HomeMy WebLinkAboutDWG 538-4W; 5542-B; Electrical Control Panel Replacement Project - Haymar Intertie; 01-27HAYMAR INTERTIE DWG SECTION SECTION DESCRIPTION 1 GENERAL 2 NETWORK WIRING 3 AC POWER 4 DC POWER 5 MISCELLANEOUS 6 IO RACK 1 7 IO RACK 2 8 IO RACK 3 99 REPORTS (PANEL BUILDER REFERENCE ONLY) DRAWING NUMBERING CONVENTION X Y . # DRAWING SECTION NUMBER SHEET LETTER SUB SHEET NUMBER (OPTIONAL) CITYWIDE ELECTRICAL CONTROL PANEL REPLACEMENT PROJECT FOR WATER AND WASTEWATER FACILITIES SHEET DWG DESCRIPTION REVISION 1 1A TABLE OF CONTENTS 0.2 2 1B DRAWING SYMBOL KEY 0.2 3 1C CONSTRUCTION COMMENTS 0.2 4 1D BILL OF MATERIAL 0.2 5 1E.1 PANEL LAYOUT EXTERIOR DETAILS 0.2 6 1E.2 PANEL LAYOUT EXTERIOR DIMENSIONS 0.2 7 1E.3 PANEL LAYOUT EXTERIOR CONDUIT ENTRY 0.2 8 1F.1 PANEL LAYOUT INTERIOR DETAILS 0.2 9 1F.2 PANEL LAYOUT INTERIOR DIMENSIONS 0.2 10 1F.3 PANEL LAYOUT INTERIOR TOP VIEW 0.2 11 1G TERMINAL STRIP DETAIL 0.2 12 1H TERMINAL STRIP DETAIL DIGITAL 0.2 13 1I TERMINAL STRIP DETAIL ANALOG 0.2 14 1J PANEL COMPONENT DETAIL 0.2 15 1K.1 NAMEPLATE DETAIL (PART 1)0.2 16 1K.2 NAMEPLATE DETAIL (PART 2)0.2 17 2A NETWORK WIRING 0.2 18 3A AC POWER DISTRIBUTION 0.2 19 4A.1 DC POWER DISTRIBUTION (PART 1)0.2 20 4A.2 DC POWER DISTRIBUTION (PART 2)0.2 21 5A PANEL I/O DETAIL 0.2 22 6A RACK 1 SLOT 1 DISCRETE INPUT 0.2 23 6B RACK 1 SLOT 2 DISCRETE OUTPUT 0.2 24 6C RACK 1 SLOT 3 ANALOG INPUT 0.2 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1A NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION TABLE OF CONTENTS.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE TABLE OF CONTENTS 1 27 CARLSBAD MUNICIPAL WATER DISTRICT NOTE: REFER TO SHEET G-003 GENERAL NOTES. ALL INFORMATION IS APPLICABLE TO THIS DESIGN. DRAWING SYMBOL KEY COMPONENT TAG NORMALLY OPEN STATUS CONTACT CROSS REFERENCE NORMALLY CLOSED STATUS CONTACT CROSS REFERENCE C/B RATING 20A SHT 2X-A1,SHT 3X-A2 CB1X01 3A01L 120VAC 3A01L to SHT 4A.1-A1 TB-XX Number Jumper Manufacturer Part # 1X22 MFG NAME XXXXXXX 1X23 1X24 MFG NAME XXXXXXX 1X25 TERMINALS NOT JUMPERED TERMINALS JUMPERED G GND3A01 GROUND BAR COMPONENT TAG C/B RATING 20A CB1X01 4241 SHT 1X-C1 CB1X01 1211 SHT 1X-C1 CB1X01 CIRCUIT BREAKER LOCATION CROSS REFERENCE COMPONENT TAG NORMALLY OPEN CONTACT LOCATION CROSS REFERENCE NORMALLY CLOSED CONTACT LOCATION CROSS REFERENCE NORMALLY OPEN CONTACT NORMALLY CLOSED CONTACT CR1X01 RELAY COIL LOCATION CROSS REFERENCE RELAY COIL LOCATION CROSS REFERENCE NC NO SHT 3X-A2 SHT 2X-A1 4241 SHT 1X-C1 CB1X01 1211 SHT 1X-C1 CB1X01 PANEL-MOUNTED GROUND BUS TERMINAL STRIP JUMPER DETAILS WIRE JUMPERS (BETWEEN TERMINALS) MECHANICAL JUMPERS 1X22 1X21 1X20 1X12 1X11 1X10 CONTROL RELAY (WITH CONTACT CROSS REFERENCE) SINGLE-POLE CIRCUIT BREAKER SINGLE-POLE CIRCUIT BREAKER (WITH AUXILIARY STATUS CONTACTS) PREFIX DESCRIPTION BAT BATTERY CB CIRCUIT BREAKER CBL CABLE GND GROUND BAR HTR HEATER LS LIMIT SWITCH LSA LIGHTNING SURGE ARRESTER LT LIGHT NETSW ETHERNET NETWORK SWITCH PB PUSH BUTTON PD POWER DISTRIBUTION TERMINAL BLOCK PSU POWER SUPPLY RECP RECEPTACLE SS SELECTOR SWITCH TB TERMINAL BLOCK TC THERMOCOUPLE CONVERTER TR TIMER RELAY TSTAT THERMOSTAT UPS UNINTERRUPTIBLE POWER SUPPLY XX YY ## COMPONENT PREFIX DRAWING SHEET NUMBER COMPONENT NUMBER (SEQUENTIAL) COMPONENT TAG NAMING CONVENTION SHT XX - Y Z LOCATION CROSS REFERENCE CONVENTION DRAWING SHEET NUMBER SHEET COLUMN LETTER SHEET ROW NUMBER A B 1 2 SHEET LOCATION COLUMN LETTER SHEET LOCATION ROW NUMBER WIRE OFF SHEET CROSS REVERENCE WIRE NUMBER WIRE LOCATION SHEET REFERENCE SIGNAL DESCRIPTION SELECTOR SWITCH, 2-POLE (TOP: NO, BOTTOM: NC) PILOT LIGHT, PUSH-TO-TEST (COLOR: A=AMBER, G=GREEN, R=RED) 100W A DIGITAL FIELD DEVICE ANALOG FIELD DEVICE LIMIT SWITCH NORMALLY CLOSED LIMIT SWITCH NORMALLY OPEN PUSH BUTTON NORMALLY OPEN PUSH BUTTON NORMALLY CLOSED MUSHROOM HEAD PUSH BUTTON RADIANT HEATER HORN OR BUZZER GENERIC DEVICE +- ELECTRICAL SYMBOL DEFINITIONS BILL OF MATERIAL TAG # REFERENCE BUBBLEDV1X02 DUPLEX RECEPTACLE SPECIAL CHARACTER DESCRIPTION L 120VAC POWER LINE VOLTAGE N 120VAC POWER NEUTRAL +24VDC POSITIVE -24VDC NEUTRAL G GROUND OTHER (A-Z)UNIQUE WIRE DESIGNATOR YY ## A DRAWING SHEET NUMBER WIRE NUMBER (SEQUENTIAL) SPECIAL DESIGNATOR CHARACTER (OPTIONAL) WIRE NUMBERING CONVENTION FUSE NUMBER TERMINAL STRIP WIRE NUMBER FUSE RATING 1X57 TB-XX 1X56 TB-XX 1X041X03 1X55 TB-XX 1X54 TB-XX 0.5A RED #12 AWG MTW WIRE COLOR, SIZE, AND TYPE DESIGNATION WIRE TYPE SYMBOLS FIELD WIRING INTERNAL PANEL WIRING SHLD SHIELDED MULTI-CONDUCTOR CABLE WITH DRAIN WIRE MULTI-CONDUCTOR CABLE WHTCBL6A01 BRNCBL6A01 CABLE TAG INDIVIDUAL CONDUCTOR COLOR FUSED TERMINAL DISCONNECT TERMINAL (FOR ANALOG SIGNAL TESTING) FEED-THROUGH TERMINAL GROUND TERMINAL (CONNECTED DIRECTLY TO DIN RAIL) PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1B NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION DRAWING SYMBOL KEY.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE DRAWING SYMBOL KEY 2 27 CARLSBAD MUNICIPAL WATER DISTRICT PANEL CONSTRUCTION COMMENTS AND SPECIAL INSTRUCTIONS ISOLATED DIN RAIL: EACH ISOLATED DIN RAIL SHALL BE INSTALLED ON INSULATED STANDOFFS TO CREATE ISOLATION BETWEEN THE DIN RAIL AND THE BACK PANEL. EACH DIN RAIL WILL HAVE A SINGLE GROUNDING TERMINAL BLOCK, WHICH IS TO BE CONNECTED DIRECTLY TO THE GROUND BUS WITH A SINGLE CONDUCTOR OF #14AWG (GREEN) WIRE. THE TERMINAL STRIPS LISTED TOGETHER BELOW SHALL BE MOUNTED ON THE SAME, CONTINUOUS ISOLATED DIN RAIL. THIS REQUIREMENT APPLIES TO: TB-AI-1 TB-DI-1 TB-DO-1 TERMINAL BLOCKS: FOR THE FOLLOWING TERMINAL BLOCKS, FIELD WIRING TERMINATES ON THE LEFT AND PANEL WIRING TERMINATES ON THE RIGHT. THIS REQUIREMENT APPLIES TO: TB-AI-1 TB-DI-1 TB-DO-1 FOR THE FOLLOWING TERMINAL BLOCKS, FIELD WIRING TERMINATES ON THE RIGHT AND PANEL WIRING TERMINATES ON THE LEFT. THIS REQUIREMENT APPLIES TO: TB-DO-RELAY FOR THE FOLLOWING TERMINAL BLOCKS, ALL PANEL WIRING SHALL TERMINATE ONLY ON THE PANEL SIDE OF THE TERMINAL. DO NOT TERMINATE PANEL WIRING ON THE FIELD SIDE OF THE TERMINAL. THIS REQUIREMENT APPLIES TO: TB-DI-1 TB-DO-1 INPUT LSA (LSA3A01) IS TO BE MOUNTED AND WIRED SUCH THAT FIELD TERMINATIONS ARE ON THE RIGHT AND PANEL WIRING IS ON THE LEFT. GROUND BUS: MOUNT GROUND BUS DIRECTLY TO BACK PANEL. BOND THE GROUND STUD ON ENCLOSURE DOOR(S) DIRECTLY TO ENCLOSURE GROUNDING STUD(S) USING SINGLE CONDUCTOR OF #14AWG (GREEN) WIRE. DO NOT GROUND CONTROL COMPONENTS TO BACK PANEL. RUN SINGLE CONDUCTORS DIRECTLY TO GROUND BUS AS SHOWN ON SHEET 3A OF DRAWING SET. ENCLOSURE AND PANEL ASSEMBLY: PANEL IS TO BE CONSTRUCTED IN CONFORMANCE WITH NEC (INCLUDING ARTICLE 409) AND UL 508A AND BEAR THE APPROPRIATE UL 508A INDUSTRIAL CONTROL PANEL LABEL CONFIRMING THE CONSTRUCTION. ATTACH WIRE DUCT TO PANEL WITH METAL FASTENERS. ENCLOSURE DOOR STOP TO BE INSTALLED WITH WELDED STUDS ON THE DOOR AND BOLTS WITH SEALING WASHERS ON THE ENCLOSURE. ROUTER IR1101 AND ANTENNA ANT-4-5G4-O TO BE PROVIDED BY CUSTOMER AND ASSEMBLED BY CONTRACTOR. DEVICE LABELS: UNLESS OTHERWISE INDICATED, ALL COMPONENT IDENTIFICATION LABELS ARE TO BE SELF ADHESIVE POLYESTER WITH BLACK THERMAL PRINTED TEXT. ADDITIONAL COMPONENT IDENTIFICATION LABELS ARE TO BE MOUNTED ON THE FRONT OF EACH DEVICE. ALL LABELS TO BE OF UNIFORM SIZE AND FONT. TEXT TO MATCH THE LABEL ON THE END BRACKET NEXT TO THE DEVICE. THIS REQUIREMENT APPLIES TO: ALL CIRCUIT BREAKERS PSU4A01 UPS4A01 ROUTER EDGE DEVICE WIRE AND TERMINAL MARKING: ALL WIRE AND TERMINAL LABELS TO BE COMPUTER PRINTED. NO HAND-WRITTEN TERMINAL OR WIRE NUMBERS ALLOWED LABEL ALL TERMINALS WITH TERMINAL MANUFACTURE MARKER STRIPS LABEL ALL WIRE/CABLE WITH HEAT SHRINK MARKING SLEEVES. PANEL WIRING: USE DUAL WIRE FERRULES WHENEVER 2 WIRES ARE INSERTED INTO A SINGLE TERMINATION POINT. DO NOT ROUTE WIRES AGAINST OR FASTENED TO COOLING VENTS OF CONTROL COMPONENTS. DO NOT ROUTE PANEL WIRING INSIDE WIRE DUCTS THAT ARE MARKED AS FIELD WIRING DO NOT USE NYLON TIE WRAPS INSIDE WIRE DUCT. WIRES AND CABLES ROUTED OUTSIDE OF WIRE DUCTS SHALL BE FIXED TO ENCLOSURE WITH WIRE SADDLES AT A MINIMUM OF EVERY 4 INCHES. WIRE SADDLES ARE TO BE MOUNTED USING THREADED STUDS WELDED TO ENCLOSURE, DO NOT USE ADHESIVE BACKED WIRE SADDLES. WIRE COLOR AND SIZES: UNLESS OTHERWISE SPECIFIED IN THE DRAWING SET, ALL WIRES TO BE SIZED AND COLORED AS FOLLOWS: 120VAC = RED, 14 AWG, MTW 120VAC NEUTRAL = WHITE, 14 AWG, MTW 120VAC NOT DISCONNECTED BY PANEL'S MAIN CIRCUIT BREAKER = ORANGE, 14 AWG, MTW 24VDC = BLUE, 16 AWG, MTW N-DC = WHITE/BLUE, 16 AWG, MTW GROUND = GREEN, 14 AWG, MTW DISCRETE INPUTS = BLUE, 18 AWG, MTW, OR MANUFACTURES MULTI-CONDUCTOR CABLE DISCRETE OUTPUTS = YELLOW, 18 AWG, MTW ANALOG INPUTS AND OUTPUTS = PURPLE, 18 AWG, MTW PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1C NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION CONSTRUCTION COMMENTS.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE CONSTRUCTION COMMENTS 3 27 CARLSBAD MUNICIPAL WATER DISTRICT ALL BILL OF MATERIAL ITEMS ARE "NO EQUAL" TO MATCH EXISTING STANDARDS, AND SHALL BE PROVIDED AS LISTED. TAG QTY MANUFACTURER PART #DESCRIPTION BACKPANEL 1 SAGINAW SCE-30P30 SUBPANEL, BENT, 27" X 27" POWDER COATED WHITE CB3A00 1 EATON FAZ-D20/1-NA-SP CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 20A, D CURVE 1 EATON Z-NHK CIRCUIT BREAKER, UL 489 BRANCH, AUXILIARY SWITCH CB3A01 1 EATON FAZ-D10/1-NA-SP CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 10A, D CURVE CB3A02 1 EATON FAZ-D4/1-NA-SP CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 4A, D CURVE CB3A03 1 EATON FAZ-D4/1-NA-SP CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 4A, D CURVE CB4A10 1 CBI QY-1-13-DM-U2-0.5A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 0.5A 80V 1 POLE CB4A11 1 CBI QY-1-13-DM-U2-6A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 6A 80V 1 POLE CB4A12 1 CBI QY-1-13-DM-U2-2A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 2A 80V 1 POLE CB4A13 1 CBI QY-1-13-DM-U2-6A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 6A 80V 1 POLE CB4A14 1 CBI QY-1-13-DM-U2-4A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 4A 80V 1 POLE CB4A15 1 CBI QY-1-13-DM-U2-2A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 2A 80V 1 POLE CB4A16 1 CBI QY-1-13-DM-U2-2A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 2A 80V 1 POLE CB4A17 1 CBI QY-1-13-DM-U2-4A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 4A 80V 1 POLE CB4A18 1 CBI QY-1-13-DM-U2-6A CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 6A 80V 1 POLE CR3A00 1 PHOENIX CONTACT 2966249 RELAY MODULE 120VAC COIL WITH BUSBAR TERMINAL 1NO CR6B08 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO 1 PHOENIX CONTACT 2966786 CONTINUOUS PLUG-IN BRIDGE MECHANICAL JUMPER, 500MM, RELAY CR6B09 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO CR6B10 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO CR6B11 1 PHOENIX CONTACT 2909661 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO DINRAIL 1 PHOENIX CONTACT 1201730 DIN RAIL 1 PHOENIX CONTACT 1201141 INSULATED DIN RAIL MOUNT DUCT-DC-1.5"1 PANDUIT F1.5X4LG6 NARROW FINGER, SLOTTED WIRING DUCT GRAY 1.5" WIDE X 4" DEEP 1 PANDUIT C1.5LG6 WIRING DUCT COVER - GRAY 1.5" WIDE DUCT-MIXED-1"1 PANDUIT F1X4LG6 NARROW FINGER, SLOTTED WIRING DUCT GRAY 1" WIDE X 4" DEEP 1 PANDUIT C1LG6 WIRING DUCT COVER - GRAY 1" WIDE EDGE DEVICE 1 ONLOGIC HX310 PANEL PC, EDGE GATEWAY, ELKHART LAKE INDUSTRIAL COMPUTER, 24VDC ENCLOSURE 1 SAGINAW SCE-30EL3012SS6LPPL ENCLOSURE, WALLMOUNT, 30" x 30" x 12", NEMA 4/4X, 316 STAINLESS STEEL GND3A01 1 SCHNEIDER PK18GTA LOAD CENTER ACCESSORY, QO/HOMELINE, GROUND BAR KIT, 18 TERMINAL LSA3A01 1 EATON AGCF12030 TRANSIENT VOLTAGE SURGE SUPPRESSOR, 120VAC, 20A LT5A01 1 BANNER WLB32C285PBQ WLB32 ADJUSTABLE LED WORKSTATION LIGHT 1 SQUARE D XZCP1141L5 M12 4 PIN CONNECTOR 16FT CABLE MISC 11 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N PD6B00 1 PHOENIX CONTACT 2966508 RELAY POWER TERMINAL 2 PHOENIX CONTACT 2966786 CONTINUOUS PLUG-IN BRIDGE MECHANICAL JUMPER, 500MM, RELAY PSU4A01 1 PULS CP20.241 1-PHASE POWER SUPPLY RACK1ECR 1 AB 5069-ECR 5069 COMPACTLOGIX/COMPACT GUARDLOGIX RIGHT END CAP WITH ADAPTER RACK1S00 1 AB 5069-L320ER COMPACTLOGIX 5380, 2 MB USER MEMORY, 16 I/Os, 40 ETHERNET/IP DEVICES 1 AB 5069-RTB6-SCREW 6 PIN SCREW TYPE POWER TERMINAL CONNECTOR 1 AB 5069-RTB4-SCREW 4 PIN SCREW TYPE POWER TERMINAL CONNECTOR RACK1S01 1 AB 5069-IB16 5069 COMPACT I/O 16 CHANNEL 24V DC SINK INPUTE MODULE 1 AB 5069-RTB18-SCREW 18 PIN SCREW TYPE TERMINAL CONNECTOR RACK1S02 1 AB 5069-OB16 5069 COMPACT I/O 16 CHANNEL 24V DC SOURCE OUTPUT MODULE 1 AB 5069-RTB18-SCREW 18 PIN SCREW TYPE TERMINAL CONNECTOR RACK1S03 1 AB 5069-IF8 5069 COMPACT I/O 8 CHANNEL VOLTAGE/CURRENT ANALOG INPUT MODULE 1 AB 5069-RTB18-SCREW 18 PIN SCREW TYPE TERMINAL CONNECTOR RECP3A01 1 HUBBELL GFR15I GFCI RECEPTACLE, 125V, 15A 1 HUBBELL 5320-0 DUPLEX RECEPTACLE GANG BOX PANEL MOUNT 1 HUBBELL SSJ26 GFCI RECEPTACLE COVER PLATE TAG QTY MANUFACTURER PART #DESCRIPTION ROUTER 1 CISCO IR1101 ROUTER, POWER INPUT 9.6 TO 60VDC, TEMP RATING: -40 TO 60C, 4 PORT ETHERNET 1 CISCO ANT-4-5G4-O DIRECT MOUNT OMNIDIRECTIONAL ANTENNA 1 EXISTING EXISTING CABLE CAT 6 ETHERNET CABLE STOP1 1 HOFFMAN ALGDSTOP2 LARGE ENCLOSURE DOOR STOP KIT SW5A01 1 TELEMECANIQUE ZCP21 LIMIT SWITCH BODY - ZCP - 1 NC + 1 NO - TERMINALS 1 TELEMECANIQUE ZCPEG11 CABLE GLAND ENTRY FOR LIMIT SWITCH 1 TELEMECANIQUE ZCE10 HEAD FOR LIMIT SWITCH - ZCE - STEEL END PLUNGER TB-AC-1 2 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A 3 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, 30-12AWG 6 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L 1 AB 1492-CJK5-50 50 IEC CENTER JUMPER, 10 PL 5mm, PLUG-IN 1 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS TB-AI-1 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A 1 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N 21 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, 30-12AWG 72 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L 1 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS 8 AB 1492-LG3 IEC SPRING CLAMP TERMINAL BLOCK, GROUNDING BLOCK, 1492-L 7 AB 1492-L3P TERMINAL BLOCK 1492, GRAY 7 AB 1492-FPK224 TERMINAL ACCESSORY 1492, BLACK 7 EATON GMC-63MA CARTRIDGE FUSE 63MA TB-DC-1 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A 3 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N 17 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, 30-12AWG 34 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L 2 AB 1492-CJK5-50 50 IEC CENTER JUMPER, 10 PL 5mm, PLUG-IN 2 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS TB-DI-1 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A 1 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N 24 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, 30-12AWG 48 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L 1 AB 1492-CJK5-50 50 IEC CENTER JUMPER, 10 PL 5mm, PLUG-IN 1 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS TB-DO-1 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A 2 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N 14 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, 30-12AWG 28 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L 1 AB 1492-CJK5-50 50 IEC CENTER JUMPER, 10 PL 5mm, PLUG-IN 1 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS TB-DOOR 2 PHOENIX CONTACT 0800886 END BRACKET - E/NS 35 N 1 PHOENIX CONTACT 1004348 END BRACKET LABEL FOR STRIP MARKING - KLM-A 5 AB 1492-L3 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, 30-12AWG 10 AB 1492-M5X10 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L 1 AB 1492-EBL3 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS UPS4A01 1 PULS UB20.241 DC UPS MODULE 24VDC, 20A OUTPUT, FOR 3.9AH TO 150AH BATTERY UPS4A02 1 PULS UZK24.071 DC UPS BATTERY KIT, 24V, 7AH PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1D NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION BILL OF MATERIAL.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE BILL OF MATERIAL 4 27 CARLSBAD MUNICIPAL WATER DISTRICT HEAT DISSIPATION AREA 0"3"6"12" LT5A01LT5A01 LT5A01 BACKPANEL BACKPANEL SW5A01 SW5A01 ENCLOSURE STOP1 STOP1 EDGE DEVICE UPS4A02 EDGE DEVICE UPS4A02 HAYMAR INTERTIE 120VAC FROM: LP-XXX CKT XX PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1E.1 1"=4" CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION PANEL LAYOUT EXTERIOR DETAILS.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE PANEL LAYOUT EXTERIOR DETAILS 5 27 CARLSBAD MUNICIPAL WATER DISTRICT 30 0 0 0 30 0"3"6"12" STOP1 HAYMAR INTERTIE 120VAC FROM: LP-XXX CKT XX 223 4 0 0 0 278 12 12 30 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1E.2 1"=4" CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION PANEL LAYOUT EXTERIOR DIMENSIONS.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE PANEL LAYOUT EXTERIOR DIMENSIONS 6 27 CARLSBAD MUNICIPAL WATER DISTRICT 0"3"6"12" STOP1 HAYMAR INTERTIE 120VAC FROM: LP-XXX CKT XX 0" 15" 0"0" 714" 12 " AVAILABLE CONDUIT ENTRY AREA (24VDC PREFERRED) AVAILABLE CONDUIT ENTRY AREA (120VAC PREFERRED) 0" 15" 0"0" 714" 12 " PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1E.3 1"=4" CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION PANEL LAYOUT CONDUIT ENTRY.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE PANEL LAYOUT EXTERIOR CONDUIT ENTRY 7 27 CARLSBAD MUNICIPAL WATER DISTRICT 0"3"6"12" HEAT DISSIPATION AREA GND3A01 SEE SHT 1J SEE SHT 1J TB-DI-1 TB-DO-1 RACK1 TB-AI-1 BACKPANEL GND3A01 LSA3A01 RECP3A01 TB-DO-RELAY TB-AC-1 DINRAIL DUCT-DC-1.5" RE C P 3 A 0 1 CB3A00 CB3A01 CB3A02 CB3A03 SEE SHT 1J DC BREAKERS PSU4A01 UPS4A01 TB-DOOR TB-DC-1 DUCT-MIXED-1"1" x 4" 1.5" x 4" PSU4A01UPS4A01 ROUTEREDGE DEVICE ACC1 CB4A10 CB4A11 CB4A12 CB4A13 CB4A14 CB4A15 CB4A16 CB4A17 CB4A18 ACC 1 ACC 1 ACC 1 ACC 1 CR3A00 ACC1 1" x 4"DUCT-DC-1" ED G E D E V I C E RACK1S00 5069-L320ER RA C K 1 S 0 1 50 6 9 - I B 1 6 RA C K 1 S 0 2 50 6 9 - O B 1 6 RA C K 1 S 0 3 50 6 9 - I F 8 1" x 4 " F I E L D W I R I N G PD6B00 CR6B08 CR6B09 CR6B10 CR6B11 ACC1 ACC1 ACC3 ACC1 ACC1 1. 5 " x 4 " F I E L D W I R I N G 1" x 4 " 1" x 4" 1" x 4" 1" x 4 " 1" x 4 " RO U T E R SEE SHT 1J AC BREAKERS UPS4A02 ACC1 ACC3 ACC 1 ACC 3 ACC1 ACC3 ACC5 AC C 1 AC C 1 ACC1 ACC1 UP S 4 A 0 2 RACK1 1.5" x 4" PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1F.1 1"=4" CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION PANEL LAYOUT INTERIOR DETAILS.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE PANEL LAYOUT INTERIOR DETAILS 8 27 CARLSBAD MUNICIPAL WATER DISTRICT 0 0 718 16 1 4 26 3 4 10 1 2 21 1 2 0"3"6"12" GND3A01 1" x 4" 1.5" x 4" PSU4A01UPS4A01 ACC1ACC 1 ACC 1 ACC 1 ACC 1 ACC1 1" x 4" ED G E D E V I C E RACK1S00 5069-L320ER RA C K 1 S 0 1 50 6 9 - I B 1 6 RA C K 1 S 0 2 50 6 9 - O B 1 6 RA C K 1 S 0 3 50 6 9 - I F 8 1" x 4 " F I E L D W I R I N G PD6B00 CR6B08 CR6B09 CR6B10 CR6B11 ACC1 ACC1 ACC3 ACC1 ACC1 1. 5 " x 4 " F I E L D W I R I N G 1" x 4 " 1" x 4" 1" x 4" 1" x 4 " 1" x 4 " RO U T E R ACC1 ACC3 ACC 1 ACC 3 ACC1 ACC3 ACC5 AC C 1 AC C 1 ACC1 ACC1 1.5" x 4" 123 4 183 4 458 263 4 5 8 27 8 61 2 83 891 4 118 14 1 8 231 8 10 1 8 1 2 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1F.2 1"=4" CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION PANEL LAYOUT INTERIOR DIMENSIONS.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE PANEL LAYOUT INTERIOR DIMENSIONS 9 27 CARLSBAD MUNICIPAL WATER DISTRICT 0"3"6"12" 0 30 0 12 DUCT-DC DUCT-AC TOP VIEW LOOKING DOWN NOTE: FRONT OF PANEL HEAT DISSIPATION AREA 61 2 RESERVED FLOOR SPACE FOR CONDUIT ENTRY RACK 1 111 2 118 28 7 8 UPS4A02EDGE DEVICE 87 8 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1F.3 1"=4" CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION PANEL LAYOUT INTERIOR TOP VIEW.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE PANEL LAYOUT INTERIOR TOP VIEW 10 27 CARLSBAD MUNICIPAL WATER DISTRICT TB-DOOR Number Jumper Manufacturer Part # TB-DOOR PHOENIX CONTACT 1004348 ACC1 PHOENIX CONTACT 0800886 5A01 AB 1492-L3 5A02 AB 1492-L3 5A03 AB 1492-L3 5A04 AB 1492-L3 5A05 AB 1492-L3 ACC2 AB 1492-EBL3 ACC3 PHOENIX CONTACT 0800886 TB-AC-1 Number Jumper Manufacturer Part # TB-AC-1 PHOENIX CONTACT 1004348 ACC1 PHOENIX CONTACT 0800886 3A01N AB 1492-L3 3A02N AB 1492-L3 3A03N AB 1492-L3 ACC2 AB 1492-EBL3 ACC3 PHOENIX CONTACT 0800886 TB-DC-1 Number Jumper Manufacturer Part # TB-DC-1 PHOENIX CONTACT 1004348 ACC1 PHOENIX CONTACT 0800886 4A10-AB 1492-L3 4A11-AB 1492-L3 4A12-AB 1492-L3 4A13-AB 1492-L3 4A14-AB 1492-L3 4A15-AB 1492-L3 4A16-AB 1492-L3 4A17-AB 1492-L3 4A18-AB 1492-L3 4A30-AB 1492-L3 4A31-AB 1492-L3 4A32-AB 1492-L3 4A33-AB 1492-L3 ACC2 AB 1492-EBL3 ACC3 PHOENIX CONTACT 0800886 4A30+AB 1492-L3 4A31+AB 1492-L3 4A32+AB 1492-L3 4A33+AB 1492-L3 ACC4 AB 1492-EBL3 ACC5 PHOENIX CONTACT 0800886 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1G NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION TERMINAL STRIP DETAIL.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE TERMINAL STRIP DETAIL 11 27 CARLSBAD MUNICIPAL WATER DISTRICT TB-DO-1 Number Jumper Manufacturer Part # TB-DO-1 PHOENIX CONTACT 1004348 ACC1 PHOENIX CONTACT 0800886 6B06A AB 1492-L3 6B06B AB 1492-L3 6B07A AB 1492-L3 6B07B AB 1492-L3 6B08A AB 1492-L3 6B08B AB 1492-L3 6B09A AB 1492-L3 6B09B AB 1492-L3 6B10A AB 1492-L3 6B10B AB 1492-L3 6B11A AB 1492-L3 6B11B AB 1492-L3 6BV1+AB 1492-L3 6BV1-AB 1492-L3 ACC2 AB 1492-EBL3 ACC3 PHOENIX CONTACT 0800886 TB-DI-1 Number Jumper Manufacturer Part # TB-DI-1 PHOENIX CONTACT 1004348 ACC1 PHOENIX CONTACT 0800886 6A04A AB 1492-L3 6A04B AB 1492-L3 6A05A AB 1492-L3 6A05B AB 1492-L3 6A06A AB 1492-L3 6A06B AB 1492-L3 6A07A AB 1492-L3 6A07B AB 1492-L3 6A08A AB 1492-L3 6A08B AB 1492-L3 6A09A AB 1492-L3 6A09B AB 1492-L3 6A10A AB 1492-L3 6A10B AB 1492-L3 6A11A AB 1492-L3 6A11B AB 1492-L3 6A12A AB 1492-L3 6A12B AB 1492-L3 6A13A AB 1492-L3 6A13B AB 1492-L3 6A14A AB 1492-L3 6A14B AB 1492-L3 6A15A AB 1492-L3 6A15B AB 1492-L3 ACC2 AB 1492-EBL3 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1H NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION TERMINAL STRIP DETAIL DIGITAL.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE TERMINAL STRIP DETAIL DIGITAL 12 27 CARLSBAD MUNICIPAL WATER DISTRICT TB-AI-1 Number Jumper Manufacturer Part # TB-AI-1 PHOENIX CONTACT 1004348 ACC1 PHOENIX CONTACT 0800886 GND AB 1492-LG3 6C00+AB 1492-L3P 6C00-AB 1492-L3 6C00B AB 1492-L3 6C00A AB 1492-L3 6C00G AB 1492-LG3 6C01+AB 1492-L3P 6C01-AB 1492-L3 6C01B AB 1492-L3 6C01A AB 1492-L3 6C01G AB 1492-LG3 6C02+AB 1492-L3P 6C02-AB 1492-L3 6C02B AB 1492-L3 6C02A AB 1492-L3 6C02G AB 1492-LG3 6C03+AB 1492-L3P 6C03-AB 1492-L3 6C03B AB 1492-L3 6C03A AB 1492-L3 6C03G AB 1492-LG3 6C04+AB 1492-L3P 6C04-AB 1492-L3 6C04B AB 1492-L3 6C04A AB 1492-L3 6C04G AB 1492-LG3 6C05+AB 1492-L3P 6C05-AB 1492-L3 6C05B AB 1492-L3 6C05A AB 1492-L3 6C05G AB 1492-LG3 6C06+AB 1492-L3P 6C06-AB 1492-L3 6C06B AB 1492-L3 6C06A AB 1492-L3 6C06G AB 1492-LG3 ACC2 AB 1492-EBL3 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1I NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION TERMINAL STRIP DETAIL ANALOG.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE TERMINAL STRIP DETAIL ANALOG 13 27 CARLSBAD MUNICIPAL WATER DISTRICT CB3A03 CB3A02 CB3A01 CB3A00 RA C K 1 S 0 3 50 6 9 - I F 8 RA C K 1 S 0 2 50 6 9 - O B 1 6 RA C K 1 S 0 1 50 6 9 - I B 1 6 RACK1S00 5069-L320ER RACK1 CB4A18 CB4A17 CB4A16 CB4A15 CB4A14 CB4A13 CB4A12 CB4A11 CB4A10 TB-DO-RELAYAC BREAKERS DC BREAKERS CR6B11 CR6B10 CR6B09 CR6B08 PD6B00 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1J NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION PANEL COMPONENT DETAIL.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE PANEL COMPONENT DETAIL 14 27 CARLSBAD MUNICIPAL WATER DISTRICT 7" 2" NOTE: LABEL TO BE CONSTRUCTED AT A LATER TIME 13 4" 1 4" TB-DC-1 TB-AC-1 TB-DI-1 TB-AI-1 TB-DOOR TB-DO-RELAY UPS4A01 PSU4A01 TB-DO-1 EDGE DEVICE ROUTER NOTE: LABELS TO BE ENGRAVED TWO-LAYER UV STABILIZED MATERIAL WITH WHITE TEXT NO LESS THAN 14" HIGH ON BLACK BACKGROUND NOTE: IDENTIFICATION LABELS FOR DIN RAIL MOUNTED COMPONENTS TO BE MOUNTED ON THE END BRACKET NEXT TO THE COMPONENT OR TERMINAL STRIP. LABELS TO BE MOUNTED ON THE LEFT OF HORIZONTAL DIN RAIL MOUNTED COMPONENTS AND ABOVE VERTICAL DIN RAIL MOUNTED COMPONENTS. LABELS TO BE SELF ADHESIVE POLYESTER WITH THERMAL PRINTED BLACK TEXT NO LESS THAN 1/8" HIGH. HAYMAR INTERTIE 120VAC FROM: LP-XXX CKT XX1" PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1K.1 2:1 CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION NAMEPLATE DETAIL 1.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE NAMEPLATE DETAIL (PART 1) 15 27 CARLSBAD MUNICIPAL WATER DISTRICT 2" 1" 1" 1 2" RECP3A01 RACK1 CB3A00 CB3A01 CB3A02 CB3A03 NOTE: IDENTIFICATION LABELS FOR COMPONENTS TO BE MOUNTED ON THE BACK PANEL NEXT TO THE COMPONENT AS SHOWN ON THE PANEL LAYOUT INTERIOR DETAILS SHEET. LABELS TO BE SELF ADHESIVE POLYESTER WITH THERMAL PRINTED BLACK TEXT NO LESS THAN 1/4" HIGH. CB4A10 CB4A11 CB4A12 CB4A13 CB4A14 CB4A15 CB4A16 CB4A17 CB4A18 UPS4A02 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 1K.2 2:1 CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION NAMEPLATE DETAIL 2.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE NAMEPLATE DETAIL (PART 2) 16 27 CARLSBAD MUNICIPAL WATER DISTRICT FIBER ETHERNET COPPER ETHERNET -USB AB SLOT0 CPU MODULE RACK1 RACK1S00 5069-L320ER USB - ETH 1 LINK 1 - ETH 2 LINK 2 PROVIDED BY CUSTOMER PROVIDED BY CUSTOMER 43 21 SHT 4A.2-B3 ROUTER 1 SHT 4A.2-B3 EDGE DEVICE PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 2A NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION NETWORK WIRING.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE NETWORK WIRING 17 27 CARLSBAD MUNICIPAL WATER DISTRICT 3A01N TB-AC-1 3A02N TB-AC-1 3A03N TB-AC-1 20A SHT 4A.2-E1,SHT 4A.2-F1 CB3A00 10A CB3A01 PSU4A01 3A01L to SHT 4A.1-A1 PSU4A01 3A01N to SHT 4A.1-A1 L LOADLINE G N L LSA3A01 SURGE SUPRESSOR INPUT TRANSIENT VOLTAGE N G 4A CB3A02 4A CB3A03 GND RECP3A01 3A00L 3A00A 3A01L 3A02L 3A01N 3A02N 3A00N 3A00N RECP3A01 to SHT 3A-E2 GROUND BAR from SHT 3A-B2 PSU4A01 to SHT 4A.1-A1 NOTE 1: 120VAC 1-PH/60HZ WITH FACILITY GROUND, SUPPLY NOT TO EXCEED 20 AMPS SERVICE GND TB-AI-1 SEL CB AUX CONTACT MODE SELECTOR ROTARY SWITCH FOR CB3A00 3A03L 3A03N RACK1 SLOT 2 DO RELAYS 3A03L to SHT 6B-E1 RACK1 SLOT 2 DO RELAYS 3A03N to SHT 6B-F1 CONTACT 4.XX ELECTRICAL TRIP CONTACT 1.XX GENERAL TRIP RED #12 AWG MTW WHT #12 AWG MTW ORG #12 AWG MTW CUSTOMER SUPPLY #1 *SEE NOTE 1 L N G GND3A01 GROUND BAR 3A01A RACK1S00 SA POWER to SHT 4A.2-C2 3A01B ROUTER to SHT 4A.2-C3 NOA2A1 SHT 6A-C4 AC POWER FAILCR3A00 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 3A NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION AC POWER DISTRIBUTION.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE AC POWER DISTRIBUTION 18 27 CARLSBAD MUNICIPAL WATER DISTRICT 24VDC DC-1 POWER SUPPLY PSU4A01 L2 / N GN D L -+ 24VDC 4A01+ to SHT 4A.2-A1 N-DC 4A01- to SHT 4A.2-D1 4A05A 4A06A 4A05B 4A06B 4A05C 4A30B 4A07A 4A30-4A07B 4A01- UPS4A01 INHIBIT 4A30B from SHT 4A.2-F1 N-DC 4A30- from SHT 4A.2-G1 120VAC 3A01L from SHT 3A-D1 3A01L 120N 3A01N from SHT 3A-E1 3A01N 4A00+4A00- 24VDC 4A06A to SHT 6A-C4 UPS4A01 ON BATTERY 4A06B to SHT 6A-D4 24VDC 4A07A to SHT 6A-C4 UPS4A01 BATTERY FAIL 4A07B to SHT 6A-D4 GROUND BAR from SHT 3A-B2 PULS DC UPS MODULE UPS4A01 +INPUT - + - 11 12 13 + OUTPUT - 3 1 2 5 6 BATTERY READY REPLACE BATTERY TEMP RTN CENTER TAP + - 4 INHIBIT BUFFERING 4A01+ 30S 1m 3m 10m 10s BUFFER TIME LIMITER BUFFER VOLTAGE DC UPS SWITCH SETTINGS 25 26 24 22.5 BATTERY SIZE >10 AH <10 AH BLUE #10 AWG MTW BLU #10 AWG MTW WHT/BLU #10 AWG MTW WHT/BLU #10 AWG MTW 4A05- 4A05+ UPS BATTERY KIT 24VDC, 7AH UPS4A02 11 12 13 TEMP RTN CENTER TAP - + BATTERY WHT/BLU #10 AWG MTW PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 4A.1 NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION DC POWER DISTRIBUTION 1 (PART 1).dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE DC POWER DISTRIBUTION (PART 1) 19 27 CARLSBAD MUNICIPAL WATER DISTRICT 4A30+ TB-DC-1 4A31+ TB-DC-1 4A32+ TB-DC-1 4A33+ TB-DC-1 4A30- TB-DC-1 4A31- TB-DC-1 4A32- TB-DC-1 4A33- TB-DC-1 4A10- TB-DC-1 4A11- TB-DC-1 4A12- TB-DC-1 4A13- TB-DC-1 4A14- TB-DC-1 4A15- TB-DC-1 4A16- TB-DC-1 4A17- TB-DC-1 UPS4A01 INHIBIT 4A30B to SHT 4A.1-A4 UPS4A01 INHIBIT 4A30- to SHT 4A.1-A4 4A18- TB-DC-1 TB-AI-1 4A12+ to SHT 6C-A1 TB-AI-1 4A12- to SHT 6C-A1 INTRUSION 4A33+ to SHT 5A-C1 INTRUSION 4A33- to SHT 5A-F1 RACK1 DO SLOT 02 4A11+ to SHT 6B-A1 RACK1 DO SLOT 02 4A11- to SHT 6B-E1 24VDC 4A01+ from SHT 4A.1-A6 N-DC 4A01- from SHT 4A.1-C6 4A30+ 4A12+ 4A33+ 4A30A 4A11- 4A30- 4A12- 4A33- 4A01- 4A30B 24VDC 4A18+ from SHT 4A.2-B4 4A18+ N-DC from SHT 4A.2-D4 4A18+ to SHT 4A.2-E1 N-DC to SHT 4A.2-H1 RACK1 DI SLOT 01 4A10+ to SHT 6A-B1 SHT 4A.2-C4 12 EDGE DEVICE 2A CB4A12 0.5A CB4A10 6A CB4A11 6A CB4A13 4A CB4A14 2A CB4A15 2A CB4A16 4A CB4A17 6A CB4A18 4A10+ 4A11+ 4A15+ 4A18+ 4A15- 4A01+ GROUND BAR from SHT 3A-B2 4A13- 4A16+ SHT 4A.2-C4 G RTV ROUTER 4A16- 4A13+ GROUND BAR from SHT 3A-B3 4A14+4A14- 4241 SHT 3A-C1 CB3A00 1211 SHT 3A-C1 CB3A00 SA POWER SHT 2A-C1 G -+ RACK1S00 MOD POWER SHT 2A-C1 -+ RACK1S00 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 4A.2 NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION DC POWER DISTRIBUTION 1 (PART 2).dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE DC POWER DISTRIBUTION (PART 2) 20 27 CARLSBAD MUNICIPAL WATER DISTRICT 24VDC 4A33+ from SHT 4A.2-F2 4A33+ N-DC 4A33- from SHT 4A.2-G2 4A33- 5A03A 5A04 PANEL INTRUSION 5A04 to SHT 6A-D5 5A01 TB-DOOR 5A01 5A02 TB-DOOR 5A02 5A03 TB-DOOR 5A04 TB-DOOR 5A05 TB-DOOR 5A05 5A08 24VDC 5A08 to SHT 6A-C5 5A01A 5A03 5A04 DOOR SWITCH ENCLOSURE SW5A01 ENCLOSURE LIGHT 1 24VDC LT5A01 BLU #16 AWG MTW BLU #16 AWG MTW BLU #16 AWG MTW WHT/BLU #16 AWG MTW BLU #18 AWG MTW BLU #18 AWG MTW BLU #18 AWG MTW BLU #18 AWG MTW PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 5A NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION PANEL IO DETAIL.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE PANEL I/O DETAIL 21 27 CARLSBAD MUNICIPAL WATER DISTRICT 6A04A TB-DI-1 6A05A TB-DI-1 6A06A TB-DI-1 6A07A TB-DI-1 6A08A TB-DI-1 6A09A TB-DI-1 6A10A TB-DI-1 6A11A TB-DI-1 6A12A TB-DI-1 6A13A TB-DI-1 6A14A TB-DI-1 6A15A TB-DI-1 6A04B TB-DI-1 6A05B TB-DI-1 6A06B TB-DI-1 6A07B TB-DI-1 6A08B TB-DI-1 6A09B TB-DI-1 6A10B TB-DI-1 6A11B TB-DI-1 6A12B TB-DI-1 6A13B TB-DI-1 6A14B TB-DI-1 6A15B TB-DI-1 24VDC 4A10+ from SHT 4A.2-B1 4A10+ 6A04 6A05 6A06 6A07 6A08 6A09 6A10 6A11 6A12 6A13 6A14 6A15 NOTE: ALL PANEL WIRING ON TB-DI-1 SHALL TERMINATE ONLY ON THE PANEL SIDE OF THE TERMINAL. DO NOT TERMINATE PANEL WIRING ON THE FIELD SIDE OF THE TERMINAL. 5A04 from SHT 5A-F2 5A08 from SHT 5A-C2 5A08 5A04 4A06A from SHT 4A.1-C4 4A06B from SHT 4A.1-C4 4A07A from SHT 4A.1-C4 4A07B from SHT 4A.1-C4 4A06A 4A07A 4A06B 4A07B 6A11A 6A11B1413 SHT 3A-E2 CR3A00 0 - Spare 5069-IB16 AB SLOT 1 RACK1S01 16-POINT DISCRETE INPUT RACK 1 IN 0 1 - Spare IN 1 2 - Spare IN 2 3 - Spare IN 3 4 - Station FloodIN 4 5 - Station IntrusionIN 5 6 - Spare IN 6 7 - Pressure Relief Valve OpenIN 7 8 - Pressure Relief Valve ClosedIN 8 9 - Spare IN 9 10 - Spare IN 10 11 - Control Panel AC Power FailIN 11 12 - Control Panel UPS On BatteryIN 12 13 - Control Panel UPS FailureIN 13 14 - Spare IN 14 15 - Control Panel IntrusionIN 15 16NC 17NC PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 6A NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION RACK1S01.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE RACK 1 SLOT 1 DISCRETE INPUT 22 27 CARLSBAD MUNICIPAL WATER DISTRICT 6B06B TB-DO-1 6B07B TB-DO-1 6B08B TB-DO-1 6B09B TB-DO-1 6B10B TB-DO-1 6B11B TB-DO-1 6BV1+ TB-DO-1 6BV1- TB-DO-1 6B06A TB-DO-1 6B07A TB-DO-1 6B08A TB-DO-1 6B09A TB-DO-1 6B10A TB-DO-1 6B11A TB-DO-1 6B06 6B07 6B08 6B09 6B10 6B11 N-DC 4A11- from SHT 4A.2-C1 4A11- 24VDC 4A11+ from SHT 4A.2-B1 4A11+ A2A1 CR6B08 A2A1 CR6B09 A2A1 CR6B10 A2A1 CR6B11 6B08A 6B09A 6B10A 6B11A 6B08B 6BV1+ 6BV1-6BV1- BB CR6B08 BB CR6B09 BB CR6B10 BB CR6B11 1 2 43 A1 A2 BB 1413 PANEL PANEL FIELD FIELD TOP 2966508 RELAY POWER DISTRIBUTION DETAIL 2909661 RELAY DETAIL 43 RELAY POWER DISTRIBUTION PD6B00120VAC 3A03L from SHT 3A-D3 120N 3A03N from SHT 3A-E3 3A03N NOTE: ALL PANEL WIRING ON TB-DO-1 SHALL TERMINATE ONLY ON THE PANEL SIDE OF THE TERMINAL. DO NOT TERMINATE PANEL WIRING ON THE FIELD SIDE OF THE TERMINAL. 3A03L 1413 CR6B11 1413 CR6B10 1413 CR6B09 1413 CR6B08 0 - Spare AB SLOT 2 16-POINT DISCRETE OUTPUT RACK 1 RACK1S02 5069-OB16 OUT 0 1 - Spare OUT 1 2 - Spare OUT 2 3 - Spare OUT 3 4 - Spare OUT 4 5 - Spare OUT 5 6 - Spare OUT 6 7 - Spare OUT 7 8 - Spare OUT 8 9 - Spare OUT 9 10 - Spare OUT 10 11 - Spare OUT 11 12 - Spare OUT 12 13 - Spare OUT 13 14 - Spare OUT 14 15 - Spare OUT 15 16LA+ 17 LA- PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 6B NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION RACK1S02.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE RACK 1 SLOT 2 DISCRETE OUTPUT 23 27 CARLSBAD MUNICIPAL WATER DISTRICT 6C00B TB-AI-1 6C01B TB-AI-1 6C02B TB-AI-1 6C03B TB-AI-1 6C00- TB-AI-1 6C01- TB-AI-1 6C02- TB-AI-1 6C03- TB-AI-1 6C00B 6C01A 6C01B 6C02A 6C02B 6C03B 24VDC to SHT 6C-E1 N-DC to SHT 6C-E1 TB-AI-1 4A12+ from SHT 4A.2-B2 TB-AI-1 4A12- from SHT 4A.2-C2 6C00+ TB-AI-1 63mA 6C01+ TB-AI-1 63mA 6C03+ TB-AI-1 63mA 6C02+ TB-AI-1 63mA SHLD 6C00G TB-AI-1 6C01G TB-AI-1 6C02G TB-AI-1 6C03G TB-AI-1 SHLD SHLD 4A12- +- +- +- SHLD +- 6C00A TB-AI-1 6C00A 6C01A TB-AI-1 6C02A TB-AI-1 6C03A TB-AI-1 6C03A 6C04B TB-AI-1 6C05B TB-AI-1 6C06B TB-AI-1 6C04- TB-AI-1 6C05- TB-AI-1 6C06- TB-AI-1 6C04A 6C04B 6C05A 6C05B 6C06A 6C06B 24VDC from SHT 6C-A6 N-DC from SHT 6C-A6 6C04+ TB-AI-1 63mA 6C05+ TB-AI-1 63mA 6C06+ TB-AI-1 63mA 6C04G TB-AI-1 6C05G TB-AI-1 6C06G TB-AI-1 SHLD SHLD SHLD +- +- +- 6C04A TB-AI-1 6C05A TB-AI-1 6C06A TB-AI-1 4A12+ 0 - Upstream 5069-IF8 AB SLOT 3 RACK1S03 8 CHANNEL ANALOG INPUT RACK 1 PressureIN 0+ 1IN 0- 2 - Downstream PressureIN 1+ 3IN 1- 4 - Pressure Reducing Valve 1 PositionIN 2+ 5IN 2- 6 - Spare IN 3+ 7IN 3- 16SHLD 8 - Discharge Flow 1IN 4+ 9IN 4- 10 - Spare IN 5+ 11IN 5- 12 - Spare IN 6+ 13IN 6- 14 - Spare IN 7+ 15IN 7- 17SHLD RACK1S03 WIRE JUMPER WIRE JUMPER WIRE JUMPER WIRE JUMPER WIRE JUMPER WIRE JUMPER WIRE JUMPER PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 6C NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION RACK1S03.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE RACK 1 SLOT 3 ANALOG INPUT 24 27 CARLSBAD MUNICIPAL WATER DISTRICT MANUFACTURER PART #QTY DESCRIPTION TAGS AB 1492-CJK5-50 5 50 IEC CENTER JUMPER, 10 PL 5mm, PLUG-IN HARDWARE TB-AC-1 TB-DC-1 TB-DI-1 TB-DO-1 AB 1492-EBL3 7 END BARRIER COMPATIBLE WITH 1492-L3 TYPE TERMINALS HARDWARE GREY TB-AI-1 TB-DC-1 TB-DI-1 TB-DO-1 TB-AC-1 TB-DOOR AB 1492-FPK224 7 TERMINAL ACCESSORY 1492, BLACK FUSE PLUG LED INDICATOR, RATED VOLTAGE 10-36VAC/DC, LEAKAGE CURRENT 1.6mA AT 24VDC FUSE ACCESSORY WITH BLOWN FUSE INDICATION TB-AI-1 AB 1492-L3 84 IEC SPRING CLAMP TERMINAL BLOCK, STANDARD FEED-THROUGH BLOCK, 1492-L, 30-12AWG FEED-THROUGH GRAY COLOR, 30-12AWG, RATED VOLTAGE 600VAC/DC ONE-CIRCUIT FEED-THROUGH BLOCK TB-AC-1 TB-AI-1 TB-DC-1 TB-DI-1 TB-DO-1 TB-DOOR AB 1492-L3P 7 TERMINAL BLOCK 1492, GRAY FUSE BLOCK GREY COLOR, 30-12 AWG, RATED VOLTAGE 600VAC/DC SINGLE CIRCUIT FUSE TERMINAL BLOCK WITH BLOWN INDICATION TB-AI-1 AB 1492-LG3 8 IEC SPRING CLAMP TERMINAL BLOCK, GROUNDING BLOCK, 1492-L FEED-THROUGH GROUND GREEN / YELLOW COLOR, 30-12AWG ONE-CIRCUIT FEED-THROUGH GROUND BLOCK TB-AI-1 AB 1492-M5X10 198 TERMINAL LABEL, 5mm X 10mm, INDIVIDUAL, SNAP ON, 1492-L TERMINAL TB-AC-1 TB-AI-1 TB-DC-1 TB-DI-1 TB-DO-1 TB-DOOR AB 5069-ECR 1 5069 COMPACTLOGIX/COMPACT GUARDLOGIX RIGHT END CAP WITH ADAPTER 5069 RACK1ECR AB 5069-IB16 1 5069 COMPACT I/O 16 CHANNEL 24V DC SINK INPUTE MODULE 5069 COMPACTLOGIX RACK1S01 AB 5069-IF8 1 5069 COMPACT I/O 8 CHANNEL VOLTAGE/CURRENT ANALOG INPUT MODULE 5069 COMPACTLOGIX RACK1S03 AB 5069-L320ER 1 COMPACTLOGIX 5380, 2 MB USER MEMORY, 16 I/Os, 40 ETHERNET/IP DEVICES 5069 COMPACTLOGIX RACK1S00 AB 5069-OB16 1 5069 COMPACT I/O 16 CHANNEL 24V DC SOURCE OUTPUT MODULE 5069 COMPACTLOGIX RACK1S02 AB 5069-RTB18-SCREW 3 18 PIN SCREW TYPE TERMINAL CONNECTOR 5069 COMPACTLOGIX RACK1S01 RACK1S03 RACK1S02 AB 5069-RTB4-SCREW 1 4 PIN SCREW TYPE POWER TERMINAL CONNECTOR 5069 COMPACTLOGIX RACK1S00 AB 5069-RTB6-SCREW 1 6 PIN SCREW TYPE POWER TERMINAL CONNECTOR 5069 COMPACTLOGIX RACK1S00 BANNER WLB32C285PBQ 1 WLB32 ADJUSTABLE LED WORKSTATION LIGHT 24VDC LT5A01 CBI QY-1-13-DM-U2-0.5A 1 CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 0.5A 80V 1 POLE 1-POLE CIRCUIT BREAKER CB4A10 CBI QY-1-13-DM-U2-2A 3 CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 2A 80V 1 POLE 1-POLE CIRCUIT BREAKER CB4A12 CB4A15 CB4A16 CBI QY-1-13-DM-U2-4A 2 CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 4A 80V 1 POLE 1-POLE CIRCUIT BREAKER CB4A14 CB4A17 CBI QY-1-13-DM-U2-6A 3 CIRCUIT BREAKER - CBI CURVE U2 QY-(13) CIRCUIT BREAKER 6A 80V 1 POLE 1-POLE CIRCUIT BREAKER CB4A11 CB4A13 CB4A18 CISCO ANT-4-5G4-O 1 DIRECT MOUNT OMNIDIRECTIONAL ANTENNA ANTENNA ROUTER CISCO IR1101 1 ROUTER, POWER INPUT 9.6 TO 60VDC, TEMP RATING: -40 TO 60C, 4 PORT ETHERNET NETWORK ROUTER MANUFACTURER PART #QTY DESCRIPTION TAGS EATON AGCF12030 1 TRANSIENT VOLTAGE SURGE SUPPRESSOR, 120VAC, 20A 120VAC LSA3A01 EATON FAZ-D10/1-NA-SP 1 CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 10A, D CURVE 1-POLE CIRCUIT BREAKER RATING=10A CB3A01 EATON FAZ-D20/1-NA-SP 1 CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 20A, D CURVE 1-POLE CIRCUIT BREAKER RATING=20A CB3A00 EATON FAZ-D4/1-NA-SP 2 CIRCUIT BREAKER, UL 489 BRANCH, 1 POLE, DIN MOUNT, 4A, D CURVE 1-POLE CIRCUIT BREAKER RATING=4A CB3A02 CB3A03 EATON GMC-63MA 7 CARTRIDGE FUSE 63MA FUSE TB-AI-1 EATON Z-NHK 1 CIRCUIT BREAKER, UL 489 BRANCH, AUXILIARY SWITCH 1-POLE CIRCUIT BREAKER CB3A00 EXISTING EXISTING CABLE 1 CAT 6 ETHERNET CABLE CABLE ROUTER HOFFMAN ALGDSTOP2 1 LARGE ENCLOSURE DOOR STOP KIT ACCESSORY STOP1 HUBBELL 5320-0 1 DUPLEX RECEPTACLE GANG BOX PANEL MOUNT REC RECP3A01 HUBBELL GFR15I 1 GFCI RECEPTACLE, 125V, 15A REC RECP3A01 HUBBELL SSJ26 1 GFCI RECEPTACLE COVER PLATE REC RECP3A01 ONLOGIC HX310 1 PANEL PC, EDGE GATEWAY, ELKHART LAKE INDUSTRIAL COMPUTER, 24VDC PROCESSOR EDGE DEVICE PANDUIT C1.5LG6 1 WIRING DUCT COVER - GRAY 1.5" WIDE 1.5 LIGHT GRAY DUCT-DC-1.5" PANDUIT C1LG6 1 WIRING DUCT COVER - GRAY 1" WIDE 1 LIGHT GRAY DUCT-MIXED-1 " PANDUIT F1.5X4LG6 1 NARROW FINGER, SLOTTED WIRING DUCT GRAY 1.5" WIDE X 4" DEEP 1.75 x 4.12 LIGHT GRAY LEAD-FREE PVC, STANDARD MOUNTING HOLES DUCT-DC-1.5" PANDUIT F1X4LG6 1 NARROW FINGER, SLOTTED WIRING DUCT GRAY 1" WIDE X 4" DEEP 1.25 x 4.08 LIGHT GRAY LEAD-FREE PVC, STANDARD MOUNTING HOLES DUCT-MIXED-1 " PHOENIX CONTACT 0800886 22 END BRACKET - E/NS 35 N ACCESSORY GRAY, FOR THE NS 35 DIN RAIL 9.5MM WIDTH TB-AI-1 TB-DC-1 TB-DI-1 TB-DO-1 MISC TB-AC-1 TB-DOOR PHOENIX CONTACT 1004348 6 END BRACKET LABEL FOR STRIP MARKING - KLM-A ACCESSORY TB-AC-1 TB-AI-1 TB-DC-1 TB-DI-1 TB-DO-1 TB-DOOR PHOENIX CONTACT 1201141 1 INSULATED DIN RAIL MOUNT NA DINRAIL PHOENIX CONTACT 1201730 1 DIN RAIL NA DINRAIL PHOENIX CONTACT 2909661 1 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO RELAY CR6B08 PHOENIX CONTACT 2909661 3 RELAY MODULE 24VDC COIL WITH BUSBAR TERMINAL 1NO RELAY CR6B09 CR6B10 CR6B11 PHOENIX CONTACT 2966249 1 RELAY MODULE 120VAC COIL WITH BUSBAR TERMINAL 1NO RELAY CR3A00 PHOENIX CONTACT 2966508 1 RELAY POWER TERMINAL POWER TERMINAL PD6B00 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 99A.1 NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION PURCHASE LIST 1.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE PURCHASE LIST (PART 1) 25 27 CARLSBAD MUNICIPAL WATER DISTRICT MANUFACTURER PART #QTY DESCRIPTION TAGS PHOENIX CONTACT 2966786 3 CONTINUOUS PLUG-IN BRIDGE MECHANICAL JUMPER, 500MM, RELAY JUMPER CR6B08 PD6B00 PULS CP20.241 1 1-PHASE POWER SUPPLY 24VDC INPUT: 120VAC,50/60Hz / OUTPUT: 24VDC, 20A PSU4A01 PULS UB20.241 1 DC UPS MODULE 24VDC, 20A OUTPUT, FOR 3.9AH TO 150AH BATTERY 24VDC UPS4A01 PULS UZK24.071 1 DC UPS BATTERY KIT, 24V, 7AH 24VDC UPS4A02 SAGINAW SCE-30EL3012SS6LPPL 1 ENCLOSURE, WALLMOUNT, 30" x 30" x 12", NEMA 4/4X, 316 STAINLESS STEEL WALL-MOUNTED ENCLOSURE ENCLOSURE SAGINAW SCE-30P30 1 SUBPANEL, BENT, 27" X 27" POWDER COATED WHITE SUBPANEL BACKPANEL SCHNEIDER PK18GTA 1 LOAD CENTER ACCESSORY, QO/HOMELINE, GROUND BAR KIT, 18 TERMINAL GROUND GND3A01 SQUARE D XZCP1141L5 1 M12 4 PIN CONNECTOR 16FT CABLE CABLE LT5A01 TELEMECANIQUE ZCE10 1 HEAD FOR LIMIT SWITCH - ZCE - STEEL END PLUNGER COMPLETE PLUNGER HEAD LINEAR SW5A01 TELEMECANIQUE ZCP21 1 LIMIT SWITCH BODY - ZCP - 1 NC + 1 NO - TERMINALS SNAP ACTION USE WITH CABLE GLAND ENTRY 1 NC + 1 NO SW5A01 TELEMECANIQUE ZCPEG11 1 CABLE GLAND ENTRY FOR LIMIT SWITCH PLASTIC BODY SW5A01 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 99A.2 NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION PURCHASE LIST 2.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE PURCHASE LIST (PART 2) 26 27 CARLSBAD MUNICIPAL WATER DISTRICT WIRENO COMPONENT 1 PIN1 COMPONENT 2 PIN2 WIRE TYPE DV6C03 -TB-AI-1 6C03A FIELD TB-AI-1 6C03+DV6C03 +FIELD DV6C06 -TB-AI-1 6C06A FIELD TB-AI-1 6C06+DV6C06 +FIELD DV6C02 -TB-AI-1 6C02A FIELD TB-AI-1 6C02+DV6C02 +FIELD DV6C05 -TB-AI-1 6C05A FIELD TB-AI-1 6C05+DV6C05 +FIELD DV6C01 -TB-AI-1 6C01A FIELD TB-AI-1 6C01+DV6C01 +FIELD DV6C04 -TB-AI-1 6C04A FIELD TB-AI-1 6C04+DV6C04 +FIELD DV6C00 -TB-AI-1 6C00A FIELD TB-AI-1 6C00+DV6C00 +FIELD CR6B11 14 DV6B11 +FIELD CR6B11 13 DV6B11 -FIELD CR6B10 14 DV6B10 +FIELD CR6B10 13 DV6B10 -FIELD CR6B09 14 DV6B09 +FIELD CR6B09 13 DV6B09 -FIELD CR6B08 14 DV6B08 +FIELD CR6B08 13 DV6B08 -FIELD DV6B07 -TB-DO-1 6B07B FIELD TB-DO-1 6B07A DV6B07 +FIELD DV6B06 -TB-DO-1 6B06B FIELD TB-DO-1 6B06A DV6B06 +FIELD DV6A09 -TB-DI-1 6A09B FIELD TB-DI-1 6A09A DV6A09 +FIELD DV6A08 -TB-DI-1 6A08B FIELD TB-DI-1 6A08A DV6A08 +FIELD DV6A07 -TB-DI-1 6A07B FIELD TB-DI-1 6A07A DV6A07 +FIELD DV6A06 -TB-DI-1 6A06B FIELD TB-DI-1 6A06A DV6A06 +FIELD DV6A05 -TB-DI-1 6A05B FIELD TB-DI-1 6A05A DV6A05 +FIELD DV6A04 -TB-DI-1 6A04B FIELD TB-DI-1 6A04A DV6A04 +FIELD RECP3A01 GND RACK1S00 G GREEN_14 PSU4A01 GND RECP3A01 GND GREEN_14 LSA3A01 G TB-AI-1 GND GREEN_14 TB-AI-1 GND GND3A01 GREEN_14 GND3A01 ROUTER G GREEN_14 ROUTER G PSU4A01 GND GREEN_14 GND3A01 LSA3A01 G GREEN_14 GND3A01 FIELD LSA3A01 N FIELD LSA3A01 L FIELD EDGE DEVICE ROUTER 4 ORANGE_CAT6 RACK1S00 -ROUTER 3 ORANGE_CAT6 3A00A CB3A00 CB3A01 RED_12 3A00L LSA3A01 L CB3A00 ORANGE_12 3A00N LSA3A01 N TB-AC-1 3A01N WHITE_12 3A01A CB3A01 CR3A00 A1 RED_14 3A01B TB-AC-1 3A01N CR3A00 A2 WHITE_14 3A01L CB3A01 PSU4A01 L RED_14 3A01N TB-AC-1 3A01N PSU4A01 L2/N WHITE_14 3A02L CB3A02 RECP3A01 RED_14 3A02N RECP3A01 TB-AC-1 3A02N WHITE_14 3A03L CB3A03 PD6B00 3 RED_14 WIRENO COMPONENT 1 PIN1 COMPONENT 2 PIN2 WIRE TYPE 3A03N TB-AC-1 3A03N PD6B00 4 WHITE_14 4A00+PSU4A01 +UPS4A01 +BLUE_10 4A00-PSU4A01 -UPS4A01 -WHT_BLU_10 4A01+UPS4A01 +CB4A10 BLUE_10 4A01-UPS4A01 -TB-DC-1 4A10-WHT_BLU_10 4A05+UPS4A02 +UPS4A01 +BLUE_16 4A05-UPS4A02 -UPS4A01 -WHT_BLU_10 4A05A UPS4A02 11 UPS4A01 11 BLUE_16 4A05B UPS4A02 12 UPS4A01 12 BLUE_16 4A05C UPS4A02 13 UPS4A01 13 BLUE_16 4A06A UPS4A01 3 TB-DI-1 6A12A BLUE_18 4A06B UPS4A01 4 TB-DI-1 6A12B BLUE_18 4A07A UPS4A01 5 TB-DI-1 6A13A BLUE_18 4A07B UPS4A01 6 TB-DI-1 6A13B BLUE_18 4A10+CB4A10 TB-DI-1 6A04A BLUE_16 4A11+CB4A11 TB-DO-1 6BV1+BLUE_16 4A11-TB-DC-1 4A11-TB-DO-1 6B06B WHT_BLU_16 4A12+CB4A12 TB-AI-1 6C00+BLUE_16 4A12-TB-DC-1 4A12-TB-AI-1 6C00-WHT_BLU_16 4A13+CB4A13 RACK1S00 +BLUE_16 4A13-RACK1S00 -TB-DC-1 4A13-WHT_BLU_16 4A14+CB4A14 RACK1S00 +BLUE_16 4A14-RACK1S00 -TB-DC-1 4A14-WHT_BLU_16 4A15+CB4A15 EDGE DEVICE 2 BLUE_16 4A15-EDGE DEVICE 1 TB-DC-1 4A15-WHT_BLU_16 4A16+CB4A16 ROUTER V BLUE_16 4A16-ROUTER RT TB-DC-1 4A16-WHT_BLU_16 4A18+CB4A18 TB-DC-1 4A30+BLUE_16 4A30+TB-DC-1 4A30+CB3A00 41 BLUE_16 4A30-TB-DC-1 4A30-UPS4A01 -WHT_BLU_16 4A30A CB3A00 42 CB3A00 11 BLUE_16 4A30B CB3A00 12 UPS4A01 +BLUE_16 4A33+TB-DC-1 4A33+TB-DOOR 5A01 BLUE_16 4A33-TB-DC-1 4A33-TB-DOOR 5A05 WHT_BLU_16 5A01 TB-DOOR 5A01 SW5A01 BLUE_16 5A01A SW5A01 TB-DOOR 5A02 BLUE_16 5A02 TB-DOOR 5A02 LT5A01 1 BLUE_16 5A03 TB-DOOR 5A03 SW5A01 BLUE_18 5A03A SW5A01 TB-DOOR 5A04 BLUE_18 5A04 TB-DOOR 5A04 TB-DI-1 6A15B BLUE_18 5A05 LT5A01 2 TB-DOOR 5A05 WHT_BLU_16 5A08 TB-DOOR 5A03 TB-DI-1 6A15A BLUE_18 6A04 TB-DI-1 6A04B RACK1S01 4 BLUE_18 6A05 TB-DI-1 6A05B RACK1S01 5 BLUE_18 6A06 TB-DI-1 6A06B RACK1S01 6 BLUE_18 6A07 TB-DI-1 6A07B RACK1S01 7 BLUE_18 6A08 TB-DI-1 6A08B RACK1S01 8 BLUE_18 6A09 TB-DI-1 6A09B RACK1S01 9 BLUE_18 6A10 TB-DI-1 6A10B RACK1S01 10 BLUE_18 6A11 TB-DI-1 6A11B RACK1S01 11 BLUE_18 6A11A TB-DI-1 6A11A CR3A00 13 BLUE_18 6A11B CR3A00 14 TB-DI-1 6A11B BLUE_18 6A12 TB-DI-1 6A12B RACK1S01 12 BLUE_18 6A13 TB-DI-1 6A13B RACK1S01 13 BLUE_18 6A14 TB-DI-1 6A14B RACK1S01 14 BLUE_18 6A15 TB-DI-1 6A15B RACK1S01 15 BLUE_18 6B06 RACK1S02 6 TB-DO-1 6B06A YELLOW_18 6B07 RACK1S02 7 TB-DO-1 6B07A YELLOW_18 6B08 RACK1S02 8 TB-DO-1 6B08A YELLOW_18 6B08A TB-DO-1 6B08A CR6B08 A1 YELLOW_18 WIRENO COMPONENT 1 PIN1 COMPONENT 2 PIN2 WIRE TYPE 6B08B CR6B08 A2 TB-DO-1 6B08B WHT_BLU_16 6B09 RACK1S02 9 TB-DO-1 6B09A YELLOW_18 6B09A TB-DO-1 6B09A CR6B09 A1 YELLOW_18 6B10 RACK1S02 10 TB-DO-1 6B10A YELLOW_18 6B10A TB-DO-1 6B10A CR6B10 A1 YELLOW_18 6B11 RACK1S02 11 TB-DO-1 6B11A YELLOW_18 6B11A TB-DO-1 6B11A CR6B11 A1 YELLOW_18 6BV1+TB-DO-1 6BV1+RACK1S02 16 BLUE_16 6BV1-RACK1S02 17 TB-DO-1 6BV1-WHT_BLU_16 6C00A TB-AI-1 6C00A RACK1S03 0 PURPLE_18 6C00B TB-AI-1 6C00B RACK1S03 1 PURPLE_18 6C01A TB-AI-1 6C01A RACK1S03 2 PURPLE_18 6C01B TB-AI-1 6C01B RACK1S03 3 PURPLE_18 6C02A TB-AI-1 6C02A RACK1S03 4 PURPLE_18 6C02B TB-AI-1 6C02B RACK1S03 5 PURPLE_18 6C03A TB-AI-1 6C03A RACK1S03 6 PURPLE_18 6C03B TB-AI-1 6C03B RACK1S03 7 PURPLE_18 6C04A TB-AI-1 6C04A RACK1S03 8 PURPLE_18 6C04B TB-AI-1 6C04B RACK1S03 9 PURPLE_18 6C05A TB-AI-1 6C05A RACK1S03 10 PURPLE_18 6C05B TB-AI-1 6C05B RACK1S03 11 PURPLE_18 6C06A TB-AI-1 6C06A RACK1S03 12 PURPLE_18 6C06B TB-AI-1 6C06B RACK1S03 13 PURPLE_18 PROJECT NO. ENGINEERING DEPARTMENT 5542-BINITIAL CITY APPROVALREVISION DESCRIPTION DATE INITIALDATE INITIALDATE ENGINEER OF WORK OTHER APPROVAL EXP.PE DATE INSPECTOR DATE REVIEWED BY: CIVIL ENGINEER "AS BUILT" ARCHITECT/ ENGINEERS STAMP SEAL A B C D E F G H 1 2 3 4 5 6 CUSTOMER INFO: DWG SCALEDRAFT DATE: A TETRA TECH COMPANY WWW.EAINTEGRATOR.COM PHONE: (949) 769-6000 SHEET SHEETS IMPROVEMENT PLAN FOR: APPROVED: EXPIRES DATE CHKD BY: DWN BY: RVWD BY: DRAWING NO. 02/26/2025 MICHAEL PACE JAKE MEYERS DAVE LEWIS 538-4W KERI MARTINEZ DISTRICT ENGINEER RCE 57189 12/31/2025 99B NO SCALE CARLSBAD MUNICIPAL WATER DISTRICT HAYMAR INTERTIE CWD HAYMAR INTERTIE PRESSURE REDUCING STATION WIRE REPORT.dwg IS S U E D F O R B I D - N O T F O R C O N S T R U C T I O N HAYMAR INTERTIE WIRE REPORT 27 27 CARLSBAD MUNICIPAL WATER DISTRICT