the form of small drops or
spray.
Standard Pendent -This deflector configuration is
normally used where the space above the piping is
I limited or where a concealed piping installation is
employed. The discharge characteristics of the
standard pendent are virtually identical to the
standard upright as described above.
Large and Small Orifice-By varying the orifice size,
a large or small orifice sprinkler is created that will
distribute as much as 40% more water or 65% less I water than the normal ½11 (15mm) orifice sprinkler.
Conventional-This deflector configuration is used
primarily in those countries where the LPG installation
rules have precedence, The sprinkler is designed to
distribute a portion of its water discharge upward
against the ceiling with the balance downward. It may
be installed in either the upright or the pendent
position. Sprinklers with conventional deflectors are
available with orifice sizes corresponding to light,
ordinary and extra-high hazard installations.
,,
Bulletin 110 Rev.S
ModelG
Automatic Sprinklers
Spray Upright,
Spray Pendent
And Conventional
Upright Pendent
Small Orifice Upright Conventional
Application and Installation
Standard sprinklers are used in fixed fire protection
systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice sizes, temperature ratings,
deflector styles and sprinkler spacings are in
accordance with the latest published standards of the
National Fire Protection Association or the approving
authority having jurisdiction.
The sprinklers must be installed with the Reliable
Model D Sprinkler Wrench, Any other type of wrench
may damage the sprinkler.
The approvals or listings of Reliable Automatic
Sprinklers by major approving organizations are
shown in the tabulated list provided on the back of this
bulletin.
·Patent No. 4,440,234
The Reliable Automatic Sprinkler Co., Inc., 525 North MacOuesten Parkway, Mount Vernon, New Yark 10552
_..
...I.
0
JJ (D < U)
Technical Data
"K" Factor
Sprinkler Type us
Standarcl-Upright (SSU) and Pendent (SSP)
Deflectors Marked to Indicate Position
Y," (15 mm) Standard Orifice with Y," NPT (A½) Thread 5.62
Xe" (11 mm) Small Orifice with Y," NPT (R,½) Thread 4.24
¾," (10 mm) Small Orifice with X" NPT (RX:) Thread 2.82
1{." (8 mm) Small Orifice with Y," NPT (RY,) Thread 1.98
'½," (20 mm) Large Orifice with Y,'' NPT (RX) Thread 7.96
'½," (20 mm) Large Orifice with¾" NPT (R¾)Thread 8.20
20 mm XHH with 20 mm Thread 8.20
1 O mm XLH with 1 O mm Thread 4.10
Conventional-Installed in Upriqht or Pendent Position
10mm XLH with 10mm Thread 4.10
15mm Standard Orifice with (RY,) Thread 5.62
20mm XHH with (R¾) Thread 8.20
Tern peratu re Rati nqs
Maximum
S~rlnkler Ambient
ating Temperature FrameC1>
Classlflcation "F ·c "F ·c Color
Ordinary 135 57 100 38 Black
Ordinary 165 74 100 38 Uncolored
Intermediate 212 100 150 66 White
High 286 141 225 107 Blue
(1i Frame color does not apply to painted or plated sprinklers
-Use sprinkler rating as identified on operating parts.
Finishes<1l
Standard Finishes
Bronze -All Temperature Ratings
Chro'.11~ -All Temperature Ratings
White l -All Temperature Ratings
Only Frame and Deflector are Painted
Soecial Application Finishes
Metric
81.0
61.0
40.6
28.5
114.7
118,2
118.2
59.1
59.1
81.0
118.2
Sprinkler Identification
Sprinkler Number (SIN}
Height Approvals ssu SSP
2 7/tl 1• (73mm) 1,2,3,4,5,6, 7 R1025 R1015
2¾" (73mm) 1, 3, 7 R1023 R1013
2¾" (73 mm) 1, 2, 3, 7 R1021 R1011 2 °//JI /0 (73 mm) 1, 3, 7 R1022 R1012
2½" (73mm) 1, 2, 3, 7 R1026 R1016
2 ';i{e" (75 mm) 1, 2, 3, 7 R1027 R1017
75.4mm 4,5,6 R1027 R1017
73mm 4,5,6 R1024 R1014
73mm 5 R1074
73mm 4,5,6 R1075
75.4 mm 4,5 R1077
Maintenance
Model G Sprinklers should be inspected quarterly and the
sprinkler system maintained in accordance with NFPA 25. Do
not clean sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove any sprinkler that has been painted
(other than factory applied) or damaged in any way. A stock of
spare sprinklers should be maintained to allow quick replace-
ment of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons and
packaging until used to minimize the potential for damage to
sprinklers that would cause improper operation or
non-Operation. Use only the Model D Sprinkler Wrench for
sprinkler removal and installation. Any other type of wrench may
damage the sprinkler.
Approval Organizations
1. Underwriters Laboratories, Inc.
2. Factory Mutual Research Corporation
3. Underwriters' Laboratories of Canada
4. Loss Prevention Council
5. Pleniere Assemblee
Bright Brass Plated -Only frame, deflector and cap are plated. 135°F (57°C), 165°F
6. VdS Schadenverhutung
7, N.Y.C. BS&A No. 587-75-SA or
N.Y.C. MEA 258-93-E (74°C), 212°F (100°C) Temp. Rating.
Black Plated -Only frame, deflector and cap are plated. All Temp. Ratings.
Polyester Coated l2l -Only frame and deflector are coated.
Lead Plated -165°F (74°C), 212°F (100°C) and 286°F (141°C) Temp. Ratings.
Wax-Coated (3l -165°F (74°C) Clear Wax, 212°F (100°C) Brown Wax.
Wax-Coated Over
Lead Plated (J) -165°F (74°C) Clear Wax, 212°F (100°C) Brown Wax.
(1) Other colors and finishes are available. Consult factory for details.
(2) UL listed and NYC MEA Approved only.
(3) 212°F ( 100°C) brown wax may be used on 286°F ( 141 °C)
sprinklers when maximum ambient temperatures do not exceed 150°F
(66°C). UL Listed, FM Approved, NYC MEA 258-93-E.
Ordering Information
Specify
1. Model G
2. Deflector
• Upright
• Pendent
• Conventional
3. Nominal Orifice
4. Inlet Thread
5. Temperature Rating
6. Finish
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual
Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manulactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualilied and
reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc.
Relialll~ (800) 431-1588 Sales Offices
(BOO) 848-6051 Sales Fax
(914) 668-3470 Corporate Offices Revision lines indicate updated or new data.
www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 11/04 PIN 0099970005
Reliabld
Product Description
The Reliable Model G Automatic Sprinkler utilizes the
center strut solder in compression principle of
construction. The fusible alloy is captured in the
cylinder of the solder capsule by a stainless steel ball.
When the fusible alloy melts, the ball moves into the
cylinder allowing the cylinder to fall away from the
sprinkler. When this happens, the lever ls released to
spring free from the sprinkler so that all of the operating
parts clear from the waterway allowing the deflector to
distribute the discharging water.
Except for the parts in the cylinder as mentioned
above, the sprinkler components are made from
copper based alloys for maximum corrosion
protection. Lead plated, wax coated or wax over lead
plated sprinklers are available for specially severe
environments. Chrome plated sprinklers are available
for decorative purposes.
All sprinklers are individually hydrostatically tested.
All sprinklers are identified as to their fusing point by
markings that appear on several of the operating parts
and by an identifying color that appears on the frame.
Sprinkler Types
Standard Upright -This deflector configuration is
normally used with exposed piping installations. Water
is distributed laterally and downward in a wide pattern
approximating a hemisphere which is completely and
I uniformly filled with water in the form of small drops or
spray.
Standard Pendent -This deflector configuration is
normally used where the space above the piping is I limited or where a concealed piping installation is
employed. The discharge characteristics of the
standard pendent are virtually identical to the
standard upright as described above.
Large and Small Orifice-By varying the orifice size,
a large or small orifice sprinkler is created that will
distribute as much as 40% more water or 65% less I water than the normal½" (15mm) orifice sprinkler.
Conventional-This deflector configuration is used
pr'1marily in those countries where the LPC installation
rules have precedence. The sprinkler is designed to
distribute a portion of its water discharge upward
against the ceiling with the balance downward. It may
be installed in either the upright or the pendent
position. Sprinklers with conventional deflectors are
available with orifice sizes corresponding to light,
ordinary and extra-high hazard installations.
Bulletin 110 Rev.S
ModelG
Automatic Sprinklers
Spray Upright,
Spray Pendent
And Conventional
Upright Pendent
Small Orifice Upright Conventional
Application and Installation
Standard sprinklers are used in fixed fire protection
systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice sizes, temperature ratings,
deflector styles and sprinkler spacings are in
accordance with the latest published standards of the
National Fire Protection Association or the approving
authority having jurisdiction.
The sprinklers must be installed with the Reliable
Model D Sprinkler Wrench. Any other type of wrench
may damage the sprinkler.
The approvals or listings of Reliable Automatic
Sprinklers by major approving organizations are
shown in the tabulated list provided on the back of this
bulletin.
*Patent No. 4,440,234
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
CD C
f :f .....
-I.
0
:0 ;)!
(I)
. '
Technical Data
"K" Factor
Sprinkler Type us
Standard-Upright (SSU) and Pendent (SSP)
Deflectors Marked to I ndlcate Position
;I," (15 mm) Standard Orifice with Y," NPT (RY,) Thread 5.62
1/,,:' ( 11 mm) Small Orifice with };" NPT {R½) Thread 4.24
%" (10 mm) Small Orifice with,½'' NPT (RY,) Thread 2.82
1/,s" (8 mm) Small Orifice with Y," NPT (R,Y,) Thread 1.98
1:1,," (20 mm) Large Orifice with½" NPT (RX:) Thread 7.96
%" (20 mm) Large Orifice with ¾" NPT (R¾)Thread 8.20
20 mm XHH with 20 mm Thread 8.20
1 O mm XLH with 1 O mm Thread 4.10
Conventional-Installed in Uoriaht or Pendent Position
10mm XL..H with 10mm Thread 4.10
15mm Standard Orifice with (RY,) Thread 5.62
20mm XHH with (R¾) Thread 8.20
Temperature Ratinas
Maximum
S~rlnkler Ambient ating Temperature Frame<1>
Classification "F ·c "F •c Color
Ordinary 135 57 100 38 Black
Ordinary 165 74 100 38 Uncolored
Intermediate 212 100 150 66 White
High 286 141 225 107 Blue
Pl Frame color does not apply to painted or plated sprinklers
-Use sprinkler rating as identified on operating parts.
Finishes(1)
Standard Finishes
Bronze -All Temperature Ratings
Chro~~ -All Temperature Ratings
White l -All Temperature Ratings
Only Frame and Deflector are Painted
SDecial ADolication Finishes
Metric
81.0
61,0
40.6
28.5
114.7
118.2
118.2
59.1
59.1
81.0
118.2
Sprinkler Identification
Sprinkler Number (SIN)
Height Approvals ssu SSP
2 ¼" (73mm) 1,2,3,4,5,6, 7 R1025 R1015
2½" (73mm) 1, 3, 7 R1023 R1013
2½" (73mm) 1, 2, 3, 7 R1021 R1011
2 7h' le (73mm) 1,3, 7 R1022 R1012
2½" (73 mm) 1, 2, 3, 7 R1026 R1016
2 1%;' (75mm) 1, 2, 3, 7 R1027 R1017
75.4mm 4,5,6 R1027 R1017
73mm 4 5,6 R1024 R1014
73mm 5 R1074
73mm 4,5,6 R1075
75.4 mm 4, 5 R1077
Maintenance
Model G Sprinklers should be inspected quarterly and the
sprinkler system maintained in accordance with NFPA 25. Do
not clean sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove any sprinkler that has been painted
( other than factory applied) or damaged in any way. A stock of
spare sprinklers should be maintained to allow quick replace-
ment of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons and
packaging until used to minimize the potential for damage to
sprinklers that would cause improper operation or
non-operation. Use only the Model D Sprinkler Wrench for
sprinkler removal and installation. Any other type of wrench may
damage the sprinkler.
I Approval Organizations
1. Underwriters Laboratories, Inc.
2. Factory Mutual Research Corporation
3. Underwriters' Laboratories of Canada
4. Loss Prevention Council 5. Pleniere Assemblee
Bright Brass Plated -Only frame, deflector and cap are plated. 135°F (57°C), 165°F 6. VdS Schadenverhutung
7. N.Y.C. BS&A No. 587-75-SA or
N.Y,C. MEA 258-93-E (74°C), 212°F (100°C) Temp. Rating.
Black Plated -Only frame, deflector and cap are plated. All Temp. Rattngs.
Polyester Coated <21 -On!y frame and deflector are coated.
Lead Plated -16S"F (74°C), 212°F (100°C) and 286°F (141°C) Temp. Ratings.
Wax-Coated l3) -165°F ( 7 4 °C) Clear Wax, 212°F ( 100°C) Brown Wax.
Wax-Coated Over
Lead Plated <3l -165°F (74°C) Clear Wax, 212°F (100°C) Brown Wax.
t1) Other colors and finishes are available, Consult factory for details.
(2) UL listed and NYC MEA Approved only.
13) 212°F (100°C) brown wax may be used on 286°F (141°C)
sprinklers when maximum ambient temperatures do not exceed 150°F
(66°C). UL Listed, FM Approved, NYC MEA 258-93-E
Ordering Information
Specify
1. Model G
2. Deflector
• Upright
• Pendent
• Conventional
3. Nominal Orifice
4. Inlet Thread
5. Temperature Rating
6. Finish
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Assoc1ation, Factory Mutual
Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and
reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc.
Reliable (BOO) 43H588 Sales Offices
(800) 848-6051 Sales Fax
(914) 668-3470 Corporate Oftices Revision lines indicate upda1ed or new data.
www.,eliab1espr,nkleccom Internet Address EG P,n!ed in U.SA 11,!)4 P/N 999997(XXJ5