HomeMy WebLinkAboutDWG 538-4BA; 5542-B; Electrical Control Panel Replacement Project - Terramar Lift Station; 01-31DWG SECTION SECTION DESCRIPTION
1 GENERAL
2 NETWORK WIRING
3 AC POWER
4 DC POWER
5 MISCELLANEOUS
6 IO RACK 1
7 IO RACK 2
8 IO RACK 3
99 REPORTS (PANEL BUILDER REFERENCE ONLY)
DRAWING NUMBERING CONVENTION
X Y . #
DRAWING SECTION NUMBER
SHEET LETTER
SUB SHEET NUMBER
(OPTIONAL)
TERRAMAR LIFT STATION
CITYWIDE ELECTRICAL CONTROL PANEL REPLACEMENT
PROJECT FOR WATER AND WASTEWATER FACILITIES
SHEET DWG DESCRIPTION REVISION
1 1A TABLE OF CONTENTS 0.2
2 1B DRAWING SYMBOL KEY 0.2
3 1C CONSTRUCTION COMMENTS 0.2
4 1D.1 BILL OF MATERIAL (PART 1)0.2
5 1D.2 BILL OF MATERIAL (PART 2)0.2
6 1E.1 PANEL LAYOUT EXTERIOR DETAILS 0.2
7 1E.2 PANEL LAYOUT EXTERIOR DIMENSIONS 0.2
8 1F.1 PANEL LAYOUT INTERIOR DETAILS 0.2
9 1F.2 PANEL LAYOUT INTERIOR DIMENSIONS 0.2
10 1F.3 PANEL LAYOUT INTERIOR TOP VIEW 0.2
11 1F.4 CUSTOM BACKPANEL 0.2
12 1G TERMINAL STRIP DETAIL 0.2
13 1H TERMINAL STRIP DETAIL DIGITAL 0.2
14 1I TERMINAL STRIP DETAIL ANALOG 0.2
15 1J PANEL COMPONENT DETAIL 0.2
16 1K.1 NAMEPLATE DETAIL (PART 1)0.2
17 1K.2 NAMEPLATE DETAIL (PART 2)0.2
18 1K.3 NAMEPLATE DETAIL (PART 3)0.2
19 2A NETWORK WIRING 0.2
20 3A AC POWER DISTRIBUTION 0.2
21 4A.1 DC POWER DISTRIBUTION (PART 1)0.2
22 4A.2 DC POWER DISTRIBUTION (PART 2)0.2
23 5A PANEL I/O DETAIL 0.2
24 6A RACK 1 SLOT 1 DISCRETE INPUT 0.2
25 6B RACK 1 SLOT 2 DISCRETE INPUT 0.2
26 6C RACK 1 SLOT 3 DISCRETE OUTPUT 0.2
27 6D RACK 1 SLOT 4 ANALOG INPUT 0.2
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1A NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION TABLE OF CONTENTS.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
TABLE OF CONTENTS
1 31
CITY OF CARLSBAD
NOTE: REFER TO SHEET G-003
GENERAL NOTES. ALL INFORMATION
IS APPLICABLE TO THIS DESIGN.
DRAWING SYMBOL KEY
COMPONENT TAG
NORMALLY OPEN
STATUS CONTACT
CROSS REFERENCE
NORMALLY CLOSED
STATUS CONTACT
CROSS REFERENCE
C/B RATING 20A
SHT 2X-A1,SHT 3X-A2
CB1X01
3A01L
120VAC
3A01L
to SHT 4A.1-A1
TB-XX
Number Jumper Manufacturer Part #
1X22 MFG NAME XXXXXXX
1X23
1X24 MFG NAME XXXXXXX
1X25
TERMINALS
NOT JUMPERED
TERMINALS
JUMPERED
G
GND3A01
GROUND BAR
COMPONENT TAG
C/B RATING 20A
CB1X01
4241
SHT 1X-C1
CB1X01
1211
SHT 1X-C1
CB1X01
CIRCUIT BREAKER
LOCATION CROSS REFERENCE
COMPONENT TAG
NORMALLY OPEN
CONTACT LOCATION
CROSS REFERENCE
NORMALLY CLOSED
CONTACT LOCATION
CROSS REFERENCE
NORMALLY OPEN CONTACT
NORMALLY CLOSED CONTACT
CR1X01
RELAY COIL
LOCATION CROSS REFERENCE
RELAY COIL
LOCATION CROSS REFERENCE
NC
NO
SHT 3X-A2
SHT 2X-A1
4241
SHT 1X-C1
CB1X01
1211
SHT 1X-C1
CB1X01
PANEL-MOUNTED
GROUND BUS
TERMINAL STRIP JUMPER DETAILS
WIRE JUMPERS
(BETWEEN
TERMINALS)
MECHANICAL
JUMPERS
1X22
1X21
1X20
1X12
1X11
1X10
CONTROL RELAY
(WITH CONTACT CROSS REFERENCE)
SINGLE-POLE CIRCUIT BREAKER
SINGLE-POLE CIRCUIT BREAKER
(WITH AUXILIARY STATUS CONTACTS)
PREFIX DESCRIPTION
BAT BATTERY
CB CIRCUIT BREAKER
CBL CABLE
GND GROUND BAR
HTR HEATER
LS LIMIT SWITCH
LSA LIGHTNING SURGE ARRESTER
LT LIGHT
NETSW ETHERNET NETWORK SWITCH
PB PUSH BUTTON
PD POWER DISTRIBUTION TERMINAL BLOCK
PSU POWER SUPPLY
RECP RECEPTACLE
SS SELECTOR SWITCH
TB TERMINAL BLOCK
TC THERMOCOUPLE CONVERTER
TR TIMER RELAY
TSTAT THERMOSTAT
UPS UNINTERRUPTIBLE POWER SUPPLY
XX YY ##
COMPONENT PREFIX
DRAWING SHEET NUMBER
COMPONENT NUMBER
(SEQUENTIAL)
COMPONENT TAG NAMING CONVENTION
SHT XX - Y Z
LOCATION CROSS REFERENCE CONVENTION
DRAWING SHEET NUMBER
SHEET COLUMN LETTER
SHEET ROW NUMBER
A B
1
2
SHEET LOCATION
COLUMN LETTER
SHEET LOCATION
ROW NUMBER
WIRE OFF SHEET
CROSS REVERENCE
WIRE NUMBER
WIRE LOCATION
SHEET REFERENCE
SIGNAL DESCRIPTION
SELECTOR SWITCH, 2-POLE
(TOP: NO, BOTTOM: NC)
PILOT LIGHT, PUSH-TO-TEST
(COLOR: A=AMBER, G=GREEN, R=RED)
100W
A
DIGITAL FIELD DEVICE
ANALOG FIELD DEVICE
LIMIT SWITCH NORMALLY CLOSED
LIMIT SWITCH NORMALLY OPEN
PUSH BUTTON NORMALLY OPEN
PUSH BUTTON NORMALLY CLOSED
MUSHROOM HEAD PUSH BUTTON
RADIANT HEATER
HORN OR BUZZER
GENERIC DEVICE
+-
ELECTRICAL SYMBOL DEFINITIONS
BILL OF MATERIAL TAG # REFERENCE
BUBBLEDV1X02
DUPLEX
RECEPTACLE
SPECIAL
CHARACTER
DESCRIPTION
L 120VAC POWER LINE VOLTAGE
N 120VAC POWER NEUTRAL
+24VDC POSITIVE
-24VDC NEUTRAL
G GROUND
OTHER (A-Z)UNIQUE WIRE DESIGNATOR
YY ## A
DRAWING SHEET NUMBER
WIRE NUMBER
(SEQUENTIAL)
SPECIAL DESIGNATOR
CHARACTER (OPTIONAL)
WIRE NUMBERING CONVENTION
FUSE NUMBER
TERMINAL STRIP
WIRE NUMBER
FUSE RATING
1X57
TB-XX
1X56
TB-XX
1X041X03
1X55
TB-XX
1X54
TB-XX
0.5A
RED #12 AWG MTW
WIRE COLOR, SIZE, AND TYPE
DESIGNATION
WIRE TYPE SYMBOLS
FIELD WIRING INTERNAL PANEL
WIRING
SHLD
SHIELDED MULTI-CONDUCTOR
CABLE WITH DRAIN WIRE
MULTI-CONDUCTOR CABLE
WHTCBL6A01
BRNCBL6A01
CABLE TAG INDIVIDUAL
CONDUCTOR COLOR
FUSED TERMINAL
DISCONNECT TERMINAL
(FOR ANALOG SIGNAL TESTING)
FEED-THROUGH TERMINAL
GROUND TERMINAL
(CONNECTED DIRECTLY TO DIN RAIL)
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1B NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION DRAWING SYMBOL KEY.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
DRAWING SYMBOL KEY
2 31
CITY OF CARLSBAD
PANEL CONSTRUCTION COMMENTS AND SPECIAL INSTRUCTIONS
ISOLATED DIN RAIL:
EACH ISOLATED DIN RAIL SHALL BE INSTALLED ON INSULATED STANDOFFS TO CREATE ISOLATION BETWEEN THE DIN RAIL AND THE BACK PANEL.
EACH DIN RAIL WILL HAVE A SINGLE GROUNDING TERMINAL BLOCK, WHICH IS TO BE CONNECTED DIRECTLY TO THE GROUND BUS WITH A SINGLE
CONDUCTOR OF #14AWG (GREEN) WIRE.
THE TERMINAL STRIPS LISTED TOGETHER BELOW SHALL BE MOUNTED ON THE SAME, CONTINUOUS ISOLATED DIN RAIL.
THIS REQUIREMENT APPLIES TO:
TB-DI-1
TB-DO-1
TB-AI-1
TERMINAL BLOCKS:
FOR THE FOLLOWING TERMINAL BLOCKS, FIELD WIRING TERMINATES ON THE LEFT AND PANEL WIRING TERMINATES ON THE RIGHT.
THIS REQUIREMENT APPLIES TO:
N/A
FOR THE FOLLOWING TERMINAL BLOCKS, FIELD WIRING TERMINATES ON THE RIGHT AND PANEL WIRING TERMINATES ON THE LEFT.
THIS REQUIREMENT APPLIES TO:
TB-DI-1
TB-DO-1
TB-AI-1
TB-DO-RELAY
FOR THE FOLLOWING TERMINAL BLOCKS, ALL PANEL WIRING SHALL TERMINATE ONLY ON THE PANEL SIDE OF THE TERMINAL. DO NOT TERMINATE
PANEL WIRING ON THE FIELD SIDE OF THE TERMINAL.
THIS REQUIREMENT APPLIES TO:
TB-DI-1
TB-DO-1
INPUT LSA (LSA3A01) IS TO BE MOUNTED AND WIRED SUCH THAT FIELD TERMINATIONS ARE ON THE RIGHT AND PANEL WIRING IS ON THE LEFT.
GROUND BUS:
MOUNT GROUND BUS DIRECTLY TO BACK PANEL.
BOND THE GROUND STUD ON ENCLOSURE DOORS DIRECTLY TO ENCLOSURE GROUNDING STUD(S) USING SINGLE CONDUCTOR OF #14AWG
(GREEN) WIRE.
DO NOT GROUND CONTROL COMPONENTS TO BACK PANEL. RUN SINGLE CONDUCTORS DIRECTLY TO GROUND BUS AS SHOWN ON SHEET 3A OF
DRAWING SET.
ENCLOSURE AND PANEL ASSEMBLY:
PANEL IS TO BE CONSTRUCTED IN CONFORMANCE WITH NEC (INCLUDING ARTICLE 409) AND UL 508A AND BEAR THE APPROPRIATE UL 508A
INDUSTRIAL CONTROL PANEL LABEL CONFIRMING THE CONSTRUCTION.
BATTERY SENSOR MODULE TO BE INSTALLED TO BACK PANEL USING ZINC PLATED STANDOFFS. INSTALL NYLON WASHERS ON BOTH SIDES OF
BOARD AT EACH MOUNTING SCREW.
ATTACH WIRE DUCT TO PANEL WITH METAL FASTENERS.
ENCLOSURE DOOR STOP TO BE INSTALLED WITH WELDED STUDS ON THE DOOR AND BOLTS WITH SEALING WASHERS ON THE ENCLOSURE.
ROUTER IR1101 AND ANTENNA ANT-4-5G4-O TO BE PROVIDED BY CUSTOMER AND ASSEMBLED BY CONTRACTOR.
DEVICE LABELS:
UNLESS OTHERWISE INDICATED, ALL COMPONENT IDENTIFICATION LABELS ARE TO BE SELF ADHESIVE POLYESTER WITH BLACK THERMAL
PRINTED TEXT.
ADDITIONAL COMPONENT IDENTIFICATION LABELS ARE TO BE MOUNTED ON THE FRONT OF EACH DEVICE. ALL LABELS TO BE OF UNIFORM SIZE
AND FONT. TEXT TO MATCH THE LABEL ON THE END BRACKET NEXT TO THE DEVICE.
THIS REQUIREMENT APPLIES TO:
ALL CIRCUIT BREAKERS
PSU4A01 UPS4A01 ROUTER OIT01 TSTAT6B01
WIRE AND TERMINAL MARKING:
ALL WIRE AND TERMINAL LABELS TO BE COMPUTER PRINTED. NO HAND-WRITTEN TERMINAL OR WIRE NUMBERS ALLOWED
LABEL ALL TERMINALS WITH TERMINAL MANUFACTURE MARKER STRIPS
LABEL ALL WIRE/CABLE WITH HEAT SHRINK MARKING SLEEVES.
PANEL WIRING:
USE DUAL WIRE FERRULES WHENEVER 2 WIRES ARE INSERTED INTO A SINGLE TERMINATION POINT.
DO NOT ROUTE WIRES AGAINST OR FASTENED TO COOLING VENTS OF CONTROL COMPONENTS.
DO NOT ROUTE PANEL WIRING INSIDE WIRE DUCTS THAT ARE MARKED AS FIELD WIRING
DO NOT USE NYLON TIE WRAPS INSIDE WIRE DUCT.
WIRES AND CABLES ROUTED OUTSIDE OF WIRE DUCTS SHALL BE FIXED TO ENCLOSURE WITH WIRE SADDLES AT A MINIMUM OF EVERY 4 INCHES.
WIRE SADDLES ARE TO BE MOUNTED USING THREADED STUDS WELDED TO ENCLOSURE, DO NOT USE ADHESIVE BACKED WIRE SADDLES.
WIRES AND CABLES ROUTED TO DOORS SHALL BE FLEXIBLE AND WRAPPED IN A WIRE LOOM. SECURE WIRING ON EACH SIDE OF THE HINGE SO
THAT ANY BENDING OR TWISTING WILL BE AROUND THE LENGTH OF THE WIRE.
HEATER WIRES TO BE ROUTED BELOW BACK PANEL ON INSIDE OF ENCLOSURE.
WIRE COLOR AND SIZES:
UNLESS OTHERWISE SPECIFIED IN THE DRAWING SET, ALL WIRES TO BE SIZED AND COLORED AS FOLLOWS:
120VAC = RED, 14 AWG, MTW
120VAC NEUTRAL = WHITE, 14 AWG, MTW
120VAC NOT DISCONNECTED BY PANEL'S MAIN CIRCUIT BREAKER = ORANGE, 14 AWG, MTW
24VDC = BLUE, 16 AWG, MTW
N-DC = WHITE/BLUE, 16 AWG, MTW
GROUND = GREEN, 14 AWG, MTW
DISCRETE INPUTS = BLUE, 18 AWG, MTW, OR MANUFACTURES MULTI-CONDUCTOR CABLE
DISCRETE OUTPUTS = YELLOW, 18 AWG, MTW
ANALOG INPUTS AND OUTPUTS = PURPLE, 18 AWG, MTW
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1C NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION CONSTRUCTION COMMENTS.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
CONSTRUCTION COMMENTS
3 31
CITY OF CARLSBAD
ALL BILL OF MATERIAL ITEMS ARE "NO EQUAL" TO MATCH EXISTING STANDARDS, AND SHALL BE PROVIDED AS LISTED.
TAG QTY MANUFACTURER PART #DESCRIPTION
BACKPANEL 1 PANEL BUILDER CUSTOM BACKPANEL CUSTOM REPLACEMENT BACKPANEL FOR EXISTING ENCLOSURE
BAT4A03 1 PHOENIX CONTACT 1134645 BATTERY MOUNTING CASE M, WALL AND SURFACE MOUNTING BATTERY CONTAINER
2 DURACELL SLADC12-20C LEAD-ACID BATTERY, 20AH, 12VDC, 13.3 LBS
CB3A00 1 EATON FAZ-D20/1-NA-SP CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 20A, D CURVE
1 EATON Z-NHK CIRCUIT BREAKER, UL 489 BRANCH, AUXILIARY SWITCH
CB3A01 1 EATON FAZ-D10/1-NA-SP CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 10A, D CURVE
CB3A02 1 EATON FAZ-D4/1-NA-SP CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 4A, D CURVE
CB3A03 1 EATON FAZ-D4/1-NA-SP CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 4A, D CURVE
CB4A10 1 CBI QY-1-13-DM-U2-0.5A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 0.5A 80V 1 POLE
1 CBI SABBM54 CIRCUIT BREAKER, 13MM, BUSBAR MODULE SINGLE PHASE, METAL
CB4A11 1 CBI QY-1-13-DM-U2-0.5A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 0.5A 80V 1 POLE
CB4A12 1 CBI QY-1-13-DM-U2-6A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 6A 80V 1 POLE
CB4A13 1 CBI QY-1-13-DM-U2-2A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 2A 80V 1 POLE
CB4A14 1 CBI QY-1-13-DM-U2-2A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 2A 80V 1 POLE
CB4A15 1 CBI QY-1-13-DM-U2-6A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 6A 80V 1 POLE
CB4A16 1 CBI QY-1-13-DM-U2-4A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 4A 80V 1 POLE
CB4A17 1 CBI QY-1-13-DM-U2-2A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 2A 80V 1 POLE
CB4A18 1 CBI QY-1-13-DM-U2-2A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 2A 80V 1 POLE
CB4A19 1 CBI QY-1-13-DM-U2-4A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 4A 80V 1 POLE
CB4A20 1 CBI QY-1-13-DM-U2-6A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 6A 80V 1 POLE
CB4A50 1 CBI QY-1-13-DM-U2-30A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 30A 80V 1 POLE
CR3A00 1 PHOENIX CONTACT 2966249 RELAY MODULE 120VAC COIL WITH BUSBAR TERMINAL 1NO
CR6C08 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO
1 PHOENIX CONTACT 2966786 CONTINUOUS PLUG-IN BRIDGE MECHANICAL JUMPER, 500MM, RELAY
CR6C09 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO
CR6C10 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO
CR6C11 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO
CR6C12 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO
CR6C13 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO
CR6C14 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO
CR6C15 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO
DINRAIL 1 PHOENIX CONTACT 1201730 DIN RAIL
1 PHOENIX CONTACT 1201141 INSULATED DIN RAIL MOUNT
DUCT-AC-1"1 PANDUIT F1X4LG6 NARROW FINGER, SLOTTED WIRING DUCT GRAY 1" WIDE X 4" DEEP
1 PANDUIT C1LG6 WIRING DUCT COVER - GRAY 1" WIDE
DUCT-DC-1.5"1 PANDUIT F1.5X4LG6 NARROW FINGER, SLOTTED WIRING DUCT GRAY 1.5" WIDE X 4" DEEP
1 PANDUIT C1.5LG6 WIRING DUCT COVER - GRAY 1.5" WIDE
DUCT-DC-2"1 PANDUIT F2X4LG6 NARROW FINGER, SLOTTED WIRING DUCT GRAY 2" WIDE X 4" DEEP
1 PANDUIT C2LG6 WIRING DUCT COVER - GRAY 2" WIDE
DUCT-DC-3"1 PANDUIT F3X4LG6 NARROW FINGER, SLOTTED WIRING DUCT GRAY 3" WIDE X 4" DEEP
1 PANDUIT C3LG6 WIRING DUCT COVER - GRAY 3" WIDE
ENCLOSURE 1 EXISTING EXISTING ENCLOSURE EXISTING ENCLOSURE
GND3A01 1 SCHNEIDER PK18GTA LOAD CENTER ACCESSORY, QO/HOMELINE, GROUND BAR KIT, 18 TERMINAL
LSA3A01 1 EATON AGCF12030 TRANSIENT VOLTAGE SURGE SUPPRESSOR, 120VAC, 20A
LT5A01 1 BANNER WLB32C285PBQ WLB32 ADJUSTABLE LED WORKSTATION LIGHT
1 SQUARE D XZCP1141L5 M12 4 PIN CONNECTOR 16FT CABLE
MISC 12 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N
OIT01 1 ONLOGIC TC401R OIT, PANEL MOUNTED TOUCHSCREEN MONITOR, 12.1" HMI, 24VDC
PD6C00 1 PHOENIX CONTACT 2966508 RELAY POWER TERMINAL
2 PHOENIX CONTACT 2966786 CONTINUOUS PLUG-IN BRIDGE MECHANICAL JUMPER, 500MM, RELAY
TAG QTY MANUFACTURER PART #DESCRIPTION
PSU4A01 1 PULS CP20.241 1-PHASE POWER SUPPLY
RACK1ECR 1 AB 5069-ECR 5069 COMPACTLOGIX/COMPACT GUARDLOGIX RIGHT END CAP WITH ADAPTER
RACK1S00 1 AB 5069-L320ER COMPACTLOGIX 5380, 2 MB USER MEMORY, 16 I/Os, 40 ETHERNET/IP DEVICES
1 AB 5069-RTB6-SCREW 6 PIN SCREW TYPE POWER TERMINAL CONNECTOR
1 AB 5069-RTB4-SCREW 4 PIN SCREW TYPE POWER TERMINAL CONNECTOR
RACK1S01 1 AB 5069-IB16 5069 COMPACT I/O 16 CHANNEL 24V DC SINK INPUTE MODULE
1 AB 5069-RTB18-SCREW 18 PIN SCREW TYPE TERMINAL CONNECTOR
RACK1S02 1 AB 5069-IB16 5069 COMPACT I/O 16 CHANNEL 24V DC SINK INPUTE MODULE
1 AB 5069-RTB18-SCREW 18 PIN SCREW TYPE TERMINAL CONNECTOR
RACK1S03 1 AB 5069-OB16 5069 COMPACT I/O 16 CHANNEL 24V DC SOURCE OUTPUT MODULE
1 AB 5069-RTB18-SCREW 18 PIN SCREW TYPE TERMINAL CONNECTOR
RACK1S04 1 AB 5069-IF8 5069 COMPACT I/O 8 CHANNEL VOLTAGE/CURRENT ANALOG INPUT MODULE
1 AB 5069-RTB18-SCREW 18 PIN SCREW TYPE TERMINAL CONNECTOR
RECP3A01 1 HUBBELL GFR15I GFCI RECEPTACLE, 125V, 15A
1 HUBBELL 5320-0 DUPLEX RECEPTACLE GANG BOX PANEL MOUNT
1 HUBBELL SSJ26 GFCI RECEPTACLE COVER PLATE
ROUTER 1 CISCO IR1101 ROUTER, POWER INPUT 9.6 TO 60VDC, TEMP RATING: -40 TO 60C, 4 PORT ETHERNET
1 CISCO ANT-4-5G4-O DIRECT MOUNT OMNIDIRECTIONAL ANTENNA
1 EXISTING EXISTING CABLE CAT 6 ETHERNET CABLE
STOP1 1 HOFFMAN ALGDSTOP2 LARGE ENCLOSURE DOOR STOP KIT
SW5A01 1 TELEMECANIQUE ZCP21 LIMIT SWITCH BODY - ZCP - 1 NC + 1 NO - TERMINALS
1 TELEMECANIQUE ZCPEG11 CABLE GLAND ENTRY FOR LIMIT SWITCH
1 TELEMECANIQUE ZCE10 HEAD FOR LIMIT SWITCH - ZCE - STEEL END PLUNGER
TB-AC-1 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A
2 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N
3 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, 30-12AWG
6 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L
1 AB 1492-CJK5-50 50 IEC CENTER JUMPER, 10 PL 5mm, PLUG-IN
1 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS
TB-AI-1 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A
2 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N
24 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, 30-12AWG
82 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L
1 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS
9 AB 1492-LG3 IEC SPRING CLAMP TERMINAL BLOCK, GROUNDING BLOCK, 1492-L
8 AB 1492-L3P TERMINAL BLOCK 1492, GRAY
8 AB 1492-FPK224 TERMINAL ACCESSORY 1492, BLACK
8 EATON GMC-63MA CARTRIDGE FUSE 63MA
TB-BATT-1 2 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N
1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A
3 AB 1492-L6 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, 22-8AWG
6 AB 1492-M6X12 TERMINAL LABEL, 6mm X 12mm, INDIVIDUAL, SNAP ON, 1492-L
1 AB 1492-CJL8-2 2 IEC CENTER JUMPER, 2 PL 8mm, PLUG-IN, YELLOW
1 AB 1492-EBL6 END BARRIER COMPATIBLE WITH 1492-L6 TYPE TERMINALS
TB-DC-1 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A
3 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N
19 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, 30-12AWG
38 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L
2 AB 1492-CJK5-50 50 IEC CENTER JUMPER, 10 PL 5mm, PLUG-IN
2 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1D.1 NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION BILL OF MATERIAL 1.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
BILL OF MATERIAL (PART 1)
4 31
CITY OF CARLSBAD
ALL BILL OF MATERIAL ITEMS ARE "NO EQUAL" TO MATCH EXISTING STANDARDS, AND SHALL BE PROVIDED AS LISTED.
TAG QTY MANUFACTURER PART #DESCRIPTION
TB-DI-1 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A
3 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N
64 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, 30-12AWG
128 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L
2 AB 1492-CJK5-50 50 IEC CENTER JUMPER, 10 PL 5mm, PLUG-IN
2 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS
TB-DO-1 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A
2 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N
18 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, 30-12AWG
36 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L
1 AB 1492-CJK5-50 50 IEC CENTER JUMPER, 10 PL 5mm, PLUG-IN
1 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS
TB-DOOR 2 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N
1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A
5 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, 30-12AWG
10 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L
1 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS
TSTAT6B01 1 PFANNENBERG 17111000010 THERMOSTAT, VOLTAGE RATING: 240VAC, DC RATING 30W, TEMP RATING: 32 TO 140 F, N.C. W/
CONTACT SPRINGS, GREY, FLZ 520
UPS4A01 1 PULS UB20.241 DC UPS MODULE 24VDC, 20A OUTPUT, FOR 3.9AH TO 150AH BATTERY
UPS4A02 1 PULS UZS24.100 SENSOR BOARD FOR BATTERY MODULES
3 MCMASTER CARR 93505A485 ZINC-PLATED STEEL THREADED 1/4" HEX STANDOFF
6 MCMASTER CARR 92150A104 NYLON SPACER
3 MCMASTER CARR 90272A108 ZINC PLATED STEEL HEX BOLT, #4-40 X 3/8"
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1D.2 NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION BILL OF MATERIAL 2.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
BILL OF MATERIAL (PART 2)
5 31
CITY OF CARLSBAD
STOP1
HEAT DISSIPATION AREA
0"3"6"12"
ENCLOSURE
STOP1
LT5A01
120VAC FROM: LP-XXX CKT XX
LT5A01 LT5A01
SW5A01
SW5A01
OIT01
OIT01
TERRAMAR
OIT01
BAT4A03
NOTE: OIT MOUNTED TO THE SWING DOOR
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1E.1 1"=6"
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION PANEL LAYOUT EXTERIOR DETAILS.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
PANEL LAYOUT EXTERIOR DETAILS
6 31
CITY OF CARLSBAD
60
0
0
0 30
STOP1
0"3"6"12"
120VAC FROM: LP-XXX CKT XX
TERRAMAR
0 0
0
23
3 8
23
3 8
443
4
523
4
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1E.2 1"=6"
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION PANEL LAYOUT EXTERIOR DIMENSIONS.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
PANEL LAYOUT EXTERIOR DIMENSIONS
7 31
CITY OF CARLSBAD
0"3"6"12"
HEAT DISSIPATION AREA
SEE SHT 1J
TB-DI-1
TB-DO-1
TB-AI-1
UPS4A02
TB-BATT-1
GND3A01
LSA3A01
RECP3A01
TB-DO-RELAY
TB-AC-1
DINRAIL
DUCT-AC-1.5"
DUCT-DC-1.5"
DUCT-DC-2"
DUCT-DC-3"
UPS4A02
SEE SHT 1J BREAKERS
PSU4A01
UPS4A01
TB-DOOR
TB-DC-1
1.5" x 4"
2"
x
4
"
F
I
E
L
D
W
I
R
I
N
G
DUCT-AC-1"1" x 4"
1.5" x 4"
1.5" x 4"
2" x 4"
3" x 4"
PSU4A01UPS4A01
ROUTER TSTAT6B01
CB
4
A
1
0
AC
C
1
CB
4
A
1
1
CB
4
A
1
2
CB
4
A
1
3
CB
4
A
1
4
CB
4
A
1
5
CB
4
A
1
6
CB
4
A
1
7
CB
4
A
1
8
CB
4
A
1
9
CB
4
A
2
0
ACC
1
ACC
1
ACC
1
ACC
1
SEE SHT 1J BREAKERS
CR3A00
1.5" x 4"
ACC
1
ACC
1
ACC
1
ACC
3
2"
x
4
"
RACK1S005069-L320ER
RA
C
K
1
S
0
1
50
6
9
-
I
B
1
6
1" x 4"DUCT-DC-1"
1" x 4"
ROUTER
AC
C
1
AC
C
3
CB4A50
RACK1
RACK1
BAT4A03
AC
C
1
GND3A01
RE
C
P
3
A
0
1
LS
A
3
A
0
1
CB3A00
CB3A01
CB3A02
CB3A03
1" x 4"
1.
5
"
x
4
"
1.
5
"
x
4
"
1.
5
"
x
4
"
ACC1
CR6C15
CR6C14CR6C13CR6C12CR6C11CR6C10CR6C09
CR6C08
ACC1
ACC1
PD6C00
1.
5
"
x
4
"
F
I
E
L
D
W
I
R
I
N
G
RA
C
K
1
S
0
2
50
6
9
-
I
B
1
6
RA
C
K
1
S
0
3
50
6
9
-
O
B
1
6
RA
C
K
1
S
0
4
50
6
9
-
I
F
8
ACC1
ACC3
ACC5
ACC1
ACC3
3" x 4"
ACC
1
ACC
3
ACC
5
ACC1
ACC3
ACC1
ACC3
CONTRACTOR TO VERIFY BACKPANEL DETAILS PRIOR TO CONSTRUCTION OF PANEL
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1F.1 1"=6"
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION PANEL LAYOUT INTERIOR DETAILS.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
PANEL LAYOUT INTERIOR DETAILS
8 31
CITY OF CARLSBAD
0
54
0 7
11
5 8
24
3 4 27
214
20
1 2
0"3"6"12"
1.5" x 4"
2"
x
4
"
F
I
E
L
D
W
I
R
I
N
G
1" x 4"
1.5" x 4"
1.5" x 4"
2" x 4"
3" x 4"
PSU4A01UPS4A01
AC
C
1
ACC
1
ACC
1
ACC
1
ACC
1
1.5" x 4"
ACC
1
ACC
1
ACC
1
ACC
3
2"
x
4
"
RACK1S005069-L320ER
RA
C
K
1
S
0
1
50
6
9
-
I
B
1
6
1" x 4"
1" x 4"
ROUTER
AC
C
1
AC
C
3
AC
C
1
GND3A01
1" x 4"
1.
5
"
x
4
"
1.
5
"
x
4
"
1.
5
"
x
4
"
ACC1
CR6C15
CR6C14CR6C13CR6C12CR6C11CR6C10CR6C09
CR6C08
ACC1
ACC1
PD6C00
1.
5
"
x
4
"
F
I
E
L
D
W
I
R
I
N
G
RA
C
K
1
S
0
2
50
6
9
-
I
B
1
6
RA
C
K
1
S
0
3
50
6
9
-
O
B
1
6
RA
C
K
1
S
0
4
50
6
9
-
I
F
8
ACC1
ACC3
ACC5
ACC1
ACC3
3" x 4"
ACC
1
ACC
3
ACC
5
ACC1
ACC3
ACC1
ACC3
CONTRACTOR TO VERIFY BACKPANEL DETAILS PRIOR TO CONSTRUCTION OF PANEL
85
8
345
8
391
8
11
8
4
73
4
221
2
10
24
293
4
1 2 22
105
8
7 8
14
1 8
14
1 2
427
8
501
2
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1F.2 1"=6"
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION PANEL LAYOUT INTERIOR DIMENSIONS.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
PANEL LAYOUT INTERIOR DIMENSIONS
9 31
CITY OF CARLSBAD
0"3"6"12"
0
0
101
2
RACK 1
DUCT-DC
DUCT-AC
TOP VIEW LOOKING DOWN
NOTE: FRONT OF PANEL
HEAT DISSIPATION AREA
OIT01
BAT4A03
RESERVED
FLOOR SPACE
FOR CONDUIT
ENTRY
15
91
2
233
8
201
4
134
28
1 4
30
1 8
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1F.3 1"=6"
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION PANEL LAYOUT INTERIOR TOP VIEW.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
PANEL LAYOUT INTERIOR TOP VIEW
10 31
CITY OF CARLSBAD
0"3"6"12"
CONTRACTOR TO VERIFY BACKPANEL DETAILS PRIOR TO CONSTRUCTION OF PANEL
0
0 27
27
50
54
4
26
3 414
Ø3
8
NOTE: 12 AWG MILD STEEL, PAINTED WHITE
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1F.4 1"=6"
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION CUSTOM BACKPANEL.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
CUSTOM BACKPANEL
11 31
CITY OF CARLSBAD
TB-BATT-1
Number Jumper Manufacturer Part #
TB-BATT-1 PHOENIX
CONTACT
1004348
ACC1 PHOENIX
CONTACT
0800886
4A01 AB 1492-L6
4A02 AB 1492-L6
4A03 AB 1492-L6
ACC2 AB 1492-EBL6
ACC3 PHOENIX
CONTACT
0800886
TB-DOOR
Number Jumper Manufacturer Part #
TB-DOOR PHOENIX
CONTACT
1004348
ACC1 PHOENIX
CONTACT
0800886
5A01 AB 1492-L3
5A02 AB 1492-L3
5A03 AB 1492-L3
5A04 AB 1492-L3
5A05 AB 1492-L3
ACC2 AB 1492-EBL3
ACC3 PHOENIX
CONTACT
0800886
TB-DC-1
Number Jumper Manufacturer Part #
TB-DC-1 PHOENIX
CONTACT
1004348
ACC1 PHOENIX
CONTACT
0800886
4A10-AB 1492-L3
4A11-AB 1492-L3
4A12-AB 1492-L3
4A13-AB 1492-L3
4A14-AB 1492-L3
4A15-AB 1492-L3
4A16-AB 1492-L3
4A17-AB 1492-L3
4A18-AB 1492-L3
4A19-AB 1492-L3
4A20-AB 1492-L3
4A30-AB 1492-L3
4A31-AB 1492-L3
4A32-AB 1492-L3
4A33-AB 1492-L3
ACC2 AB 1492-EBL3
ACC3 PHOENIX
CONTACT
0800886
4A30+AB 1492-L3
4A31+AB 1492-L3
4A32+AB 1492-L3
4A33+AB 1492-L3
ACC4 AB 1492-EBL3
ACC5 PHOENIX
CONTACT
0800886
TB-AC-1
Number Jumper Manufacturer Part #
TB-AC-1 PHOENIX
CONTACT
1004348
ACC1 PHOENIX
CONTACT
0800886
3A01N AB 1492-L3
3A02N AB 1492-L3
3A03N AB 1492-L3
ACC2 AB 1492-EBL3
ACC3 PHOENIX
CONTACT
0800886
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1G NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION TERMINAL STRIP DETAIL.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
TERMINAL STRIP DETAIL
12 31
CITY OF CARLSBAD
TB-DI-1
Number Jumper Manufacturer Part #
TB-DI-1 PHOENIX
CONTACT
1004348
ACC1 PHOENIX
CONTACT
0800886
6A00A AB 1492-L3
6A00B AB 1492-L3
6A01A AB 1492-L3
6A01B AB 1492-L3
6A02A AB 1492-L3
6A02B AB 1492-L3
6A03A AB 1492-L3
6A03B AB 1492-L3
6A04A AB 1492-L3
6A04B AB 1492-L3
6A05A AB 1492-L3
6A05B AB 1492-L3
6A06A AB 1492-L3
6A06B AB 1492-L3
6A07A AB 1492-L3
6A07B AB 1492-L3
6A08A AB 1492-L3
6A08B AB 1492-L3
6A09A AB 1492-L3
6A09B AB 1492-L3
6A10A AB 1492-L3
6A10B AB 1492-L3
6A11A AB 1492-L3
6A11B AB 1492-L3
6A12A AB 1492-L3
6A12B AB 1492-L3
6A13A AB 1492-L3
6A13B AB 1492-L3
6A14A AB 1492-L3
6A14B AB 1492-L3
6A15A AB 1492-L3
6A15B AB 1492-L3
ACC2 AB 1492-EBL3
ACC3 PHOENIX
CONTACT
0800886
6B00A AB 1492-L3
6B00B AB 1492-L3
6B01A AB 1492-L3
6B01B AB 1492-L3
6B02A AB 1492-L3
6B02B AB 1492-L3
6B03A AB 1492-L3
6B03B AB 1492-L3
6B04A AB 1492-L3
6B04B AB 1492-L3
6B05A AB 1492-L3
6B05B AB 1492-L3
6B06A AB 1492-L3
6B06B AB 1492-L3
6B07A AB 1492-L3
6B07B AB 1492-L3
6B08A AB 1492-L3
6B08B AB 1492-L3
6B09A AB 1492-L3
6B09B AB 1492-L3
6B10A AB 1492-L3
6B10B AB 1492-L3
6B11A AB 1492-L3
6B11B AB 1492-L3
6B12A AB 1492-L3
6B12B AB 1492-L3
6B13A AB 1492-L3
6B13B AB 1492-L3
6B14A AB 1492-L3
TB-DI-1
Number Jumper Manufacturer Part #
6B14B AB 1492-L3
6B15A AB 1492-L3
6B15B AB 1492-L3
ACC4 AB 1492-EBL3
ACC5 PHOENIX
CONTACT
0800886
TB-DO-1
Number Jumper Manufacturer Part #
TB-DO-1 PHOENIX
CONTACT
1004348
ACC1 PHOENIX
CONTACT
0800886
6C08A AB 1492-L3
6C08B AB 1492-L3
6C09A AB 1492-L3
6C09B AB 1492-L3
6C10A AB 1492-L3
6C10B AB 1492-L3
6C11A AB 1492-L3
6C11B AB 1492-L3
6C12A AB 1492-L3
6C12B AB 1492-L3
6C13A AB 1492-L3
6C13B AB 1492-L3
6C14A AB 1492-L3
6C14B AB 1492-L3
6C15A AB 1492-L3
6C15B AB 1492-L3
6CV1+AB 1492-L3
6CV1-AB 1492-L3
ACC2 AB 1492-EBL3
ACC3 PHOENIX
CONTACT
0800886
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1H NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION TERMINAL STRIP DETAIL DIGITAL.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
TERMINAL STRIP DETAIL DIGITAL
13 31
CITY OF CARLSBAD
TB-AI-1
Number Jumper Manufacturer Part #
TB-AI-1 PHOENIX
CONTACT
1004348
ACC1 PHOENIX
CONTACT
0800886
GND AB 1492-LG3
6D00+AB 1492-L3P
6D00-AB 1492-L3
6D00B AB 1492-L3
6D00A AB 1492-L3
6D00G AB 1492-LG3
6D01+AB 1492-L3P
6D01-AB 1492-L3
6D01B AB 1492-L3
6D01A AB 1492-L3
6D01G AB 1492-LG3
6D02+AB 1492-L3P
6D02-AB 1492-L3
6D02B AB 1492-L3
6D02A AB 1492-L3
6D02G AB 1492-LG3
6D03+AB 1492-L3P
6D03-AB 1492-L3
6D03B AB 1492-L3
6D03A AB 1492-L3
6D03G AB 1492-LG3
6D04+AB 1492-L3P
6D04-AB 1492-L3
6D04B AB 1492-L3
6D04A AB 1492-L3
6D04G AB 1492-LG3
6D05+AB 1492-L3P
6D05-AB 1492-L3
6D05B AB 1492-L3
6D05A AB 1492-L3
6D05G AB 1492-LG3
6D06+AB 1492-L3P
6D06-AB 1492-L3
6D06B AB 1492-L3
6D06A AB 1492-L3
6D06G AB 1492-LG3
6D07+AB 1492-L3P
6D07-AB 1492-L3
6D07B AB 1492-L3
6D07A AB 1492-L3
6D07G AB 1492-LG3
ACC2 AB 1492-EBL3
ACC3 PHOENIX
CONTACT
0800886
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1I NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION TERMINAL STRIP DETAIL ANALOG.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
TERMINAL STRIP DETAIL ANALOG
14 31
CITY OF CARLSBAD
TB-DO-RELAYBREAKERS
RA
C
K
1
S
0
4
50
6
9
-
I
F
8
RA
C
K
1
S
0
3
50
6
9
-
O
B
1
6
RA
C
K
1
S
0
2
50
6
9
-
I
B
1
6
RACK1
RA
C
K
1
S
0
1
50
6
9
-
I
B
1
6
RACK1S00
5069-L320ER
CB3A03
CB3A02
CB3A01
CB3A00
PD6C00
CR6C08
CR6C09
CR6C10
CR6C11
CR6C12
CR6C13
CR6C14
CR6C15
CB
4
A
2
0
CB
4
A
1
9
CB
4
A
1
8
CB
4
A
1
7
CB
4
A
1
6
CB
4
A
1
5
CB
4
A
1
4
CB
4
A
1
3
CB
4
A
1
2
CB
4
A
1
1
CB
4
A
1
0
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1J NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION PANEL COMPONENT DETAIL.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
PANEL COMPONENT DETAIL
15 31
CITY OF CARLSBAD
7"
1"TERRAMAR
120VAC FROM: LP-XXX CKT XX
NOTE: LABEL TO BE CONSTRUCTED
AT A LATER TIME
NOTE: LABELS TO BE ENGRAVED TWO-LAYER UV
STABILIZED MATERIAL WITH WHITE TEXT NO LESS
THAN 14" HIGH ON BLACK BACKGROUND
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1K.1 2:1
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION NAMEPLATE DETAIL 1.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
NAMEPLATE DETAIL (PART 1)
16 31
CITY OF CARLSBAD
2"
1"
1"
1
2"
UPS4A02
LSA3A01
RECP3A01
RACK1
CB3A00
CB3A01
CB3A02
CB3A03
NOTE: IDENTIFICATION LABELS FOR COMPONENTS TO BE MOUNTED ON THE BACK
PANEL NEXT TO THE COMPONENT AS SHOWN ON THE PANEL LAYOUT INTERIOR
DETAILS SHEET. LABELS TO BE SELF ADHESIVE POLYESTER WITH THERMAL
PRINTED BLACK TEXT NO LESS THAN 1/4" HIGH.
CB4A10
CB4A11
CB4A12
CB4A13
CB4A14
CB4A15
CB4A16
CB4A17
CB4A18
CB4A19
CB4A20
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1K.2 2:1
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION NAMEPLATE DETAIL 2.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
NAMEPLATE DETAIL (PART 2)
17 31
CITY OF CARLSBAD
13
4"
1
4"
TB-DC-1
TB-AC-1
TB-BATT-1
TB-DI-1
TB-AI-1
TB-DOOR
TB-DO-RELAY
UPS4A01
PSU4A01
TB-DO-1
NOTE: IDENTIFICATION LABELS FOR DIN RAIL MOUNTED COMPONENTS TO BE
MOUNTED ON THE END BRACKET NEXT TO THE COMPONENT OR TERMINAL STRIP.
LABELS TO BE MOUNTED ON THE LEFT OF HORIZONTAL DIN RAIL MOUNTED
COMPONENTS AND ABOVE VERTICAL DIN RAIL MOUNTED COMPONENTS. LABELS
TO BE SELF ADHESIVE POLYESTER WITH THERMAL PRINTED BLACK TEXT NO LESS
THAN 1/8" HIGH.
TSTAT6B01
ROUTER
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
1K.3 2:1
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION NAMEPLATE DETAIL 3.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
NAMEPLATE DETAIL (PART 3)
18 31
CITY OF CARLSBAD
FIBER ETHERNET
COPPER ETHERNET
-USB
AB
SLOT 0
CPU MODULE
RACK 1
RACK1S00
5069-L320ER
USB
-
ETH 1
LINK 1
-
ETH 2
LINK 2
PROVIDED BY CUSTOMER
PROVIDED BY CUSTOMER
1
2
SHT 4A.2-B4
OIT01
43
21
SHT 4A.2-B4
ROUTER
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
2A NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION NETWORK WIRING.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
NETWORK WIRING
19 31
CITY OF CARLSBAD
3A01N
TB-AC-1
3A02N
TB-AC-1
3A03N
TB-AC-1
20A
SHT 4A.2-E1,SHT 4A.2-F1
CB3A00
10A
CB3A01
PSU4A01
3A01L
to SHT 4A.1-A1
PSU4A01
3A01N
to SHT 4A.1-A1
L
LOADLINE
G
N
L
LSA3A01
SURGE SUPRESSOR
INPUT TRANSIENT VOLTAGE
N
G
4A
CB3A02
4A
CB3A03
GND
RECP3A01
3A00L 3A00A
3A01L
3A02L
3A01N
3A02N
3A00N 3A00N
GROUND BAR
from SHT 3A-B2
NOTE 1: 120VAC 1-PH/60HZ WITH FACILITY GROUND, SUPPLY
NOT TO EXCEED 20 AMPS SERVICE
GND
TB-AI-1
SEL
CB AUX CONTACT MODE
SELECTOR ROTARY SWITCH
FOR CB3A00
3A03L 3A03N
RACK1 SLOT 3 DO RELAYS
3A03L
to SHT 6C-E1
RACK1 SLOT 3 DO RELAYS
3A03N
to SHT 6C-F1
CONTACT 4.XX ELECTRICAL TRIP
CONTACT 1.XX GENERAL TRIP
RED #12 AWG MTW
WHT #12 AWG MTW
ORG #12 AWG MTW
CUSTOMER SUPPLY #1
*SEE NOTE 1
L
N
G
GND3A01
GROUND BAR
3A01A 3A01B
RECP3A01
to SHT 3A-E2
PSU4A01
to SHT 4A.1-A1
RACK1S00 SA POWER
to SHT 4A.2-C3
ROUTER
to SHT 4A.2-C4
NOA2A1 SHT 6B-C4
AC POWER FAILCR3A00
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
3A NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION AC POWER DISTRIBUTION.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
AC POWER DISTRIBUTION
20 31
CITY OF CARLSBAD
24VDC
DC-1 POWER SUPPLY
PSU4A01
L2
/
N
GN
D
L
-+
24VDC
4A01+
to SHT 4A.2-A1
N-DC
4A01-
to SHT 4A.2-D1
4A01
TB-BATT-1
4A02
TB-BATT-1
4A03-
4A04+4A04-4A02-
4A05A 4A06A
4A05B 4A06B
4A05C
4A30B 4A07A
4A30-4A07B
4A01-
UPS4A01 INHIBIT
4A30B
from SHT 4A.2-F1
N-DC
4A30-
from SHT 4A.2-G1
120VAC
3A01L
from SHT 3A-D1
3A01L
120N
3A01N
from SHT 3A-E1
3A01N
4A00+4A00-
24VDC
4A06A
to SHT 6B-C4
UPS4A01 ON BATTERY
4A06B
to SHT 6B-D4
24VDC
4A07A
to SHT 6B-C4
UPS4A01 BATTERY FAIL
4A07B
to SHT 6B-D4
GROUND BAR
from SHT 3A-B2
PULS
DC UPS MODULE
PULSUB20.241
UPS4A01
+INPUT -
+
-
11
12
13
+
OUTPUT -
3
1
2
5
6
BATTERY READY
REPLACE
BATTERY
TEMP
RTN
CENTER TAP
+
-
4
INHIBIT
BUFFERING
BATTERY SENSOR
MODULE
UPS4A02
11
12
13
TEMP
RTN
CENTER TAP
E1
4A01+
4A05D
30S
1m
3m
10m
10s
BUFFER TIME
LIMITER
BUFFER
VOLTAGE
DC UPS SWITCH SETTINGS
25 26
24 22.5
BATTERY
SIZE
>10 AH
<10 AH
BLUE
#10 AWG MTW
WHT/BLUE
#10 AWG MTW
12V
20AH
+-
BAT4A03
BLU #10 AWG MTW WHT/BLU #10 AWG MTW
WHT/BLU #10 AWG MTW
4A02+4A03+
4A03
TB-BATT-1
30A
CB4A50
12V
20AH
-+
BAT4A03
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
4A.1 NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION DC POWER DISTRIBUTION 1 (PART 1).dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
DC POWER DISTRIBUTION (PART 1)
21 31
CITY OF CARLSBAD
4A30+
TB-DC-1
4A31+
TB-DC-1
4A32+
TB-DC-1
4A33+
TB-DC-1
4A30-
TB-DC-1
4A31-
TB-DC-1
4A32-
TB-DC-1
4A33-
TB-DC-1
4A10-
TB-DC-1
4A11-
TB-DC-1
4A12-
TB-DC-1
4A13-
TB-DC-1
4A14-
TB-DC-1
4A15-
TB-DC-1
4A16-
TB-DC-1
UPS4A01 INHIBIT
4A30B
to SHT 4A.1-A4
UPS4A01 INHIBIT
4A30-
to SHT 4A.1-A4
RACK1 DI SLOT 01
4A10+
to SHT 6A-B1
4A17-
TB-DC-1
TB-AI-1
4A13+
to SHT 6D-A1
TB-AI-1
4A13-
to SHT 6D-A1
INTRUSION
4A33+
to SHT 5A-C1
INTRUSION
4A33-
to SHT 5A-F1
RACK1 DO SLOT 03
4A12+
to SHT 6C-A1
RACK1 DO SLOT 03
4A12-
to SHT 6C-E1
24VDC
4A01+
from SHT 4A.1-A6
N-DC
4A01-
from SHT 4A.1-C6
4A20-
TB-DC-1
4A30+
4A13+
4A33+
4A30A
4A12-
4A30-
4A13-
4A33-
4A01-
RACK1 DI SLOT 02
4A11+
to SHT 6B-B1
4A30B
24VDC
4A20+
from SHT 4A.2-B4
4A20+
N-DC
from SHT 4A.2-D4
4A20+
to SHT 4A.2-E1
N-DC
to SHT 4A.2-H1
SHT 2A-C5
1112
OIT01
4A18-
TB-DC-1
4A19-
TB-DC-1
2A
CB4A14
0.5A
CB4A10
0.5A
CB4A11
6A
CB4A12
2A
CB4A13
6A
CB4A15
4A
CB4A16
2A
CB4A17
2A
CB4A18
4A
CB4A19
6A
CB4A20
4A11+
4A12+
4A19+
4A10+
4A20+
4A19-
4A01+
GROUND BAR
from SHT 3A-B3
4A15-
4A18+4A18-
4A15+
GROUND BAR
from SHT 3A-B3
4A16+4A16-
SHT 2A-D3
G
RTV
ROUTER
4241
SHT 3A-C1
CB3A00
1211
SHT 3A-C1
CB3A00
MOD POWER SHT 2A-C1
-+
RACK1S00
SA POWER SHT 2A-C1
G
-+
RACK1S00
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
4A.2 NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION DC POWER DISTRIBUTION 1 (PART 2).dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
DC POWER DISTRIBUTION (PART 2)
22 31
CITY OF CARLSBAD
24VDC
4A33+
from SHT 4A.2-F2
4A33+
N-DC
4A33-
from SHT 4A.2-G2
4A33-
5A03A 5A04
PANEL INTRUSION
5A04
to SHT 6B-D5
5A01
TB-DOOR
5A01 5A02
TB-DOOR
5A02
5A03
TB-DOOR
5A04
TB-DOOR
5A05
TB-DOOR
5A05
5A08
24VDC
5A08
to SHT 6B-C5
5A01A
5A03 5A04
DOOR SWITCH
ENCLOSURE
SW5A01
ENCLOSURE LIGHT 1
24VDC
LT5A01
BLU #16 AWG MTW
BLU #16 AWG MTW BLU #16 AWG MTW
WHT/BLU #16 AWG MTW
BLU #18 AWG MTWBLU #18 AWG MTWBLU #18 AWG MTW
BLU #18 AWG MTW
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
5A NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION PANEL IO DETAIL.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
PANEL I/O DETAIL
23 31
CITY OF CARLSBAD
6A00A
TB-DI-1
6A01A
TB-DI-1
6A02A
TB-DI-1
6A03A
TB-DI-1
6A04A
TB-DI-1
6A05A
TB-DI-1
6A06A
TB-DI-1
6A07A
TB-DI-1
6A08A
TB-DI-1
6A09A
TB-DI-1
6A10A
TB-DI-1
6A11A
TB-DI-1
6A12A
TB-DI-1
6A13A
TB-DI-1
6A14A
TB-DI-1
6A15A
TB-DI-1
6A00B
TB-DI-1
6A01B
TB-DI-1
6A02B
TB-DI-1
6A03B
TB-DI-1
6A04B
TB-DI-1
6A05B
TB-DI-1
6A06B
TB-DI-1
6A07B
TB-DI-1
6A08B
TB-DI-1
6A09B
TB-DI-1
6A10B
TB-DI-1
6A11B
TB-DI-1
6A12B
TB-DI-1
6A13B
TB-DI-1
6A14B
TB-DI-1
6A15B
TB-DI-1
24VDC
4A10+
from SHT 4A.2-B1
4A10+
6A00
6A01
6A02
6A03
6A04
6A05
6A06
6A07
6A08
6A09
6A10
6A11
6A12
6A13
6A14
6A15
NOTE: ALL PANEL WIRING ON TB-DI-1 SHALL TERMINATE ONLY
ON THE PANEL SIDE OF THE TERMINAL. DO NOT TERMINATE
PANEL WIRING ON THE FIELD SIDE OF THE TERMINAL.
0
-
Pump 1
5069-IB16
AB
SLOT 1
RACK1S01
16-POINT DISCRETE INPUT
RACK 1
General FaultIN 0
1
-
Pump 1
High TemperatureIN 1
2
-
Pump 1
RemoteIN 2
3
-
Pump 1
Seal FailIN 3
4
-
Pump 1
RunningIN 4
5
-
Spare
IN 5
6
-
Spare
IN 6
7
-
Spare
IN 7
8
-
High High Wet Well
LevelIN 8
9
-
Low Low Wet Well
LevelIN 9
10
-
High Wet Well
LevelIN 10
11
-
Low Wet Well
LevelIN 11
12
-
Spare
IN 12
13
-
Spare
IN 13
14
-
Spare
IN 14
15
-
Spare
IN 15
16NC
17NC
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
6A NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION RACK1S01.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
RACK 1 SLOT 1 DISCRETE INPUT
24 31
CITY OF CARLSBAD
6B00A
TB-DI-1
6B01A
TB-DI-1
6B02A
TB-DI-1
6B03A
TB-DI-1
6B04A
TB-DI-1
6B05A
TB-DI-1
6B06A
TB-DI-1
6B07A
TB-DI-1
6B08A
TB-DI-1
6B09A
TB-DI-1
6B10A
TB-DI-1
6B11A
TB-DI-1
6B12A
TB-DI-1
6B13A
TB-DI-1
6B14A
TB-DI-1
6B15A
TB-DI-1
6B00B
TB-DI-1
6B01B
TB-DI-1
6B02B
TB-DI-1
6B03B
TB-DI-1
6B04B
TB-DI-1
6B05B
TB-DI-1
6B06B
TB-DI-1
6B07B
TB-DI-1
6B08B
TB-DI-1
6B09B
TB-DI-1
6B10B
TB-DI-1
6B11B
TB-DI-1
6B12B
TB-DI-1
6B13B
TB-DI-1
6B14B
TB-DI-1
6B15B
TB-DI-1
24VDC
4A11+
from SHT 4A.2-B1
4A11+
6B00
6B01
6B02
6B03
6B04
6B05
6B06
6B07
6B08
6B09
6B10
6B11
6B12
6B13
6B14
6B15
NOTE: ALL PANEL WIRING ON TB-DI-1 SHALL TERMINATE ONLY
ON THE PANEL SIDE OF THE TERMINAL. DO NOT TERMINATE
PANEL WIRING ON THE FIELD SIDE OF THE TERMINAL.
5A04
from SHT 5A-F2
5A08
from SHT 5A-C2
5A08 5A04
4A06A
from SHT 4A.1-C4
4A06B
from SHT 4A.1-C4
4A07A
from SHT 4A.1-C4
4A07B
from SHT 4A.1-C4
4A06A
4A07A
4A06B
4A07B
21
TSTAT6B016B10A 6B10B
6B11A 6B11B1413
SHT 3A-E2
CR3A00
0
-
Pump 2
5069-IB16
AB
SLOT 2
RACK1S02
16-POINT DISCRETE INPUT
RACK 1
General FaultIN 0
1
-
Pump 2
High TemperatureIN 1
2
-
Pump 2
RemoteIN 2
3
-
Pump 2
Seal FailIN 3
4
-
Pump 2
RunningIN 4
5
-
Spare
IN 5
6
-
Spare
IN 6
7
-
Spare
IN 7
8
-
Station
IntrusionIN 8
9
-
Spare
IN 9
10
-
Control Panel
High TemperatureIN 10
11
-
Control Panel
AC Power FailIN 11
12
-
Control Panel UPS
On BatteryIN 12
13
-
Control Panel UPS
FailureIN 13
14
-
Spare
IN 14
15
-
Control Panel
IntrusionIN 15
16NC
17NC
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
6B NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION RACK1S02.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
RACK 1 SLOT 2 DISCRETE INPUT
25 31
CITY OF CARLSBAD
6C08B
TB-DO-1
6C09B
TB-DO-1
6C10B
TB-DO-1
6C11B
TB-DO-1
6C12B
TB-DO-1
6C13B
TB-DO-1
6C14B
TB-DO-1
6C15B
TB-DO-1
6CV1+
TB-DO-1
6CV1-
TB-DO-1
6C08A
TB-DO-1
6C09A
TB-DO-1
6C10A
TB-DO-1
6C11A
TB-DO-1
6C12A
TB-DO-1
6C13A
TB-DO-1
6C14A
TB-DO-1
6C15A
TB-DO-1
6C08
6C09
6C10
6C11
6C12
6C13
6C14
6C15
N-DC
4A12-
from SHT 4A.2-C2
4A12-
24VDC
4A12+
from SHT 4A.2-B2
4A12+
A2A1
CR6C08
A2A1
CR6C09
A2A1
CR6C10
A2A1
CR6C11
A2A1
CR6C12
A2A1
CR6C13
A2A1
CR6C14
A2A1
CR6C15
6C08A
6C09A
6C10A
6C11A
6C12A
6C13A
6C14A
6C15A
6C08B
6CV1+
6CV1-6CV1-
BB
CR6C08
BB
CR6C09
BB
CR6C10
BB
CR6C11
BB
CR6C12
BB
CR6C13
BB
CR6C14
BB
CR6C15
1 2 43
A1 A2 BB 1413
PANEL
PANEL
FIELD
FIELD
TOP
2966508 RELAY POWER DISTRIBUTION DETAIL
2909661 RELAY DETAIL
43
RELAY POWER DISTRIBUTION
PD6C00120VAC
3A03L
from SHT 3A-D3
120N
3A03N
from SHT 3A-E3
3A03N
NOTE: ALL PANEL WIRING ON TB-DO-1 SHALL TERMINATE ONLY
ON THE PANEL SIDE OF THE TERMINAL. DO NOT TERMINATE
PANEL WIRING ON THE FIELD SIDE OF THE TERMINAL.
3A03L
1413
CR6C08
1413
CR6C09
1413
CR6C10
1413
CR6C11
1413
CR6C12
1413
CR6C13
1413
CR6C14
1413
CR6C15
0
-
Spare
AB
SLOT 3
16-POINT DISCRETE OUTPUT
RACK 1
RACK1S03
5069-OB16
OUT 0
1
-
Spare
OUT 1
2
-
Spare
OUT 2
3
-
Spare
OUT 3
4
-
Spare
OUT 4
5
-
Spare
OUT 5
6
-
Spare
OUT 6
7
-
Spare
OUT 7
8
-
Pump 1
Start OUT 8
9
-
Pump 2
Start OUT 9
10
-
Spare
OUT 10
11
-
Sprayer
(Future)
Start OUT 11
12
-
Spare
OUT 12
13
-
Spare
OUT 13
14
-
Spare
OUT 14
15
-
Spare
OUT 15
16LA+
17 LA-
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
6C NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION RACK1S03.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
RACK 1 SLOT 3 DISCRETE OUTPUT
26 31
CITY OF CARLSBAD
6D00B
TB-AI-1
6D01B
TB-AI-1
6D02B
TB-AI-1
6D03B
TB-AI-1
6D00-
TB-AI-1
6D01-
TB-AI-1
6D02-
TB-AI-1
6D03-
TB-AI-1
6D00B
6D01A
6D01B
6D02A
6D02B
6D03B
24VDC
to SHT 6D-E1
N-DC
to SHT 6D-E1
TB-AI-1
4A13+
from SHT 4A.2-B2
TB-AI-1
4A13-
from SHT 4A.2-C24A13+
6D00+
TB-AI-1
63mA
6D01+
TB-AI-1
63mA
6D03+
TB-AI-1
63mA
6D02+
TB-AI-1
63mA
SHLD
6D00G
TB-AI-1
6D01G
TB-AI-1
6D02G
TB-AI-1
6D03G
TB-AI-1
SHLD
SHLD
4A13-
+-
+-
+-
SHLD
+-
6D00A
TB-AI-1
6D00A
6D01A
TB-AI-1
6D02A
TB-AI-1
6D03A
TB-AI-1
6D03A
6D04B
TB-AI-1
6D05B
TB-AI-1
6D06B
TB-AI-1
6D07B
TB-AI-1
6D04-
TB-AI-1
6D05-
TB-AI-1
6D06-
TB-AI-1
6D07-
TB-AI-1
6D04A
6D04B
6D05A
6D05B
6D06A
6D06B
6D07A
6D07B
24VDC
from SHT 6D-A6
N-DC
from SHT 6D-A6
6D04+
TB-AI-1
63mA
6D05+
TB-AI-1
63mA
6D07+
TB-AI-1
63mA
6D06+
TB-AI-1
63mA
6D04G
TB-AI-1
6D05G
TB-AI-1
6D06G
TB-AI-1
6D07G
TB-AI-1
SHLD
SHLD
SHLD
SHLD
+-
+-
+-
+-
6D04A
TB-AI-1
6D05A
TB-AI-1
6D06A
TB-AI-1
6D07A
TB-AI-1
0
-
Wet Well
5069-IF8
AB
SLOT 4
RACK1S04
8 CHANNEL ANALOG INPUT
RACK 1
LevelIN 0+
1IN 0-
2
-
Discharge
FlowIN 1+
3IN 1-
4
-
Spare
IN 2+
5IN 2-
6
-
Discharge
(Future)
PressureIN 3+
7IN 3-
16SHLD
8
-
Spare
IN 4+
9IN 4-
10
-
Spare
IN 5+
11IN 5-
12
-
Spare
IN 6+
13IN 6-
14
-
Spare
IN 7+
15IN 7-
17SHLD
RACK1S04
WIRE JUMPER
WIRE JUMPER
WIRE JUMPER
WIRE JUMPER
WIRE JUMPER
WIRE JUMPER
WIRE JUMPER
WIRE JUMPER
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
6D NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION RACK1S04.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
RACK 1 SLOT 4 ANALOG INPUT
27 31
CITY OF CARLSBAD
MANUFACTURER PART #QTY DESCRIPTION TAGS
AB 1492-CJK5-50 6 50 IEC CENTER JUMPER, 10 PL 5mm, PLUG-IN
HARDWARE
TB-AC-1
TB-DC-1
TB-DI-1
TB-DO-1
AB 1492-CJL8-2 1 2 IEC CENTER JUMPER, 2 PL 8mm, PLUG-IN, YELLOW
HARDWARE
TB-BATT-1
AB 1492-EBL3 8 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS
HARDWARE
GREY
TB-AC-1
TB-AI-1
TB-DC-1
TB-DI-1
TB-DO-1
TB-DOOR
AB 1492-EBL6 1 END BARRIER COMPATIBLE WITH 1492-L6 TYPE TERMINALS
HARDWARE
GREY
TB-BATT-1
AB 1492-FPK224 8 TERMINAL ACCESSORY 1492, BLACK
FUSE PLUG
LED INDICATOR, RATED VOLTAGE 10-36VAC/DC, LEAKAGE CURRENT 1.6mA AT 24VDC
FUSE ACCESSORY WITH BLOWN FUSE INDICATION
TB-AI-1
AB 1492-L3 133 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, 30-12AWG
FEED-THROUGH
GRAY COLOR, 30-12AWG, RATED VOLTAGE 600VAC/DC
ONE-CIRCUIT FEED-THROUGH BLOCK
TB-AC-1
TB-AI-1
TB-DC-1
TB-DI-1
TB-DO-1
TB-DOOR
AB 1492-L3P 8 TERMINAL BLOCK 1492, GRAY
FUSE BLOCK
GREY COLOR, 30-12 AWG, RATED VOLTAGE 600VAC/DC
SINGLE CIRCUIT FUSE TERMINAL BLOCK WITH BLOWN INDICATION
TB-AI-1
AB 1492-L6 3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, 22-8AWG
FEED-THROUGH
GRAY COLOR, 22-8AWG, RATED VOLTAGE 600VAC/DC
ONE-CIRCUIT FEED-THROUGH BLOCK
TB-BATT-1
AB 1492-LG3 9 IEC SPRING CLAMP TERMINAL BLOCK, GROUNDING BLOCK, 1492-L
FEED-THROUGH GROUND
GREEN / YELLOW COLOR, 30-12AWG
ONE-CIRCUIT FEED-THROUGH GROUND BLOCK
TB-AI-1
AB 1492-M5X10 300 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L
TERMINAL
TB-AC-1
TB-AI-1
TB-DC-1
TB-DI-1
TB-DO-1
TB-DOOR
AB 1492-M6X12 6 TERMINAL LABEL, 6mm X 12mm, INDIVIDUAL, SNAP ON, 1492-L
TERMINAL
TB-BATT-1
AB 5069-ECR 1 5069 COMPACTLOGIX/COMPACT GUARDLOGIX RIGHT END CAP WITH ADAPTER
5069
RACK1ECR
AB 5069-IB16 2 5069 COMPACT I/O 16 CHANNEL 24V DC SINK INPUTE MODULE
5069 COMPACTLOGIX
RACK1S01
RACK1S02
AB 5069-IF8 1 5069 COMPACT I/O 8 CHANNEL VOLTAGE/CURRENT ANALOG INPUT MODULE
5069 COMPACTLOGIX
RACK1S04
AB 5069-L320ER 1 COMPACTLOGIX 5380, 2 MB USER MEMORY, 16 I/Os, 40 ETHERNET/IP DEVICES
5069 COMPACTLOGIX
RACK1S00
AB 5069-OB16 1 5069 COMPACT I/O 16 CHANNEL 24V DC SOURCE OUTPUT MODULE
5069 COMPACTLOGIX
RACK1S03
AB 5069-RTB18-SCREW 4 18 PIN SCREW TYPE TERMINAL CONNECTOR
5069 COMPACTLOGIX
RACK1S03
RACK1S04
RACK1S01
RACK1S02
AB 5069-RTB4-SCREW 1 4 PIN SCREW TYPE POWER TERMINAL CONNECTOR
5069 COMPACTLOGIX
RACK1S00
AB 5069-RTB6-SCREW 1 6 PIN SCREW TYPE POWER TERMINAL CONNECTOR
5069 COMPACTLOGIX
RACK1S00
BANNER WLB32C285PBQ 1 WLB32 ADJUSTABLE LED WORKSTATION LIGHT
24VDC
LT5A01
CBI QY-1-13-DM-U2-0.5A 1 CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 0.5A 80V 1 POLE
1-POLE CIRCUIT BREAKER
CB4A11
MANUFACTURER PART #QTY DESCRIPTION TAGS
CBI QY-1-13-DM-U2-0.5A 1 CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 0.5A 80V 1 POLE
1-POLE CIRCUIT BREAKER
CB4A10
CBI QY-1-13-DM-U2-2A 4 CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 2A 80V 1 POLE
1-POLE CIRCUIT BREAKER
CB4A17
CB4A18
CB4A13
CB4A14
CBI QY-1-13-DM-U2-30A 1 CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 30A 80V 1 POLE
1-POLE CIRCUIT BREAKER
CB4A50
CBI QY-1-13-DM-U2-4A 2 CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 4A 80V 1 POLE
1-POLE CIRCUIT BREAKER
CB4A16
CB4A19
CBI QY-1-13-DM-U2-6A 3 CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 6A 80V 1 POLE
1-POLE CIRCUIT BREAKER
CB4A20
CB4A12
CB4A15
CBI SABBM54 1 CIRCUIT BREAKER, 13MM, BUSBAR MODULE SINGLE PHASE, METAL
BUSBAR
CB4A10
CISCO ANT-4-5G4-O 1 DIRECT MOUNT OMNIDIRECTIONAL ANTENNA
ANTENNA
ROUTER
CISCO IR1101 1 ROUTER, POWER INPUT 9.6 TO 60VDC, TEMP RATING: -40 TO 60C, 4 PORT ETHERNET
NETWORK
ROUTER
DURACELL SLADC12-20C 2 LEAD-ACID BATTERY, 20AH, 12VDC, 13.3 LBS
12VDC
BAT4A03
EATON AGCF12030 1 TRANSIENT VOLTAGE SURGE SUPPRESSOR, 120VAC, 20A
120VAC
LSA3A01
EATON FAZ-D10/1-NA-SP 1 CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 10A, D CURVE
1-POLE CIRCUIT BREAKER
RATING=10A
CB3A01
EATON FAZ-D20/1-NA-SP 1 CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 20A, D CURVE
1-POLE CIRCUIT BREAKER
RATING=20A
CB3A00
EATON FAZ-D4/1-NA-SP 2 CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 4A, D CURVE
1-POLE CIRCUIT BREAKER
RATING=4A
CB3A02
CB3A03
EATON GMC-63MA 8 CARTRIDGE FUSE 63MA
FUSE
TB-AI-1
EATON Z-NHK 1 CIRCUIT BREAKER, UL 489 BRANCH, AUXILIARY SWITCH
1-POLE CIRCUIT BREAKER
CB3A00
EXISTING EXISTING CABLE 1 CAT 6 ETHERNET CABLE
CABLE
ROUTER
EXISTING EXISTING ENCLOSURE 1 EXISTING ENCLOSURE
ENCLOSURE
ENCLOSURE
HOFFMAN ALGDSTOP2 1 LARGE ENCLOSURE DOOR STOP KIT
ACCESSORY
STOP1
HUBBELL 5320-0 1 DUPLEX RECEPTACLE GANG BOX PANEL MOUNT
REC
RECP3A01
HUBBELL GFR15I 1 GFCI RECEPTACLE, 125V, 15A
REC
RECP3A01
HUBBELL SSJ26 1 GFCI RECEPTACLE COVER PLATE
REC
RECP3A01
MCMASTER CARR 90272A108 3 ZINC PLATED STEEL HEX BOLT, #4-40 X 3/8"
NA
UPS4A02
MCMASTER CARR 92150A104 6 NYLON SPACER
NA
UPS4A02
MCMASTER CARR 93505A485 3 ZINC-PLATED STEEL THREADED 1/4" HEX STANDOFF
NA
UPS4A02
ONLOGIC TC401R 1 OIT, PANEL MOUNTED TOUCHSCREEN MONITOR, 12.1" HMI, 24VDC
OIT
OIT01
PANDUIT C1.5LG6 1 WIRING DUCT COVER - GRAY 1.5" WIDE
1.5
LIGHT GRAY
DUCT-DC-1.5"
PANDUIT C1LG6 1 WIRING DUCT COVER - GRAY 1" WIDE
1
LIGHT GRAY
DUCT-AC-1"
PANDUIT C2LG6 1 WIRING DUCT COVER - GRAY 2" WIDE
2
LIGHT GRAY
DUCT-DC-2"
PANDUIT C3LG6 1 WIRING DUCT COVER - GRAY 3" WIDE
3
LIGHT GRAY
DUCT-DC-3"
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
99A.1 NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION PURCHASE LIST 1.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
PURCHASE LIST (PART 1)
28 31
CITY OF CARLSBAD
MANUFACTURER PART #QTY DESCRIPTION TAGS
PANDUIT F1.5X4LG6 1 NARROW FINGER, SLOTTED WIRING DUCT GRAY 1.5" WIDE X 4" DEEP
1.75 x 4.12
LIGHT GRAY
LEAD-FREE PVC, STANDARD MOUNTING HOLES
DUCT-DC-1.5"
PANDUIT F1X4LG6 1 NARROW FINGER, SLOTTED WIRING DUCT GRAY 1" WIDE X 4" DEEP
1.25 x 4.08
LIGHT GRAY
LEAD-FREE PVC, STANDARD MOUNTING HOLES
DUCT-AC-1"
PANDUIT F2X4LG6 1 NARROW FINGER, SLOTTED WIRING DUCT GRAY 2" WIDE X 4" DEEP
2.25 x 4.09
LIGHT GRAY
LEAD-FREE PVC, STANDARD MOUNTING HOLES
DUCT-DC-2"
PANDUIT F3X4LG6 1 NARROW FINGER, SLOTTED WIRING DUCT GRAY 3" WIDE X 4" DEEP
3.25 x 4.11
LIGHT GRAY
LEAD-FREE PVC, STANDARD MOUNTING HOLES
DUCT-DC-3"
PANEL BUILDER CUSTOM BACKPANEL 1 CUSTOM REPLACEMENT BACKPANEL FOR EXISTING ENCLOSURE
BACKPANEL
SEE SEPARTATE DETAIL DRAWING
BACKPANEL
PFANNENBERG 17111000010 1 THERMOSTAT, VOLTAGE RATING: 240VAC, DC RATING 30W, TEMP RATING: 32 TO 140 F, N.C. W/ CONTACT SPRINGS, GREY, FLZ 520
THERMOSTAT
TSTAT6B01
PHOENIX CONTACT 0800886 28 END BRACKET - E/NS 35 N
ACCESSORY
GRAY, FOR THE NS 35 DIN RAIL
9.5MM WIDTH
TB-AC-1
TB-AI-1
TB-DC-1
TB-DI-1
TB-DO-1
MISC
TB-BATT-1
TB-DOOR
PHOENIX CONTACT 1004348 7 END BRACKET LABEL FOR STRIP MARKING - KLM-A
ACCESSORY
TB-AC-1
TB-AI-1
TB-BATT-1
TB-DC-1
TB-DI-1
TB-DO-1
TB-DOOR
PHOENIX CONTACT 1134645 1 BATTERY MOUNTING CASE M, WALL AND SURFACE MOUNTING BATTERY CONTAINER
MOUNTING MATERIAL
BAT4A03
PHOENIX CONTACT 1201141 1 INSULATED DIN RAIL MOUNT
NA
DINRAIL
PHOENIX CONTACT 1201730 1 DIN RAIL
NA
DINRAIL
PHOENIX CONTACT 2909661 7 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO
RELAY
CR6C09
CR6C10
CR6C11
CR6C12
CR6C13
CR6C14
CR6C15
PHOENIX CONTACT 2909661 1 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO
RELAY
CR6C08
PHOENIX CONTACT 2966249 1 RELAY MODULE 120VAC COIL WITH BUSBAR TERMINAL 1NO
RELAY
CR3A00
PHOENIX CONTACT 2966508 1 RELAY POWER TERMINAL
POWER TERMINAL
PD6C00
PHOENIX CONTACT 2966786 3 CONTINUOUS PLUG-IN BRIDGE MECHANICAL JUMPER, 500MM, RELAY
JUMPER
CR6C08
PD6C00
PULS CP20.241 1 1-PHASE POWER SUPPLY
24VDC
INPUT: 120VAC,50/60Hz / OUTPUT: 24VDC, 20A
PSU4A01
PULS UB20.241 1 DC UPS MODULE 24VDC, 20A OUTPUT, FOR 3.9AH TO 150AH BATTERY
24VDC
UPS4A01
PULS UZS24.100 1 SENSOR BOARD FOR BATTERY MODULES
24VDC
UPS4A02
SCHNEIDER PK18GTA 1 LOAD CENTER ACCESSORY, QO/HOMELINE, GROUND BAR KIT, 18 TERMINAL
GROUND
GND3A01
SQUARE D XZCP1141L5 1 M12 4 PIN CONNECTOR 16FT CABLE
CABLE
LT5A01
MANUFACTURER PART #QTY DESCRIPTION TAGS
TELEMECANIQUE ZCE10 1 HEAD FOR LIMIT SWITCH - ZCE - STEEL END PLUNGER
COMPLETE PLUNGER HEAD
LINEAR
SW5A01
TELEMECANIQUE ZCP21 1 LIMIT SWITCH BODY - ZCP - 1 NC + 1 NO - TERMINALS
SNAP ACTION
USE WITH CABLE GLAND ENTRY
1 NC + 1 NO
SW5A01
TELEMECANIQUE ZCPEG11 1 CABLE GLAND ENTRY FOR LIMIT SWITCH
PLASTIC BODY
SW5A01
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
99A.2 NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION PURCHASE LIST 2.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
PURCHASE LIST (PART 2)
29 31
CITY OF CARLSBAD
WIRENO COMPONENT 1 PIN1 COMPONENT 2 PIN2 WIRE TYPE
DV6D07 -TB-AI-1 6D07A FIELD
TB-AI-1 6D07+DV6D07 +FIELD
DV6D06 -TB-AI-1 6D03A FIELD
TB-AI-1 6D03+DV6D06 +FIELD
DV6D05 -TB-AI-1 6D06A FIELD
TB-AI-1 6D06+DV6D05 +FIELD
DV6D04 -TB-AI-1 6D02A FIELD
TB-AI-1 6D02+DV6D04 +FIELD
DV6D03 -TB-AI-1 6D05A FIELD
TB-AI-1 6D05+DV6D03 +FIELD
DV6D02 -TB-AI-1 6D01A FIELD
TB-AI-1 6D01+DV6D02 +FIELD
DV6D01 -TB-AI-1 6D04A FIELD
TB-AI-1 6D04+DV6D01 +FIELD
DV6D00 -TB-AI-1 6D00A FIELD
TB-AI-1 6D00+DV6D00 +FIELD
CR6C15 14 DV6C15 +FIELD
CR6C15 13 DV6C15 -FIELD
CR6C14 14 DV6C14 +FIELD
CR6C14 13 DV6C14 -FIELD
CR6C13 14 DV6C13 +FIELD
CR6C13 13 DV6C13 -FIELD
CR6C12 14 DV6C12 +FIELD
CR6C12 13 DV6C12 -FIELD
CR6C11 14 DV6C11 +FIELD
CR6C11 13 DV6C11 -FIELD
CR6C10 14 DV6C10 +FIELD
CR6C10 13 DV6C10 -FIELD
CR6C09 14 DV6C09 +FIELD
CR6C09 13 DV6C09 -FIELD
CR6C08 14 DV6C08 +FIELD
CR6C08 13 DV6C08 -FIELD
DV6B08 -TB-DI-1 6B09B FIELD
TB-DI-1 6B09A DV6B08 +FIELD
DV6B07 -TB-DI-1 6B08B FIELD
TB-DI-1 6B08A DV6B07 +FIELD
DV6B06 -TB-DI-1 6B07B FIELD
TB-DI-1 6B07A DV6B06 +FIELD
DV6B05 -TB-DI-1 6B06B FIELD
TB-DI-1 6B06A DV6B05 +FIELD
DV6B04 -TB-DI-1 6B05B FIELD
TB-DI-1 6B05A DV6B04 +FIELD
DV6B03 -TB-DI-1 6B04B FIELD
TB-DI-1 6B04A DV6B03 +FIELD
DV6B02 -TB-DI-1 6B03B FIELD
TB-DI-1 6B03A DV6B02 +FIELD
DV6B02 -TB-DI-1 6B02B FIELD
TB-DI-1 6B02A DV6B02 +FIELD
DV6B01 -TB-DI-1 6B01B FIELD
TB-DI-1 6B01A DV6B01 +FIELD
DV6B00 -TB-DI-1 6B00B FIELD
TB-DI-1 6B00A DV6B00 +FIELD
DV6A15 -TB-DI-1 6A15B FIELD
TB-DI-1 6A15A DV6A15 +FIELD
DV6A14 -TB-DI-1 6A14B FIELD
TB-DI-1 6A14A DV6A14 +FIELD
DV6A13 -TB-DI-1 6A13B FIELD
TB-DI-1 6A13A DV6A13 +FIELD
DV6A12 -TB-DI-1 6A12B FIELD
TB-DI-1 6A12A DV6A12 +FIELD
WIRENO COMPONENT 1 PIN1 COMPONENT 2 PIN2 WIRE TYPE
DV6A11 -TB-DI-1 6A11B FIELD
TB-DI-1 6A11A DV6A11 +FIELD
DV6A10 -TB-DI-1 6A10B FIELD
TB-DI-1 6A10A DV6A10 +FIELD
DV6A09 -TB-DI-1 6A09B FIELD
TB-DI-1 6A09A DV6A09 +FIELD
DV6A08 -TB-DI-1 6A08B FIELD
TB-DI-1 6A08A DV6A08 +FIELD
DV6A07 -TB-DI-1 6A07B FIELD
TB-DI-1 6A07A DV6A07 +FIELD
DV6A06 -TB-DI-1 6A06B FIELD
TB-DI-1 6A06A DV6A06 +FIELD
DV6A05 -TB-DI-1 6A05B FIELD
TB-DI-1 6A05A DV6A05 +FIELD
DV6A04 -TB-DI-1 6A04B FIELD
TB-DI-1 6A04A DV6A04 +FIELD
DV6A03 -TB-DI-1 6A03B FIELD
TB-DI-1 6A03A DV6A03 +FIELD
DV6A02 -TB-DI-1 6A02B FIELD
TB-DI-1 6A02A DV6A02 +FIELD
DV6A01 -TB-DI-1 6A01B FIELD
TB-DI-1 6A01A DV6A01 +FIELD
DV6A00 -TB-DI-1 6A00B FIELD
TB-DI-1 6A00A DV6A00 +FIELD
RECP3A01 GND RACK1S00 G GREEN_14
PSU4A01 GND RECP3A01 GND GREEN_14
LSA3A01 G TB-AI-1 GND GREEN_14
TB-AI-1 GND GND3A01 GREEN_14
GND3A01 ROUTER G GREEN_14
ROUTER G PSU4A01 GND GREEN_14
GND3A01 LSA3A01 G GREEN_14
GND3A01 FIELD
LSA3A01 N FIELD
LSA3A01 L FIELD
ROUTER 1 OIT01 ORANGE_CAT6
RACK1S00 -ROUTER 3 ORANGE_CAT6
3A00A CB3A00 CB3A01 RED_12
3A00L LSA3A01 L CB3A00 ORANGE_12
3A00N LSA3A01 N TB-AC-1 3A01N WHITE_12
3A01A CB3A01 CR3A00 A1 RED_14
3A01B TB-AC-1 3A01N CR3A00 A2 WHITE_14
3A01L CB3A01 PSU4A01 L RED_14
3A01N TB-AC-1 3A01N PSU4A01 L2/N WHITE_14
3A02L CB3A02 RECP3A01 RED_14
3A02N RECP3A01 TB-AC-1 3A02N WHITE_14
3A03L CB3A03 PD6C00 3 RED_14
3A03N TB-AC-1 3A03N PD6C00 4 WHITE_14
4A00+PSU4A01 +UPS4A01 +BLUE_10
4A00-PSU4A01 -UPS4A01 -WHT_BLU_10
4A01+UPS4A01 +CB4A10 BLUE_10
4A01-UPS4A01 -TB-DC-1 4A10-WHT_BLU_10
4A02+CB4A50 UPS4A01 +BLUE_10
4A02-TB-BATT-1 4A03 UPS4A01 -WHT_BLU_10
4A03+BAT4A03 +CB4A50 BLUE_10
4A03-TB-BATT-1 4A01 BAT4A03 -WHT_BLU_10
4A04+TB-BATT-1 4A02 BAT4A03 +BLUE_10
4A04-BAT4A03 -TB-BATT-1 4A03 WHT_BLU_10
4A05A UPS4A02 11 UPS4A01 11 BLUE_16
4A05B UPS4A02 12 UPS4A01 12 BLUE_16
4A05C UPS4A02 13 UPS4A01 13 BLUE_16
WIRENO COMPONENT 1 PIN1 COMPONENT 2 PIN2 WIRE TYPE
4A05D TB-BATT-1 4A02 UPS4A02 E1 BLUE_18
4A06A UPS4A01 3 TB-DI-1 6B12A BLUE_18
4A06B UPS4A01 4 TB-DI-1 6B12B BLUE_18
4A07A UPS4A01 5 TB-DI-1 6B13A BLUE_18
4A07B UPS4A01 6 TB-DI-1 6B13B BLUE_18
4A10+CB4A10 TB-DI-1 6A00A BLUE_16
4A11+CB4A11 TB-DI-1 6B00A BLUE_16
4A12+CB4A12 TB-DO-1 6CV1+BLUE_16
4A12-TB-DC-1 4A12-TB-DO-1 6C08B WHT_BLU_16
4A13+CB4A13 TB-AI-1 6D00+BLUE_16
4A13-TB-DC-1 4A13-TB-AI-1 6D00-WHT_BLU_16
4A15+CB4A15 RACK1S00 +BLUE_16
4A15-RACK1S00 -TB-DC-1 4A15-WHT_BLU_16
4A16+CB4A16 RACK1S00 +BLUE_16
4A16-RACK1S00 -TB-DC-1 4A16-WHT_BLU_16
4A18+CB4A18 ROUTER V BLUE_16
4A18-ROUTER RT TB-DC-1 4A18-WHT_BLU_16
4A19+CB4A19 OIT01 12 BLUE_16
4A19-OIT01 11 TB-DC-1 4A19-WHT_BLU_16
4A20+CB4A20 TB-DC-1 4A30+BLUE_16
4A30+TB-DC-1 4A30+CB3A00 41 BLUE_16
4A30-TB-DC-1 4A30-UPS4A01 -WHT_BLU_16
4A30A CB3A00 42 CB3A00 11 BLUE_16
4A30B CB3A00 12 UPS4A01 +BLUE_16
4A33+TB-DC-1 4A33+TB-DOOR 5A01 BLUE_16
4A33-TB-DC-1 4A33-TB-DOOR 5A05 WHT_BLU_16
5A01 TB-DOOR 5A01 SW5A01 BLUE_16
5A01A SW5A01 TB-DOOR 5A02 BLUE_16
5A02 TB-DOOR 5A02 LT5A01 1 BLUE_16
5A03 TB-DOOR 5A03 SW5A01 BLUE_18
5A03A SW5A01 TB-DOOR 5A04 BLUE_18
5A04 TB-DOOR 5A04 TB-DI-1 6B15B BLUE_18
5A05 LT5A01 2 TB-DOOR 5A05 WHT_BLU_16
5A08 TB-DOOR 5A03 TB-DI-1 6B15A BLUE_18
6A00 TB-DI-1 6A00B RACK1S01 0 BLUE_18
6A01 TB-DI-1 6A01B RACK1S01 1 BLUE_18
6A02 TB-DI-1 6A02B RACK1S01 2 BLUE_18
6A03 TB-DI-1 6A03B RACK1S01 3 BLUE_18
6A04 TB-DI-1 6A04B RACK1S01 4 BLUE_18
6A05 TB-DI-1 6A05B RACK1S01 5 BLUE_18
6A06 TB-DI-1 6A06B RACK1S01 6 BLUE_18
6A07 TB-DI-1 6A07B RACK1S01 7 BLUE_18
6A08 TB-DI-1 6A08B RACK1S01 8 BLUE_18
6A09 TB-DI-1 6A09B RACK1S01 9 BLUE_18
6A10 TB-DI-1 6A10B RACK1S01 10 BLUE_18
6A11 TB-DI-1 6A11B RACK1S01 11 BLUE_18
6A12 TB-DI-1 6A12B RACK1S01 12 BLUE_18
6A13 TB-DI-1 6A13B RACK1S01 13 BLUE_18
6A14 TB-DI-1 6A14B RACK1S01 14 BLUE_18
6A15 TB-DI-1 6A15B RACK1S01 15 BLUE_18
6B00 TB-DI-1 6B00B RACK1S02 0 BLUE_18
6B01 TB-DI-1 6B01B RACK1S02 1 BLUE_18
6B02 TB-DI-1 6B02B RACK1S02 2 BLUE_18
6B03 TB-DI-1 6B03B RACK1S02 3 BLUE_18
6B04 TB-DI-1 6B04B RACK1S02 4 BLUE_18
6B05 TB-DI-1 6B05B RACK1S02 5 BLUE_18
6B06 TB-DI-1 6B06B RACK1S02 6 BLUE_18
6B07 TB-DI-1 6B07B RACK1S02 7 BLUE_18
6B08 TB-DI-1 6B08B RACK1S02 8 BLUE_18
6B09 TB-DI-1 6B09B RACK1S02 9 BLUE_18
WIRENO COMPONENT 1 PIN1 COMPONENT 2 PIN2 WIRE TYPE
6B10 TB-DI-1 6B10B RACK1S02 10 BLUE_18
6B10A TB-DI-1 6B10A TSTAT6B01 1 BLUE_18
6B10B TSTAT6B01 2 TB-DI-1 6B10B BLUE_18
6B11 TB-DI-1 6B11B RACK1S02 11 BLUE_18
6B11A TB-DI-1 6B11A CR3A00 13 BLUE_18
6B11B CR3A00 14 TB-DI-1 6B11B BLUE_18
6B12 TB-DI-1 6B12B RACK1S02 12 BLUE_18
6B13 TB-DI-1 6B13B RACK1S02 13 BLUE_18
6B14 TB-DI-1 6B14B RACK1S02 14 BLUE_18
6B15 TB-DI-1 6B15B RACK1S02 15 BLUE_18
6C08 RACK1S03 8 TB-DO-1 6C08A YELLOW_18
6C08A TB-DO-1 6C08A CR6C08 A1 YELLOW_18
6C08B CR6C08 A2 TB-DO-1 6C08B WHT_BLU_16
6C09 RACK1S03 9 TB-DO-1 6C09A YELLOW_18
6C09A TB-DO-1 6C09A CR6C09 A1 YELLOW_18
6C10 RACK1S03 10 TB-DO-1 6C10A YELLOW_18
6C10A TB-DO-1 6C10A CR6C10 A1 YELLOW_18
6C11 RACK1S03 11 TB-DO-1 6C11A YELLOW_18
6C11A TB-DO-1 6C11A CR6C11 A1 YELLOW_18
6C12 RACK1S03 12 TB-DO-1 6C12A YELLOW_18
6C12A TB-DO-1 6C12A CR6C12 A1 YELLOW_18
6C13 RACK1S03 13 TB-DO-1 6C13A YELLOW_18
6C13A TB-DO-1 6C13A CR6C13 A1 YELLOW_18
6C14 RACK1S03 14 TB-DO-1 6C14A YELLOW_18
6C14A TB-DO-1 6C14A CR6C14 A1 YELLOW_18
6C15 RACK1S03 15 TB-DO-1 6C15A YELLOW_18
6C15A TB-DO-1 6C15A CR6C15 A1 YELLOW_18
6CV1+TB-DO-1 6CV1+RACK1S03 16 BLUE_16
6CV1-RACK1S03 17 TB-DO-1 6CV1-WHT_BLU_16
6D00A TB-AI-1 6D00A RACK1S04 0 PURPLE_18
6D00B TB-AI-1 6D00B RACK1S04 1 PURPLE_18
6D01A TB-AI-1 6D01A RACK1S04 2 PURPLE_18
6D01B TB-AI-1 6D01B RACK1S04 3 PURPLE_18
6D02A TB-AI-1 6D02A RACK1S04 4 PURPLE_18
6D02B TB-AI-1 6D02B RACK1S04 5 PURPLE_18
6D03A TB-AI-1 6D03A RACK1S04 6 PURPLE_18
6D03B TB-AI-1 6D03B RACK1S04 7 PURPLE_18
6D04A TB-AI-1 6D04A RACK1S04 8 PURPLE_18
6D04B TB-AI-1 6D04B RACK1S04 9 PURPLE_18
6D05A TB-AI-1 6D05A RACK1S04 10 PURPLE_18
6D05B TB-AI-1 6D05B RACK1S04 11 PURPLE_18
6D06A TB-AI-1 6D06A RACK1S04 12 PURPLE_18
6D06B TB-AI-1 6D06B RACK1S04 13 PURPLE_18
6D07A TB-AI-1 6D07A RACK1S04 14 PURPLE_18
6D07B TB-AI-1 6D07B RACK1S04 15 PURPLE_18
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
99B.1 NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION WIRE REPORT 1.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
WIRE REPORT (PART 1)
30 31
CITY OF CARLSBAD
THIS SHEET INTENTIONALLY
LEFT BLANK
PROJECT NO.
ENGINEERING DEPARTMENT
5542-BINITIAL
CITY APPROVALREVISION DESCRIPTION
DATE INITIALDATE INITIALDATE
ENGINEER OF WORK OTHER APPROVAL
EXP.PE
DATE
INSPECTOR DATE
REVIEWED BY:
CIVIL ENGINEER
"AS BUILT"
ARCHITECT/
ENGINEERS
STAMP SEAL
A B C D E F G H
1
2
3
4
5
6
CUSTOMER INFO:
DWG SCALEDRAFT DATE:
A TETRA TECH COMPANY
WWW.EAINTEGRATOR.COM
PHONE: (949) 769-6000
SHEET SHEETS
IMPROVEMENT PLAN FOR:
APPROVED:
EXPIRES DATE
CHKD BY:
DWN BY:
RVWD BY:
DRAWING NO.
02/26/2025
MICHAEL PACE
JAKE MEYERS
DAVE LEWIS 538-4BA
KERI MARTINEZ
PRINCIPAL ENGINEER RCE 57189 12/31/2025
99B.2 NO SCALE
CITY OF CARLSBAD
TERRAMAR LIFT STATION
CWD TERRAMAR LIFT STATION WIRE REPORT 2.dwg
IS
S
U
E
D
F
O
R
B
I
D
-
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TERRAMAR LIFT STATION
WIRE REPORT (PART 2)
31 31
CITY OF CARLSBAD