HomeMy WebLinkAboutDWG 538-4R; 5542-B; Electrical Control Panel Replacement Project - Elm Reservoir; 01-31CITYWIDE ELECTRICAL CONTROL PANEL REPLACEMENT PROJECT FOR WATER AND WASTEWATER FACILITIES DWG SECTION SECTION DESCRIPTION 1 GENERAL 2 NETWORK WIRING 3 AC POWER 4 DC POWER 5 MISCELLANEOUS 6 IO RACK 1 7 IO RACK 2 8 IO RACK 3 99 REPORTS (PANEL BUILDER REFERENCE ONLY) DRAWING NUMBERING CONVENTION X Y . # DRAWING SECTION NUMBER SHEET LETTER SUB SHEET NUMBER (OPTIONAL) ELM RESERVOIR SHEET DWG DESCRIPTION REVISION 1 1A TABLE OF CONTENTS 0.2 2 1B DRAWING SYMBOL KEY 0.2 3 1C CONSTRUCTION COMMENTS 0.2 4 1D.1 BILL OF MATERIAL (PART 1)0.2 5 1D.2 BILL OF MATERIAL (PART 2)0.2 6 1E.1 PANEL LAYOUT EXTERIOR DETAILS 0.2 7 1E.2 PANEL LAYOUT EXTERIOR DIMENSIONS 0.2 8 1E.3 PANEL LAYOUT EXTERIOR CONDUIT ENTRY 0.2 9 1F.1 PANEL LAYOUT INTERIOR DETAILS 0.2 10 1F.2 PANEL LAYOUT INTERIOR DIMENSIONS 0.2 11 1F.3 PANEL LAYOUT INTERIOR TOP VIEW 0.2 12 1G TERMINAL STRIP DETAIL 0.2 13 1H TERMINAL STRIP DETAIL DIGITAL 0.2 14 1I TERMINAL STRIP DETAIL ANALOG 0.2 15 1J PANEL COMPONENT DETAIL 0.2 16 1K.1 NAMEPLATE DETAIL (PART 1)0.2 17 1K.2 NAMEPLATE DETAIL (PART 2)0.2 18 1K.3 NAMEPLATE DETAIL (PART 3)0.2 19 2A NETWORK WIRING 0.2 20 3A AC POWER DISTRIBUTION 0.2 21 4A.1 DC POWER DISTRIBUTION (PART 1)0.2 22 4A.2 DC POWER DISTRIBUTION (PART 2)0.2 23 5A PANEL I/O DETAIL 0.2 24 6A RACK 1 SLOT 1 DISCRETE INPUT 0.2 25 6B RACK 1 SLOT 2 DISCRETE OUTPUT 0.2 26 6C RACK 1 SLOT 3 ANALOG INPUT 0.2 27 6D RACK 1 SLOT 4 ANALOG INPUT 0.2 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1A NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR TABLE OF CONTENTS.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR TABLE OF CONTENTS 1 31 CITY OF CARLSBAD NOTE: REFER TO SHEET G-003 GENERAL NOTES. ALL INFORMATION IS APPLICABLE TO THIS DESIGN. DRAWING SYMBOL KEY COMPONENT TAG NORMALLY OPEN STATUS CONTACT CROSS REFERENCE NORMALLY CLOSED STATUS CONTACT CROSS REFERENCE C/B RATING 20A SHT 2X-A1,SHT 3X-A2 CB1X01 3A01L 120VAC 3A01L to SHT 4A.1-A1 TB-XX Number Jumper Manufacturer Part # 1X22 MFG NAME XXXXXXX 1X23 1X24 MFG NAME XXXXXXX 1X25 TERMINALS NOT JUMPERED TERMINALS JUMPERED G GND3A01 GROUND BAR COMPONENT TAG C/B RATING 20A CB1X01 4241 SHT 1X-C1 CB1X01 1211 SHT 1X-C1 CB1X01 CIRCUIT BREAKER LOCATION CROSS REFERENCE COMPONENT TAG NORMALLY OPEN CONTACT LOCATION CROSS REFERENCE NORMALLY CLOSED CONTACT LOCATION CROSS REFERENCE NORMALLY OPEN CONTACT NORMALLY CLOSED CONTACT CR1X01 RELAY COIL LOCATION CROSS REFERENCE RELAY COIL LOCATION CROSS REFERENCE NC NO SHT 3X-A2 SHT 2X-A1 4241 SHT 1X-C1 CB1X01 1211 SHT 1X-C1 CB1X01 PANEL-MOUNTED GROUND BUS TERMINAL STRIP JUMPER DETAILS WIRE JUMPERS (BETWEEN TERMINALS) MECHANICAL JUMPERS 1X22 1X21 1X20 1X12 1X11 1X10 CONTROL RELAY (WITH CONTACT CROSS REFERENCE) SINGLE-POLE CIRCUIT BREAKER SINGLE-POLE CIRCUIT BREAKER (WITH AUXILIARY STATUS CONTACTS) PREFIX DESCRIPTION BAT BATTERY CB CIRCUIT BREAKER CBL CABLE GND GROUND BAR HTR HEATER LS LIMIT SWITCH LSA LIGHTNING SURGE ARRESTER LT LIGHT NETSW ETHERNET NETWORK SWITCH PB PUSH BUTTON PD POWER DISTRIBUTION TERMINAL BLOCK PSU POWER SUPPLY RECP RECEPTACLE SS SELECTOR SWITCH TB TERMINAL BLOCK TC THERMOCOUPLE CONVERTER TR TIMER RELAY TSTAT THERMOSTAT UPS UNINTERRUPTIBLE POWER SUPPLY XX YY ## COMPONENT PREFIX DRAWING SHEET NUMBER COMPONENT NUMBER (SEQUENTIAL) COMPONENT TAG NAMING CONVENTION SHT XX - Y Z LOCATION CROSS REFERENCE CONVENTION DRAWING SHEET NUMBER SHEET COLUMN LETTER SHEET ROW NUMBER A B 1 2 SHEET LOCATION COLUMN LETTER SHEET LOCATION ROW NUMBER WIRE OFF SHEET CROSS REVERENCE WIRE NUMBER WIRE LOCATION SHEET REFERENCE SIGNAL DESCRIPTION SELECTOR SWITCH, 2-POLE (TOP: NO, BOTTOM: NC) PILOT LIGHT, PUSH-TO-TEST (COLOR: A=AMBER, G=GREEN, R=RED) 100W A DIGITAL FIELD DEVICE ANALOG FIELD DEVICE LIMIT SWITCH NORMALLY CLOSED LIMIT SWITCH NORMALLY OPEN PUSH BUTTON NORMALLY OPEN PUSH BUTTON NORMALLY CLOSED MUSHROOM HEAD PUSH BUTTON RADIANT HEATER HORN OR BUZZER GENERIC DEVICE +- ELECTRICAL SYMBOL DEFINITIONS BILL OF MATERIAL TAG # REFERENCE BUBBLEDV1X02 DUPLEX RECEPTACLE SPECIAL CHARACTER DESCRIPTION L 120VAC POWER LINE VOLTAGE N 120VAC POWER NEUTRAL +24VDC POSITIVE -24VDC NEUTRAL G GROUND OTHER (A-Z)UNIQUE WIRE DESIGNATOR YY ## A DRAWING SHEET NUMBER WIRE NUMBER (SEQUENTIAL) SPECIAL DESIGNATOR CHARACTER (OPTIONAL) WIRE NUMBERING CONVENTION FUSE NUMBER TERMINAL STRIP WIRE NUMBER FUSE RATING 1X57 TB-XX 1X56 TB-XX 1X041X03 1X55 TB-XX 1X54 TB-XX 0.5A RED #12 AWG MTW WIRE COLOR, SIZE, AND TYPE DESIGNATION WIRE TYPE SYMBOLS FIELD WIRING INTERNAL PANEL WIRING SHLD SHIELDED MULTI-CONDUCTOR CABLE WITH DRAIN WIRE MULTI-CONDUCTOR CABLE WHTCBL6A01 BRNCBL6A01 CABLE TAG INDIVIDUAL CONDUCTOR COLOR FUSED TERMINAL DISCONNECT TERMINAL (FOR ANALOG SIGNAL TESTING) FEED-THROUGH TERMINAL GROUND TERMINAL (CONNECTED DIRECTLY TO DIN RAIL) PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1B NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR DRAWING SYMBOL KEY.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR DRAWING SYMBOL KEY 2 31 CITY OF CARLSBAD PANEL CONSTRUCTION COMMENTS AND SPECIAL INSTRUCTIONS ISOLATED DIN RAIL: EACH ISOLATED DIN RAIL SHALL BE INSTALLED ON INSULATED STANDOFFS TO CREATE ISOLATION BETWEEN THE DIN RAIL AND THE BACK PANEL. EACH DIN RAIL WILL HAVE A SINGLE GROUNDING TERMINAL BLOCK, WHICH IS TO BE CONNECTED DIRECTLY TO THE GROUND BUS WITH A SINGLE CONDUCTOR OF #14AWG (GREEN) WIRE. THE TERMINAL STRIPS LISTED TOGETHER BELOW SHALL BE MOUNTED ON THE SAME, CONTINUOUS ISOLATED DIN RAIL. THIS REQUIREMENT APPLIES TO: TB-DI-1 TB-DO-1 TB-AI-1 TERMINAL BLOCKS: FOR THE FOLLOWING TERMINAL BLOCKS, FIELD WIRING TERMINATES ON THE BOTTOM AND PANEL WIRING TERMINATES ON THE TOP. THIS REQUIREMENT APPLIES TO: TB-DO-RELAY FOR THE FOLLOWING TERMINAL BLOCKS, FIELD WIRING TERMINATES ON THE RIGHT AND PANEL WIRING TERMINATES ON THE LEFT. THIS REQUIREMENT APPLIES TO: TB-AI-1 TB-DI-1 TB-DO-1 FOR THE FOLLOWING TERMINAL BLOCKS, ALL PANEL WIRING SHALL TERMINATE ONLY ON THE PANEL SIDE OF THE TERMINAL. DO NOT TERMINATE PANEL WIRING ON THE FIELD SIDE OF THE TERMINAL. THIS REQUIREMENT APPLIES TO: TB-DI-1 TB-DO-1 INPUT LSA (LSA3A01) IS TO BE MOUNTED AND WIRED SUCH THAT FIELD TERMINATIONS ARE ON THE BOTTOM AND PANEL WIRING IS ON THE TOP. GROUND BUS: MOUNT GROUND BUS DIRECTLY TO BACK PANEL. BOND THE GROUND STUD ON ENCLOSURE DOORS DIRECTLY TO ENCLOSURE GROUNDING STUD(S) USING SINGLE CONDUCTOR OF #14AWG (GREEN) WIRE. DO NOT GROUND CONTROL COMPONENTS TO BACK PANEL. RUN SINGLE CONDUCTORS DIRECTLY TO GROUND BUS AS SHOWN ON SHEET 3A OF DRAWING SET. ENCLOSURE AND PANEL ASSEMBLY: PANEL IS TO BE CONSTRUCTED IN CONFORMANCE WITH NEC (INCLUDING ARTICLE 409) AND UL 508A AND BEAR THE APPROPRIATE UL 508A INDUSTRIAL CONTROL PANEL LABEL CONFIRMING THE CONSTRUCTION. BATTERY SENSOR MODULE TO BE INSTALLED TO BACK PANEL USING ZINC PLATED STANDOFFS. INSTALL NYLON WASHERS ON BOTH SIDES OF BOARD AT EACH MOUNTING SCREW. ATTACH WIRE DUCT TO PANEL WITH METAL FASTENERS. ENCLOSURE DOOR STOP TO BE INSTALLED WITH WELDED STUDS ON THE DOOR AND BOLTS WITH SEALING WASHERS ON THE ENCLOSURE. ROUTER IR1101 AND ANTENNA ANT-4-5G4-O TO BE PROVIDED BY CUSTOMER AND ASSEMBLED BY CONTRACTOR. ONLOGIC HX310 EDGE DEVICE TO BE PROVIDED BY CUSTOMER AND ASSEMBLED BY CONTRACTOR. DEVICE LABELS: UNLESS OTHERWISE INDICATED, ALL COMPONENT IDENTIFICATION LABELS ARE TO BE SELF ADHESIVE POLYESTER WITH BLACK THERMAL PRINTED TEXT. ADDITIONAL COMPONENT IDENTIFICATION LABELS ARE TO BE MOUNTED ON THE FRONT OF EACH DEVICE. ALL LABELS TO BE OF UNIFORM SIZE AND FONT. TEXT TO MATCH THE LABEL ON THE END BRACKET NEXT TO THE DEVICE. THIS REQUIREMENT APPLIES TO: ALL CIRCUIT BREAKERS PSU4A01 UPS4A01 ROUTER EDGE DEVICE TSTAT6A01 WIRE AND TERMINAL MARKING: ALL WIRE AND TERMINAL LABELS TO BE COMPUTER PRINTED. NO HAND-WRITTEN TERMINAL OR WIRE NUMBERS ALLOWED LABEL ALL TERMINALS WITH TERMINAL MANUFACTURE MARKER STRIPS LABEL ALL WIRE/CABLE WITH HEAT SHRINK MARKING SLEEVES. PANEL WIRING: USE DUAL WIRE FERRULES WHENEVER 2 WIRES ARE INSERTED INTO A SINGLE TERMINATION POINT. DO NOT ROUTE WIRES AGAINST OR FASTENED TO COOLING VENTS OF CONTROL COMPONENTS. DO NOT ROUTE PANEL WIRING INSIDE WIRE DUCTS THAT ARE MARKED AS FIELD WIRING DO NOT USE NYLON TIE WRAPS INSIDE WIRE DUCT. WIRES AND CABLES ROUTED OUTSIDE OF WIRE DUCTS SHALL BE FIXED TO ENCLOSURE WITH WIRE SADDLES AT A MINIMUM OF EVERY 4 INCHES. WIRE SADDLES ARE TO BE MOUNTED USING THREADED STUDS WELDED TO ENCLOSURE, DO NOT USE ADHESIVE BACKED WIRE SADDLES. WIRES AND CABLES ROUTED TO DOORS SHALL BE FLEXIBLE AND WRAPPED IN A WIRE LOOM. SECURE WIRING ON EACH SIDE OF THE HINGE SO THAT ANY BENDING OR TWISTING WILL BE AROUND THE LENGTH OF THE WIRE. WIRE COLOR AND SIZES: UNLESS OTHERWISE SPECIFIED IN THE DRAWING SET, ALL WIRES TO BE SIZED AND COLORED AS FOLLOWS: 120VAC = RED, 14 AWG, MTW 120VAC NEUTRAL = WHITE, 14 AWG, MTW 120VAC NOT DISCONNECTED BY PANEL'S MAIN CIRCUIT BREAKER = ORANGE, 14 AWG, MTW 24VDC = BLUE, 16 AWG, MTW N-DC = WHITE/BLUE, 16 AWG, MTW GROUND = GREEN, 14 AWG, MTW DISCRETE INPUTS = BLUE, 18 AWG, MTW, OR MANUFACTURES MULTI-CONDUCTOR CABLE DISCRETE OUTPUTS = YELLOW, 18 AWG, MTW ANALOG INPUTS AND OUTPUTS = PURPLE, 18 AWG, MTW PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1C NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR CONSTRUCTION COMMENTS.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR CONSTRUCTION COMMENTS 3 31 CITY OF CARLSBAD ALL BILL OF MATERIAL ITEMS ARE "NO EQUAL" TO MATCH EXISTING STANDARDS, AND SHALL BE PROVIDED AS LISTED. TAG QTY MANUFACTURER PART #DESCRIPTION BACKPANEL 1 HOFFMAN A48P36 45" X 33" PANEL FOR 48" X 36" TYPE 3R, 4, 4X, 12 AND 13 ENCLOSURES BAT4A03 1 PHOENIX CONTACT 1134645 BATTERY MOUNTING CASE M, WALL AND SURFACE MOUNTING BATTERY CONTAINER 2 DURACELL SLADC12-20C LEAD-ACID BATTERY, 20AH, 12VDC, 13.3 LBS CB3A00 1 EATON FAZ-D20/1-NA-SP CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 20A, D CURVE 1 EATON Z-NHK CIRCUIT BREAKER, UL 489 BRANCH, AUXILIARY SWITCH CB3A01 1 EATON FAZ-D10/1-NA-SP CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 10A, D CURVE CB3A02 1 EATON FAZ-D4/1-NA-SP CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 4A, D CURVE CB3A03 1 EATON FAZ-D4/1-NA-SP CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 4A, D CURVE CB3A04 1 EATON FAZ-D4/1-NA-SP CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 4A, D CURVE CB4A10 1 CBI QY-1-13-DM-U2-0.5A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 0.5A 80V 1 POLE 1 CBI SABBM54 CIRCUIT BREAKER, 13MM, BUSBAR MODULE SINGLE PHASE, METAL CB4A11 1 CBI QY-1-13-DM-U2-6A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 6A 80V 1 POLE CB4A12 1 CBI QY-1-13-DM-U2-2A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 2A 80V 1 POLE CB4A13 1 CBI QY-1-13-DM-U2-2A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 2A 80V 1 POLE CB4A14 1 CBI QY-1-13-DM-U2-6A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 6A 80V 1 POLE CB4A15 1 CBI QY-1-13-DM-U2-0.5A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 0.5A 80V 1 POLE CB4A16 1 CBI QY-1-13-DM-U2-6A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 6A 80V 1 POLE CB4A17 1 CBI QY-1-13-DM-U2-4A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 4A 80V 1 POLE CB4A18 1 CBI QY-1-13-DM-U2-2A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 2A 80V 1 POLE CB4A19 1 CBI QY-1-13-DM-U2-2A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 2A 80V 1 POLE CB4A20 1 CBI QY-1-13-DM-U2-4A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 4A 80V 1 POLE CB4A21 1 CBI QY-1-13-DM-U2-6A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 6A 80V 1 POLE CB4A50 1 CBI QY-1-13-DM-U2-30A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 30A 80V 1 POLE CR3A00 1 PHOENIX CONTACT 2966249 RELAY MODULE 120VAC COIL WITH BUSBAR TERMINAL 1NO CR6B08 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO 1 PHOENIX CONTACT 2966786 CONTINUOUS PLUG-IN BRIDGE MECHANICAL JUMPER, 500MM, RELAY CR6B09 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO CR6B10 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO CR6B11 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO CR6B12 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO CR6B13 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO CR6B14 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO CR6B15 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO DINRAIL 1 PHOENIX CONTACT 1201730 DIN RAIL 1 PHOENIX CONTACT 1201141 INSULATED DIN RAIL MOUNT DUCT-AC-1"1 PANDUIT F1X4LG6 NARROW FINGER, SLOTTED WIRING DUCT GRAY 1" WIDE X 4" DEEP 1 PANDUIT C1LG6 WIRING DUCT COVER - GRAY 1" WIDE DUCT-DC-1.5"1 PANDUIT F1.5X4LG6 NARROW FINGER, SLOTTED WIRING DUCT GRAY 1.5" WIDE X 4" DEEP 1 PANDUIT C1.5LG6 WIRING DUCT COVER - GRAY 1.5" WIDE DUCT-DC-2"1 PANDUIT F2X4LG6 NARROW FINGER, SLOTTED WIRING DUCT GRAY 2" WIDE X 4" DEEP 1 PANDUIT C2LG6 WIRING DUCT COVER - GRAY 2" WIDE DUCT-DC-3"1 PANDUIT F3X4LG6 NARROW FINGER, SLOTTED WIRING DUCT GRAY 3" WIDE X 4" DEEP 1 PANDUIT C3LG6 WIRING DUCT COVER - GRAY 3" WIDE EDGE DEVICE 1 ONLOGIC HX310 PANEL PC, EDGE GATEWAY, ELKHART LAKE INDUSTRIAL COMPUTER, 24VDC ENCLOSURE 1 HOFFMAN A48H3612SSLP STAINLESS STEEL TYPE 4X ENCLOSURE GND3A01 1 SCHNEIDER PK18GTA LOAD CENTER ACCESSORY, QO/HOMELINE, GROUND BAR KIT, 18 TERMINAL LSA3A01 1 EATON AGCF12030 TRANSIENT VOLTAGE SURGE SUPPRESSOR, 120VAC, 20A LT5A01 1 BANNER WLB32C570PBQ WLB32 ADJUSTABLE LED WORKSTATION LIGHT 1 SQUARE D XZCP1141L5 M12 4 PIN CONNECTOR 16FT CABLE MISC 12 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N TAG QTY MANUFACTURER PART #DESCRIPTION PD6B00 1 PHOENIX CONTACT 2966508 RELAY POWER TERMINAL 2 PHOENIX CONTACT 2966786 CONTINUOUS PLUG-IN BRIDGE MECHANICAL JUMPER, 500MM, RELAY PSU4A01 1 PULS CP20.241 1-PHASE POWER SUPPLY RACK1ECR 1 AB 5069-ECR 5069 COMPACTLOGIX/COMPACT GUARDLOGIX RIGHT END CAP WITH ADAPTER RACK1S00 1 AB 5069-L320ER COMPACTLOGIX 5380, 2 MB USER MEMORY, 16 I/Os, 40 ETHERNET/IP DEVICES 1 AB 5069-RTB6-SCREW 6 PIN SCREW TYPE POWER TERMINAL CONNECTOR 1 AB 5069-RTB4-SCREW 4 PIN SCREW TYPE POWER TERMINAL CONNECTOR RACK1S01 1 AB 5069-IB16 5069 COMPACT I/O 16 CHANNEL 24V DC SINK INPUTE MODULE 1 AB 5069-RTB18-SCREW 18 PIN SCREW TYPE TERMINAL CONNECTOR RACK1S02 1 AB 5069-OB16 5069 COMPACT I/O 16 CHANNEL 24V DC SOURCE OUTPUT MODULE 1 AB 5069-RTB18-SCREW 18 PIN SCREW TYPE TERMINAL CONNECTOR RACK1S03 1 AB 5069-IF8 5069 COMPACT I/O 8 CHANNEL VOLTAGE/CURRENT ANALOG INPUT MODULE 1 AB 5069-RTB18-SCREW 18 PIN SCREW TYPE TERMINAL CONNECTOR RACK1S04 1 AB 5069-IF8 5069 COMPACT I/O 8 CHANNEL VOLTAGE/CURRENT ANALOG INPUT MODULE 1 AB 5069-RTB18-SCREW 18 PIN SCREW TYPE TERMINAL CONNECTOR RECP3A01 1 HUBBELL GFR15I GFCI RECEPTACLE, 125V, 15A 1 HUBBELL 5320-0 DUPLEX RECEPTACLE GANG BOX PANEL MOUNT 1 HUBBELL SSJ26 GFCI RECEPTACLE COVER PLATE ROUTER 1 CISCO IR1101 ROUTER, POWER INPUT 9.6 TO 60VDC, TEMP RATING: -40 TO 60C, 4 PORT ETHERNET 1 CISCO ANT-4-5G4-O DIRECT MOUNT OMNIDIRECTIONAL ANTENNA 1 EXISTING EXISTING CABLE CAT 6 ETHERNET CABLE STOP1 1 HOFFMAN ALGDSTOP2 LARGE ENCLOSURE DOOR STOP KIT SW5A01 1 TELEMECANIQUE ZCP21 LIMIT SWITCH BODY - ZCP - 1 NC + 1 NO - TERMINALS 1 TELEMECANIQUE ZCPEG11 CABLE GLAND ENTRY FOR LIMIT SWITCH 1 TELEMECANIQUE ZCE10 HEAD FOR LIMIT SWITCH - ZCE - STEEL END PLUNGER TB-AC-1 2 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A 1 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS 4 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, IEC - 2.5mm WIRE CROSS SECTION 8 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L 1 AB 1492-CJK5-50 50 IEC CENTER JUMPER, 10 PL 5mm, PLUG-IN TB-AI-1 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A 3 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N 48 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, IEC - 2.5mm WIRE CROSS SECTION 162 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L 2 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS 17 AB 1492-LG3 IEC SPRING CLAMP TERMINAL BLOCK, GROUNDING BLOCK, 1492-L 16 AB 1492-L3P TERMINAL BLOCK 1492, GRAY 16 AB 1492-FPK224 TERMINAL ACCESSORY 1492, BLACK 16 EATON GMC-63MA CARTRIDGE FUSE 63MA TB-BATT-1 2 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A 3 AB 1492-L6 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, IEC - 6mm WIRE CROSS SECTION 6 AB 1492-M6X12 TERMINAL LABEL, 6mm X 12mm, INDIVIDUAL, SNAP ON, 1492-L 1 AB 1492-CJL8-2 2 IEC CENTER JUMPER, 2 PL 8mm, PLUG-IN, YELLOW 1 AB 1492-EBL6 END BARRIER COMPATIBLE WITH 1492-L6 TYPE TERMINALS TB-DC-1 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A 2 AB 1492-CJK5-50 50 IEC CENTER JUMPER, 10 PL 5mm, PLUG-IN 3 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N 22 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, IEC - 2.5mm WIRE CROSS SECTION PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1D.1 NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR BILL OF MATERIAL 1.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR BILL OF MATERIAL (PART 1) 4 31 CITY OF CARLSBAD ALL BILL OF MATERIAL ITEMS ARE "NO EQUAL" TO MATCH EXISTING STANDARDS, AND SHALL BE PROVIDED AS LISTED. TAG QTY MANUFACTURER PART #DESCRIPTION 44 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L 2 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS TB-DI-1 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A 1 AB 1492-CJK5-50 50 IEC CENTER JUMPER, 10 PL 5mm, PLUG-IN 2 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N 32 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, IEC - 2.5mm WIRE CROSS SECTION 64 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L 1 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS TB-DO-1 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A 1 AB 1492-CJK5-50 50 IEC CENTER JUMPER, 10 PL 5mm, PLUG-IN 2 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N 34 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, IEC - 2.5mm WIRE CROSS SECTION 68 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L 1 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS TB-DOOR 2 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A 1 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS 5 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, IEC - 2.5mm WIRE CROSS SECTION 10 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L TSTAT6A01 1 PFANNENBERG 17111000010 THERMOSTAT, VOLTAGE RATING: 240VAC, DC RATING 30W, TEMP RATING: 32 TO 140 F, N.C. W/ CONTACT SPRINGS, GREY, FLZ 520 UPS4A01 1 PULS UB20.241 DC UPS MODULE 24VDC, 20A OUTPUT, FOR 3.9AH TO 150AH BATTERY UPS4A02 1 PULS UZS24.100 SENSOR BOARD FOR BATTERY MODULES 3 MCMASTER CARR 93505A485 ZINC-PLATED STEEL THREADED 1/4" HEX STANDOFF 6 MCMASTER CARR 92150A104 NYLON SPACER 3 MCMASTER CARR 90272A108 ZINC PLATED STEEL HEX BOLT, #4-40 X 3/8" VENT01 1 HOFFMAN HH05SS04004X 12.33 X 7.70 X 3.40 FILTER FAN SHROUD 1 HOFFMAN HH05PS004 7.41 X 3.43 X 0.96 PEST SCREENS VENT02 1 HOFFMAN HH05SS04004X 12.33 X 7.70 X 3.40 FILTER FAN SHROUD 1 HOFFMAN HH05PS004 7.41 X 3.43 X 0.96 PEST SCREENS PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1D.2 NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR BILL OF MATERIAL 2.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR BILL OF MATERIAL (PART 2) 5 31 CITY OF CARLSBAD STOP1 HEAT DISSIPATION AREA 0"3"6"12" ENCLOSURE STOP1 LT5A01 120VAC FROM: LP-XXX CKT XX LT5A01 LT5A01 TEST BACKPANEL SW5A01 ELM RESERVOIR VENT01 VENT02 EDGE DEVICE EDGE DEVICE VENT01 VENT02 SW5A01 BAT4A03 BAT4A03 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1E.1 1"=6" CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR PANEL LAYOUT EXTERIOR DETAILS.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR PANEL LAYOUT EXTERIOR DETAILS 6 31 CITY OF CARLSBAD 48 0 0 0 STOP1 0"3"6"12" 120VAC FROM: LP-XXX CKT XX TEST ELM RESERVOIR 0 373 8 0 0 258 13 1 8 161 8 6 618 36 43 421 4 12 1 8 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1E.2 1"=6" CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR PANEL LAYOUT EXTERIOR DIMENSIONS.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR PANEL LAYOUT EXTERIOR DIMENSIONS 7 31 CITY OF CARLSBAD STOP1 0"3"6"12" 120VAC FROM: LP-XXX CKT XX TEST ELM RESERVOIR 0" 253 4" 0"0" 11 3 8" AVAILABLE CONDUIT ENTRY AREA (24VDC PREFERRED) AVAILABLE CONDUIT ENTRY AREA (120VAC PREFERRED) 0" 253 4" 0"0" 11 3 8" 181 8" 578" 578" PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1E.3 1"=6" CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR PANEL LAYOUT CONDUIT ENTRY.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR PANEL LAYOUT EXTERIOR CONDUIT ENTRY 8 31 CITY OF CARLSBAD 0"3"6"12" HEAT DISSIPATION AREA GND3A01 SEE SHT 1J SEE SHT 1J TB-DI-1 TB-DO-1 TB-AI-1 BACKPANEL UPS4A02 TB-BATT-1 GND3A01LSA3A01RECP3A01TB-DO-RELAY TB-AC-1 DINRAIL DUCT-AC-1.5" DUCT-DC-1.5" DUCT-DC-2" DUCT-DC-3" UPS4A02 RECP3A01LSA3A01 CB3 A 0 0 CB3 A 0 1 CB3 A 0 2 CB3 A 0 3 CB3 A 0 4 PSU4A01 UPS4A01 TB-DOOR 3" x 4" 2" x 4 " F I E L D W I R I N G DUCT-AC-1"1" x 4" 1.5" x 4" 1.5" x 4" 2" x 4" 3" x 4" ACC 1 PSU4A01UPS4A01 ROUTER CR 6 B 1 5 CR 6 B 1 4 CR 6 B 1 3 CR 6 B 1 2 CR 6 B 1 1 CR 6 B 1 0 CR 6 B 0 9 CR 6 B 0 8 CB4 A 1 0 AC C 1 AC C 1 CB4 A 1 1 CB4 A 1 2 CB4 A 1 3 CB4 A 1 4 CB4 A 1 5 CB4 A 1 6 CB4 A 1 7 CB4 A 1 8 CB4 A 1 9 CB4 A 2 0 CB4 A 2 1 ACC 1 ACC 1 ACC 1 ACC 1 SEE SHT 1J DC BREAKERS CR3A00 PD 6 B 0 0 ACC 1 ACC 1 ACC 1 ACC 3 AC C 1 AC C 3 3" x 4 " RACK1S005069-L320ER 1" x 4"DUCT-DC-1" ROUTER SUPPLIED BY CUSTOMER ACC 1 ACC 3 CB4A50 RACK 1 RACK 1 ACC 1 ACC 3 ACC 5 RA C K 1 S 0 1 50 6 9 - I B 1 6 RA C K 1 S 0 2 50 6 9 - O B 1 6 RA C K 1 S 0 3 50 6 9 - I F 8 RA C K 1 S 0 4 50 6 9 - I F 8 ACC1 ACC3 ACC1 ACC3 1" x 4 " 1.5" x 4" 1.5" x 4" FIELD WIRING 1.5" x 4" TB-DC-1 BAT4A03 SEE SHT 1J AC BREAKERS 1" x 4 " TSTAT6A01 ACC 1 ACC 1 1" x 4" 1" x 4 " EDGE DEVICE ED G E D E V I C E ACC1 ACC3 ACC5 SUPPLIED BY CUSTOMER PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1F.1 1"=6" CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR PANEL LAYOUT INTERIOR DETAILS.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR PANEL LAYOUT INTERIOR DETAILS 9 31 CITY OF CARLSBAD 0 0 958 33 297 8 14 3 8 20 1 8 0"3"6"12" GND3A01 3" x 4" 2" x 4 " F I E L D W I R I N G 1" x 4" 1.5" x 4" 1.5" x 4" 2" x 4" 3" x 4" ACC 1 PSU4A01UPS4A01 CR 6 B 1 5 CR 6 B 1 4 CR 6 B 1 3 CR 6 B 1 2 CR 6 B 1 1 CR 6 B 1 0 CR 6 B 0 9 CR 6 B 0 8 AC C 1 AC C 1 ACC 1 ACC 1 ACC 1 ACC 1 PD 6 B 0 0 ACC 1 ACC 1 ACC 1 ACC 3 AC C 1 AC C 3 3" x 4 " RACK1S005069-L320ER 1" x 4" ROUTERACC 1 ACC 3 ACC 1 ACC 3 ACC 5 RA C K 1 S 0 1 50 6 9 - I B 1 6 RA C K 1 S 0 2 50 6 9 - O B 1 6 RA C K 1 S 0 3 50 6 9 - I F 8 RA C K 1 S 0 4 50 6 9 - I F 8 ACC1 ACC3 ACC1 ACC3 1" x 4 " 1.5" x 4" 1.5" x 4" FIELD WIRING 1.5" x 4" 1" x 4 " ACC 1 ACC 1 1" x 4" 1" x 4 " ED G E D E V I C E ACC1 ACC3 ACC5 45 411 2 221 8 241 4 0 63 8 111 8 141 8 185 8 337 8 2 6 17 1 4 405 8 45 25 1 8 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1F.2 1"=6" CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR PANEL LAYOUT INTERIOR DIMENSIONS.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR PANEL LAYOUT INTERIOR DIMENSIONS 10 31 CITY OF CARLSBAD 0"3"6"12" 0 0 RACK 1 DUCT-DC DUCT-AC TOP VIEW LOOKING DOWN NOTE: FRONT OF PANEL HEAT DISSIPATION AREA VENT01 6 51 4 BAT4A03 RESERVED FLOOR SPACE FOR CONDUIT ENTRY 61 4 0 EDGE DEVICE VENT02 36 131 8 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1F.3 1"=6" CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR PANEL LAYOUT INTERIOR TOP VIEW.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR PANEL LAYOUT INTERIOR TOP VIEW 11 31 CITY OF CARLSBAD TB-AC-1 Number Jumper Manufacturer Part # TB-AC-1 PHOENIX CONTACT 1004348 ACC1 PHOENIX CONTACT 0800886 3A01N AB 1492-L3 3A02N AB 1492-L3 3A03N AB 1492-L3 3A04N AB 1492-L3 ACC2 AB 1492-EBL3 ACC3 PHOENIX CONTACT 0800886 TB-BATT-1 Number Jumper Manufacturer Part # TB-BATT-1 PHOENIX CONTACT 1004348 ACC1 PHOENIX CONTACT 0800886 4A01 AB 1492-L6 4A02 AB 1492-L6 4A03 AB 1492-L6 ACC2 AB 1492-EBL6 ACC3 PHOENIX CONTACT 0800886 TB-DOOR Number Jumper Manufacturer Part # TB-DOOR PHOENIX CONTACT 1004348 ACC1 PHOENIX CONTACT 0800886 5A01 AB 1492-L3 5A02 AB 1492-L3 5A03 AB 1492-L3 5A04 AB 1492-L3 5A05 AB 1492-L3 ACC2 AB 1492-EBL3 ACC3 PHOENIX CONTACT 0800886 TB-DC-1 Number Jumper Manufacturer Part # TB-DC-1 PHOENIX CONTACT 1004348 ACC1 PHOENIX CONTACT 0800886 4A10-AB 1492-L3 4A11-AB 1492-L3 4A12-AB 1492-L3 4A13-AB 1492-L3 4A14-AB 1492-L3 4A15-AB 1492-L3 4A16-AB 1492-L3 4A17-AB 1492-L3 4A18-AB 1492-L3 4A19-AB 1492-L3 4A20-AB 1492-L3 4A21-AB 1492-L3 4A30-AB 1492-L3 4A31-AB 1492-L3 4A32-AB 1492-L3 4A33-AB 1492-L3 4A34-AB 1492-L3 ACC2 AB 1492-EBL3 ACC3 PHOENIX CONTACT 0800886 4A30+AB 1492-L3 4A31+AB 1492-L3 4A32+AB 1492-L3 4A33+AB 1492-L3 4A34+AB 1492-L3 ACC4 AB 1492-EBL3 ACC5 PHOENIX CONTACT 0800886 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1G NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR TERMINAL STRIP DETAIL.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR TERMINAL STRIP DETAIL 12 31 CITY OF CARLSBAD TB-DI-1 Number Jumper Manufacturer Part # TB-DI-1 PHOENIX CONTACT 1004348 ACC1 PHOENIX CONTACT 0800886 6A00A AB 1492-L3 6A00B AB 1492-L3 6A01A AB 1492-L3 6A01B AB 1492-L3 6A02A AB 1492-L3 6A02B AB 1492-L3 6A03A AB 1492-L3 6A03B AB 1492-L3 6A04A AB 1492-L3 6A04B AB 1492-L3 6A05A AB 1492-L3 6A05B AB 1492-L3 6A06A AB 1492-L3 6A06B AB 1492-L3 6A07A AB 1492-L3 6A07B AB 1492-L3 6A08A AB 1492-L3 6A08B AB 1492-L3 6A09A AB 1492-L3 6A09B AB 1492-L3 6A10A AB 1492-L3 6A10B AB 1492-L3 6A11A AB 1492-L3 6A11B AB 1492-L3 6A12A AB 1492-L3 6A12B AB 1492-L3 6A13A AB 1492-L3 6A13B AB 1492-L3 6A14A AB 1492-L3 6A14B AB 1492-L3 6A15A AB 1492-L3 6A15B AB 1492-L3 ACC2 AB 1492-EBL3 ACC3 PHOENIX CONTACT 0800886 TB-DO-1 Number Jumper Manufacturer Part # TB-DO-1 PHOENIX CONTACT 1004348 ACC1 PHOENIX CONTACT 0800886 6B00A AB 1492-L3 6B00B AB 1492-L3 6B01A AB 1492-L3 6B01B AB 1492-L3 6B02A AB 1492-L3 6B02B AB 1492-L3 6B03A AB 1492-L3 6B03B AB 1492-L3 6B04A AB 1492-L3 6B04B AB 1492-L3 6B05A AB 1492-L3 6B05B AB 1492-L3 6B06A AB 1492-L3 6B06B AB 1492-L3 6B07A AB 1492-L3 6B07B AB 1492-L3 6B08A AB 1492-L3 6B08B AB 1492-L3 6B09A AB 1492-L3 6B09B AB 1492-L3 6B10A AB 1492-L3 6B10B AB 1492-L3 6B11A AB 1492-L3 6B11B AB 1492-L3 6B12A AB 1492-L3 6B12B AB 1492-L3 6B13A AB 1492-L3 6B13B AB 1492-L3 6B14A AB 1492-L3 6B14B AB 1492-L3 6B15A AB 1492-L3 6B15B AB 1492-L3 6BV1+AB 1492-L3 6BV1-AB 1492-L3 ACC2 AB 1492-EBL3 ACC3 PHOENIX CONTACT 0800886 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1H NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR TERMINAL STRIP DETAIL DIGITAL.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR TERMINAL STRIP DETAIL DIGITAL 13 31 CITY OF CARLSBAD TB-AI-1 Number Jumper Manufacturer Part # TB-AI-1 PHOENIX CONTACT 1004348 ACC1 PHOENIX CONTACT 0800886 GND AB 1492-LG3 6C00+AB 1492-L3P 6C00-AB 1492-L3 6C00B AB 1492-L3 6C00A AB 1492-L3 6C00G AB 1492-LG3 6C01+AB 1492-L3P 6C01-AB 1492-L3 6C01B AB 1492-L3 6C01A AB 1492-L3 6C01G AB 1492-LG3 6C02+AB 1492-L3P 6C02-AB 1492-L3 6C02B AB 1492-L3 6C02A AB 1492-L3 6C02G AB 1492-LG3 6C03+AB 1492-L3P 6C03-AB 1492-L3 6C03B AB 1492-L3 6C03A AB 1492-L3 6C03G AB 1492-LG3 6C04+AB 1492-L3P 6C04-AB 1492-L3 6C04B AB 1492-L3 6C04A AB 1492-L3 6C04G AB 1492-LG3 6C05+AB 1492-L3P 6C05-AB 1492-L3 6C05B AB 1492-L3 6C05A AB 1492-L3 6C05G AB 1492-LG3 6C06+AB 1492-L3P 6C06-AB 1492-L3 6C06B AB 1492-L3 6C06A AB 1492-L3 6C06G AB 1492-LG3 6C07+AB 1492-L3P 6C07-AB 1492-L3 6C07B AB 1492-L3 6C07A AB 1492-L3 6C07G AB 1492-LG3 ACC2 AB 1492-EBL3 ACC3 PHOENIX CONTACT 0800886 6D00+AB 1492-L3P 6D00-AB 1492-L3 6D00B AB 1492-L3 6D00A AB 1492-L3 6D00G AB 1492-LG3 6D01+AB 1492-L3P 6D01-AB 1492-L3 6D01B AB 1492-L3 6D01A AB 1492-L3 6D01G AB 1492-LG3 6D02+AB 1492-L3P 6D02-AB 1492-L3 6D02B AB 1492-L3 6D02A AB 1492-L3 6D02G AB 1492-LG3 6D03+AB 1492-L3P 6D03-AB 1492-L3 6D03B AB 1492-L3 6D03A AB 1492-L3 6D03G AB 1492-LG3 TB-AI-1 Number Jumper Manufacturer Part # 6D04+AB 1492-L3P 6D04-AB 1492-L3 6D04B AB 1492-L3 6D04A AB 1492-L3 6D04G AB 1492-LG3 6D05+AB 1492-L3P 6D05-AB 1492-L3 6D05B AB 1492-L3 6D05A AB 1492-L3 6D05G AB 1492-LG3 6D06+AB 1492-L3P 6D06-AB 1492-L3 6D06B AB 1492-L3 6D06A AB 1492-L3 6D06G AB 1492-LG3 6D07+AB 1492-L3P 6D07-AB 1492-L3 6D07B AB 1492-L3 6D07A AB 1492-L3 6D07G AB 1492-LG3 ACC4 AB 1492-EBL3 ACC5 PHOENIX CONTACT 0800886 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1I NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR TERMINAL STRIP DETAIL ANALOG.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR TERMINAL STRIP DETAIL ANALOG 14 31 CITY OF CARLSBAD TB-DO-RELAYAC BREAKERS RACK1 RACK1S00 5069-L320ER RA C K 1 S 0 3 50 6 9 - I F 8 RA C K 1 S 0 2 50 6 9 - O B 1 6 RA C K 1 S 0 1 50 6 9 - I B 1 6 RA C K 1 S 0 4 50 6 9 - I F 8 DC BREAKERS CB 4 A 1 0 CB 4 A 1 1 CB 4 A 1 2 CB 4 A 1 3 CB 4 A 1 4 CB 4 A 1 5 CB 4 A 1 6 CB 4 A 1 7 CB 4 A 1 8 CB 4 A 1 9 CB 4 A 2 0 CB 4 A 2 1 CB 3 A 0 0 CB 3 A 0 1 CB 3 A 0 2 CB 3 A 0 3 CB 3 A 0 4 PD 6 B 0 0 CR 6 B 0 8 CR 6 B 0 9 CR 6 B 1 0 CR 6 B 1 1 CR 6 B 1 2 CR 6 B 1 3 CR 6 B 1 4 CR 6 B 1 5 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1J NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR PANEL COMPONENT DETAIL.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR PANEL COMPONENT DETAIL 15 31 CITY OF CARLSBAD 7" 1"ELM RESERVOIR 120VAC FROM: LP-XXX CKT XX NOTE: LABEL TO BE CONSTRUCTED AT A LATER TIME NOTE: LABELS TO BE ENGRAVED TWO-LAYER UV STABILIZED MATERIAL WITH WHITE TEXT NO LESS THAN 14" HIGH ON BLACK BACKGROUND PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1K.1 2:1 CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR NAMEPLATE DETAIL 1.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR NAMEPLATE DETAIL (PART 1) 16 31 CITY OF CARLSBAD 2" 1" 1" 1 2" UPS4A02 LSA3A01 RECP3A01 RACK1 CB3A00 CB3A01 CB3A02 CB3A03 CB3A04 NOTE: IDENTIFICATION LABELS FOR COMPONENTS TO BE MOUNTED ON THE BACK PANEL NEXT TO THE COMPONENT AS SHOWN ON THE PANEL LAYOUT INTERIOR DETAILS SHEET. LABELS TO BE SELF ADHESIVE POLYESTER WITH THERMAL PRINTED BLACK TEXT NO LESS THAN 1/4" HIGH. CB4A10 CB4A11 CB4A12 CB4A13 CB4A14 CB4A15 CB4A16 CB4A17 CB4A18 CB4A19 CB4A20 CB4A21 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1K.2 2:1 CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR NAMEPLATE DETAIL 2.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR NAMEPLATE DETAIL (PART 2) 17 31 CITY OF CARLSBAD 13 4" 1 4" TB-DC-1 TB-AC-1 TB-BATT-1 TB-DI-1 TB-AI-1 TB-DOOR TB-DO-RELAY UPS4A01 PSU4A01 TB-DO-1 NOTE: IDENTIFICATION LABELS FOR DIN RAIL MOUNTED COMPONENTS TO BE MOUNTED ON THE END BRACKET NEXT TO THE COMPONENT OR TERMINAL STRIP. LABELS TO BE MOUNTED ON THE LEFT OF HORIZONTAL DIN RAIL MOUNTED COMPONENTS AND ABOVE VERTICAL DIN RAIL MOUNTED COMPONENTS. LABELS TO BE SELF ADHESIVE POLYESTER WITH THERMAL PRINTED BLACK TEXT NO LESS THAN 1/8" HIGH. TSTAT6A01 ROUTER EDGE DEVICE PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1K.3 2:1 CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR NAMEPLATE DETAIL 3.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR NAMEPLATE DETAIL (PART 3) 18 31 CITY OF CARLSBAD FIBER ETHERNET COPPER ETHERNET -USB AB SLOT0 CPU MODULE RACK1 RACK1S00 5069-L320ER USB - ETH 1 LINK 1 - ETH 2 LINK 2 PROVIDED BY CUSTOMER PROVIDED BY CUSTOMER 43 21 SHT 4A.2-B4 ROUTER 1 SHT 4A.2-B4 EDGE DEVICE PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 2A NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR NETWORK WIRING.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR NETWORK WIRING 19 31 CITY OF CARLSBAD 3A01N TB-AC-1 3A02N TB-AC-1 3A03N TB-AC-1 3A04N TB-AC-1 20A SHT 4A.2-E1,SHT 4A.2-F1 CB3A00 10A CB3A01 PSU4A01 3A01L to SHT 4A.1-A1 PSU4A01 3A01N to SHT 4A.1-A1 L LOADLINE G N L LSA3A01 SURGE SUPRESSOR INPUT TRANSIENT VOLTAGE N G 4A CB3A02 4A CB3A03 4A CB3A04 GND RECP3A01 3A00L 3A00A 3A01L 3A02L 3A01N 3A02N 3A00N 3A00N GROUND BAR from SHT 3A-B2 NOTE 1: 120VAC 1-PH/60HZ WITH FACILITY GROUND, SUPPLY NOT TO EXCEED 20 AMPS SERVICE GND TB-AI-1 SEL CB AUX CONTACT MODE SELECTOR ROTARY SWITCH FOR CB3A00 3A04L 3A04N RACK1 SLOT 2 DO RELAYS 3A04L to SHT 6B-E1 RACK1 SLOT 2 DO RELAYS 3A04N to SHT 6B-F1 CONTACT 4.XX ELECTRICAL TRIP CONTACT 1.XX GENERAL TRIP RED #12 AWG MTW WHT #12 AWG MTW ORG #12 AWG MTW CUSTOMER SUPPLY #1 *SEE NOTE 1 L N G GND3A01 GROUND BAR 3A01A 3A01B RECP3A01 to SHT 3A-E2 PSU4A01 to SHT 4A.1-A1 RACK1S00 SA POWER to SHT 4A.2-C3 ROUTER to SHT 4A.2-C4 NOA2A1SHT 6A-C4 AC POWER FAILCR3A00 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 3A NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR AC POWER DISTRIBUTION.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR AC POWER DISTRIBUTION 20 31 CITY OF CARLSBAD 24VDC DC-1 POWER SUPPLY PSU4A01 L2 / N GN D L -+ 24VDC 4A01+ to SHT 4A.2-A1 N-DC 4A01- to SHT 4A.2-D1 4A01 TB-BATT-1 4A02 TB-BATT-1 4A03- 4A04+4A04-4A02- 4A05A 4A06A 4A05B 4A06B 4A05C 4A30B 4A07A 4A30-4A07B 4A01- UPS4A01 INHIBIT 4A30B from SHT 4A.2-F1 N-DC 4A30- from SHT 4A.2-G1 120VAC 3A01L from SHT 3A-D1 3A01L 120N 3A01N from SHT 3A-E1 3A01N 4A00+4A00- 24VDC 4A06A to SHT 6A-C4 UPS4A01 ON BATTERY 4A06B to SHT 6A-D4 24VDC 4A07A to SHT 6A-C4 UPS4A01 BATTERY FAIL 4A07B to SHT 6A-D4 GROUND BAR from SHT 3A-B2 PULS DC UPS MODULE PULSUB20.241 UPS4A01 +INPUT - + - 11 12 13 + OUTPUT - 3 1 2 5 6 BATTERY READY REPLACE BATTERY TEMP RTN CENTER TAP + - 4 INHIBIT BUFFERING BATTERY SENSOR MODULE UPS4A02 11 12 13 TEMP RTN CENTER TAP E1 4A01+ 4A05D 30S 1m 3m 10m 10s BUFFER TIME LIMITER BUFFER VOLTAGE DC UPS SWITCH SETTINGS 25 26 24 22.5 BATTERY SIZE >10 AH <10 AH BLUE #10 AWG MTW WHT/BLUE #10 AWG MTW 12V 20AH +- BAT4A03 BLU #10 AWG MTW WHT/BLU #10 AWG MTW WHT/BLU #10 AWG MTW 4A02+4A03+ 4A03 TB-BATT-1 30A CB4A50 12V 20AH -+ BAT4A03 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 4A.1 NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR DC POWER DISTRIBUTION 1 (PART 1).dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR DC POWER DISTRIBUTION (PART 1) 21 31 CITY OF CARLSBAD 4A30+ TB-DC-1 4A31+ TB-DC-1 4A32+ TB-DC-1 4A33+ TB-DC-1 4A34+ TB-DC-1 4A30- TB-DC-1 4A31- TB-DC-1 4A32- TB-DC-1 4A33- TB-DC-1 4A34- TB-DC-1 4A10- TB-DC-1 4A11- TB-DC-1 4A12- TB-DC-1 4A13- TB-DC-1 4A14- TB-DC-1 4A15- TB-DC-1 4A16- TB-DC-1 4A17- TB-DC-1 UPS4A01 INHIBIT 4A30B to SHT 4A.1-A4 UPS4A01 INHIBIT 4A30- to SHT 4A.1-A4 RACK1 DI SLOT 01 4A10+ to SHT 6A-B1 4A18- TB-DC-1 INTRUSION 4A33+ to SHT 5A-C1 INTRUSION 4A33- to SHT 5A-F1 TB-AI-1 4A12- to SHT 6C-A1 24VDC 4A01+ from SHT 4A.1-A6 N-DC 4A01- from SHT 4A.1-C6 4A21- TB-DC-1 4A30+ 4A33+ 4A30A 4A12- 4A30- 4A33- 4A01- TB-AI-1 4A12+ to SHT 6C-A1 4A30B 24VDC 4A21+ from SHT 4A.2-B4 4A21+ N-DC from SHT 4A.2-D5 4A21+ to SHT 4A.2-E1 N-DC to SHT 4A.2-H1 4A19- TB-DC-1 4A20- TB-DC-1 0.5A CB4A15 0.5A CB4A10 6A CB4A11 2A CB4A12 2A CB4A13 6A CB4A14 6A CB4A16 4A CB4A17 2A CB4A18 2A CB4A19 2A CB4A20 6A CB4A21 4A11+ 4A12+ 4A10+ 4A21+ 4A01+ GROUND BAR from SHT 3A-B3 4A16- 4A19+4A19- 4A16+ GROUND BAR from SHT 3A-B3 4A17+4A17- SHT 2A-D3 G RTV ROUTER 4241 SHT 3A-C1 CB3A00 1211 SHT 3A-C1 CB3A00 SHT 2A-F2 12 EDGE DEVICE4A20+4A20- RACK1 DO SLOT 02 4A11+ to SHT 6B-A1 RACK1 DO SLOT 02 4A11- to SHT 6B-E1 4A11- SA POWER SHT 2A-C1 G -+ RACK1S00 MOD POWER SHT 2A-C1 -+ RACK1S00 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 4A.2 NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR DC POWER DISTRIBUTION 1 (PART 2).dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR DC POWER DISTRIBUTION (PART 2) 22 31 CITY OF CARLSBAD 24VDC 4A33+ from SHT 4A.2-F2 4A33+ N-DC 4A33- from SHT 4A.2-G2 4A33- 5A03A 5A04 PANEL INTRUSION 5A04 to SHT 6A-D5 5A01 TB-DOOR 5A01 5A02 TB-DOOR 5A02 5A03 TB-DOOR 5A04 TB-DOOR 5A05 TB-DOOR 5A05 5A08 24VDC 5A08 to SHT 6A-C5 5A01A 5A03 5A04 DOOR SWITCH ENCLOSURE SW5A01 ENCLOSURE LIGHT 1 24VDC LT5A01 BLU #16 AWG MTW BLU #16 AWG MTW BLU #16 AWG MTW WHT/BLU #16 AWG MTW BLU #18 AWG MTWBLU #18 AWG MTWBLU #18 AWG MTW BLU #18 AWG MTW PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 5A NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR PANEL IO DETAIL.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR PANEL I/O DETAIL 23 31 CITY OF CARLSBAD 6A00A TB-DI-1 6A01A TB-DI-1 6A02A TB-DI-1 6A03A TB-DI-1 6A04A TB-DI-1 6A05A TB-DI-1 6A06A TB-DI-1 6A07A TB-DI-1 6A08A TB-DI-1 6A09A TB-DI-1 6A10A TB-DI-1 6A11A TB-DI-1 6A12A TB-DI-1 6A13A TB-DI-1 6A14A TB-DI-1 6A15A TB-DI-1 6A00B TB-DI-1 6A01B TB-DI-1 6A02B TB-DI-1 6A03B TB-DI-1 6A04B TB-DI-1 6A05B TB-DI-1 6A06B TB-DI-1 6A07B TB-DI-1 6A08B TB-DI-1 6A09B TB-DI-1 6A10B TB-DI-1 6A11B TB-DI-1 6A12B TB-DI-1 6A13B TB-DI-1 6A14B TB-DI-1 6A15B TB-DI-1 24VDC 4A10+ from SHT 4A.2-B1 4A10+ 6A00 6A01 6A02 6A03 6A04 6A05 6A06 6A07 6A08 6A09 6A10 6A11 6A12 6A13 6A14 6A15 NOTE: ALL PANEL WIRING ON TB-DI-1 SHALL TERMINATE ONLY ON THE PANEL SIDE OF THE TERMINAL. DO NOT TERMINATE PANEL WIRING ON THE FIELD SIDE OF THE TERMINAL. 5A04 from SHT 5A-F2 5A08 from SHT 5A-C2 5A08 5A04 4A06A from SHT 4A.1-C4 4A06B from SHT 4A.1-C4 4A07A from SHT 4A.1-C4 4A07B from SHT 4A.1-C4 4A06A 4A07A 4A06B 4A07B 21 TSTAT6A016A10A 6A10B 6A11A 6A11B1413 SHT 3A-E2 CR3A00 0 - Site Intrusion 5069-IB16 AB SLOT 1 RACK1S01 16-POINT DISCRETE INPUT RACK 1 IN 0 1 - Spare IN 1 2 - Mixer Running (Future)IN 2 3 - Spare IN 3 4 - Spare IN 4 5 - Spare IN 5 6 - Spare IN 6 7 - Spare IN 7 8 - Spare IN 8 9 - Spare IN 9 10 - Control Panel High TemperatureIN 10 11 - Control Panel AC Power FailIN 11 12 - Control Panel UPS On BatteryIN 12 13 - Control Panel UPS FailureIN 13 14 - SpareIN 14 15 - Control Panel IntrusionIN 15 16NC 17NC PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 6A NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR RACK1S01.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR RACK 1 SLOT 1 DISCRETE INPUT 24 31 CITY OF CARLSBAD 6B00B TB-DO-1 6B01B TB-DO-1 6B02B TB-DO-1 6B03B TB-DO-1 6B04B TB-DO-1 6B05B TB-DO-1 6B06B TB-DO-1 6B07B TB-DO-1 6B08B TB-DO-1 6B09B TB-DO-1 6B10B TB-DO-1 6B11B TB-DO-1 6B12B TB-DO-1 6B13B TB-DO-1 6B14B TB-DO-1 6B15B TB-DO-1 6BV1+ TB-DO-1 6BV1- TB-DO-1 6B00A TB-DO-1 6B01A TB-DO-1 6B02A TB-DO-1 6B03A TB-DO-1 6B04A TB-DO-1 6B05A TB-DO-1 6B06A TB-DO-1 6B07A TB-DO-1 6B08A TB-DO-1 6B09A TB-DO-1 6B10A TB-DO-1 6B11A TB-DO-1 6B12A TB-DO-1 6B13A TB-DO-1 6B14A TB-DO-1 6B15A TB-DO-1 6B00 6B01 6B02 6B03 6B04 6B05 6B06 6B07 6B08 6B09 6B10 6B11 6B12 6B13 6B14 6B15 N-DC 4A11- from SHT 4A.2-C1 4A11- 24VDC 4A11+ from SHT 4A.2-B1 4A11+ A2A1 CR6B08 A2A1 CR6B09 A2A1 CR6B10 A2A1 CR6B11 A2A1 CR6B12 A2A1 CR6B13 A2A1 CR6B14 A2A1 CR6B15 6B08A 6B09A 6B10A 6B11A 6B12A 6B13A 6B14A 6B15A 6B08B 6BV1+ 6BV1-6BV1- BB CR6B08 BB CR6B09 BB CR6B10 BB CR6B11 BB CR6B12 BB CR6B13 BB CR6B14 BB CR6B15 1 2 43 A1 A2 BB 1413 PANEL PANEL FIELD FIELD TOP 2966508 RELAY POWER DISTRIBUTION DETAIL 2909661 RELAY DETAIL 43 RELAY POWER DISTRIBUTION PD6B00120VAC 3A04L from SHT 3A-D3 120N 3A04N from SHT 3A-E3 3A04N NOTE: ALL PANEL WIRING ON TB-DO-1 SHALL TERMINATE ONLY ON THE PANEL SIDE OF THE TERMINAL. DO NOT TERMINATE PANEL WIRING ON THE FIELD SIDE OF THE TERMINAL. 0 - Spare AB SLOT 2 16-POINT DISCRETE OUTPUT RACK 1 RACK1S02 5069-OB16 OUT 0 1 - Spare OUT 1 2 - Spare OUT 2 3 - Spare OUT 3 4 - Spare OUT 4 5 - Spare OUT 5 6 - Spare OUT 6 7 - Spare OUT 7 8 - Spare OUT 8 9 - Spare OUT 9 10 - Mixer Run (Future)OUT 10 11 - Spare OUT 11 12 - Spare OUT 12 13 - Spare OUT 13 14 - Spare OUT 14 15 - Spare OUT 15 16LA+ 17 LA- 3A04L 1413 CR6B08 1413 CR6B09 1413 CR6B10 1413 CR6B11 1413 CR6B12 1413 CR6B13 1413 CR6B14 1413 CR6B15 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 6B NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR RACK1S02.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR RACK 1 SLOT 2 DISCRETE OUTPUT 25 31 CITY OF CARLSBAD 6C00B TB-AI-1 6C01B TB-AI-1 6C02B TB-AI-1 6C03B TB-AI-1 6C00- TB-AI-1 6C01- TB-AI-1 6C02- TB-AI-1 6C03- TB-AI-1 6C00B 6C01A 6C01B 6C02A 6C02B 6C03B 24VDC to SHT 6C-E1 N-DC to SHT 6C-E1 TB-AI-1 4A12+ from SHT 4A.2-B2 TB-AI-1 4A12- from SHT 4A.2-C24A12+ 6C00+ TB-AI-1 63mA 6C01+ TB-AI-1 63mA 6C03+ TB-AI-1 63mA 6C02+ TB-AI-1 63mA SHLD 6C00G TB-AI-1 6C01G TB-AI-1 6C02G TB-AI-1 6C03G TB-AI-1 SHLD SHLD 4A12- +- +- +- SHLD +- 6C00A TB-AI-1 6C00A 6C01A TB-AI-1 6C02A TB-AI-1 6C03A TB-AI-1 6C03A 6C04B TB-AI-1 6C05B TB-AI-1 6C06B TB-AI-1 6C07B TB-AI-1 6C04- TB-AI-1 6C05- TB-AI-1 6C06- TB-AI-1 6C07- TB-AI-1 6C04A 6C04B 6C05A 6C05B 6C06A 6C06B 6C07A 6C07B 24VDC from SHT 6C-A6 N-DC from SHT 6C-A6 6C04+ TB-AI-1 63mA 6C05+ TB-AI-1 63mA 6C07+ TB-AI-1 63mA 6C06+ TB-AI-1 63mA 6C04G TB-AI-1 6C05G TB-AI-1 6C06G TB-AI-1 6C07G TB-AI-1 SHLD SHLD SHLD SHLD +- +- +- +- 6C04A TB-AI-1 6C05A TB-AI-1 6C06A TB-AI-1 6C07A TB-AI-1 24VDC to SHT 6D-A1 N-DC to SHT 6D-A1 0 - Spare 5069-IF8 AB SLOT 3 RACK1S03 8 CHANNEL ANALOG INPUT RACK 1 IN 0+ 1IN 0- 2 - Spare IN 1+ 3IN 1- 4 - Spare IN 2+ 5IN 2- 6 - Spare IN 3+ 7IN 3- 16SHLD 8 - Spare IN 4+ 9IN 4- 10 - Spare IN 5+ 11IN 5- 12 - Spare IN 6+ 13IN 6- 14 - Spare IN 7+ 15IN 7- 17SHLD RACK1S03 WIRE JUMPER WIRE JUMPER WIRE JUMPER WIRE JUMPER WIRE JUMPER WIRE JUMPER WIRE JUMPER WIRE JUMPER PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 6C NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR RACK1S03.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR RACK 1 SLOT 3 ANALOG INPUT 26 31 CITY OF CARLSBAD 6D00B TB-AI-1 6D01B TB-AI-1 6D02B TB-AI-1 6D03B TB-AI-1 6D00- TB-AI-1 6D01- TB-AI-1 6D02- TB-AI-1 6D03- TB-AI-1 6D00B 6D01A 6D01B 6D02A 6D02B 6D03B 24VDC to SHT 6D-E1 N-DC to SHT 6D-E1 24VDC from SHT 6C-E6 N-DC from SHT 6C-E6 6D00+ TB-AI-1 63mA 6D01+ TB-AI-1 63mA 6D03+ TB-AI-1 63mA 6D02+ TB-AI-1 63mA SHLD 6D00G TB-AI-1 6D01G TB-AI-1 6D02G TB-AI-1 6D03G TB-AI-1 SHLD SHLD +- +- +- SHLD +- 6D00A TB-AI-1 6D00A 6D01A TB-AI-1 6D02A TB-AI-1 6D03A TB-AI-1 6D03A 6D04B TB-AI-1 6D05B TB-AI-1 6D06B TB-AI-1 6D07B TB-AI-1 6D04- TB-AI-1 6D05- TB-AI-1 6D06- TB-AI-1 6D07- TB-AI-1 6D04A 6D04B 6D05A 6D05B 6D06A 6D06B 6D07A 6D07B 24VDC from SHT 6D-A6 N-DC from SHT 6D-A6 6D04+ TB-AI-1 63mA 6D05+ TB-AI-1 63mA 6D07+ TB-AI-1 63mA 6D06+ TB-AI-1 63mA 6D04G TB-AI-1 6D05G TB-AI-1 6D06G TB-AI-1 6D07G TB-AI-1 SHLD SHLD SHLD SHLD +- +- +- +- 6D04A TB-AI-1 6D05A TB-AI-1 6D06A TB-AI-1 6D07A TB-AI-1 0 - Reservoir 5069-IF8 AB SLOT 4 RACK1S04 8 CHANNEL ANALOG INPUT RACK 1 LevelIN 0+ 1IN 0- 2 - Spare IN 1+ 3IN 1- 4 - Spare IN 2+ 5IN 2- 6 - Spare IN 3+ 7IN 3- 16SHLD 8 - Tank Temperature (Future)IN 4+ 9IN 4- 10 - Spare IN 5+ 11IN 5- 12 - Spare IN 6+ 13IN 6- 14 - Spare IN 7+ 15IN 7- 17SHLD RACK1S04 WIRE JUMPER WIRE JUMPER WIRE JUMPER WIRE JUMPER WIRE JUMPER WIRE JUMPER WIRE JUMPER WIRE JUMPER PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 6D NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR RACK1S04.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR RACK 1 SLOT 4 ANALOG INPUT 27 31 CITY OF CARLSBAD MANUFACTURER PART #QTY DESCRIPTION TAGS AB 1492-CJK5-50 5 50 IEC CENTER JUMPER, 10 PL 5mm, PLUG-IN HARDWARE TB-AC-1 TB-DC-1 TB-DI-1 TB-DO-1 AB 1492-CJL8-2 1 2 IEC CENTER JUMPER, 2 PL 8mm, PLUG-IN, YELLOW HARDWARE TB-BATT-1 AB 1492-EBL3 8 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS HARDWARE GREY TB-AI-1 TB-DC-1 TB-DI-1 TB-DO-1 TB-AC-1 TB-DOOR AB 1492-EBL6 1 END BARRIER COMPATIBLE WITH 1492-L6 TYPE TERMINALS HARDWARE GREY TB-BATT-1 AB 1492-FPK224 16 TERMINAL ACCESSORY 1492, BLACK FUSE PLUG LED INDICATOR, RATED VOLTAGE 10-36VAC/DC, LEAKAGE CURRENT 1.6mA AT 24VDC FUSE ACCESSORY WITH BLOWN FUSE INDICATION TB-AI-1 AB 1492-L3 145 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, IEC - 2.5mm WIRE CROSS SECTION FEED-THROUGH GRAY COLOR, 30-12AWG, RATED VOLTAGE 600VAC/DC ONE-CIRCUIT FEED-THROUGH BLOCK TB-AI-1 TB-DC-1 TB-DI-1 TB-DO-1 TB-AC-1 TB-DOOR AB 1492-L3P 16 TERMINAL BLOCK 1492, GRAY FUSE BLOCK GREY COLOR, 30-12 AWG, RATED VOLTAGE 600VAC/DC SINGLE CIRCUIT FUSE TERMINAL BLOCK WITH BLOWN INDICATION TB-AI-1 AB 1492-L6 3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, IEC - 6mm WIRE CROSS SECTION FEED-THROUGH GRAY COLOR, 22-8AWG, RATED VOLTAGE 600VAC/DC ONE-CIRCUIT FEED-THROUGH BLOCK TB-BATT-1 AB 1492-LG3 17 IEC SPRING CLAMP TERMINAL BLOCK, GROUNDING BLOCK, 1492-L FEED-THROUGH GROUND GREEN / YELLOW COLOR, 30-12AWG ONE-CIRCUIT FEED-THROUGH GROUND BLOCK TB-AI-1 AB 1492-M5X10 356 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L TERMINAL TB-AI-1 TB-DC-1 TB-DI-1 TB-DO-1 TB-AC-1 TB-DOOR AB 1492-M6X12 6 TERMINAL LABEL, 6mm X 12mm, INDIVIDUAL, SNAP ON, 1492-L TERMINAL TB-BATT-1 AB 5069-ECR 1 5069 COMPACTLOGIX/COMPACT GUARDLOGIX RIGHT END CAP WITH ADAPTER 5069 RACK1ECR AB 5069-IB16 1 5069 COMPACT I/O 16 CHANNEL 24V DC SINK INPUTE MODULE 5069 COMPACTLOGIX RACK1S01 AB 5069-IF8 2 5069 COMPACT I/O 8 CHANNEL VOLTAGE/CURRENT ANALOG INPUT MODULE 5069 COMPACTLOGIX RACK1S03 RACK1S04 AB 5069-L320ER 1 COMPACTLOGIX 5380, 2 MB USER MEMORY, 16 I/Os, 40 ETHERNET/IP DEVICES 5069 COMPACTLOGIX RACK1S00 AB 5069-OB16 1 5069 COMPACT I/O 16 CHANNEL 24V DC SOURCE OUTPUT MODULE 5069 COMPACTLOGIX RACK1S02 AB 5069-RTB18-SCREW 4 18 PIN SCREW TYPE TERMINAL CONNECTOR 5069 COMPACTLOGIX RACK1S01 RACK1S02 RACK1S03 RACK1S04 AB 5069-RTB4-SCREW 1 4 PIN SCREW TYPE POWER TERMINAL CONNECTOR 5069 COMPACTLOGIX RACK1S00 AB 5069-RTB6-SCREW 1 6 PIN SCREW TYPE POWER TERMINAL CONNECTOR 5069 COMPACTLOGIX RACK1S00 BANNER WLB32C570PBQ 1 WLB32 ADJUSTABLE LED WORKSTATION LIGHT 24VDC LT5A01 CBI QY-1-13-DM-U2-0.5A 1 CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 0.5A 80V 1 POLE 1-POLE CIRCUIT BREAKER CB4A15 MANUFACTURER PART #QTY DESCRIPTION TAGS CBI QY-1-13-DM-U2-0.5A 1 CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 0.5A 80V 1 POLE 1-POLE CIRCUIT BREAKER CB4A10 CBI QY-1-13-DM-U2-2A 4 CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 2A 80V 1 POLE 1-POLE CIRCUIT BREAKER CB4A18 CB4A19 CB4A12 CB4A13 CBI QY-1-13-DM-U2-30A 1 CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 30A 80V 1 POLE 1-POLE CIRCUIT BREAKER CB4A50 CBI QY-1-13-DM-U2-4A 2 CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 4A 80V 1 POLE 1-POLE CIRCUIT BREAKER CB4A17 CB4A20 CBI QY-1-13-DM-U2-6A 4 CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 6A 80V 1 POLE 1-POLE CIRCUIT BREAKER CB4A14 CB4A21 CB4A11 CB4A16 CBI SABBM54 1 CIRCUIT BREAKER, 13MM, BUSBAR MODULE SINGLE PHASE, METAL BUSBAR CB4A10 CISCO ANT-4-5G4-O 1 DIRECT MOUNT OMNIDIRECTIONAL ANTENNA ANTENNA ROUTER CISCO IR1101 1 ROUTER, POWER INPUT 9.6 TO 60VDC, TEMP RATING: -40 TO 60C, 4 PORT ETHERNET NETWORK ROUTER DURACELL SLADC12-20C 2 LEAD-ACID BATTERY, 20AH, 12VDC, 13.3 LBS 12VDC BAT4A03 EATON AGCF12030 1 TRANSIENT VOLTAGE SURGE SUPPRESSOR, 120VAC, 20A 120VAC LSA3A01 EATON FAZ-D10/1-NA-SP 1 CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 10A, D CURVE 1-POLE CIRCUIT BREAKER RATING=10A CB3A01 EATON FAZ-D20/1-NA-SP 1 CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 20A, D CURVE 1-POLE CIRCUIT BREAKER RATING=20A CB3A00 EATON FAZ-D4/1-NA-SP 3 CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 4A, D CURVE 1-POLE CIRCUIT BREAKER RATING=4A CB3A02 CB3A03 CB3A04 EATON GMC-63MA 16 CARTRIDGE FUSE 63MA FUSE TB-AI-1 EATON Z-NHK 1 CIRCUIT BREAKER, UL 489 BRANCH, AUXILIARY SWITCH 1-POLE CIRCUIT BREAKER CB3A00 EXISTING EXISTING CABLE 1 CAT 6 ETHERNET CABLE CABLE ROUTER HOFFMAN A48H3612SSLP 1 STAINLESS STEEL TYPE 4X ENCLOSURE WALL-MOUNT ENCLOSURE 48 x 36 x 12 IN, STEEL, WATER/DUST-TIGHT SEAL FOR ELECTRICAL/ELECTRONIC COMPONENTS IN CORROSIVE ENVIROMENT ENCLOSURE HOFFMAN A48P36 1 45" X 33" PANEL FOR 48" X 36" TYPE 3R, 4, 4X, 12 AND 13 ENCLOSURES PANEL BACKPANEL HOFFMAN ALGDSTOP2 1 LARGE ENCLOSURE DOOR STOP KIT ACCESSORY STOP1 HOFFMAN HH05PS004 2 7.41 X 3.43 X 0.96 PEST SCREENS HARDWARE STAINLESS STEEL 304, BRUSHED VENT01 VENT02 HOFFMAN HH05SS04004X 2 12.33 X 7.70 X 3.40 FILTER FAN SHROUD HARDWARE STAINLESS STEEL 304, BRUSHED VENT01 VENT02 HUBBELL 5320-0 1 DUPLEX RECEPTACLE GANG BOX PANEL MOUNT REC RECP3A01 HUBBELL GFR15I 1 GFCI RECEPTACLE, 125V, 15A REC RECP3A01 HUBBELL SSJ26 1 GFCI RECEPTACLE COVER PLATE REC RECP3A01 MCMASTER CARR 90272A108 3 ZINC PLATED STEEL HEX BOLT, #4-40 X 3/8" NA UPS4A02 MCMASTER CARR 92150A104 6 NYLON SPACER NA UPS4A02 MCMASTER CARR 93505A485 3 ZINC-PLATED STEEL THREADED 1/4" HEX STANDOFF NA UPS4A02 ONLOGIC HX310 1 PANEL PC, EDGE GATEWAY, ELKHART LAKE INDUSTRIAL COMPUTER, 24VDC PROCESSOR EDGE DEVICE PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 99A.1 NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR PURCHASE LIST 1.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR PURCHASE LIST (PART 1) 28 31 CITY OF CARLSBAD MANUFACTURER PART #QTY DESCRIPTION TAGS PANDUIT C1.5LG6 1 WIRING DUCT COVER - GRAY 1.5" WIDE 1.5 LIGHT GRAY DUCT-DC-1.5" PANDUIT C1LG6 1 WIRING DUCT COVER - GRAY 1" WIDE 1 LIGHT GRAY DUCT-AC-1" PANDUIT C2LG6 1 WIRING DUCT COVER - GRAY 2" WIDE 2 LIGHT GRAY DUCT-DC-2" PANDUIT C3LG6 1 WIRING DUCT COVER - GRAY 3" WIDE 3 LIGHT GRAY DUCT-DC-3" PANDUIT F1.5X4LG6 1 NARROW FINGER, SLOTTED WIRING DUCT GRAY 1.5" WIDE X 4" DEEP 1.75 x 4.12 LIGHT GRAY LEAD-FREE PVC, STANDARD MOUNTING HOLES DUCT-DC-1.5" PANDUIT F1X4LG6 1 NARROW FINGER, SLOTTED WIRING DUCT GRAY 1" WIDE X 4" DEEP 1.25 x 4.08 LIGHT GRAY LEAD-FREE PVC, STANDARD MOUNTING HOLES DUCT-AC-1" PANDUIT F2X4LG6 1 NARROW FINGER, SLOTTED WIRING DUCT GRAY 2" WIDE X 4" DEEP 2.25 x 4.09 LIGHT GRAY LEAD-FREE PVC, STANDARD MOUNTING HOLES DUCT-DC-2" PANDUIT F3X4LG6 1 NARROW FINGER, SLOTTED WIRING DUCT GRAY 3" WIDE X 4" DEEP 3.25 x 4.11 LIGHT GRAY LEAD-FREE PVC, STANDARD MOUNTING HOLES DUCT-DC-3" PFANNENBERG 17111000010 1 THERMOSTAT, VOLTAGE RATING: 240VAC, DC RATING 30W, TEMP RATING: 32 TO 140 F, N.C. W/ CONTACT SPRINGS, GREY, FLZ 520 THERMOSTAT TSTAT6A01 PHOENIX CONTACT 0800886 28 END BRACKET - E/NS 35 N ACCESSORY GRAY, FOR THE NS 35 DIN RAIL 9.5MM WIDTH TB-AI-1 TB-DC-1 TB-DI-1 TB-DO-1 MISC TB-AC-1 TB-BATT-1 TB-DOOR PHOENIX CONTACT 1004348 7 END BRACKET LABEL FOR STRIP MARKING - KLM-A ACCESSORY TB-AC-1 TB-AI-1 TB-BATT-1 TB-DC-1 TB-DI-1 TB-DO-1 TB-DOOR PHOENIX CONTACT 1134645 1 BATTERY MOUNTING CASE M, WALL AND SURFACE MOUNTING BATTERY CONTAINER MOUNTING MATERIAL BAT4A03 PHOENIX CONTACT 1201141 1 INSULATED DIN RAIL MOUNT NA DINRAIL PHOENIX CONTACT 1201730 1 DIN RAIL NA DINRAIL PHOENIX CONTACT 2909661 7 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO RELAY CR6B09 CR6B10 CR6B11 CR6B12 CR6B13 CR6B14 CR6B15 PHOENIX CONTACT 2909661 1 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO RELAY CR6B08 PHOENIX CONTACT 2966249 1 RELAY MODULE 120VAC COIL WITH BUSBAR TERMINAL 1NO RELAY CR3A00 PHOENIX CONTACT 2966508 1 RELAY POWER TERMINAL POWER TERMINAL PD6B00 PHOENIX CONTACT 2966786 3 CONTINUOUS PLUG-IN BRIDGE MECHANICAL JUMPER, 500MM, RELAY JUMPER CR6B08 PD6B00 MANUFACTURER PART #QTY DESCRIPTION TAGS PULS CP20.241 1 1-PHASE POWER SUPPLY 24VDC INPUT: 120VAC,50/60Hz / OUTPUT: 24VDC, 20A PSU4A01 PULS UB20.241 1 DC UPS MODULE 24VDC, 20A OUTPUT, FOR 3.9AH TO 150AH BATTERY 24VDC UPS4A01 PULS UZS24.100 1 SENSOR BOARD FOR BATTERY MODULES 24VDC UPS4A02 SCHNEIDER PK18GTA 1 LOAD CENTER ACCESSORY, QO/HOMELINE, GROUND BAR KIT, 18 TERMINAL GROUND GND3A01 SQUARE D XZCP1141L5 1 M12 4 PIN CONNECTOR 16FT CABLE CABLE LT5A01 TELEMECANIQUE ZCE10 1 HEAD FOR LIMIT SWITCH - ZCE - STEEL END PLUNGER COMPLETE PLUNGER HEAD LINEAR SW5A01 TELEMECANIQUE ZCP21 1 LIMIT SWITCH BODY - ZCP - 1 NC + 1 NO - TERMINALS SNAP ACTION USE WITH CABLE GLAND ENTRY 1 NC + 1 NO SW5A01 TELEMECANIQUE ZCPEG11 1 CABLE GLAND ENTRY FOR LIMIT SWITCH PLASTIC BODY SW5A01 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 99A.2 NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR PURCHASE LIST 2.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR PURCHASE LIST (PART 2) 29 31 CITY OF CARLSBAD WIRENO COMPONENT 1 PIN1 COMPONENT 2 PIN2 WIRE TYPE DV6D07 -TB-AI-1 6D07A FIELD TB-AI-1 6D07+DV6D07 +FIELD DV6D03 -TB-AI-1 6D03A FIELD TB-AI-1 6D03+DV6D03 +FIELD DV6D06 -TB-AI-1 6D06A FIELD TB-AI-1 6D06+DV6D06 +FIELD DV6D02 -TB-AI-1 6D02A FIELD TB-AI-1 6D02+DV6D02 +FIELD DV6D05 -TB-AI-1 6D05A FIELD TB-AI-1 6D05+DV6D05 +FIELD DV6D01 -TB-AI-1 6D01A FIELD TB-AI-1 6D01+DV6D01 +FIELD DV6D04 -TB-AI-1 6D04A FIELD TB-AI-1 6D04+DV6D04 +FIELD DV6D00 -TB-AI-1 6D00A FIELD TB-AI-1 6D00+DV6D00 +FIELD DV6C07 -TB-AI-1 6C07A FIELD TB-AI-1 6C07+DV6C07 +FIELD DV6C03 -TB-AI-1 6C03A FIELD TB-AI-1 6C03+DV6C03 +FIELD DV6C06 -TB-AI-1 6C06A FIELD TB-AI-1 6C06+DV6C06 +FIELD DV6C02 -TB-AI-1 6C02A FIELD TB-AI-1 6C02+DV6C02 +FIELD DV6C05 -TB-AI-1 6C05A FIELD TB-AI-1 6C05+DV6C05 +FIELD DV6C01 -TB-AI-1 6C01A FIELD TB-AI-1 6C01+DV6C01 +FIELD DV6C04 -TB-AI-1 6C04A FIELD TB-AI-1 6C04+DV6C04 +FIELD DV6C00 -TB-AI-1 6C00A FIELD TB-AI-1 6C00+DV6C00 +FIELD CR6B15 14 DV6B15 +FIELD CR6B15 13 DV6B15 -FIELD CR6B14 14 DV6B14 +FIELD CR6B14 13 DV6B14 -FIELD CR6B13 14 DV6B13 +FIELD CR6B13 13 DV6B13 -FIELD CR6B12 14 DV6B12 +FIELD CR6B12 13 DV6B12 -FIELD CR6B11 14 DV6B11 +FIELD CR6B11 13 DV6B11 -FIELD CR6B10 14 DV6B10 +FIELD CR6B10 13 DV6B10 -FIELD CR6B09 14 DV6B09 +FIELD CR6B09 13 DV6B09 -FIELD CR6B08 14 DV6B08 +FIELD CR6B08 13 DV6B08 -FIELD DV6B07 -TB-DO-1 6B07B FIELD TB-DO-1 6B07A DV6B07 +FIELD DV6B06 -TB-DO-1 6B06B FIELD TB-DO-1 6B06A DV6B06 +FIELD DV6B05 -TB-DO-1 6B05B FIELD TB-DO-1 6B05A DV6B05 +FIELD DV6B04 -TB-DO-1 6B04B FIELD TB-DO-1 6B04A DV6B04 +FIELD DV6B03 -TB-DO-1 6B03B FIELD TB-DO-1 6B03A DV6B03 +FIELD DV6B02 -TB-DO-1 6B02B FIELD TB-DO-1 6B02A DV6B02 +FIELD WIRENO COMPONENT 1 PIN1 COMPONENT 2 PIN2 WIRE TYPE DV6B01 -TB-DO-1 6B01B FIELD TB-DO-1 6B01A DV6B01 +FIELD DV6B00 -TB-DO-1 6B00B FIELD TB-DO-1 6B00A DV6B00 +FIELD DV6A09 -TB-DI-1 6A09B FIELD TB-DI-1 6A09A DV6A09 +FIELD DV6A08 -TB-DI-1 6A08B FIELD TB-DI-1 6A08A DV6A08 +FIELD DV6A07 -TB-DI-1 6A07B FIELD TB-DI-1 6A07A DV6A07 +FIELD DV6A06 -TB-DI-1 6A06B FIELD TB-DI-1 6A06A DV6A06 +FIELD DV6A05 -TB-DI-1 6A05B FIELD TB-DI-1 6A05A DV6A05 +FIELD DV6A04 -TB-DI-1 6A04B FIELD TB-DI-1 6A04A DV6A04 +FIELD DV6A03 -TB-DI-1 6A03B FIELD TB-DI-1 6A03A DV6A03 +FIELD DV6A03 -TB-DI-1 6A02B FIELD TB-DI-1 6A02A DV6A03 +FIELD DV6A01 -TB-DI-1 6A01B FIELD TB-DI-1 6A01A DV6A01 +FIELD DV6A00 -TB-DI-1 6A00B FIELD TB-DI-1 6A00A DV6A00 +FIELD RECP3A01 GND RACK1S00 G GREEN_14 PSU4A01 GND RECP3A01 GND GREEN_14 LSA3A01 G TB-AI-1 GND GREEN_14 TB-AI-1 GND GND3A01 GREEN_14 GND3A01 ROUTER G GREEN_14 ROUTER G PSU4A01 GND GREEN_14 GND3A01 LSA3A01 G GREEN_14 GND3A01 FIELD LSA3A01 N FIELD LSA3A01 L FIELD EDGE DEVICE ROUTER 4 ORANGE_CAT6 RACK1S00 -ROUTER 3 ORANGE_CAT6 3A00A CB3A00 CB3A01 RED_12 3A00L LSA3A01 L CB3A00 ORANGE_12 3A00N LSA3A01 N TB-AC-1 3A01N WHITE_12 3A01A CB3A01 CR3A00 A1 RED_14 3A01B TB-AC-1 3A01N CR3A00 A2 WHITE_14 3A01L CB3A01 PSU4A01 L RED_14 3A01N TB-AC-1 3A01N PSU4A01 L2/N WHITE_14 3A02L CB3A02 RECP3A01 RED_14 3A02N RECP3A01 TB-AC-1 3A02N WHITE_14 3A04L CB3A04 PD6B00 3 RED_14 3A04N TB-AC-1 3A04N PD6B00 4 WHITE_14 4A00+PSU4A01 +UPS4A01 +BLUE_10 4A00-PSU4A01 -UPS4A01 -WHT_BLU_10 4A01+UPS4A01 +CB4A10 BLUE_10 4A01-UPS4A01 -TB-DC-1 4A10-WHT_BLU_10 4A02+CB4A50 UPS4A01 +BLUE_10 4A02-TB-BATT-1 4A03 UPS4A01 -WHT_BLU_10 4A03+BAT4A03 +CB4A50 BLUE_10 4A03-TB-BATT-1 4A01 BAT4A03 -WHT_BLU_10 4A04+TB-BATT-1 4A02 BAT4A03 +BLUE_10 4A04-BAT4A03 -TB-BATT-1 4A03 WHT_BLU_10 4A05A UPS4A02 11 UPS4A01 11 BLUE_16 4A05B UPS4A02 12 UPS4A01 12 BLUE_16 4A05C UPS4A02 13 UPS4A01 13 BLUE_16 WIRENO COMPONENT 1 PIN1 COMPONENT 2 PIN2 WIRE TYPE 4A05D TB-BATT-1 4A02 UPS4A02 E1 BLUE_18 4A06A UPS4A01 3 TB-DI-1 6A12A BLUE_18 4A06B UPS4A01 4 TB-DI-1 6A12B BLUE_18 4A07A UPS4A01 5 TB-DI-1 6A13A BLUE_18 4A07B UPS4A01 6 TB-DI-1 6A13B BLUE_18 4A10+CB4A10 TB-DI-1 6A00A BLUE_16 4A11+CB4A11 TB-DO-1 6BV1+BLUE_16 4A12+CB4A12 TB-AI-1 6C00+BLUE_16 4A12-TB-DC-1 4A12-TB-AI-1 6C00-WHT_BLU_16 4A12-TB-DC-1 4A11-TB-DO-1 6B00B WHT_BLU_16 4A16+CB4A16 RACK1S00 +BLUE_16 4A16-RACK1S00 -TB-DC-1 4A16-WHT_BLU_16 4A17+CB4A17 RACK1S00 +BLUE_16 4A17-RACK1S00 -TB-DC-1 4A17-WHT_BLU_16 4A19+CB4A20 EDGE DEVICE 2 BLUE_16 4A19+CB4A19 ROUTER V BLUE_16 4A19-EDGE DEVICE 1 TB-DC-1 4A20-WHT_BLU_16 4A19-ROUTER RT TB-DC-1 4A19-WHT_BLU_16 4A21+CB4A21 TB-DC-1 4A30+BLUE_16 4A30+TB-DC-1 4A30+CB3A00 41 BLUE_16 4A30-TB-DC-1 4A30-UPS4A01 -WHT_BLU_16 4A30A CB3A00 42 CB3A00 11 BLUE_16 4A30B CB3A00 12 UPS4A01 +BLUE_16 4A33+TB-DC-1 4A33+TB-DOOR 5A01 BLUE_16 4A33-TB-DC-1 4A33-TB-DOOR 5A05 WHT_BLU_16 5A01 TB-DOOR 5A01 SW5A01 BLUE_16 5A01A SW5A01 TB-DOOR 5A02 BLUE_16 5A02 TB-DOOR 5A02 LT5A01 1 BLUE_16 5A03 TB-DOOR 5A03 SW5A01 BLUE_18 5A03A SW5A01 TB-DOOR 5A04 BLUE_18 5A04 TB-DOOR 5A04 TB-DI-1 6A15B BLUE_18 5A05 LT5A01 2 TB-DOOR 5A05 WHT_BLU_16 5A08 TB-DOOR 5A03 TB-DI-1 6A15A BLUE_18 6A00 TB-DI-1 6A00B RACK1S01 0 BLUE_18 6A01 TB-DI-1 6A01B RACK1S01 1 BLUE_18 6A02 TB-DI-1 6A02B RACK1S01 2 BLUE_18 6A03 TB-DI-1 6A03B RACK1S01 3 BLUE_18 6A04 TB-DI-1 6A04B RACK1S01 4 BLUE_18 6A05 TB-DI-1 6A05B RACK1S01 5 BLUE_18 6A06 TB-DI-1 6A06B RACK1S01 6 BLUE_18 6A07 TB-DI-1 6A07B RACK1S01 7 BLUE_18 6A08 TB-DI-1 6A08B RACK1S01 8 BLUE_18 6A09 TB-DI-1 6A09B RACK1S01 9 BLUE_18 6A10 TB-DI-1 6A10B RACK1S01 10 BLUE_18 6A10A TB-DI-1 6A10A TSTAT6A01 1 BLUE_18 6A10B TSTAT6A01 2 TB-DI-1 6A10B BLUE_18 6A11 TB-DI-1 6A11B RACK1S01 11 BLUE_18 6A11A TB-DI-1 6A11A CR3A00 11 BLUE_18 6A11B CR3A00 14 TB-DI-1 6A11B BLUE_18 6A12 TB-DI-1 6A12B RACK1S01 12 BLUE_18 6A13 TB-DI-1 6A13B RACK1S01 13 BLUE_18 6A14 TB-DI-1 6A14B RACK1S01 14 BLUE_18 6A15 TB-DI-1 6A15B RACK1S01 15 BLUE_18 6B00 RACK1S02 0 TB-DO-1 6B00A YELLOW_18 6B01 RACK1S02 1 TB-DO-1 6B01A YELLOW_18 6B02 RACK1S02 2 TB-DO-1 6B02A YELLOW_18 6B03 RACK1S02 3 TB-DO-1 6B03A YELLOW_18 6B04 RACK1S02 4 TB-DO-1 6B04A YELLOW_18 6B05 RACK1S02 5 TB-DO-1 6B05A YELLOW_18 6B06 RACK1S02 6 TB-DO-1 6B06A YELLOW_18 WIRENO COMPONENT 1 PIN1 COMPONENT 2 PIN2 WIRE TYPE 6B07 RACK1S02 7 TB-DO-1 6B07A YELLOW_18 6B08 RACK1S02 8 TB-DO-1 6B08A YELLOW_18 6B08A TB-DO-1 6B08A CR6B08 A1 YELLOW_18 6B08B CR6B08 A2 TB-DO-1 6B08B WHT_BLU_16 6B09 RACK1S02 9 TB-DO-1 6B09A YELLOW_18 6B09A TB-DO-1 6B09A CR6B09 A1 YELLOW_18 6B10 RACK1S02 10 TB-DO-1 6B10A YELLOW_18 6B10A TB-DO-1 6B10A CR6B10 A1 YELLOW_18 6B11 RACK1S02 11 TB-DO-1 6B11A YELLOW_18 6B11A TB-DO-1 6B11A CR6B11 A1 YELLOW_18 6B12 RACK1S02 12 TB-DO-1 6B12A YELLOW_18 6B12A TB-DO-1 6B12A CR6B12 A1 YELLOW_18 6B13 RACK1S02 13 TB-DO-1 6B13A YELLOW_18 6B13A TB-DO-1 6B13A CR6B13 A1 YELLOW_18 6B14 RACK1S02 14 TB-DO-1 6B14A YELLOW_18 6B14A TB-DO-1 6B14A CR6B14 A1 YELLOW_18 6B15 RACK1S02 15 TB-DO-1 6B15A YELLOW_18 6B15A TB-DO-1 6B15A CR6B15 A1 YELLOW_18 6BV1+TB-DO-1 6BV1+RACK1S02 16 BLUE_16 6BV1-RACK1S02 17 TB-DO-1 6BV1-WHT_BLU_16 6C00A TB-AI-1 6C00A RACK1S03 0 PURPLE_18 6C00B TB-AI-1 6C00B RACK1S03 1 PURPLE_18 6C01A TB-AI-1 6C01A RACK1S03 2 PURPLE_18 6C01B TB-AI-1 6C01B RACK1S03 3 PURPLE_18 6C02A TB-AI-1 6C02A RACK1S03 4 PURPLE_18 6C02B TB-AI-1 6C02B RACK1S03 5 PURPLE_18 6C03A TB-AI-1 6C03A RACK1S03 6 PURPLE_18 6C03B TB-AI-1 6C03B RACK1S03 7 PURPLE_18 6C04A TB-AI-1 6C04A RACK1S03 8 PURPLE_18 6C04B TB-AI-1 6C04B RACK1S03 9 PURPLE_18 6C05A TB-AI-1 6C05A RACK1S03 10 PURPLE_18 6C05B TB-AI-1 6C05B RACK1S03 11 PURPLE_18 6C06A TB-AI-1 6C06A RACK1S03 12 PURPLE_18 6C06B TB-AI-1 6C06B RACK1S03 13 PURPLE_18 6C07A TB-AI-1 6C07A RACK1S03 14 PURPLE_18 6C07B TB-AI-1 6C07B RACK1S03 15 PURPLE_18 6D00A TB-AI-1 6D00A RACK1S04 0 PURPLE_18 6D00B TB-AI-1 6D00B RACK1S04 1 PURPLE_18 6D01A TB-AI-1 6D01A RACK1S04 2 PURPLE_18 6D01B TB-AI-1 6D01B RACK1S04 3 PURPLE_18 6D02A TB-AI-1 6D02A RACK1S04 4 PURPLE_18 6D02B TB-AI-1 6D02B RACK1S04 5 PURPLE_18 6D03A TB-AI-1 6D03A RACK1S04 6 PURPLE_18 6D03B TB-AI-1 6D03B RACK1S04 7 PURPLE_18 6D04A TB-AI-1 6D04A RACK1S04 8 PURPLE_18 6D04B TB-AI-1 6D04B RACK1S04 9 PURPLE_18 6D05A TB-AI-1 6D05A RACK1S04 10 PURPLE_18 6D05B TB-AI-1 6D05B RACK1S04 11 PURPLE_18 6D06A TB-AI-1 6D06A RACK1S04 12 PURPLE_18 6D06B TB-AI-1 6D06B RACK1S04 13 PURPLE_18 6D07A TB-AI-1 6D07A RACK1S04 14 PURPLE_18 6D07B TB-AI-1 6D07B RACK1S04 15 PURPLE_18 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 99B.1 NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR WIRE REPORT 1.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR WIRE REPORT (PART 1) 30 31 CITY OF CARLSBAD THIS SHEET INTENTIONALLY LEFT BLANK PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 RYAN KING JAKE MEYERS DAVE LEWIS 538-4R KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 99B.2 NO SCALE CITY OF CARLSBAD ELM RESERVOIR CWD ELM RESERVOIR WIRE REPORT 2.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N ELM RESERVOIR WIRE REPORT (PART 2) 31 31 CITY OF CARLSBAD