HomeMy WebLinkAbout955 TAMARACK AVE; ; FA0500496/27/24,1:45 PM FA050049 Permit Data City of Carlsbad Fire Alarm Permit Job Address: 955 TAMARACK AV Permit Type: FALARM Parcel No: 2060501800 Lot #: 0 Permit No: FA050049 Status: ISSUED Applied 7/13/2005 Approved: 7/19/2005 Reference No.: Issued: 7/19/2005 PC #: Inspector: Project Title: RITE AID FIRE ALARM PLAN CHECK & INSPECTIONS Applicant: NATIONAL SERVICE & CONTROLS, INC 34880 AVENUE G 909-795-3999 Owner: MASUE TRUST C/O RITE AID # 5621 P0 BOX 3165 HARRISBURG PA Fees ($) Add'I_Fees($) Total ($) Balance($)____ 0 12 0 about:blank 1/1 IntelliKnight® Model 5700 Single Loop Addressable Fire Alarm Control System The affordable addressable lntelliKnight Model 5700 is a 50 point class leading single loop addressable fire alarm control/communicator system that provides you with the revolutionary value and performance of addressable sensing technology combined with exclusive, built-in digital communication, distributed intelligent power, that includes an easy to use interface. Powerful features such as drift compensation and maintenance alert are delivered in this powerful FACP from Silent Knight. For more information about the lntelliKnight system, or to locate your nearest source, please call 1-800-446-6444, or in Minnesota, call 763-493-6435. Description • Built-in synchronization for The lntelliKnight 5700 performs drift appliances from Gentex®, Faraday, compensation and calibration checks System Sensor® and Wheelock®. on each of the sensors in the system. Built-in annunciator with 80-character The basic lntelliKnight 5700 system LCD display. can be enhanced by adding modules RS-485 bus provides communication such as the Remote Annunciator, the to system accessories. Serial/Parallel Interface (for printing Up or Download programming, event system reports), and an Intelligent history, or detector status via remote Power Module. The Model 5700 also or direct connection. features a powerful built-in dual line fire Built-in RS-232 interface for communicator that allows for reporting programming via PC. of all system activity to a remote Built-in Form C trouble relay rated at monitoring location. 2.5 amps at 24 VDC. Features Two built-in Form C programmable Uø to 50 addressable points. r.td ,t) t A 'tifl(' Up to 125 zones and 125 output . Approvals: groups. Model 5700 Uses standard wire—no shielded or UL Listed / NFPA 72 (File No. S2766) -Central Station Mechanical Specifications: twisted pair required. -DACT Dimensions: Built-in digital communicator. -Local Protective 12-3/4"W X 15-1/8H X 3-3/8°D Central station reporting by Point or Signalling System (32.39 X 38.42 X 8.57 cm) by Zone. -Water Deluge Weight: 11.5 lbs. (5.2 kg) Supports Class B (Style 4) and Class Releasing Service Color: Red A (Style 6 or 7) configuration for SLC. Distributed, intelligent power. Drift compensation. 13 pre-programmed output cadences, (including ANSI-3.41), and 4 programmable outputs. Notification circuits can be configured as I Class A (Style Z) or 2 Class B (Style Y), or auxiliary power for resettable, constant, or door holder power. CSFM Listed Specifications Primary AC: 120 VAC, 60 Hz, 1.5A Total Accessory Load: 2.5A at 24 VDC 2.5 amps at 24 VDC of power-limited notification power Standby Current: 160 mA Alarm Current 330 mA Notification/Aux power circuits: 2.5 amps of power-limited power per circuit at 24 VDC. Telephone Requirements: FCC Part 15 and Part 68 approved Type of Jack: RJ3I X (two required) r SILENT KNIGHT - SLC Sensor Devices 5D500-MIM SD505-APS Addressable photoelectric smoke detector. 50505-AHS Addressable heat sensor. SD505-6AB Mini Dry Contact Input Module. A miniature version of the addressable input module which is designed to be used with pull stations and other normally open dry contact inputs where a smaller size is desired. SD500-ARM na, 5496 5700 -14 - o ,4 '--) 1 Addressable Duct smoke detector with built- in relay module detects products of combustion present in air moving through an HVAC system. Provides form C alarm contact. The 5D505-ADHR is compatible with the 5D505-DTS, which provides remote annunciation and testing capabilities for the SD505-ADl-IR. Use with SD505-APS. SD500-PS/PSDA Addressable Pull Station with visible LED. Intelligent SLC Modules SD500-AIM Dry Contact Input Module. Designed to used with normally open dry contacts. Mounts in a 4 inch square electrical box. It features an indicator LED to show alarm status and a coverplate. comes with a coverplate. SD500-LED An LED driver capable of driving 80 LEDs through the SLC loop. Up to 40 SD500- LEDs can be used per system. SD500-LIM Addressable short circuit isolator module for SLC devices S-BUS Accessories The following items listed are devices that connected to the lntelliKnights RS-485 Bus 5860 Remote Fire Annunciator The 5860 features the same 80 character backlit LCD display keypad and firefighters keyswitch as the 5820. The system can be fully programmed and operated from any remote annunciator. 5880 LED/t0 Module Features 40 LED outputs, 8 normally open dry contact inputs and one piezo output. 5496 Intelligent Power Module The 5496 is a 6 amp.notification power expander that provides four additional power-limited notification appliance circuit. 5865-3 and 5865-4 Remote LED Annunciator I. Features 30 . . Programmable LEDs (15 j red and 15 yellow) outputs M and piezo sounder. The ,4f 5865-4 adds a silence and II reset switch switch to the package. 5883 Relay Board Features 10 General purpose Form C relays. Used with 5880 module. 5824 Serial/Parallel Gateway Module Has one parallel and one RS-232 serial port for connecting any standard IBM-compatible printer to the InteIhKnight system. Interfaces with building control system. SKSS Silent Knight Software Suite 5660 Up Download Software User-friendly, WindowsTM software for remote programming of the lntelliKnight panel using a PC. 5670 Facility Management Software Powerful end-user software allows viewing of detector status and event history via modem or direct connection. Six inch base designed for use with detector Addressable Relay Module. Features 2 head models S0505-APS,and SD505-AHS. Form C output relays, designed to mount on SD505-61B a 4 inch square electrical box. Provides indicator LED to show output status and Short circuit isolator base for 50505-AHS, and SD505-APS detectors. SD505-ADH Duct Housing. Detects smoke in HVAC ducts. Use with SD505-APS. SD505-ADHRIDTS SILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369-4927 800-446-6444 or in Minnesota 763-493-6435 FAX: 763-493-6475 World Wide Web: httpi/www.silentknight.com MADE IN AMERICA FORM# 350392-Preliminary, Rev. 10/03 Copyright © 2003 Silent Knight CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7170-0559:144 Page 1 of I CATEGORY: Control Unit (High-Rise) LISTEE: Silent Knight Security, 7550 Meridian Cirde #100, Maple Grove, MN 55369 Contact: Brian Foltz (763) 493-6400 *F (763) 391-5464 DESIGN: Models lFP-50 and 5700 Fire Alarm Control Units. Power limited, automatic, manual, local, remote station, central station, watertlow, water releasing and sprinkler supervisory service. Refer to listee's data sheet for additional detailed product description and operational considerations. System components: IFP-50, 5700 Control Units 7628 EOL Resistor 586015860R/RA-1000 Annunciator 5897 Power Supply 5496 Power Module 5824 Serial/Parallel Interface 5865-3/5965-4 LED Annunciator 5880 LED 10 Module 5883 Relay Interface Board SD500-LlM Line Isolation Module S0505-61 B Isolation Base RA-100 Remote Annunciator 3158 Reverse Polarity Module 5220 Direct Connect Module RATING: 120 VAC Primary, 24 VDC Secondary INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as control units for use in high-rise structures when used in conjunction with Model SKE- 360 Voice-Tone Evacuation Unit (CSFM Listing No. 6912-0559:122); EVAX Audio Adjunct System Models EVAX-25 (CSFM Listing No. 06911-1446:100), EVAX-50 or EVAX-50E (CSFM Listing No. 06911-1446:102); EVX-2ZA or EVX-4Z Zone Splitters (CSFM Listing No. 06912- 1446:101); HMX-MP or HMX-DP Voice Evacuation System (CSFM Listing No. 06911- 1448:103), two-way firefighter telephone and separately listed electrically and functionally compatible initiating and indicating devices. Also suitable for non-high rise applications where the voice evacuation and two-way firefighter telephone are not required. Refer to listee's Installation Instruction Manual for details. These control units can generate a distinctive three-pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 1999 Edition. NOTE: For Fire Alarm Verification Feature (delay of fire alarm sicinat, the maximum Retard/Reset/Restart period shall not exceed 30 seconds. 'Rev. 05-28-2004 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results andlor other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Dote Issued: MAY 9, 2005 Listing Expires June 30, 2006 Authonzed By: DIANE K. AREND, Senior Deputy Program Manager Model SD500.AIM Addressable Input Module And Model SD500-MIM l Miniature Input Module lntelliKnight's addressable contact monitor modules combine fast response with pin-point location ID. A combination that saves lives and property. The SD500-AIM and SD500-MIM are addressable input modules for use with Silent Knight's lritelliKnight fire control panel. The SD500-AIM and SD500-MIM are designed to be used with pull stations, water flow switches, and other applications requiring dry contact alarm initiation devices. The SD500-AIM addressable input module mounts to a 4"-square box. The SD500-MIM mini input module fits inside a single gang box. The modules are supervised, single input contact monitors. Using an EOL resister, they monitor for alarm contact closures and for open circuit wiring fault conditions. The SD500-AIM and SD500-MIM offer a compact design for adaptability and pleasing aesthetics as well as easy installation and stable operation—a flexible solution for all your fire protection needs. Model SD500-AIM and SDSOO-MIM Input Modules The addressable input modules expand the flexibility of the lntelliKriight system by allowing the use of contact type inputs. Typical applications include manual pull stations and water flow switches. Featum Operates on Class A (Style 6 & Style 7) or Class B (Style 4)SLC Loop. Single contact monitor. Up to 127 modules per SLC loop. SD500-MIM mounts in a single gang box. SD500-AIM mounts in a 4"-square or double gang electrical box, and has an attractive ivory cover plate. SD500-AIMIMM are DIP switch programmable. Accepts up to 14 gauge wire. Both modules UL 864 listed; comply with NFPA 72 2500 ft max. wiring distance from input module to contact. CSFM listed. MEA429-92-E, Vol. 9 FM approved SU500-AIM 0on Each addressable input module is programmed with a unique SLC loop address. The module supervises the wiring to the contact with an End Of Line (EOL) resistor. If a fault occurs in the wiring, the module alerts the FACP. SILENT KNIGHT a Spedftcatlons Operating Voltage: 24 VDC Standby Current: 0.55 mA Alarm Current: 0.55 mA Ambient Temperature: 32°F to 120°F (0°C to 49°C) Mounting: SD500-AIM double gang box or 4°-square electrical box SDSOO-MIM single gang box Cj r - SD500-MIM Model SDSOO-AIM and SDSOO-MIM v._ Addressable Input and Mini Input Modules Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable input modules Silent Knight SD500-AIM or SD500-MIM. The modules shall be UL listed and compatible with Silent Knight's lntelliKnight FACPs. The SD500-MIM shall fit inside a single gang electrical box. The SD500-AIM shall be supplied with a plastic cover and shall be suitable for mounting to a 4"-square or double gang electrical box. The SD500-AIM addressable input module must provide a monitor LED that is visible from outside the cover plate. Model 50500-AIM FRONT VIEW BACK VIEW L 4.71r Model SD500-MIM hue" DSILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369-4927 8004146-6444 or in Minnesota 763-493-6435 FAX: 763-493-6475 World Wide Web: http://www.silentknight.com MADE IN AMERICA FORM# 350231, Rev. 11/01 Copyright © 2001 Silent Knight CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No 7300-0559:132 Page 1 of 1 CATEGORY Misc. Devices/Control Unit Accessories LISTEE: Silent Knight Security, 7550 Meridian Circle, Maple Grove, MN 55369 Contact Brian Foltz (783) 493-6400 *F (763) 391-5464 DESIGN: Models SD500-FRCM, SD500-FRCM-4 Monitor Modules and Model 5D505-ARM Relay Module. Models SD500-ARM, SDSOO-AIM, SD500-MIM Addressable Input Modules. Models SD500-FRCM and S0500-FRCM-4 monitor modules provide inputs for control unit communication circuit and one Style B (Class B) contact closure initiating device circuits. Models SD505-ARM and SD500-ARM provide inputs for a control unit communication circuit and have two sets of dry relay contacts. Models SD500-AIM and -MIM provide additional input circuits. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: SD500-FRCM, -FRCM-4, -ARM, -AIM, -MIM: 24 VDC SD505-ARM: 120 VAC, 30 VOC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as control unit accessories for use with listee's separately listed compatible lire alarm control units. Refer to listee's Installation Instruction Manual for details. XLF: 7300-0410:145 Rev. 05-27-2004 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and!or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed This listing should not be used to verily correct operational requirements or installation FIE criteria. Refer to Iistee's data sheet, installation instructions and/or other suitable information sources. Date Issued: MAY 9, 2005 Listing Expires June 30, 2006 Authonzed By: DIANE K. AREND, Senior Deputy Program Manager Addressable !:! Photoelectric Type Smoke Detector Detect smoldering fires quickly and get help fast with InteHiKnight® photoelectric smoke detectors. lntelliKnight addressable photoelectric smoke detectors are the clear choice for commercial settings where smoldering fires are a threat. In addition to accurately detecting a smoldering fire, each SD505-APS photoelectric detector has a unique address, which is recognized by the lntelliKnight panel. No precious seconds are wasted in determining location of an alarm. The SD505-APS compensates automatically for contamination in the environment. And detector testing is simple—even from a remote site. Like other lntelliKnight detector models, the SD505-APS offers a low profile for pleasing aesthetics. The lntelliKnight family of detectors has been designed to use a common base, Model SD505-6AB, allowing complete application and placement flexibility. Combine all this with the features you've come to expect from Silent Knight smoke detectors—easy installation, stable operation, RF/transient protection, and vandal-resistant locking—and it adds up to a flexible solution for all your fire protection needs. Model SD505-APS The light received is converted into Analog I Addressable an electronic signal. Under normal - Photoelectric Type conditions, the status LED blinks Smoke Detector approximately every 15 seconds, The SD505-APS is particularly indicating that the head is suited to detecting dense smoke communicating with the loop. The typical of fires involving materials LED lights continuously during the such as soft furnishings, plastic, alarm period. foam or other similar mtriIQ Features which tend to smolder and produce • Low profile, 2 inches, including large visible particles, base The detector features automatic compensation for contamination and a simple detector calibration test procedure that can be run from the panel or remotely (using the WindowsTM based downloading software). Operation The SD505-APS units made up of an LED light source and a silicon photo diode receiving element. In a normal standby condition, the receiving element receives no light from the pulsing light source. In the event or fire, smoke enters the detector and light is reflected from the smoke particles to the receiving element. Simple and reliable addressing without mechanical switches Automatic compensation for sensor contamination Built-in lire test feature Simple detector calibration testing through the control panel or remotely through a WindowsTM based computer software. Vandal-resistance locking features Field cleanable UL listed, meets NFPA 72 Ch 7 requirements CSFM approved MEA approved FM Approved SD505-APS Smoke Detector Specifications Operating Voltage: 17-41 VDC Current Consumption: Standby: .55 mA Alarm: .55 mA Ambient Temperature: 32°F to 120°F (0°C to 49°C) Mounting: 4" Square, 4" OCT, Single gang mud ring Relative Humidity: 85% noncondensing Air Velocity: 0 - 300 FPM Compatible Bases: S0505-6AB (Sold Separately) (6" Base) SD505-4AB (4" Base) DSILENT KNIGHT by Honeywell 0 (" 01 fl. / Diameter= 3-15116' Height = 2 inches, including base Diameter= 5-15/16' 0 iDj Model SD505-APS Addressable Photoelectric Type Smoke Detector Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable photoelectric smoke detector Silent Knight 50505-APS. The combination detector head, and twist-lock base, shall be UL® listed compatible with Silent Knight's IntelliKnight fire control panels. The base shall permit direct interchange with Silent Knight S0505-AIS Ionization Smoke Detector, or 5D505- AHS Heat Detector. Base shall be the appropriate twist-lock base SD505-6AB. The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch. The calibration of the detector shall be capable of being selected and measured by the control panel without the need for external test apparatus. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable as required. The 5D505-APS shall automatically perform a functional test of the detector. The test method shall simulate effects of products of combustion in the chamber to ensure testing of detector circuits. Model SD505-6AB Detector Base Model S0505-APS Detector Head (front view) (front view) D SILENT This document is not intended to be used for installation purposes. We try to T'-,P- keep our product information up-to-date and accurate. We cannot cover all 1L' specific applications or anticipate all requirements. All specifications are 1 subject to change without notice. For more information, contact Silent Knight by Honeywell 7550 Meridian Circle Suite 100, Maple Grove, Mn 553694927. Phone: (800) 328-0103, Fax: (763) 493-6475. MADE IN AMERICA FORM# 350225 Rev C,. 05/05 Copyright © 2005 Silent Knight CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7272-0559:129 Page 1 of 1 CATEGORY: Photoelectric Smoke Detector USTEE: Silent Knight Security, 7550 Meridian Circle, Maple Grove, MN 55369 Contact: Brian Foltz (763) 493-6400 *F (763)391-5464 DESIGN: Model SD505-APS analog addressable photoelectric type smoke detectorwith model SD505- 4AB and SD505-6AB bases. Unit consists of resistors, capacitors, diodes, transistors, LED, photo diode, mounted on a printed wiring board inside an enclosure. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 39.5 VOC INSTALLATION In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model designation, electrical rating and UL label. APPROVAL: Listed as photoelectric smoke detector for use with listee's separately listed compatible tire alarm control units. Refer to listee's Installation Instruction Manual for details. XLF: 7272-0410:149 'Rev. 05.27-2004 cm This listing is based upon technical data submitted by the applicant CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify coned operational requirements or installation criteria Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: MAY 9 2005 Listing Expires June 30, 2006 Authorized By. DIANE K. AREND, Senior Deputy Program Manager SD500-PS and SD500-PSDA Addressable Pull-Station lntelliKnight's addressable pull stations combine fast response with pin-point location ID. The SD500-PS and SD500-PSDA are a single action or dual action addressable manual fire alarm pull station for use with Silent Knight's lntelliKnight lire control panel. Extremely easy to operate, the SD500-PS/PSDA provides a fast and practical means of manually initiating a tire alarm signal. The lntelliKnight panel recognizes each manual pull station by its specific address saving precious seconds in determining the location of an alarm. The SD500-PS/PSDA mounts to a single gang box and features a rugged metal construction that lasts and lasts. - Combine all this with the features you've come to expect from Silent Knight - easy installation and stable operation - and it adds up to a flexible solution for all your fire protection needs. Model SD500-PS & • Extremely easy to operate SD500-PSDA Addressable Pull Station The SD500-PS is a single action addressable fire pull station, and the SD500--PSDA is a dual action addressable fire pull station. The SD500-PS/PSDA feature rugged metal construction A terminal strip on back of the pull station allows interconnection of the pull station to the SLC of an lntelliKnight control panel. The SD500-PS/PSDA is designed for indoor use in non- explosive environments. The normally open initiating point contacts are gold-plated to avoid risk of corrosion. The SD500- PS/PSDA has been tested by UL for compliance to the requirements of the Americans with Disabilities ACT (ADA). Features UL Listed CSFM listed ADA compliant Key reset (Same key as Silent Knight enclosures) Surface mount back box available Terminals - accept up to 14 gauge wire Corrosion-resistant gold-plated contacts. Reflective label makes it easier to locate in low light Operation The SD500-PS/PSDA single action pull stations are operated by a pull on the front pull cover of the station. A plunger switch, wired to a self contained addressable module, is released as the pull station opens to initiate the alarm. Once operated, the cover hangs down and can be seen up to 100 feet away. The pull station is reset by returning the front cover to the normal upright position and relocking the station with a reset key. The reset keys are the same keys used on Silent Knight enclosures. The SD500-PS/PSDA includes a status LED which blinks, indicating that the addressable module is communicating with the loop. The status LED lights continuously during an alarm. A dip switch on the addressable module is used to set the unique address. Specifications Operating Voltage: 24VDC Standby Current: .55mA Alarm Current: .55mA SD500-PS Ambient Temperature: 32°F to 120°F (0°C to 49°C) Mounting: Single gang box - Optional Red Surface Mount Box PS-SMBB SILENT KNIGHT FACP Wiring r II SD500-PS and SD500-PSDA Addressable Pull-Station Engineering Specifications Manual pull station shall be addressable Module SD500-PS/SD500-PSDA. Equipment shall be made of 14 gauge C.R.S.(Cold Rolled Steel), painted with a red enamel . The label shall contain the words Fire Alarm and be made of a reflective material embossed text 3/8 inches tall. Operating instruction shall be clearly visible on the same label. Manual station Shall contain a key operated test and reset lock using a lock plate actuator, the key shall match the control panel. Manual station shall contain four terminal blocks with two connected to the addressable module and two connect to the SLC loop. Manual station shall provide data to the control panel with an ID address programmed by dip switch settings Manual stations shall be Underwriters Laboratories Inc. listed and installed within the limits defined in the American Disabilities Act. Ilk I J LJT'\ I 'S 'S cz Mounting to Single Gang Electrical Box .. r ;--.'• S'..,,. 2...-. S ' 'Si " . S. S. .5 S. D In Mounting to Optional Surface Mount Box Installing SD500-LK SILIENT I1c1 KNIGHT k 7550 Meridian Circle, Maple Grove, MN 55369-4927 800-446-6444 or in Minnesota 763493-6435 FAX: 763-493-6475 World Wide Web: http-J/www.silentknight.com tvttkI Iii Must be Dimensions tn Dew MADE IN AMERICA FORM# 350342, Rev. 09/03 Copyright © 2003 Silent Knight CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7150-0559:136 Page 1 of 1 CATEGORY: Boxes/Pull Stations LISTEE: Silent Knight Security, 7550 Meridian Circle, Maple Grove, MN 55369 Contact: Brian Foltz (763) 493-6400 FAX (763) 391-5454 DESIGN: Model PS-SKSA and SD500-PS fire alarm pull boxes. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 30 VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as fire alarm pull station use with separately listed compatible fire alarm control units. For indoor use only. 0 Rev. 05-28-2004 This listing is based upon technical data submitted by the applicant CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Dote Issued: MAY 9. 2005 Listing Expires June 30,, 2006 Authorized By: DIANE K. AREND, Senior Deputy Program Manager -- Models Available Strobes Red White S1224MC S1224MCW S1224MCP S1224MCPW S1224MCK S1224MCSP Horn/Strobes Red White P1224MC P1224MCW P1224MCP P1224MCPW PI224MCK P1224MCSP Horns Red White H12/24 H12/24W H12/24K Product Overview Operates on either 12V or 24V SpectrAlert° Selectable Output Horns, Strobes, and Horn/Strobes offer enhanced fea- Widest range of candela options: tures that include the widest range of candela options available and the capability to 12V: 15 and 15/75 candela recognize and self-adjust for either 12 or 24 volt operation. With an overall feature 24V 15, 15/75, 30, 75, 110 candela set that combines performance, installation ease, flexibility, and a consistent, aesthetically pleasing appearance, the SpectrAlert Selectable Output devices Easy candela selection provide both the innovation and efficiency synonymous with the SpectrAlert name. Lower current draw Easy DIP switch selection for horn options Easy mounting with QuickClick Synchronlzable with MDL Sync.CircultTh module Meets (JL1971, NFPA72, and ADA signaling requirements All strobe and horn/strobe models incorporate a new patent-pending voltage booster design that has a more consistent flash bulb voltage over the range of candela selections. The benefit to the customer is a high quality strobe device. 0 @ LISTED 7125-1209:222 55512 S4011 7135-1209:223 F <C> MEA approved 12202E 3014150 126-02-E Performance. SpectrAlert selectable output wall-mount horns, strobes, and horn/strobes offer key performance features long associated with the SpectrAlert name. The select- able candela strobes and horn/strobes offer average current draws that are not only lower than conventional fixed-candela SpectrAlert products, but also lower than similar selectable candela products. By consuming less current, the ability to connect even more devices per loop is possible, resulting in a lower installed cost. Installation. SpectrAlert selectable output horns, strobes, and horn/strobes offer the same installation-friendly features synonymous with the SpectrAlert name, such as the option of 2- and 4-wire operation; the ability to use standard size back boxes with no encroachment into the box; and universal mounting incorporating the labor-saving QuickC(ick" feature. Such labor-savings features make wire connections simple and fast, further reducing installed cost. Flexibility. SpectrAlert selectable output strobes and horn/strobes offer the broadest range of candela options. In addition, the selectable output strobes and horn/strobes can operate on either 12V or 24V, with no setting required; the device recognizes and self-adjusts to the correct current automatically. Temporal 3 or Continuous tone options continue to be available, in either an Electromechanical or 3kHz pattern. Aesthetics. SpectrAlert selectable output horns, strobes, and horn/strobes incorporate the same stylish, low profile design of the conventional SpectrAlert products, for a con- sistent and aesthetically pleasing appearance across the entire product line. Engineering Specifications General SpectrAlert horns, strobes and horn/strobes shall be capable of mounting to a standard 4" x 4' x lh/z' back box or a single gang 2" x 4" x 1I" back box using the universal mounting plate included with each SpectrAlert product. Also, SpectrAlert prod- ucts, when used in conjunction with the accessory Sync-Circuit Module, shall be powered from a non-coded power supply and -shall operate on 12 or 24 volts. 12 volt rated devices shall have an operating voltage range of 9-17.5 volts. 24-volt rated devices shall have an operating voltage range or 17-33 volts. SpectrAlert products shall have an operating temperature of 32° to 120°F and operate from a regulated DC or full wave rectified, unfiltered power supply. Strobe- Strobe shall be a System Sensor SpectrAlert Model listed to UL 1971 and be approved for fire protective service. The strobe shall be wired as a primary signaling notification appliance and comply with the Americans with Disabilities Act require- ments for visible signaling appliances, flashing at 1Hz over the strobe's entire operating voltage range. The -strobe light -shall con- sist of a xenon flash tube and associated lens/reflector system. Horn/Strobe Combination Horn/Strobe shall be a System Sensor SpectrAlert Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. Horn/strobe shall be wired as a primary signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two tone options, two audibility options (at 24 volts) and the option to switch between a temporal 3 pattern and a non-temporal continuous pattern. Strobes shall be powered independently of the sounder with the removal of factory installed jumper wires. The horn on horn/ -strobe models -shall operate on a coded or non-coded power sup- ply (the strobe must be powered continuously). Synchronization Module Module shall be a System Sensor Sync'Circuit listed to UL 464 and shall be approved for fire protective service. The module -shall synchronize SpectrAlert -strobes at 1Hz and horns at temporal 3. Also, the module shall -silence the horns on horn! -strobe models, while operating the strobes, over a single pair of wires. The module shall be capable of mounting to a 411/16 x 411/16" x 2I" back box and -shall control two Style Y (class B) or one Style Z (class A) circuit. Module -shall be capable of multiple zone synchronization by daisy chaining multiple modules together and re-synchronizing each other along the chain. The module shall not operate on a coded power supply. Specifications Walk Test SpectrAlert horn/strobe and horn only work on walk tests" with time dura- tions of 4 seconds or greater Input Terminals 12 to 18 AWG Dimensions Strobe and horn/strobe with universal plate 5" x 5 /a x 215/16 Strobe and horn/strobe with small footprint plate 3/8 X 5/8" x 2/16" Horn with universal mounting plate 5" x 5/ x 1/16" Horn without mounting plate 2/ie' x 5/1.6" X 1/16" Weight, horn only 7.2 oz. Weight, strobe and horn/strobe 8.8 oz. Mounting 4 x 4 x 1/2" or 2" x 4 x standard boxes Operating Temperature (Indoor) 32°F to 120°F (0°C to 49°C) Maximum humidity (Indoor) 95% as tested per UL464 Outdoor (K Series) Operating Temperature —40°F to 151°F (-40°C to 66°C) Outdoor rating NEMA 314 (per UL 50) Voltages 12 or 24VDC and FWR unfiltered Operating voltage range 12V: 8-17.5V; 24V: 16-33V Operating voltage range (with Sync.Circuit module, MDL> 12V: 9-17.5V; 24V: 17-33V U.S. Patent Numbers 5,593,569 5,914,665 6,049,446 Horn Current Draw Measurements (RMS): Selectable Horn Tones DC FWR 12V sw 12V zv Temporal Low Volume Electromechanical 15 23 13 23 3000 Hz Interrupted 15 33 13 23 High Volume Electromechanical 36 53 20 44 3000 Hz Interrupted 43 57 21 40 Non- Temporal Low Volume Electromechanical 16 37 19 29 3000 Hz Interrupted 16 32 18 33 High Volume Electromechanical 38 49 46 49 3000 Hz Interrupted 1 44 56 42 58 NO1E Horn/strobe current draw can be calculated by adding the strobe Current draw to the horn current draw for the chosen setting. SpectrAlert Current Draw Series Candela Setting FWR Operating Current-Strobe (mA RMS) DC Operating Current- Strobe (mA RMS) 12V I 24V 12V 24V S1224MC Strobes 15 112 64 127 59 15/75 135 74 127 69 30 93 90 75 158 160 110 208 209 P1224MC Horn/Strobes 15 112 64 127 59 15/75 135 74 127 69 30 93 90 75 158 160 110 208 209 SpectrAlert Mounting and Operation Candela Selections For strobe candela selection, adjust slide switch located on the rear of the product while watching the viewing window on the side of the reflector. Permissible Candela Settings Candela Operating Voltage Setting 12V 24V 15 OK OK 15/75 OK OK 30 OK 75 OK 110 OK A0133-OD Horn Sound Measurements (dBA): Selectable Horn Tones I 8-17.5V 1 18-33V Temporal Low Volume Electromechanical 67 75 3000 Hz interrupted 68 75 High Volume Electromechanical 71 80 3000 Hz interrupted 72 81 Now Temporal Low Volume Electromechanical 71 79 3000 Hz interrupted 72 79 High Volume Electromechanical 76 84 3000 Hz interrupted 77 86 DIP Switch Operation Viewing 'd Typical weatherproof mounting with universal plate 1_WBB 1Plate I' Factory DIP Switch OFF ON Default I Low i.il High Temporal FORE -1 Non-Temporal I Ia_1 _ II Electromech. II I 3000Hz hEll::I Base (rear) AG 110-00 r- #8-36 x 1/2 Fiat Head / Screw (4 total) 1 (7==\ A0120-OO Gasket —/ \—Conduit Entrance slot Paper Liner For Plate Gasket CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7135-1653:163 Page 1 of 1 CATEGORY: Audible Devices LISTEE: System Sensor, Unincorporated Div. of Honeywell Int'l Inc., 3825 Ohio Avenue, St. Charles IL 60174 Contact: Trish Linhart (630) 377-6580 ext. 1185 FAX (630) 377-7245 DESIGN: Models P1224MC, PI224MCW, PI224MCSP, P1224MCSPW, P1224MCP, P1224MCPW, P1224MCK, and P1224MCWK combination horn/strobes with selectable candela. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: Electrical: 8-33 VDC/FWR 12124 VDC/FWR Selectable :15cd, 15/75cd 24 VDC/FWR Selectable: 30cd, 75cd, 110cd INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. These sounder/strobe combination units are not intended for field assembly. MARKING: Listee's name, model number, rating, and UL label. APPROVAL: Listed as horn strobes for use with separately listed compatible fire alarm control units. Suitable for the hearing impaired application. For wall mount and indoor use only. Models with suffix "K" are suitable for extended indoor operation temperatures 32 to 150° F (0 to 66 °C) and have NEMA type 3R enclosure rating for outdoor use. Units can generate the distinctive three-pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 1999 Edition. Refer to manufacturer's Installation Manual for details. NOTE: Formerly 7135-1209:223 06-20-05 """... This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: JUNE 20, 2005 Listing Expires June 30, 2006 Authorized By: DIANE K. AREND, Senior Deputy Program Manager U.S. Pat No. 3921989 Canadian Pat No. 1009680 Other Patents Pending Potter Electric, Rd., 1990 POTTER VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD UL, ULCandCSFM Usted,FM and LPCBApproved,NYMEA Accepted, CE Marked Service Pressure: Up to 450 PSI (31 BAR) Minimum FlowRateforAlarm: 10GPM (38 LPM) Maximum Surge: 18 FPS (5,5 mis) ContactRatings: Two sets of SPOT (Form C) 15.0 Amps at 1251250VAC 2.0 Amps at 3OVDC Resistive Conduit Entrances: Two knockouts provided for 112" conduit Environmental Specifications: Suitable for indoor or outdoor use with factory installed gasket and die-cast housing. NEMA4JIP54 Rated Enclosure - use with appropriate conduit fitting. Temperature Range: 40°F/1 20°F, 4.5Ci49C Non-corrosive sleeve factory installed in saddle. Caution: This device is not intended for applications in explosive environments. Sizes Available: Steel Pipe schedules 10 thru 40, sizes 2" thru 8" BS 1387 pipe 50mm thru 200mm Note: For copper or plastic pipe use Model VSR-CF. Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-130 Residential occupancy up to four stories NFPA-1 3R National Fire Alarm Code NFPA-72 Optional: CoverTamper Switch Kit, StockNo. 0090018 GENERAL INFORMATION INSTALLATION: See F The Model VSR-F is a vane type waterfiow switch for use on These devices may be mounted on horizontal or vertical pipe. wet sprinkler systems. It is UL Listed and FM Approved for On horizontal pipe they should be installed on the top side of the use on steel pipe; schedules 10 through 40, sizes 2" thru 8" pipe where they will be accessible. The units should not be in- (50mm thru 200mm). stalled within 6" (15cm) of a fitting which changes the direction of LPC approved sizes are 2" thru 8" (50mm thru 200mm). the waterfiow or within 24" (60 cm) of a valve or drain. The unit may also be used as a sectional waterfiow detector on large systems. The unit contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic re- tard. The switches are actuated when a flow of 10 gallons per minute (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. ENCLOSURE: The unit is enclosed in a general purpose, die- cast housing. The cover is held in place with two tamper resis- tant screws which require a special key for removal. A field in- stallable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin no. 5400775 for installation instructions of this switch. Drain the system and drill a hole in the pipe using a circular saw in a slow speed drill. The 2' (50mm) and 2 1/2' (65mm) devices require a hole with a diameter of 1114" + 1" - 1/16" (33mm ±2mm). All other sizes require a hole with a diameter of 2":0/8" (50mm ±2mm). Clean the inside pipe of all growth or other material for a dis- tance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterilow. Install the saddle strap and tighten nuts alternately to an eventual 50 ft-lbs. (68 n-m) of torque (see Fig. 2). The vane must not rub the inside of the pipe or bind in any way. Specifications subject to change without notice. Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO. 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • wwN.pottersignal.com -- ---- PRINTED IN USA MKT. #8800001 - REV W PAGE 1 OF 2 MFG 05400761 -7102 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7770-0328:001 Page 1 of I CATEGORY: Valves/Switches LISTEE: Potter Electric Signal Co., 2081 Craig Road, St. Louis, MO 63146 Contact: Brad Serangeli (800) 325-3936 Fax (314) 878-7264 DESIGN: Vane and pressure type water flow alarm switches listed below. Refer to listee's data sheet for detailed product description and operational considerations. Vane Types: VSR-CF VSR-D VSR-F VSR-SF VSR-FE-2 VS-SP VS-F VSR-SFG VSR-SFT VSG *VSR Pressure Type: WFS-13 WFSR-C WFSPD-B PS-10A PS-100A WFSR-F INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number and UL or FM label. APPROVAL: Listed as watertlow alarm switches for use with fire sprinkler systems. Vane models may be used in wet pipe systems; pressure models may be used in wet or dry systems. Model VSR-CF is for use on K, L or M copper pipe (2", 2-1/2", 3", 4") and listed CPVC pipe (2", 2-1/2", 3"). Model VSR-SF for use on 1", 1-1/4" and 1-1/2" steel, copper or listed plastic pipe. Model VSG is for low flow rate. Model VSR-SFG and VSR-SFT are for use on 1", 1-1/4" and 1-1/2" plastic pipe. Models VS-F, VSR-F, VSR-FE and VSR-FE-2 is for use on 2", 2-1/2", 3", 3-1/2", 40, 5, 6', 8' and 10" pipe. *Model VSR is for use on steel pipe sizes from 2" through 8". Vane type switches may be used outdoors when the outdoor temperature never falls below 40°F. *Rev. 06-05-2000 h.Zo This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: MAY 18, 2005 Listing Expires June 30, 2006 Authorized By: DIANE K. AREND, Senior Deputy Program Manager Page 1 of . Home I v News I Product I v Customer Service I v Contact Us I v Help I v Search July 9, 2005 The professional choice in tire safety. Company History News Highlights Press Releases Invensys Sites Fl REX Job Opportunities Employee Login Smoke Narm Duct Smoke Detectors Universal Voltage Models 230 VAC, 115 VAC, 24 VAC or 24 VDC operation 2650-660 Ionization • 2650-661 Photoelectric FIREX®, the recognized leader in residential fire protection, brings you the latest in duct smoke detection technology. FIREX® Duct Smoke Detectors provide early detection of smoke and products of combustion present in air moving through an HVAC duct. These devices are designed for prevention of smoke recirculation in areas by the air handling systems. Fans, blowers, and complete systems may be shut down in the event of smoke detection. Our universal voltage models will operate on any one of four input voltages. Air sampling is accomplished by two tubes, which protrude into the duct. An exhaust tube of one standard length(7") is provided with each FIREX® Duct Smoke Detector. Intake sampling tubes, which must be ordered separately, are available in three standard lengths. Duct smoke detector mounting is accomplished by the use of a mounting template and four sheet metal screws, which are provided. file :1/C :\DOCUME 1 \TERR1M- 1 \LOCALS 1 \Temp\142M4UA27.htm 7/9/2005 Page 2 of 5 High Temperature Design - - 0 Rated to 155 T (ionization model) - for rool.to)) and other mstallations Alerts When Dirty - where high tacratures can Automatically indicates when ( cause Problem tlutiflt enstnc! i recimmirtat. - Interconnect I Up to 30 Models r • r—Front ounte Up 1030 models Test / Reset Button interconnected to provide I 1'oridi.s quick and accurate Complete HVAC System \ , testing of protection-4-,ontrolling all connecied blowers. fins and damper& Installation Flexibility Fast and easy mounting to rc!elaliglllar ducts. Detector Accessories Download Manual You will need Adobe Acrobat Readerto view the manuals. If you do not have this installed, you can download it from Adobe's web site. Additional Features Four sheet metal screws provide • Compatible with building automation & fire alarm easier mounting systems UL 268A listed • Dust filtering included in detector head Factory set tube alignment Mechanical installation without cover removal Built-in power supply No additional screens or filters to clean Common or individual remote reset Common or individual fan shutdown relay operation file :1/C :\DOCUME 1 \TERR1M-- 1 \LOCALS 1 \Temp\H2M4UA27.htm 7/9/2005 Page 3 of 5 Installation template included Large terminal connection screws Power supervisory relay included Common or individual remote alarm indication, i.e. red LED, horn, strobe Common or individual head removed remote indication Two independent form "C" alarm contacts standard One horn/strobe operated by up to 15 detectors Wiring Cecco Remote (S000c'crnI I2.OA IZOA 10 T,ou1G ISO 18 is l '8 I d . ii I0nt wil bc ,cS$Od, FIRE cCIccr 1 C43 \.._.... Am ..__./ •17000 00(TOCIS 115 VAC 0 5050 Hz 0.1 A.L I 3 3 5 1 0 ITS tAC Ooothn 24 'JAG IIIpIM I 3 3 'I 8 8 23 VAC OOion 24 'JOG UVA 0$ A. Mt. I 3 3 £ 3 2$ V000ffibOn Product Specifications Item: 2650-660 - 115 Volt AC, 230 Volt AC, 24 Volt AC or 24 Volt DC ionization 2650-661 - 115 Volt AC, 230 Volt AC, 24 Volt AC or 24 Volt DC photoelectric 532 - Sampling tube for 6 to 2.5 duct widths Approval: Underwriters Laboratories Listed 268A) Ambient Temperature: (UL file :1/C :\DOCUME1 \TERRIM 1 \LOCALS- 1 \Temp\H2M4UA27.htm 7/9/2005 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 3240-1595:114 Page 1 of I CATEGORY: Duct Smoke Detector Housing/Base LISTEE: lnvensys Climate Controls Americas, 191 E. North Ave., Carol Stream, IL 60188-2064 Contact: Tom Barakat (630) 260-7262 FAX (630) 260-7290 DESIGN: Models 2650-660 and 2650-661 duct smoke detector units. Units consist of an enclosure, relay, and electrical components, listed open area detector and sampling and exhausted tubes. All units are four-wire duct detectors. Model 2650-660 employs an ionization smoke detector head and Model 2650-661 employs a photoelectric smoke detector head. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 24 VAC, 24VDC, 115 VAC or 230 VAC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as duct detectors for use with separately listed compatible fire alarm control units when installed in HVAC systems with air velocity between 500 and 4000 ft./min. XLF: 3240-1004:108 NOTE: Formerly 3240-1093:124 02-06-2003 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: JUNE 8, 2005 Listing Expires June 30, 2006 Authorized By: DIANE K. AREND, Senior Deputy Program Manager Fig OIG Top View r Fig 01W 01 /01W - BUTTERFLY VALVE INSTALLATION INSTRUCTIONS Upper & Lower Shafts: 416 Stainless Steel Body Coating: Fusion Bonded Nylon 11 v Disc Encapsulation Material; SBR SIZE 2.5" 3" 4" 6" 8" A 1.81 1.81 2.05 2.21 2.36 AA 2.85 3.47 4.47 6.61 8.61 B 3.81 3.82 4.57 5.83 5.27 C 6.00 1 6.00 6.00 6.00 6.00 0 7.60 7.60 7.60 7.60 7.60 E 10.30 10.77 12.86 15.73 17.56 F 5.35 5.58 6.68 8.36 9.28 H 1.72 2.39 3.31 5.60 7.49 Wt.G 16 20 24 37 43 WLW 20 20 25 34 44 8" SIZE ONLY =CLLRRENCE DIAMEIER FOR DISK = MINIMUM ALLOWABLE PIPE I.D. PIPE CONNECTION SPECIFICATIONS Figure OIG (Grooved End) Pressure Rating: Fig. OIG - 300psi Fnd Connpr.tinns Mating pipo and couplings to conform to ANSIIA'.MNA CBOS for nutsidA, grorwA, and gasket dimpnsinns For use with cut grooves in steel pipe of schedule 40 to 160. Installation: Valves to be installed by person(s) certified by authority having jurisdiction to install grooved end fittings in a lire protection system. Place gasket over pipe or fitting to which valve is to be joined. Position valve against mating pipe or fitting. Slide gasket into position on valve and install coupling according to coupling manufacturer's directions. Figure 01W (Wafer End) Pressure Rating: Fig. 01W- 300ps1 End Connections: For installation between two ANSI B16.1, 125 pound flanges pipe schedule 10 to 80. See diagram and chart above for minimum inside diameter of pipe. Two flanged mating pieces should be placed at a distance apart that is slightly larger than the length of the valve (dim. "B") A minimum of 2 studs should be placed, through adjacent flange holes, between which the lower trunnion of the valve will be placed. Place valve between flanges so that lower trunnion and larger rib section fIt between adjacent studs. Place remaining studs around valve and tighten alternating sides until desired torque is reached. SIZE 2.5" 3" 4" 6" 8" Number of studs 4 4 8 8 8 Stud Size (in) 518 518 5/8 3/4 3/4 Stud Length (in. minimum) 5.5 5.5 6.5 7 75 Recommended Torque (minimum) 1 30 1 30 1 30 1 40 50 Kennedy ValveIULJFM Butterfly Valves 10-3 KENNEDY VALVE () Division of McWane, Inc. 4G> 1021 E..Water St., Elmira, NY 14901 (607) 734-2211 APPROVED GROOVED END BUTTERFLY VALVES 2-112" to 8" Irm Figure 01G. 300ps1 with Supervisory Tamper Switch UL 1091 Listed for Indoor or Ambient Outdoor Service Without Direct Exposure to Precipitation or Being Submerged Supervisory Tamper Switch & Auxiliary Switch Electrical Specs, Max: 28 VDC, 120 VAC, 0.25 AMP Tamper Switch Auxiliary Switch WIRE COLOR MODE A BLACK N/O B BLACK N/O C BLUE COMMON D BLUE COMMON E BLUEINHITE COMMON F BLACK/WHITE N/O H RED N/C Upper & Lower Shafts: 416 Stainless Steel Body Coating: Fusion Bonded Nylon 11 Disc Encapsulation Material: SBR WOE UI v USA SIZE AAdia B C D E F Wt# 2.5 2.85 3.81 6.0 7.6 10.30 5.35 16 3.47 3.82 60 7.6 10.77 5.58 20 4.47 4.57 60 7.6 12.86 6.68 24 6" 661 5.83 60 7.6 1573 8.36 37 8" 1 8.61 5.27 1 6.0 1 7.6 1 17.56 1 9.28 1 43 Kennedy Valve/ULIFM Butterfly Valves 10-1 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7770-1440:101 Page 1 of I CATEGORY: Valves/Switches LISTEE: Kennedy Valve, 1021 East Water Street, Elmira, NY 14901 Contact: John A. Chalk (607) 734-2211 Fax (800) 952-4771 DESIGN: Figures 01 G grooved-end and 01W wafer end butterfly valves in the 2-1/2', 3', 4", 6" and 8" sizes. These valves may employ internal supervisory tamper switches. The 4, 5, 6, and 8" size valves incorporated a new EPDM disc rubber Compound Buckhorn 060-3. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING:- Rated pressure: 300 psi INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, rating, and UL label. APPROVAL: Listed as butterfly valves for use as a water supply control valve for fire protection systems. Suitable for indoor/outdoor use. Refer to listee's Installation Instruction Manual for details. 12-19-2004 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: MAY 17, 2005 Listing Expires June 30, 2006 Authorized By: DIANE K. A REND, Senior Deputy Program Manager