HomeMy WebLinkAbout5040 TIERRA DEL ORO ST; ; AS1401916/27/24, 3:40 PM 0 AS140191 Permit Data
City of Carlsbad
Sprinkler Permit
5040 TIERRA DEL
Job Address:
ORO ST
Permit Type: SPRINK
Parcel No: 2100200700
Lot #: 0
Reference No.:
Permit No: AS140191
Status: ISSUED
Applied 7/25/2014
Approved: 8/6/2014
Issued: 8/6/2014
PC #: Inspector:
Project Title: PORTER RESIDENCE NEW SPRINKLER SYSTEM FOR
RESIDENCE: EXERCISE ROOM, BEDROOM #3, AND ELEVATOR
AT 1ST FLOOR (416 SF) NEW MASTER
BEDROOM/BATH/CLOSET, VEIW ROOM, AND OFFICE AT 2ND
FLOOR (1257 SF) TOTAL NEW LIVING SPACE: 1,673 DF
EXISTING LIVING SPACE: 2,431 SF TOTAL LIVING SPACE: 4,104
SF NEW WATERPROOF BALCONY AT 2ND FLOOR (300 SF)
COVERED ENTRY (105 DF) EXISTING GARAGE: 388 SF
Applicant:
ALPHA FIRE PROTECTION
500 HACIENDA DR #180
VISTA, CA
760-727-6993
Owner:
COOK JOAN D SEPARATE PROPERTY
TRUST 05-15-81
7040 AVEN IDA ENCINAS #104-369
CARLSBAD CA
Fees ($) Add'I Fees ($) j Total ($) Balance ($)
470 * 0 470 0
about:blank 1/1
2.
ALPHA FIRE PROTECTION
RESIDENTIAL FIRE SPRINKLER SYSTEM
:7/10/
JOB ADDRESS: 5040 TIERRA DEL ORo, CARLSBAD, CA.
ASSESSOR'S PARCEL NUMBER: 210-020-07
OWNER'S NAME: PORTER
OWNER'S ADDRESS: SAME
OWNER'S PHONE NUMBER:
GENERAL CONTRACTOR'S NAME: BH WORTHING CONSTRUCTION
GENERAL CONTRACTOR'S ADDRESS:
GENERAL CONTRACTOR'S PHONE NUMBER:
SPRINKLER CONTRACTOR'S NAME: ALPHA FIRE PROTECTION
SPRINKLER CONTRACTOR'S ADDRESS: 4203 GENESEE AVE #103-424 SAN DIEGO, CA 92117
SPRINKLER CONTRACTOR'S PHONE NUMBER: (760) 727-6993
CALIFORNIA STATE LICENSE #582853 EXPIRES 12-31-2015
HYDRAULIC NOTES:
WATER METER SIZE: 1" (NEW)
METER ELEVATION: -30 AMSL
PRESSURE AT METER: 93 PSI
FLOW (GPM): HOUSE SIDE OF METER: 50 GPM
PAD ELEVATION: 31'
PRESSURE AT PAD: 893 PSI
PIPE LENGTH: METER To PAD: 15'
Pipe Type/Size: PVC —1 1/4"
SPRINKLER TABLE:
FROM LINDA ONTIVEROS
@ CARLSBAD WATER DEPT (760) 602-2750
DATE: 7-21-14
SYMB COMPANY & MODEL ORF TYPE TEMP K-FAT CANOPY QTY
Tyco LF-II 1/2 SSP RR Sin#2524
165 Degree 4.9 White Concealed 29
Tyco TY-FRB
Sin # 3231 1/2 SSP 200 Degree 5.6 White
Recessed/none
7
Total 41
PIPE TABLE:
TYPE MFG MODEL AREA OF USE
CPVC TYCO BLAZEMASTER SYSTEM
STEEL ALLIED SCHEDULE 40 NONE USED
COPPER MULLER TYPES M & L SUPPLY
PVC SPEARS SCHEDULE 40 SUPPLY
NOTE: PIPE MUST BE U.L. OR F.M. LISTED FOR RESIDENTIAL FIRE SPRINKLER USE.
PLANS MUST STATE:
"PIPE WILL BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS."
"A COPY OF PIPE MANUFACTURER'S INSTALLATION INSTRUCTION PAMPHLET MUST BE KEPT ON-SITE."
Alpha Fire- Hydraulic Calculations
Contract Name: R (ZT€ Sheet / of (
Calculation for: 2.-/11/2 OW Date:
Nozzle
Type &
Location
Flow
In
GPM -
Pipe
Size
Inches
Fittings
And
Devices
Pipe
Fittings
Total
Friction
Loss
psi/fl
Required
Pressure
psi
Elevation
Node
Notes
q TypecP
Diameter 7(
C-Factor / $Z)
Ln Pt UP, 70 I
13 Ft 12.. Pf 3,77
Tot 16' Pe
q
Q
Type
Diameter
C-Factor
Ln Pt 20-14 7
Ft Pf
Tot Pe
q
Q
Type C/o C
Diameter
C-Factor /
oC Ln 7
gq
PtI(p,70 p
Ft 11 pf 3 qq
Tot 1cl Pe .-' ç
Q
40
Type C,-
Diameter f
C-Factor / f?
'2 IM Ln5
2 '-1 9 3
PtZO,? 3
4 Ft 2,2- Pf L9, 40
Tot 7 5 Pe 4,33 c
q
Q q D
Type&Q
C-Factor ico
Lu 4LA.6
07 7 7
Tot 9O,5
Pt
Diameter t't
Ft 3 Pf C
Pe,j0
q
Q
(.L9
Type,
Diameter 4
C-Factorl o
7. Tr,,
a—C (ii
Ln
,
gj,; 73
It
It 7 Pi
Tot (7 Pe 3 L)
q
Q
q 0
Type Al C U
Diameter it1
C-Factor I D
c, Ln
; 0
Pt 571 ( (p A/ $6/'
i-PJ Ft i q Z. ,4 c1
To 2. 7, Pe
Q
LI
Type CC V
Diameter? kj
C-Factor 15D
ic Ln (q
/ Tot e?
Pt L (ii. 7
34)
611Z Ft Pf
- Pe ..-'
q
Q
5
Type P V c,-
Diameter)1
CFactorO
Ln /
/oqc)
Pt ( Z 3e ?
Ft Pf
Tot /5 Pe 3
q
Q
Type
Diamete11 /
C-Factor
Ln Pt '°' '' /11
t o Ft Pf 4,5.
Tot - Pe ..TIO
_
q
Q
1.)
Type it j
Diameter
C-Factor )
Ln(2.
qqqq
Pt7(O,, 10
3 0
Ft Pf qq
Tot I ' Pe 30
q
Q
Type
Diameter
C-Factor
Ln Ptgo.g It
, 7
Ft Pf
Tot Pc
Fire Protection
Products
Worldwide l
Contacts www.tyco-flre.com
RAPID RESPONSE Series LFII Residential
49 K-factor Concealed Pendent Sprinklers, Flat Plate
Wet Pipe and Dry Pipe Systems
General
Description
The TYCO RAPID RESPONSE Se-
ries LFII Residential 4.9 K-factor Con-
cealed Pendent Sprinklers (TY3596)
are decorative, fast response, fus-
ible solder sprinklers designed for use
in residential occupancies such as
homes, apartments, dormitories, and
hotels.
The cover plate assembly conceals
the sprinkler operating components
above the ceiling. The flat profile of the
cover plate provides the optimum aes-
thetically appealing sprinkler design.
In addition, the concealed design of
the Series LFII Residential Concealed
Pendent Sprinklers (TY3596) provides
1/2 inch (12,7 mm) vertical adjustment.
This adjustment provides a measure of
flexibility when cutting fixed sprinkler
drops.
The Series LFlI Residential Concealed
Sprinklers are intended for use in the
following scenarios:
wet and dry pipe residential sprin-
kler systems for one- and two-fam-
ily dwellings and mobile homes per
NFPA 13D
wet and dry pipe residential sprin-
kler systems for residential occu-
pancies up to and including four
stories in height per NFPA 13R
wet and dry pipe sprinkler systems
for the residential portions of any
occupancy per NFPA 13
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 6
The Series LFII Residential Concealed
Pendent Sprinklers (TY3596) has been
designed with heat sensitivity and wa-
ter distribution characteristics proven
to help in the control of residential fires
and to improve the chance for occu-
pants to escape or be evacuated.
The Series LFII Residential Concealed
Pendent Sprinklers (TY3596) are
shipped with a Disposable Protective
Cap. The Protective Cap is temporar-
ily removed for installation, and then
it can be replaced to help protect the
sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro-
tective Cap can also be used to mark
the center of the ceiling hole into plas-
ter board, ceiling tiles, etc. by gently
pushing the ceiling product against
the Protective Cap. When the ceiling
installation is complete the Protective
Cap is removed and the Cover Plate
Assembly installed.
Dry Pipe System Application
The Series LFII Residential Concealed
Pendent Sprinklers offers a laboratory
approved option for designing dry pipe
residential sprinkler systems, whereas,
most residential sprinklers are labora-
tory approved for wet systems only.
Through extensive testing, it has been
determined that the number of design
sprinklers (hydraulic design area) for
the Series LFII Residential Concealed
Pendent Sprinklers (TY3596) need not
be increased over the number of de-
sign sprinklers (hydraulic design area)
as specified for wet pipe sprinkler sys-
tems, as is accustomed for density/
area sprinkler systems designed per
NFPA 13.
Consequently, the Series LFll Residen-
tial Concealed Pendent Sprinklers of-
fer the features of non-water filled pipe
in addition to not having to increase
the number of design sprinklers (hy-
draulic design area) for systems de-
signed to NFPA 13,13D, or 13R.
FEBRUARY 2014
LNO _TIC E
The Series LFII Residential Con-
cealed Pendent Sprinklers (TY3596)
described herein must be installed
and maintained in compliance with
this document and with the applica-
ble standards of the National Fire Pro-
faction Association, in addition to the
standards of any authorities having ju-
risdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Sprinkler
Identification
Number
1Y3596
TFP442
SPRINKLER-
SUPPORT CliP
ASSEMBI
/OPERATE
j
SPRINKLE
COVER
PLATE
RETAJNEI
7/8" (22,2
1-1/8" (28,6
ii
DISPOSABLE DEFLECTOR IN
TFP442
Page 2 of 6
BODY
(1/2" NPT) -
CAP
SADDLE -
SUPPORT
CUP WITH -
ROLL FORMED
THREADS
GUIDE
PIN
7
GUIDE PIN
HOUSING
DEFLECTOR -
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 2
W-TYPE 18
SPRINKLER WRENCH
SEALING
ASSEMBLY
SPRINKLER
WRENCHING
AREA
COMPRESSION
SCREW
LEVER
SOLDER LINK H H ELEMENT
II
I DEFLECTOR J - L (OPERATED
POSITION)
SPRINKLER/SUPPORT CUP
ASSEMBLY
THREAD INTO
SUPPORT
CUP UNTIL
MOUNTING
SURFACE IS
FLUSH WITH
CEILING
RETAINER
WITH THREAD
- DIMPLES
EJECTION
SPRING
SOLDER -' COVER PLATE/RETAINER '-.. COVER
TAB ASSEMBLY PLATE
FIGURE 1
RAPID RESPONSE SERIES LFII RESIDENTIAL
CONCEALED PENDENT SPRINKLER (TV3596)
2-1/2° DIA.
(63,5 mm) 1/2 (12,7 mm) FACE OF
1/2° THREADED SPRINKLER
NPT ADJUSTMENT FITTING
1-7/8±1/4
(47,6 mm
1/8 GAP j *6,4 mm)
mm)
I Ea
COVER- SPRINKLER-
j
MOUNTING
RETAINER SUPPORT CUP 3/16" SURFACE ASSEMBLY ASSEMBLY (4,8 mm)
3-3/16" DIA
(81,0 mm) ' TIP PROTECTIVE CAP OPERATED POSITION
FIGURE 3
RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER (TY3596)
INSTALLATION DIMENSIONS/PROTECTIVE CAP/ACTIVATED DEFLECTOR
TFP442
Page 3 of 6
Technical
Data
Approvals
UL and C-UL Listed. NYC Approved
under MEA 44-03-E-2NSF. Certified to
NSF/ANSI 61.
The TYCO RAPID RESPONSE Series
LFII Residential Concealed Pendent
Sprinklers are only listed with the Se-
ties LFII Concealed Cover Plates hav-
ing a factory-applied finish.
These Cover Plates and their part
numbers can be found in the Ordering
Procedure section at the end of this
data sheet.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 4.9 GPM/psi112 (70,6 LPM/bar112)
Temperature Rating
160°F (71°C) Sprinkler with 139°F
(59°C) Cover Plate
Vertical Adjustment
1/2 inch (12,7 mm)
Finishes
Refer to Ordering Procedure section
Physical Characteristics
Body ..............Brass Cap..............................Bronze
Saddle ............................Brass
Sealing Assembly ................Beryllium
Nickel WI TEFLON
Soldered Link Halves ................. Nickel
Lover ............................. Bronze
Compression Screw .................Brass
Deflector .................. Copper or Brass
Guide Pin Housing.......Bronze
Guide Pins .........Stainless Steel or Bronze
Support Cup ........................Steel
Cover Plate .......................Copper
Retainer ...........................Brass Cover Plate Ejection Spring.....Stainless Steel
Operation
When exposed to heat from a fire, the
Cover Plate, which is normally sol-
dered to the Support Cup at three
points, falls away to expose the Sprin-
kler Assembly. At this point the De-
flector supported by the Arms drops
down to its operated position. The fus-
ible link of the Sprinkler Assembly is
comprised of two link halves that are
soldered together with a thin layer of
solder. When the rated temperature is
reached, the solder melts and the two
link halves separate allowing the sprin-
kler to activate and flow water.
Design Criteria
The TYCO RAPID RESPONSE Series
LFIl Residential Concealed Pendent
Sprinklers (TY3596) are UL and C-UL
Listed for installation in accordance
with this section.
Note: When conditions exist that are
outside the scope of the provided cri-
teria, refer to the Residential Sprinkler
Design Guide TFP490 for the manu-
facturer's recommendations that may
be acceptable to the authority having
jurisdiction.
System Types
Per the UL Listing, wet pipe and dry
pipe systems may be utilized. Per the
C-UL Listing, only wet pipe systems
may be utilized.
Refer to Technical Data Sheet 1FP485
about the use of residential sprinklers
in residential dry pipe systems.
Ceiling Types
Smooth fiat horizontal, or beamed, or
sloped, in accordance with the 2013
Edition of NFPA 13D, 13R, or 13 as
applicable.
Hydraulic Design
(NFPA 130 and 13R)
For systems designed to NFPA 13D
or NFPA 13R, the minimum required
sprinkler flow rates are given in Ta-
bles A and B as a function of tem-
perature rating and the maximum
allowable coverage areas. The sprin-
kler flow rate is the minimum re-
quired discharge from each of the
total number of "design sprinklers" as
specified in NFPA 13D or NFPA 13R.
The number of "design sprinklers"
specified in NFPA 13D and 13R for wet
pipe systems is to be applied when
designing dry pipe systems.
Hydraulic Design
(NFPA 13)
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is to be the greater of the following:
The flow rates given in Tables A
and B as a function of temperature
rating and the maximum allowable
coverage area.
A minimum discharge of 0.1 gpm/
ft2 over the "design area" comprised
of the four most hydraulically
demanding sprinklers for actual
coverage areas protected by the
four sprinklers.
The number of "design sprinklers"
specified in NFPA 13 for wet pipe sys-
tems is to be applied when designing
dry pipe systems.
Dry Pipe System Water Delivery
When using the Series LFII Residen-
tial Concealed Pendent Sprinklers
(TY3596) in dry pipe sprinkler systems,
the time for water delivery must not ex-
ceed 15 seconds for the most remote
operating sprinkler.
Obstruction to Water Distribution
Sprinklers are to be located in accor-
dance with the obstruction rules of
NFPA 130, 13R, and 13 as applicable
for residential sprinklers as well as with
the obstruction criteria described with-
in the Technical Data Sheet TFP490.
Operational Sensitivity
The sprinklers are to be installed rela-
tive to the ceiling mounting surface as
shown in Figure 3.
Sprinkler Spacing
The minimum spacing between sprin-
klers is 8 feet (2,4 m). The maximum
spacing between sprinklers cannot ex-
ceed the length of the coverage area
(Ref. Table A or B) being hydraulically
calculated (e.g., maximum 12 feet for a
12 ft. x 12 ft. coverage area, or 20 feet
for a 20 ft. x 20 ft. coverage area).
The Series LFII must not be used in
applications where the air pressure
above the ceiling is greater than that
below. Down drafts through the Sup-
port Cup could delay sprinkler opera-
tion in a fire situation.
TFP442 Page 4 of 6
WET PIPE SYSTEM
Minimum Flow and Residual Pressure °' Maximum
Coverage Maximum
Spacing Ordinary Temp. Rating Minimum Area
Ft. x Ft. Ft. 160°F (71°C)
__________ Deflector to installation Spacing
flow Pressure (m x m) (iii) Ceiling Type Ft.
GPM PSI (m)
(L/min) (bar)
12x12 12 13 TO Smooth (3,7 X 3,7) (3,7) (49,2) (0,48) Ceilings
7/8 to 1-1/8
14x14 14 13 7.0 inches
(4,3x4,3) (4,3) (49,2) (0,48)
Beamed
Ceilings per
NFPA 130 or Concealed
13R,
S
(2,4)
16 x 16
(4,9 x 4,9)
16
(4,9)
13
(49,2)
7.0
(0,48) or 13.
Installed in
18x18 18 17 12.0 beam
(5,5x5,5) (5,5) (64,3) (0,83) 7/8to1-1/8
inches below
bottom of 20 x 20 20 20 16.7
(6,1 x 6,1) (6,1) (75,7) (1,15) beam
For coverage area dimensions less than or between those Indicated, use the minimum required flow for the next
highest coverage area for which hydraulic design criteria are stated.
Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are
calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section.
For NFPA 13 residential applications, the greater of 0.1 gpm/tt2 over the design area of the flow in accordance with
the criteria in this table must be used.
TABLE A
WET PIPE SYSTEM
SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT-PLATE CONCEALED PENDENT SPRINKLER (TV3596)
NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA
DRY PIPE SYSTEM
Minimum Flow and Residual Pressure 01, °'
Maximum
Coverage Maximum
Spacing Ordinary Temp. Rating Minimum Area'1
Ft. x Ft. Ft 160°F (71°C) Deflector to Installation Spacing
Flow Pressure (m x m) (m) Ceiling Type Ft.
GPM PSI (m)
(L/min) (bar)
12x12 12 13 7.0 Smooth
(3,7 x 3,7) (3,7) (49,2) (0,48) Ceilings
7/8 to 1-1/8
14 x 14 14 14 8.2 inches
(4,3x4,3) (4,3) (53,0) (0,57) Beamed
Ceilings per
NFPA 130 or Concealed a
(2,4)
16 x 16
(4,9x4,9)
16
(4,9)
15
(56,8)
9.4
(0,65) 13R, or 13.
installed in
18x18 18 18 13.5 beam
(5,5x5,5) (5,5) (68,1) (0,93) 7/8to1-1/8
inches below
bottom of 20 x 20 20 21 18.4
(6,1 x 6,1) (6,1) (79,5) (1,27) beam
For coverage area dimensions less than or between those indicated, use the minimum required flow for the next
highest coverage area for which hydraulic design criteria are stated.
Requirement is based on minimum flow In GPM (2M) from each sprinkler. The associated residual pressures are
calculated using the nominal K-factor. Refer to Hydraulic Design under the Design Criteria section.
For NFPA 13 residential applications, the greater of 0.1 gpm/ft2 over the design area of the flow In accordance
with the criteria in this table must be used.
TABLES
DRY PIPE SYSTEM
RAPID RESPONSE SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT-PLATE CONCEALED PENDENT (TY3596)
NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA
Fire Protection
Products
Worldwide Contacts I www.tyco-flre.com
Series 7Y-FRB - 28,4.21 56, and 80 K-Factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The TYCO Series TY-FRB, 2.8, 4.2,
5.6, and 8.0 K-factor, Upright, Pen-
dent, and Recessed Pendent Sprin-
klers described in this data sheet are
quick response, standard coverage,
decorative 3 mm glass bulb-type spray
sprinklers designed for use in light or
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
ping malls.
The recessed version of the Series TY-
FRB Pendent Sprinkler, where applica-
ble, is intended for use in areas with a
finished ceiling. This recessed pendent
sprinkler uses one of the following:
A two-piece Style 10 (1/2 inch NPT)
or Style 40 (3/4 inch NPT) Recessed
Escutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a
A two-piece Style 20 (1/2 inch NPT)
or Style 30 (3/4 inch NPT) Recessed
Escutcheon with 1/4 inch (6,4 mm) of
recessed adjustment or up to 1/2 inch
(12,7 mm) of total adjustment from the
flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Corrosion-resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be obtained
when exposed to corrosive atmo-
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently dam-
age a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10
spheres. Although corrosion-resistant
coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently,
it is recommended that the end user
be consulted with respect to the suit-
ability of these coatings for any given
corrosive environment. The effects of
ambient temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level of the Series TY-
FRB Pendent Sprinklers is detailed
in Technical Data Sheet TFP356, and
Sprinkler Guards are detailed in Tech-
nical Data Sheet TFP780.
NOTICE
The Series TY-FRB, 2.8, 4.2, 5.6,
and 8.0 K-factor, Upright, Pendent,
and Recessed Pendent Sprinklers
described herein must be installed
and maintained in compliance with
this document and with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
OCTOBER 2013
Sprinkler
Identification
Number (SIN)
TY1131: Upright 2.81K, 1/2" NPT
1Y1231: Pendent 2.81K, 1/2" NPT
1Y2131: Upright 4.2K, 1/2- NPT
TY2231: Pendent 4.2K, 112 NPT
TY3131: Upright 5.6K, 1/2"NPT
TY3231: Pendent 5.61K, 1/2" NPT
TY4131: Upright 8.0K, 3/4" NPT
1Y4231: Pendent 8.0K, 3/4" NPT
TY4831: Upright 8.01K, 1/2" NPT
1Y4931: Pendent 8.01K, 1/2- NPT
TFPI7I
STYLE 10 or 20 -*--- 2-7/8° (73,0 mm) DEA. -..
RECESSED
ESCUTCHEON RECESSED PENDENT CROSS SECTION
TFPI7I
Page 2 of 10
3 - Sealing 5 - Compression
Assembly Screw
4-Bulb 6Deflector*
* Temperature rating -- Pipe thread connections per 1 - Frame
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button
Deflector. special request. PLATE SEATING
SURFACE
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
W/2X'
I 2-3/16"
**
mm)
T WREN
(55,6
FLATS
UPRIGHT
2 mm)
rI
1/4"
STYLE 10 or 20
RECESSED
PENDENT ESCUTCHEON
1- 2-7/8" (73,0 mm) DlA.
RECESSED PENDENT CROSS SECTION
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT ((1 131) AND PENDENT (7Y1231) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON
PLATE SEATING
SURFACE
* Temperature rating -- Pipe thread connections per
Is indicated on ISO 7-1 can be provided on
Deflector. special request.
1 - Frame 3 - Sealing 5 - Compression
2 - Button Assembly Screw
4 - Bulb 6 - Deflector*
OMINAL
(556
WN I WRENCH
FLATS
UPRIGHT PENDENT
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT ('rf2131) AND PENDENT (r?'2231) SPRINKLERS
4.2 K-FACTOR, 1/2 INCH NPT
TFPI7I
Page 6 of 10
SPRINKLER FINISH (See Note 8)
K
FACTOR TYPE TEMPERATURE BULB LIQUID
COLOR
NATURAL
BRASS I CHROME
PLATED
I SIGNAL***
WHITE
LEAD
COATED
5.6
1/2" NPT
PENDENT
TY3231)
and
UPRIGHT
(TY3131)
135°F (57°C) Orange
1, 2, 3, 4, 5, 6, 7
Blue
1, 2, 3, 5
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286°F (141°C)
RECESSED
PENDENT (TY3231)*
Figure 10
135°F (57°C) Orange
1, 2,4, 5
Blue
N/A
155°F (68°C) Red
175°F (79°C) Yellow
200°F (83°C) Green
286-F (141-C)
RECESSED
PENDENT (TY3231)**
Figure 11
135°F (57°C) Orange
1, 2, 3,4, 5
Blue
N/A
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286°F (141°C)
8.0
3/4" NPT
PENDENT
(1Y4231)
and
UPRIGHT
(TY4131)
135°F (57°C) Orange
1, 2, 3, 4, 5, 6, 7
Blue
1, 2, 5
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286-F (141-C)
RECESSED
PENDENT (1Y4231)*
Figure 12
135°F (57°C) Orange
1, 2, 5
Blue
N/A
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286°F (141°C)
RECESSED
PENDENT (TY4231)**
Figure 13
135°F (57°C) Orange
1, 2, 3, 5
Blue
N/A
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286°F (141°C)
8.0
1/2" NPT
PENDENT
(TY4931)
and
UPRIGHT
(1Y4831)
135°F (57°C) Orange
1, 2, 4,5, 6
Blue
1,2, 5
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
288°F (141°C)
NOTES: Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k104) as Quick Response Sprinklers. However, LPCB does not rate
the thermal sensitivity of recessed sprinklers.
Approved by the City of New York under MEA 354-01-E.
VCIS Approved (For details, contact Tyco Fire Suppression & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377.)
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a106) as Quick Response Sprinklers.
Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. Where Lead-Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved
as a Corrosion-Resistant Sprinklers.
* Installed with Style 10 (1/2" NP1) or Style 40(3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A. Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS FOR
5.6 AND 8.0 K-FACTOR SPRINKLERS
f)