HomeMy WebLinkAbout2480 IMPALA DR; ; CBC2022-0238; PermitBuilding Permit Finaled
{"Cityof
Carlsbad
Commercial Permit
Print Date: 03/17/2025
Job Address:
Permit Type:
Parcel#:
Valuation:
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Occu pant Load:
Code Edition:
Sprinkled:
Project Title:
2480 IMPALA DR, CARLSBAD, CA 92010-7226
BLDG-Commercial Work Class:
2090502600 Track#:
$0.00 Lot#:
Project#:
Plan#:
Construction Type:
Orig. Plan Check #:
Plan Check#:
Cogen
Permit No:
Status:
Applied:
Issued:
CBC2022-0238
Issued -Active
07/01/2022
10/05/2022
Finaled Close Out:
Final Inspection: 11/29/2023
INSPECTOR: Alvarado, Tony
Description: CARLSBAD FLEET SERVICES: ELECTRICAL UPGRADES AND INSTALLATION OF 2 CHARGING STATIONS
FEE
BUILDING PLAN CHECK
Total Fees: $267.80
Property Owner:
CITY OF CARLSBAD
CURTIS JACKSON
1200 CARLSBAD VILLAGE DR
CARLSBAD, CA 92008-1989
(760} 434-2836
Tot al Payments To Date: $0.00
Contractor:
AM ORTEGA CONSTRUCTION INC
10125 CHANNEL RD
LAKESIDE, CA 92040-1703
(619} 390-1988
Balance Due:
AMOUNT
$267.80
$267.80
Please take NOTICE that approval of your project includes t he "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a}, and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Building Division Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 442-339-2719 I 760-602-8560 f I www.carlsbadca.gov
...
( City of
Carlsbad
COMMERCIAL
BUILDING PERMIT
APPLICATION
B-2
Plan Check ce:zOcZ..,-0232.)
Est. Value
PC Deposit ¾7, KD
Date ::{-\ -· 2..:6
Job Address 2480 IMPALA DRIVE, CARLSBAD, CA 92010
Tenant Name#: CARLSBAD FLEET SERVICES
Suite: _____ .APN: ___________ _
Lot #: ____ Vear Built: _________ _
Year Built: __ _ Occupancy: __ _ Construction Type: __ _ Fire sprinklers@'ESONO A/C:€}YESQNO
BRIEF DESCRIPTION OF WORK: INSTALL (1) TERMINATOR, (1) 2500KVA TRANSFORMER, (1) 4000A SWITCHGEAR, AND (2) DC FAST ELECTRIC
VEHICLE CHARGERS. ALSO INSTALLING (1) CONCRETE ISLAND (58'X15) TO HOLD NEW TRANSFORMER & SWITCHGEAR.
D Addition/New: ____________ New SF and Use, __________ .New SF and Use
______ SF Deck, SF Patio Cover, SF Other (Specify) ___ _
~Tenant Improvement: _87_0 ____ SF, Existing Use: _P_A_RK_IN_G _____ Proposed Use: EV CHARGING
_____ SF, Existing Use: Proposed Use: ______ _
D Pool/Spa: _____ SF Additional Gas or Electrical Features? ____________ _
D Solar: ___ KW,. ___ Modules, Mounted:ORoof OGround
D Re roof: _____________________________________ _
~ Plumbing/Mechanical/Electrical ELECTRICAL IMPROVEMENTS REQUIRED TO ACCOMO
D Other:--------------------------------------
PRIMARY APPLICANT
Na me: Martin Paul (Asplundh Construction)
Address: 3574 Ruffin Rd
PROPERTY OWNER
Name: City of Carlsbad
City: San Diego
Phone: 714-737-7388
State:_c_A __ .Zip: 92123
Address: 1200 Carlsbad Village Drive
City: Carlsbad State:_c_A __ .Zip: 92000
Phone: 760-434-2020
Email: mpaul99@asplundh.com Email: help@carlsbadca.gov
DESIGN PROFESSIONAL CONTRACTOR OF RECORD
Name: Business Name: AM Ortega Construction, Inc. ------------------Address: Address: 10125 CHANNEL RD
City: ________ .State: ___ Zip: _____ City: Lakeside State:_c_A __ Zip: 92040
Phone: Phone: 619-390-1988
Email: Email: ESTIMATING@AMORTEGA.COM
Architect State License: CSLB License #:_4_86_3_11 ______ Class:_a ______ _
Carlsbad Business License# (Required):_B_Lo_s_1_20_8_59_4 ___ _
APPLICANT CERT/FICA TION: I certify that I have read the application and state that the above information is correct and that the
information on the plans is accurate. I agree to comply with all City ordinances and State laws relating to building
construction.
NAME (PRINT): Edgar Bautista SIGN:
1635 Faraday Ave Carlsbad, CA 92008 Ph: 442-339-2719 Fa><: 760-602-8558
llgnedb'l'E.S.U-. lnk)•~•~-com . 202'l 01123 06:25:31-0T'OO DATE: 06/23/2022
Email: Building@carlsbadca.gov
REV. 07/21
THIS PAGE REQUIRED AT PERMIT ISSUANCE PLAN CHECK NUMBER: ______ _
A BUILDING PERMIT CAN BE ISSUED TO EITHER A STATE LICENSED CONTRACTOR OR A PROPERTY OWNER. IF THE PERSON
SIGNING THIS FORM IS AN AGENT FOR EITHER ENTITY AN AUTHORIZATION FORM OR LETTER IS REQUIRED PRIOR TO
PERMIT ISSUANCE.
(OPTION A): LICENSED CONTRACTOR DECLARATION:
I herebyaffirmunderpenaltyof perjury that I am licensed under provisions of Chapter 9 (commencing with Section 7000) of Division]
of the Business and Professions Code, and my license is in full force and effect. I also affirm under penalty of perjury one of the
following declarations(CHOOSE ONE}:
D1 have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the Labor Code, for the performance of the
work which this permit is issued. Policy No. _____________________________________ _
-OR-
(!]1 have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
My workers' compensation insurance carrier and policy number are: Insurance Company Name: _A1_••-"'-'"'_"•_nc_•_se,v1c_ .. _. ,_nc_. _____________ _
Policy No. 543o32,5 Expiration Date: _101_0_112_022 _____________ _
-OR-
Ocertificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become
subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage is unlawful and shall subject an employer to
criminal penalties and civil fines up to $100,000.00, in addition the to the cost of compensation, damages as provided for in Section 3706 of the Labor Code,
interest and attorney's fees.
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name:. ____________________ .Lender's Address: ___________________ _
CONTRACTOR CERTIFICATION: I certify that I have read the application and state that the above information is correct and that
the information on the plans is accurate. I agree to comply with all City ordinances and State laws relating to building
construction.
NAME (PRINT): Edgar Bautista SIGNATURE:
ign&d by Edgar Bautista
• DATE: 06/23/2022
Note: If the person signing above is an authorized agent for the contractor provide a letter of authorization on contractor letterhead.
-OR -
(OPTION B): OWNER-BUILDER DECLARATION:
I hereby affirm that I am exempt from Contractor's License Law for the following reason: n I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec.
7o'44, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does such
work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold
within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
-OR-
D1, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects wit h contractor(s) licensed
pursuant to the Contractor's License Law).
-OR-□1 am exempt under Business and Professions Code Division 3, Chapter 9, Article 3 for this reason:
AND, D FORM 8-61 "Owner Builder Acknowledgement and Verification Form" is required for any permit issued to a property owner.
By my signature below I acknowledge that, except for my personal residence in which I must have resided for at least one year prior to completion of the
improvements covered by this permit, I cannot legally sell a structure that I have built as an owner-builder if it has not been constructed in its entirety by licensed
contractors./ understand that a copy of the applicable law, Section 7044 of the Business and Professions Code, is available upon request when this application is
submitted or at the following Web site: http://www.leginfo.ca.gov/calaw.html.
OWNER CERT/FICA TION: I certify that I have read the application and state that the above information is correct and that the
information on the plans is accurate. I agree to comply with all City ordi nonces and State laws relating to bui [ding
construction.
NAME {PRINT): SIGN: __________ DATE: ______ _
Note: If the person signing above is an authorized agent for the property owner include form 8-62 signed by property owner.
1635 Faraday Ave Carlsbad, CA 92008 Ph: 442-339-2719 Fax: 760-602-8558 Email: Building@carlsbadca.gov
2 REV. 07/21
{ City of
Carlsbad
Non-residential
EV Charging
B-65C
Development Services
Building Division
1635 Faraday Avenue
442-339-2719
www .carlsbadca.gov
NON-RESIDENTIAL ELECTRICAL VEHICLE CHARGING STATIONS EXPEDITED REVIEW
ELIGIBILITY CHECKLIST
GENERAL
The purpose of this checklist is to determine eligibility and clarify the minimum building code requirements when
preparing plans and documents for expedited plan review of EV charging stations in compliance with Carlsbad
Municipal Code Chapter 18.22 and Government Code Section 65850.7. as amended by AB1236 in 2015.
Type of Charging Station(s) Power Levels (proposed circuit rating) Check One
Level 1 110/120 volt alternating current (VAC) at 15 or 20 Amps □
Level 2 -3.3 kilowatt (Kw) (Low) 208/240 VAC at 20 or 30 Amps D
Level 2 -6.6 kW (medium) 208/240 VAC at 40 Amps D
Level 2 -9.6 kW (high) 208/240 VAC at 50 Amps D
Level 2 -19.2 Kw (highest) 208/240 VAC at 100 Amps D
Other (provide detail): Provide rating: a
DCFC -62.5 kW 480/277V VAC at 100 Amps
Permit Application Requirements:
A. Does the application include EVCS manufacture's specs and installation guidelines? 0Y ON
Electrical Load Calculation Worksheet:
A. Is an electrical load calculation worksheet included? (CEC 220) 0Y ON
B. Based on the load calculation worksheet, is a new electrical service panel upgrade DY []] N
required?
1) If yes, do plans include electrical service panel upgrade? □Y □N
C. Is the charging circuit appropriately sized for a continuous load of 125%? []] y □N
D. If charging equipment proposed is a Level 2 -9 kW station with a circuit rating of 50 amps EJY DN
or higher, is a completed circuit card with electrical calculations included with the single line
diagram?
Site Plan and Single Line Drawing:
A. Is a site plane and separate electrical plan with single-line diagram included with the permit m Y ON
application?
1) If mechanical ventilation requirements are triggered for indoor venting requirements DY []] N
(CEC 625,29 {D}), is mechanical plan included with the permit application?
□ □
1
8. Is the site fully dimensioned and drawn to scale? Iii y O N
1) Showing location, size, and use of all structures [Ely □N
2) Showing location of electrical panel to charging system [Ely □N
3) Showing type of charging system and mounting [Ely □N
Compliance with the 2019 California Electrical Code:
A. Does the application include EVCS manufacture's specs and installation guidelines? [Ely □N
8. Does the electrical plan identify the amperage and location of existing electrical service DY IT! N
panel?
1) If yes, does the existing panel schedule show room for additional breakers? DY □N
C. Is the charging unit rated more than 60 amps or more than 150 V to ground? [Ely □N
1) If yes, are disconnecting mean provided in a readily accessible location in line of site [Ely □N
and within 50' of EVCS. (CEC 625.23)
D. Does the charging equipment have a Nationally Recogn ized Testing Laboratory (NRTL) @Y □N
approved listing mark? (UL 2202/UL 2200)
E. If trenching is required, is the trenching detail called out? lEIY ON
1) Is the trenching in compliance with electrical feeder requirements from structure to @Y □N
structure? (CEC 225)
2) Is the trenching in compliance with minimum cover requirements for wiring methods or @Y □N
circuits? (18" for direct burial per CEC 300)
Compliance with 2019 California Green Building Standards Code (CGBSC}:
A. Does the CAL Green EV Readiness installation requirements apply to this project? NO
1) Do the plans demonstrate conformance with CGBSC Table 5.106.5.3.3 for the minimum DY □N
required number of charging spaces?
2) Do the construction plans comply with the design requirements set forth in CGBSC DY □N
5.106.5.3.1 for single charging spaces or CGBSC 5.106.5.3.2 for multiple charging spaces?
Compliance with 2019 California Building Code, Chapter 11-B Accessibility Features:
A. Do the plans clearly depict al required accessible EVCS features for the disabled? DY [El N
1) Do the plans identify the correct number and type of accessible EVCS stalls required in DY IT! N
accordance with Table 118-228.3.2.1?
2) Do the plans detail compliance with the accessible EVCS features required by CBC 118-DY IT! N
812 and Figure 118-812.9?
Project Address: 2480 IMPALA DRIVE, CARLSBAD, CA 92010
Applicant Signature: _Mi_~_'RTl_l N_?i_~_()._'l _____________________ _
Applicant's Printed Name/Date: MARTIN PAUL 6/20/2022
2
,. • ♦ •
INSTRUCTIONS
Information provide in this document is general and intended as a guide only. Each project is unique and
additional requirements may be enforced as deemed appropriate.
This checklist is intended for an expedited EVCS permitting process. Submit electronically on the City's website
or submit (2) sets of hard copy plans minimum 11" x 17" or larger. To submit electronic plans on the City's
website you must submit a permit application on line and upload plans at: building@carlsbadca.gov Please
complete this form by checking the appropriate boxes based on information presented on the plans and
supporting documentation. If any items are checked "NO", please revise plans to comply with the eligibility
checklist. Otherwise, the permit application may go through the standard plan review and approval process.
In most cases, expedited plan review will be performed over the counter hours or it may take up to 10 business
days to complete expedited review for large and/or complex projects. Building counter staff will determine
eligibility for over the counter ex pedited review at the time of building permit application.
PERMIT FEES
Permit fees will be in accordance with current Adopted Fee Schedule. Please contact Building Division
Technicians for additional information.
INSPECTION PROCEDURES
One inspection is required after the new wiring and charger unit is installed. However, additional inspections
may be required depending on the scope of work. The building inspector will let you know if there are
additional inspections. For each inspection, the Permit Card and Approved Owner Copy ofthe plans must be
presented to the inspector. The manufacture's installation guidelines shall be available for the building
inspector at the job site during the inspection as well. A representative of the installing contractor must be on-
site for all inspections.
Permits shall become invalid unless the work authorized by such permit is commenced within 180 days after
its issuance.
To schedule an inspection, use the Building Division Online Inspection Request HERE or contact the
Building Division at 442-339-2725.
3
PERMIT INSPECTION HISTORY for (CBC2022-0238)
Permit Type: BLDG-Commercial
Work Class: Cogen
Status:
Scheduled
Date
Closed -Finaled
Actual Inspection Type
Start Date
Checklist Item
Application Date: 07/01/2022 Owner: CITY OF CARLSBAD
Issue Date: 10/05/2022 Subdivision: RANCHO AGUA HEDIONDA POR
OF
Expiration Date: 02/26/2024 Address: 2480 IMPALA DR
CARLSBAD, CA 92010-7226 IVR Number: 41712
Inspection No. Inspection Primary Inspector Reinspection Inspection
Status
COMMENTS Passed
BLDG-Building Deficiency 1 . New electrical power service electrical
vehicle charging stations-switchgear 4000
amp.
Yes
11/29/2023 11/29/2023 BLDG-Final Inspection
Checklist Item
BLDG-Structural Final
BLDG-Electrical Final
Monday, March 17, 2025
2. Verified all grounding; wire size,
grounding type, torqued down all
lugs-verified.
3. Switchgear cabinet anchoring system to
ew concrete pad -OK.
4. Underground Steel rebar reinforcement
foundation system -verified per engineer's
plans and detail specifications -approved.
231701-2023
COMMENTS
Passed
November 29, 2023:
Tony Alvarado
1. fleet services, location, switchgear
(new), for electrical vehicle charging
systems (EV), per electrical engineers
plans of detail specifications -approved.
November 29, 2023:
1. fleet services, location, switchgear
(new), for electrical vehicle charging
systems (EV), per electrical engineers
plans of detail specifications -approved.
Complete
Passed
Yes
Yes
Page 2 of 2
Building Permit Inspection History Finaled
{cityof
Carlsbad
Permit Type:
Work Class:
Status:
Scheduled
Date
08/28/2023
PERMIT INSPECTION HISTORY for (CBC2022-0238)
BLDG-Commercial
Cogen
Closed -Finaled
Actual Inspection Type
Start Date
08/28/2023 BLDG-11
Foundation/Ftg/Piers
(Rebar)
Checklist Item
Application Date: 07/01/2022
Issue Date: 10/05/2022
Expiration Date: 02/26/2024
IVR Number: 4171 2
Inspection No. Inspection
Status
222238-2023 Passed
COMMENTS
Owner: CITY OF CARLSBAD
Subdivision: RANCHO AGUA HEDIONDA POR
OF
Address: 2480 IMPALA DR
CARLSBAD, CA 92010-7226
Primary Inspector Reinspection Inspection
Tony Alvarado Complete
Passed
BLDG-Building Deficiency 1. New electrical power service electrical
vehicle charging stations-switchgear 4000
amp.
Yes
BLDG-31
Underground/Conduit •
Wiring
Checklist Item
2. Verified all grounding; wire size,
grounding type, torqued down all
lugs-verified.
3. Switchgear cabinet anchoring system to
ew concrete pad -OK.
4. Underground Steel rebar reinforcement
foundation system -verified per engineer's
plans and detail specifications -approved.
Pending:
(a) final electrical inspection for completed
and installed EV charging systems.
(b) Informed Contractor representative.
222237-2023 Passed Tony Alvarado
COMMENTS
BLDG-Building Deficiency 1. New electrical power service electrical
vehicle charging stations-switchgear 4000
amp.
BLDG-34 Rough
Electrical
2. Verified all grounding; wire size,
grounding type, torqued down all
lugs-verified.
3. Switchgear cabinet anchoring system to
ew concrete pad -OK.
4. Underground Steel rebar reinforcement
foundation system -verified per engineer's
plans and detail specifications -approved.
Pending:
(a) final electrical inspection for completed
and installed EV charging systems.
(b) Informed Contractor representative.
222051-2023 Passed Tony Alvarado
Complete
Passed
Yes
Complete
Monday, March 17, 2025 Page 1 of 2
1'.,rue North
COMPLIANCE SERVICES
September 23, 2022
City of Carlsbad
Community Development Department -Building Division
1635 Faraday Ave.
City of Carlsbad -FINAL REVIEW
City Permit No: CBC2022-0238
True North No.: 22-018-065
Carlsbad, CA 92008
Plan Review: EV Charging Stations
Address: 2480 Impala Dr, Carlsbad, CA
Applicant Name: Martin Paul
Applicant Email: mpaul99@asplundh.com
OCCUPANCY AND BUILDING SUMMARY:
Occupancy Groups: NI A
OccupantLoad:NIA
Type of Construction: NIA
Sprinklers: NI A
Stories: NI A
Area of Work (sq. ft.): NIA sq. ft.
The plans have been reviewed for coordination with the permit application.
Valuation: Confirmed
Scope of Work: Confirmed
Floor Area: Confirmed
Attn: Building & Safety Department,
True North Compliance Services, Inc. has completed the final review of the following documents for the project
referenced above on behalf of the City of Carlsbad:
l.
2.
Drawings: One (1) copy dated September 7, 2022, by Asplundh Construction.
Load Study: One (1) copy dated March 30, 2022.
The 2019 California Building, Mechanical, Plumbing, and Electrical Codes (i.e., 2018 IBC, UMC, UPC, and 2017
NEC, as amended by the State of California), 20 I 9 California Green Building Standards Code, 2019 California
Existing Building Code, and 2019 California Energy Code, as applicable, were used as the basis of our review.
Please note that our review has been completed and we have no further comments.
We have enclosed the above noted documents bearing our review stamps for your use. Please call if you have any
questions or if we can be of further assistance.
Sincerely,
True North Compliance Services
Review By: Doug Gallagher -Plans Examiner
True North Compliance Services, Inc.
3939 Atlantic Avenue Suite 116, Long Beach, CA 90807
T / 562. 733.8030
Transmittal Letter
August 25, 2022
City of Carlsbad
Community Development Department -Building Division
1635 Faraday Ave.
Carlsbad, CA 92008
Plan Review: EV Charging Stations
Address: 2480 Impala Dr., Carlsbad CA
Applicant Name: Martin Paul
Applicant Email: mpaul99@asplundh.com
True North
COM PLIANCE SE RVICES
SECOND REVIEW
City Pennit No: CBC2022-0238
True North No.: 22-018-065
True North Compliance Services, Inc. has completed the second review of the following documents for the project
referenced above on behalf of the City of Carlsbad:
1. Drawings: Electronic copy by Asplundh Planning.
2. Load Study: Electronic copy.
Attn: Permit Technician, the plans have been reviewed for coordination with the pennit application. See below
for additional information:
Valuation:
Scope of Work:
Floor Area:
See Notes Below
Confirmed
Confirmed
Notes: Valuation not included on the pennit application. Based on the PC deposit, the valuation appears
to be low for the scope of work proposed.
Our comments follow on the attached list. Please call if you have any questions or if we can be of further
assistance.
Sincerely,
True North Compliance Services
Review By: Jonah Glen -Plans Examiner
True North Compliance Services; Inc.
3939 Atlantic Avenue Suite 116, Long Beach, CA 90807
T / 562.733.8030
EV Charging Stations
2480 Impala Dr.
August 26, 2022
RESUBMITTAL INSTRUCTIONS:
City of Carlsbad-SECOND REVIEW
City Permit No.: CBC2022-0238
True North No.: 22-018-065
Page2
Plan Review Comments
Deliver THREE corrected sets of plans and TWO corrected calculations/reports directly to the City of
Carlsbad Building Division, 1635 Faraday Ave., Carlsbad, CA 92008, (442) 339-2719. The City will route the
plans to True North, Planning and Land Development Engineering Departments (if applicable) for continued
review.
Note: If this project requires FIRE PREVE~TION review, ensure that you follow their specific instructions
for resubmittal review. The City will not route plans back to Dennis Grubb & Associates for continued Fire
Prevention review.
GENERAL NFORMATION:
A. The following comments are referred to the 20 I 9 California Building, Mechanical. Plumbing, Electrical
Codes, California Green Building Standards Code, and Energy Code (i.e., 2018 IBC, UMC, UPC, and 2017
NEC, as amended by the State of California).
B. There may be other comments generated by the Building Division and/or other City departments that will
also require your attention and response. This attached list of comments, then, is only a portion of the plan
review. Contact the City for other items.
C. Respond in writing to each comment by marking the attached co1mnent list or creating a response letter.
Indicate which details, specification, or calculation shows the required information. Your complete and
clear responses will expedite the re-check.
D. Please be sure to include the architect and engineer's stamp and signature on all sheets of the drawings and
on the coversheets of specifications and calculations per CBPC 5536.1 and CBPC 6735. This item will be
verified prior to plan approval.
OCCUPANCY & BUILDING SUMMARY:
Occupancy Groups: N/A
Occupant Load: N/A
Type of Construction: N/ A
Sprinklers: NIA
Stories: NIA
Area of Work (sq. ft.): NIA
ARCHITECTURAL COMMENTS:
Al. Please provide an overall site plan showing to scale the size and location of new construction and existing
structures on the site, distances from property lines, and the street in respect to the property. CBC 107.2.6
PC1: Comment above not addressed. The google maps Image provided does not address comment above.
The exact location of proposed work was not shown on site plan. Please provide a full site plan clarifying
location of proposed work.
EV Charging Stations
2480 Impala Dr.
August 26, 2022
ACCESSIBILITY COMMENTS:
No comments.
MECHANICAL COMMENTS:
No comments.
ELECTRICAL COMMENTS:
No comments.
PLUMBING COMMENTS:
No comments.
GREEN BUILDING COMMENTS:
No comments.
ENERGY COMPLIANCE COMMENTS:
No comments.
STRUCTURAL COMMENTS:
No comments.
City of Carlsbad-SECOND REVIEW
City Permit No.: CBC2022-0238
True North No.: 22-018-065
Page3
If you have any questions regarding the above comments, please contact Jonah Glen for plan review comments
via email (ionahg@tncservices.com) or telephone (5 10) 415-6942.
[END)
I
Transmittal Letter
July 21, 2022
City of Carlsbad
Community Development Department -Building Division
1635 Faraday Ave.
Carlsbad, CA 92008
Plan Review: EV Charging Stations
Address: 2480 Impala Dr., Carlsbad CA
Applicant Name: Martin Paul
Applicant Email: mpauJ99@asplundh.com
Tn1eNorth
COMPLI ANCE SERVICES
FIRST REVIEW
City Pennit No: CBC2022-0238
True North No.: 22-018-065
True North Compliance Services, Inc. has completed the first review of the following documents for the project
referenced above on behalf of the City of Carlsbad:
1. Drawings: Electronic copy dated June 16, 2022, by Asplundh Planning.
2. Load Studv: Electronic copy.
Attn: Permit Technician, the plans have been reviewed for coordination with the permit application. See below
for additional information:
Valuation:
Scope of Work:
Floor Area:
See Notes Below
Confirmed
Confirmed
Notes: Valuation not included on the permit application. Based on the PC deposit, the valuation appears
to be low for the scope of work proposed.
Our comments follow on the attached list. Please call if you have any questions or if we can be of further
assistance.
Sincerely,
True North Compliance Services
Review By: Jonah Glen -Plans Examiner
True North Compliance Services, Inc.
3939 Atlantic Avenue Suite 116, Long Beach, CA 90807
T / 562.733.8030
EV Charging Stations
2480 Impala Dr.
July 21, 2022
RESUBMITTAL INSTRUCTIONS:
Plan Review Comments
City of Carlsbad-FIRST REVIEW
City Pennit No.: CBC2022-0238
True North No.: 22-018-065
Page 2
Deliver THREE corrected sets of plans and TWO corrected calculations/reports directly to the City of
Carlsbad Building Division, 1635 Faraday Ave., Carlsbad, CA 92008, (442) 339-2719. The City will route the
plans to True North, Planning and Land Development Engineering Departments (if applicable) for continued
1·eview.
Note: If this project requires FIRE PREVENTION review, ensure that you follow their specific instructions
for resubmittal review. The City will not route plans back to Dennis Grubb & Associates for continued Fire
Prevention review.
GENERAL INFORMATION:
A. The following comments are referred to the 2019 California Building, Mechanical, Plumbing, Electrical
Codes, California Green Building Standards Code, and Energy Code (i.e., 2018 me, UMC, UPC, and 2017
NEC, as amended by the State of California).
B. There may be other comments generated by the Building Division and/or other City departments that will
also require your attention and response. This attached list of comments, then, is only a portion of the plan
review. Contact the City for other items.
C. Respond in writing to each comment by marking the attached comment list or creating a response letter.
Indicate which details, specification, or calculation shows the required infonnation. Your complete and
clear responses will expedite the re-check.
D. Please be sure to include the architect and engineer's stamp and signature on all sheets of the drawings and
on the coversheets of specifications and calculations per CBPC 5536.1 and CBPC 6735. This item will be
verified prior to plan approval.
OCCUPANCY & BUILDING SUMMARY:
Occupancy Groups: NI A
Occupant Load: NIA
Type of Constrnction: NI A
Sprinklers: NIA
Stories: NI A
Area of Work (sq. ft.): NIA
ARCHITECTURAL COMMENTS:
Al. On the cover sheet of the plan, provide the following building data:
a) Occupancy Group(s) of the building in accordance with CBC 302.
b) Provide a clear scope of work indicating the full extent of work within the property lines per CBC
107.2.1.
c) Please clarify the extent of work to be completed by SDG&E.
d) Multiple notes on the plans refer to utility drawings, which appear not to have been provided. Please
provide utility plans for review.
EV Charging Stations
2480 Impala Dr.
City of Carlsbad-FIRST REVIEW
City Pem1it No.: CBC2022-0238
True North No.: 22-018-065
Page 3
July 21, 2022
A2. Please provide an overall site plan showing to scale the size and location of new construction and existing
structures on the site, distances from property lines, and the street in respect to the property. CBC 107.2.6
A3. As the proposed improvements include work in the public right of way, please coordinate with the
Engineering Department for encroachment permits.
ACCESSIBILITY COMMENTS:
D 1. Accessibility information was not provided. Please address the following:
a) Clarify the intended use of the proposed EVCS .
b) If EVCS will be accessible to the public, provide enlarged plans, details, and notes to show
compliance with CBC Chapter 1 l B as indicated below. Additional comments may apply.
i) Provide details for the accessible EVCS. This includes the following:
(1) Show the flat ground surfaces per CBC 1 lB-812.3 for both the vehicle space and
access aisle.
(2) Vertical clearance per CBC 1 lB-812.4.
(3) Provide details showing the width and marking of the required accessible EVCS.
Per CBC 118-812.6, the van accessible shall be 144 inches wide, 108 inches for
standard, and 120 inches for ambulatory.
(4) Please show the required access aisles including their location, marking, and
lettering per CBC l lB-812. 7. (An access aisle is not required for the ambulatory
EVCS.)
(5) Provide details for surface marking of all accessible EVCS per CBC l lB-812.9.
ii) Clarify the location of the accessible EVCS on the plans. Verify that an accessible route
has been provided to the building entrance per CBC l lB-812.5.1.
( 1) Per CBC l lB-812.5 .2, provide a detail showing the location of the EV Charger
and verify an accessible route is provided from the vehicle to the charger.
(2) Per CBC l lB-812.5.3 verify that barriers will be provided to prevent the vehicle
from interfering with the accessible routes.
(3) The accessible route is not permitted, by CBC 1 lB-812.5.4, to pass behind other
vehicles for the van or standard accessible EVCS .
(4) Per CBC l lB-812.5.5 the charging cables cannot interfere with the required
accessible route.
iii) Per CBC 1 lB-812.8 .3 please provide information for accessible signage for the van and
standard accessible EVCS.
MECHANICAL COMMENTS:
No comments.
ELECTRICAL COMMENTS:
E 1. Sheet 2 of 9: Please clarify how the existing gas and electrical lines will be protected at new trenching in
the area of work.
. ...
EV Charging Stations
2480 Impala Dr.
July 21, 2022
PLUMBING COMMENTS:
No comments.
GREEN BUILDING COMMENTS:
No comments.
ENERGY COMPLIANCE COMMENTS:
No comments.
STRUCTURAL COMMENTS:
S 1. Provide anchorage details for the proposed EVCS.
S2. Provide anchorage details for new transfonner and electrical panel.
City of Carlsbad-FIRST REVIEW
City Pennit No.: CBC2022-0238
True North No.: 22-018-065
Page -I
If you have any questions regarding the above comments, please contact Jonah Glen for plan review comments
via email Uonahg@tncservices.com) or telephone (510) 415-6942.
[END]
ARCIDTECTURAL COMMENTS:
Al. Please provide an overall site plan showing to scale the size and location of new construction and
existing structures on the site, distances from property lines, and the street in respect to the property.
CBC 107.2.6
PC2: Comment above not addressed. The google maps image provided does not address comment
above. The exact location of proposed work was not shown on site plan. Please provide a full site
plan clarifying location of proposed work.
A 1. PC2: Added new site plan to cover sheet detailing to scale the entire property with
existing structures, property lines, and area of work. Also added additional dimension lines from
property lines on design sheets.
SEP I 9 ZDZZ
Version 1.1 JUL O 1 2022
FR22-0121 REVISED
LOAD STUDY --FUSING REQUEST --DISTRIBUTION PLANNING WORKSHEEfi1TY OF CARLSBAD
GENERAL INFORMATION BUILDING DIVISION
IN-SERVICE DATE: 12/31/2022
SUPERCEDES LOAD STUDY DATED: TODA Y'S DATE: 3/30/2022
JOB# 300000393485 !Planner RUBEN RUIZ
PN # 300000393337 !Phone# 714-812-6238 T.B. 1127-E1
Project title MD190021 -CITY OF CARLSBAD
Address 2480 IMPALA DRIVE, CARLSBAD, CA 92010
Cross Street ORION ST DFIS Pg#
Type of project: CLEAN TRANSPORT!# of lots/units/meters SQ. Ftq of Lots/Units
Developer / Contact Name Phone#
Substation PALOMAR AIRPORT Station# Struct. ID# D162768
Circuit 586 Panel # 1 Size: NIA
Construction & Operations Center: NC Panel # 2 Size: N/A
LOAD STUDY REQUEST
EXISTING CUSTOMER LOAD: Demand
DESCRIPTION OF LOAD kW DEMAND
CUSTOMER LOAD BEING ADDED: Connected Primary Voltage 12 kV
Proposed XFMR Sizes: 2500 And Secondary Voltage 277/480
DESCRIPTION OF LOAD kW DEMAND
Load range from super data book kW High Demand from CISCO if available kW
Motors: No Total Motor Load HP Largest Motor HP
starts per: N/A Power Factor:
Motor Types : N/A Multiple Motors -Simultaneous Starts: No
DISTRIBUTION WORK FLOW & PLANNING:
DWP Estimated Demand: kW
Limit inrush to: kVA starts per:
REMARKS:
Tech. Senior Approval Dist Ping Eng Phone# Date
FUSING REQUEST
JN#: 300000393485 REF#: 31
Neutral Source: None Boosted: No
Load Balance Table
Fae# Fuse Cabinet: No Largest X y z 3 Total KVA
CP/Fuse Cabinet Location XFMR Phase Added
New 200A TERMINATOR Existinq
0239560 Addinq
New Existinq
0239561 Addinq 2059 2059 2059
Exist Existinq
Addinq
New Existinq
Adding
Fault Indicator Req'd: No Size:
Cable Pole# Existing fused (@ OK
Change From: to:
Install D162768 CMPT 4 Fused av.
fuse cab: install: change:
fuse cab: install: change:
fuse cab: install: change:
Special Instructions: 586-42 SWITCH POSTION TO PROVIDE PROTECTION
Engineer Approval: JESSE SANTOS Date: 3/30/2022
PLANNER COMMENTS: SKETCH ATTACHED: YES
INSTALL NEW 200A TERMINATOR D239560; FEED FROM CMPT 4 586-42.
FROM TERMINATOR FEED NEW 1-2500 HNS TRANSFORMER D239561.
FROM D240170 1-2500 HNS TRANSFORMER INSTALL (1) NEW 4000A SWITCH GEAR (277/480).
FOR (2) ELECTRIC VEHICLE CHARGERS. PLAN FOR (26) ADDITIONAL EV CHARGERS.
PLEASE ADVISE IF ANY FUSING UPGRADES ARE REQUIRED. REFRENCE 60% DESIGN.
DISTRIBUTION PLANNING WORKSHEET
Date Info Needed (Allow 5 Days): I Estimated In-Service Date:
SKETCH ATTACHED: N/A
PLANNER COMMENTS:
KEY: • Represents Future Switch ATTACHED MAPS:
(INITAIL)i(ULTIMATE) D Represents Existing Switch
(SEPARATE TRENCH)** LO Represents Local Distribution
FDR Represents Feeder
Cable Example: 1000 = 1000KCMIL
**NOTE: FUTURE FACILITIES FOR CONSIDERATION ONLY-NO INSTALLATION REQUIRED AT THIS TIME
DATE DISTRIBUTION PLANNING ENGINEER EXT
. .
DPSS # 300000393485
□ FUSE REQUEST 0 DISTRIBUTION PLANNING WORKSHEET
•
soa,. Date of Release 04/21/2022 /f™ Release Expiration Date 04/21/2023
San Diego Gas & Electric -Environmental Release -jeTS 5268401
Shakira'Jat C ~, v~ I Project Name Clean Transportation, MD190021 -3-Project Manager 858-654-11863 39348 UJ n .. I Project Number lsAP I 300000393485 I Primary Env. Lead (Contact) Krtt~einicke -.I. iU22
6 ~i -0@,f!:: 0 " -
!Field Env. I Environmental Construction Compliance -,t..u1rv '"L.Se G Dtvi Ai • Representative Lead Sto"
)
To the extent this Release is provided to Contractor for the performance of the projed or services described herein, it is Contractor's own and sole responsibility to understand,
interpret and comply with all applicable federal, state or local laws, rules, regulations, including any orders or guidance from any governmental or quasi-governmental
authority with jurisdiction over this project ("Laws"). Company disclaims all responsibility or liability with respect to Contractor's understanding or interpretation of Laws based
on the information provided in this document, and Contractor shall not rely upon or use this Release to understand, interpret or comply with the Laws.
Environmental Requirements Quick Check (see below for For questions and/or to schedule monitors, contact (5-Day Notice
details) Required):
Pre-Construction Survey required NO Biolooical monitor NO
Pre-Construction Environmental Training required NO Cultural monitor YES
Notify Env. Lead at least 2 weeks prior to scheduled NO Paleo monitor NO Kristen Reinicke 619-385-094 7
construction date
Env. Access Protocol exists; 10-day notification required NO Aquatic monitor NO
Stormwater monitor NO
PROJECT DESCRIPTION AS RELEASED:
Project Name: Clean Transportation, MD190021 -3-393485, Carlsbad
Project Desc: Clean Transportation, MD190021 -3-393485 -City of Carlsbad INSTALL 1-4\" PRI CONDUIT FROM EXISTING 0162768
TO NEW 3421 FUSE CAB 0239560. FROM 0239560 INSTALL 1-4\" CONDUIT TO NEW 1-2000KVA HNS 0239561. INSTALL 10-5\" SEC
CONDUIT FROM 0239561 TO NEW 2000A 277/480V SWITCH BOARD (LOCATION 7). FROM SWITCH BOARD FEED 2 NEW ELECTRIC
VEHICLE CHARGING STATIONS AT CITY OF CARLSBAD: STUB FOR 24 EV CHARGING STATIONS. TRENCHING WILL OCCUR ON
PRIVATE PROPERTY. PLEASE REFERENCE 60% DESIGN & SOIL CALC.
Project General Construction Constraints:
✓ Based on the project description provided by the client, no vegetation trimming by SDG&E is proposed, or approved, for this project.
✓ Vehicles will remain on existing access roads at all times (including areas to turn around) unless otherwise specified in the Project
Description listed above. Crews shall obey 15 mph speed limit while driving on all unpaved access roads.
This project release applies only to the project as described and scoped. If there Is a change In the scope and the project does not match
the description, contact the environmental lead because this release is no longer valid.
!HAZARDOUS MATERIALS IEnv. Speciallst:James Scruggs:619-876-7622 . During grading, excavation, trenching, potholing, soil boring or other soil disturbing activities, if any odor, discoloration or
otherwise suspect materials are encountered indicating possible contamination, work must be stopped and sampling/testing
conducted to confirm. Soil export shall follow the SDG&E Environmental Services BMP for Surplus Soil. Work with the FER
for soil export or any hazardous waste disposal. . If SDG&E employee, use only approved products. If Contract employee, (M)SDS for materials should be in vehicle or readily
available. . Any chemicals, including paint, must be product approved through the Safety and Environmental Product Approval (SEPA)
process found on the Safety website. The Safety Data Sheet (previously Material Safety Data Sheet) SDS is required for this
process. . Before installation of equipment containing chemical products, the chemicals must be product approved through the Safety
and Environmental Product Approval (SEPA) process found on the Safety website. The Safety Data Sheet (previously
Material Safety Data Sheet) SDS is required for this process. . Handle all waste material and welding hazardous material under standard company practices. No material is to be left on site . . Report any and all spills, such as fuel or vehicle leaks, to the Field Environmental Representative immediately. Ali spills or
leaks must be immediately contained and/or cleaned up. Upon installation of new material, work with the FER to determine if
the HMBP will need revision of inventory items. . When Petromat, other fibrous material, or subsurface suspected asbestos-containing materials (e.g. Transite or Orangeburg
pipe, asphaltic pipe coatings) are discovered during disturbance, excavation, repair or removal of pavement, work
immediately must be halted in that area and cordoned off. Work must be redirected to another location at least 50 feet away
from the discovery. A Company-approved asbestos consultant must be called to perform sampling of the suspected
material. Photos of exposed Petromat and/or other suspected material should be taken to illustrate the type, condition and
location. No disturbance of the discovery area is permitted until lab analysis confirms asbestos is not present. If asbestos is
detected above one tenth of one percent (0.1%), the material is an Asbestos Containing Construction Material (ACCM) and
subject to hazardous material requirements of Cal/OSHA, SDG&E and possibly other agencies. The Asbestos Consultant
should e-mail lab results as soon as they are available to the project manager, Environmental and Safety Compliance. Rush
sampling and analysis for results usually takes 1 to 2 days. Only a Company-approved Asbestos Abatement Contractor is
Page 1 of2
permitted to handle, package or abate ACCM. The Asbestos Consultant is required to develop a work plan for ACCM with the
Abatement Contractor.
Standard constraints: . If hazardous material is released and may be a reportable quantity, contact SDG&E Trouble and Environmental Operations .
jCULTURAL RESOURCES IEnv. Specialist:Kristen Reinicke:619-385-0947
. A qualified archaeological monitor is required for all ground-disturbing activities. Please contact the Cultural Resource Lead
to arrange for a monitor at least 5 business days prior to work. In the event of a discovery, the monitor shall halt work in the
area of concern and shall contact SDG&E Cultural Resources Lead immediately to determine the appropriate course of
action. The monitor will not undertake any additional work at a discovery without prior authorization from SDG&E. In the
event that imported fill or subsurface bedrock is identified subsurface, the archaeologist may cease monitoring. . Archaeological tailgate training is required. Please contact the Cultural Resources Lead at least one week before
construction precon is scheduled to arrange attendance.
Standard constraints: . CONFIDENTIAL INFORMATION. Information about archaeological site locations and discoveries is confidential. This information is
protected by federal, state, and local laws and violations can result in fines and imprisonment. It is illegal to make or give out maps that
show locations of archaeological sites or to tell/share with others where a site is located. Project information provided to protect
archaeological sites must remain confidential. . If archaeological or historical objects or features are discovered, they must be reported to the Cultural Resources Specialist
immediately for evaluation. These objects or features may be buried under fill or pavement, or may be on the surface. Examples of
discoveries can include (but are not limited to): artifacts such as old cans or bottles, arrowheads/lithic artifacts, pottery sherds, human
remains (e.g. bone or possible bone), black/burnt soils.
Standard Project Constraints
Crews shall carefully inspect all trees and shrubs that will be affected by SDG&E activities for active bird nests. No active
Natural nests or their occupants shall be harmed. If active nests are identified, the crew shall stop work and contact the Natural
Resources Resource lead.
Work crews should follow the operational protocols, as stated in SDG&E NCCP (Section 7.1 Operational Protocols), to avoid,
minimize, or mitigate impacts to resources as a result of project-related activities.
Paleo If fossils are discovered, they must be reported to the Cultural Resources Specialist immediately for evaluation. These objects
Resources may be buried several feet below the surface. Examples of discoveries can include (but are not limited to): shell or bone that
appear to be stone, plant impressions in stone, and burrows or trace fossils.
Aquatic None. Resources
Construction crews shall implement applicable sediment and erosion control Best Management Practices (BMPs) as specified
I
in the SDG&E BMP Manual for Water Quality Construction (BMP Manual).
Water If a non-stormwater discharge occurs (a discharge that is anything but rain, e.g., a broken sprinkler head, water leaking from
Quallty I baker tank, fuel leaks, ground water dewatering, etc.), notify the Stormwater Contact.
If a small, localized spill occurs, such as vehicle leak, it should be cleaned up with a spill kit and the Stormwater Contact shall
be notified.
Each jurisdiction where SDG&E performs work has laws and regulations that must be complied with during construction,
Land including encroachment, traffic control and noise. Work must be implemented in conformance with these laws and regulations
Planning as applicable or a waiver, alternative compliance, or consultation must be completed with the jurisdiction prior to the initiation
of any staging, site preparation or work.
Air None. Re11ources
Site None. Assessment
Post
Construction None Compliance /
Sunrise
Page 2 of 2
I Project Name: 1MD190021-CITY OF CARLSBAD
I Planner: l Ruben Ruiz l Datel" I Internal Order# l 3-393337 l SAP or DPSS #I
2/24/2022 ~
3-393485 1
User Input Cells
Heading Cells
Locked Cells
Project part of a Common Plan of Development or Sale (CPD/SJ? No Drop Down Cells
Common Plan -Soil Disturbance Area (acres) 0.00
Project Work Area (acres) 0.05
Project soil disturbance area -Subtotal (acres) 0.05
Contingency (%) 10
Project Soll Disturbance Area (acres) 0.06
Project Type Component Type Additional Description Default Length Width Radius Quantity Work Area Permit Soll Disturbance I Double Click Buttons (feet) (feet) (feet) (Sq. feet) Exclusion (%) Area (Sq. feet)
Electric Distribution -Trench Unpaved 4" PRIMARY Custom 507 1.5 761 0 761 ADO DELETE DUPLICATE Underground NA 1 -1-Electric Distribution -Trench Unpaved 5" SECONDARY Custom 45 1.5 NA 68 0 68 ADO DELETE DUPLICATE Underground 1 -Electric Distribution -Trench Paved 1.5" SERVICE Underground Custom 252 1.5 NA 1 378 0 378 ADO DELETE DUPUCATE -Electric Transmission -Pads and 3427 XMFR 9.2 8.7 80 0 80 ADO DELETE DUPLICATE Underground Substructure Yes NA 1 -Electric Distribution -Other SWITCH BOARD 148 ADO DELETE DUPLICATE Underground NA Custom 6.25 11.85 NA 2 148 0 -Electric Distribution -Pads and
Underground Substructure 3421 FUSE CAB Yes 5.2 5 NA 1 26 0 26 ADD DELETE DUPLICATE -Electric Distribution -Other NA DC CHARGER Underground Custom 4 4 NA 2 32 0 32 ADO DELETE DUPLICATE -Electric Distribution -Staging/Laydown NA Material Laydown Custom 25 625 625 ADD DELETE DUPLICATE Underground 25 NA 1 0 areas -
..
Building Permit Finaled
Revision Permit
Print Date: 03/17/2025
Job Address: 2480 IMPALA DR, CARLSBAD, CA 92010-7226
Permit No:
Status:
(cityof
Carlsbad
PREV2023-0052
Closed -Finaled
Permit Type: BLDG-Permit Revision Work Class: Commercial Permit Revision
Parcel#: 2090502600 Track#:
Valuation: $0.00 Lot#:
Occupancy Group: b
#of Dwelling Units:
Bedrooms:
Bathrooms:
Occupant Load:
Code Edition: 2022
Sprinkled:
Project Title:
Project#:
Plan#:
Construction Type:
Orig. Plan Check#:
Plan Check#:
Applied: 04/07/2023
Issued: 07/06/2023
Finaled Close Out: 03/17/2025
Final Inspection:
INSPECTOR:
Description: REVISION: SHEETS 5 AND 7: CARLSBAD FLEET SERVICES: ELECTRICAL UPGRADES AND INSTALLATION OF 2 CHARGING STATII
FEE
BUILDING PLAN CHECK FEE (manual)
BUILDING PLAN CHECK REVISION ADMIN FEE
Property Owner:
CITY OF CARLSBAD
CURTIS JACKSON
1200 CARLSBAD VILLAGE DR
CARLSBAD, CA 92008-1989
(760) 434-2836
Total Fees: $395.00 Total Payments To Date:
Building Division
$395.00
Contractor:
AM ORTEGA CONSTRUCTION INC
10125 CHANNEL RD
LAKESIDE, CA 92040-1703
(619) 390-1988
Balance Due:
AMOUNT
$360.00
$35.00
$0.00
Page 1 of 1