Vertical Sidewall Conventional
Model Fl FR56 Series
Quick Response
Standard Spray
m
Upright Pendent
Horizontal Sidewall Recessed
Pendent/Fl/F2
AS 12- W 2—Qulletin 014 Rev. F
Reliable
Model Fl FR56 Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
Model Fl FR56 Recessed Sprinkler Types
Standard Pendent/F1/F2/FP
Horizontal Sidewall
Model Fl FR56 Concealed Sprinkler Types
Standard Pendent
Listing & Approvals
Underwriters Laboratories Inc. and Certified for
Canada (cULus).
Factory Mutual Approvals (FM)
Loss Prevention Council (LPCB, UK)
VdS SchadenverhUtung GmbH
UL Listing Category
Sprinklers, Automatic & Open (VNIV)
Quick Response Sprinkler
Product Description
Reliable Models F1FR56 Series Sprinklers are quick re-
sponse sprinklers which combine the durability of a stan-
dard sprinkler with the attractive low profile of a decorative
sprinkler.
The Models F1FR56 Series Recessed automatic sprin-
klers utilize a 3.0 mm frangible glass bulb. These sprin-
klers have demonstrated response times in laboratory tests
which are five to ten times faster than standard response
sprinklers. This quick response enables the Model F1 FR56
Series sprinklers to apply water to a fire much faster than
standard sprinklers of the same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely manu-
factured glass capsule. This glass bulb is specially con-
structed to provide fast thermal response.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid
expands, forcing the bubble smaller and smaller as the liq-
uid pressure increases. Continued heating forces the liquid
to push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
Hecesseci
Horizontal Sidewall
Application
Quick response sprinklers are used in fixed fire protec-
tion systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflec-
tor style and sprinkler type are in accordance with the lat-
est published standards of the National Fire Protection As-
sociation or the approving Authority Having Jurisdiction.
Quick response sprinklers are intended for installation as
specified in NFPA 13. Quick response sprinklers and stan-
dard response sprinklers should not be intermixed.
E33
Recessed
Pendent/FP
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
s— 2 5/8" 0/A. [66.7mm] HOLE IN CEILING
2 5/76" 014. [58.7mm] -
CUP
C
" X 7/2" REDUCER
I I I I
I /
CEILING
FACE OF PITYiNG
TO FACE OF CEILING
DIMENSION(f)
ADJUSTMENT'
O?4F002
(I) REFER TO F? ESCUTCHEON DATA TABLE FOR APPROVALS AND DIMENSIONS,
2 27/32" 014. 0I4FGOI
(72.2mm]
(I) REFER TO TI & F2 ESCUTCHEON DATA TABLE FOR APPROVALS AND DIMENSIONS.
2 1/4" HOLE 014
(57.2mm] '
7 75/76" 074
[ [49.2mm]
L---s-.c
E 1
TURN COLLAR LINIIL PONT AGAINST SPRINKLER
WRENCH BOSS--
ADJUSTMENT flWWB
1" 5 7/2" REDUCER
FACE OF FITTING TO
CEILING DIMENSION
I/B" _j [3.2-j
Model F1FR56 Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model 0 Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread Nominal K Factor
Size US Metric
Sprinkler
Height
Approval
Organization
Sprinkler Identification Number
(SIN)
Upright Pendent
Standard-Upright (SSU) and pendent Deflectors Marked to Indicate Position
1//'15mm ½" NPT(R1/s) 5.6 T 80 1 2.25" (57mm) 1,2,3,4 RA 1425(1I 1 RAi4142
Conventional-Install in Upright or Pendent Position
15mm 1 ½" NPT(R½) 5.6 80 57mm 3,4 RA1475
cULus listed corrosion resistant (Polyester coated) sprinkler.
Polyester coated FM approved sprinkler.
S.'
Upright
Pendent Conventional
Model Fl FR56 Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model GFR2 Sprinkler Wrench
Installation Data:
Nominal Thread K Factor J Sprinkler Sprinkler Identification Number
Orifice
------------
Size US Metric j Height (SIN)
½" (15mm) ½" NPT(R½) 5.6 80 2.25" (57mm) RA1414
Refer to escutcheon data table for approvals and dimensions.
Model F1FR56/F1 or F2 Model F1FR56/FP
2.
Horizontal Sidewall
Model Fl FR56 Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
Nominal Nominal K Factor Sprinkler Approval Sprinkler
US
I
Metric Orifice Thread Size Height Organizations Identification
Numbers (SIN)
1/2"(15mm) ½" NPT(R1/2) 5.6 8.0 2.25(57mm) 123,4
RA1485 15mm ½" NFT (R1/2) 5.6 8.0 2.25" (57mm) 40
LPC Approval is for pendent position only.
Sprinkler Type Deflector to Ceiling Distance
(Min. - Max.)
Upright 4" (102mm) - 12" (305mm)
Pendent 4" (102mm) - 12' (305mm)
Vertical Sidewall
Model Fl FR56 Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW
Installation Wrench: Model D Sprinkler Wrench
Installation Data: Horizontal Sidewall
Nominal K Factor Sprinkler Approval Organizations
_________________
Sprinkler
Nominal Orifice Thread Size Height and Type of Approval Identification Ordinary Numbers (SIN) US Metric Light Hazard Hazard
½"(lSmm) 1 ½" NFl (R1/2) 5.6 80 2.63" (67mm) 1,2 1 RA1435
(i) FACE OF FITTING
DIMENSION 1 1/4" /1/N.
[31.8mm] 2 1/4" HOLE 0/A. /8" 4-12"
TO FACE OFCEILING
[5 7.2mm] .2mm] [1016mm3048mm]
CEILING TO
1"X 1/2" REDUCER
-
DEFLECTOR
227/I2"D/A.
1 15/6"DIA.il
[49.2m
[72.2mm
TURN COLR
TIGHT AGAINST SPRINKLER
WRENCH BOSS.
(1) A DJUSTMENT o IJFGO3A
REFER TO ESCUTCHEON DATA TABLE FOR APPROVALS AND DIMENSIONS.
FM APPROVED FOR 4" - 6" [ID 1.6MM - 152.4MM] CEILING TO DEFLECTOR.
Note: For Recessed HSW Sprinklers use installation wrench GFR2.
3.
Model Fl FR56 Quick Response Concealed Pendent Sprinklers
Installation Wrench: Model AOl Sprinkler Wrench
Technical Data:
Nominal "K" Factor Thread Temp. Rating Max. Bulb Sprinkler
Sprinkler Cover • Orifice US Metric • Size Model Ambient Color Approvals Identification
Temp Number(SIN)
½" (15mm) 5.6 80 ½" NPT F1FR 135°F/57°C 135°F157°C 100°F/38°C Orange 1,2 RA1414
½" (15mm) i 5.6 80 ½" NPT F1FR 155°F168°C 135°F/57°C 100°F/38°C Red 1, 2,40) RA1414
½' (15mm) 5.6 80 ½' NPT F1FR 175°F/79°C 165°F/74°C 100°F/38°C Yellow 1,2 RA1414
1/2" (15mm) 5.6 80 ½" NPT F1FR 200°F/93°C 165°F/741C 100°F/380C Green 1,2 RA1414'
For VdS only = 155"F/68°C Norbuib and 1/2" [12,7mm] adjustment.
1" x 7/2" REDUCING
TEE OR ELBOW
2 5/8" 0/A,
2 5/16 0/A - -' -I HOLE IN CEILING
CUP
03666 1 1/2" MAX.
FACE OF FITTING
TO FACE OF CEILING
/ 'SD T; T7'>7'7 DIMENSION
CEILING —" - ,
112 " MAX.
COVER ADJUSTMENT
H"
15/16
COVER PLATE
ASSEMBLY 3 5/16 0/A.
SPRINKLER
1/2" ADJUSTMENT o,,;co,
Figure 1
1" x 1/2" REDUCING TEE OR ELBOW
2 5/16" 0/A -
CUP --.,.
CEILING
5/16" MAX
COVER ADJUSTMENT
COVER PLATE— ASSEMBLY
SPRINKLER
r'-t 2 5/8" 0/A.
-I HOLE IN CEILING
1 1/2" MAX.
FACE OF FITTING
TO FACE OF CEILING
DIMENSION
3/4"
— 3 5/16" 0/A.
5/16" ADJUSTMENT 017-2
Figure 2
Installation Aid
A protective cap is included for use during installation,
Important: The F1FR56 Sprinkler with Model COP cover
plate is not an FM Approved combination.
Installation
Quick response sprinklers are intended for installation
as specified in NFPA 13. Quick response sprinklers and
standard response sprinklers should not be intermixed,
The Model F1FR56 Recessed Quick Response Sprin-
klers are to be installed as shown. The Model Fl or F2 Es-
cutcheons illustrated are the only recessed escutcheons
to be used with the Model F1FR56 Sprinklers. The use
of any other recessed escutcheon will void all approvals
and negate all warranties.
When installing Model Fl FR56 Sprinklers, use the Mod-
el D Sprinkler Wrench. Use the Model GFR2 Wrench for
installing F1FR56 Recessed Pendent Sprinklers. Any
other type of wrench may damage these sprinklers.
NOTE: A leak tight ½" NPT (R1I2) sprinkler joint can
be obtained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m).
Do not tighten sprinklers over maximum recommended
torque. It may cause leakage or impairment of the sprin-
klers.
The Model F1FR56/ COP Concealed Sprinkler uses the
½" orifice, ½" NPT (R1/2), 135°F (57°C), 155°F (68°C),
175°F (79°C) or 200°F (93°C) Model F1FR56 Pendent
*DuPont Registered Trade Mark
Sprinkler with a threaded Model COP cup which is fac-
tory attached to the sprinkler. The assembly is complet-
ed by the installation of the attractive, low profile, 135°F
(57°C) or 165°F (74°C) rated Model COP push on cover
plate assembly. The cover plate and sprinkler cup as-
semblies are joined using a cover plate skirt with flexible
tabs for threaded engagement. A choice of two cover
plate assemblies provide either ½" (13mm) or /i€" (8mm)
of cover adjustment.
Do not install these sprinklers in ceiling which have
positive pressure in the space above.
After a 2 /8" (67mm) diameter hole is cut in the ceil-
ing, the sprinkler is easily installed with the Model RO1
Wrench. A Teflon* based thread sealant should be
applied to the sprinkler threads only. The Model AOl
Wrench is then used to engage the sprinkler wrenching
surfaces and to install the sprinkler in the fitting. When
inserting or removing the wrench from the sprinkler/cup
assembly, care should be taken to prevent damage to
the sprinkler. DO NOT WRENCH ON ANY OTHER PART
OF THE SPRINKLER, The cover plate is then pushed
onto the cup. Final adjustment is made by hand turning
the cover plate until the skirt flange makes full contact
with the ceiling. Cover plate removal requires turning in
the counter clockwise direction.
After installation, inspect all sprinklers to ensure that
there is a gap between the cover plate and ceiling and
that the four cup slots are open and free from any air flow
impediment to the space above.
Concealed cover plate/cup assemblies are listed only
for use with specific sprinklers. The use of any other con-
cealed cover plate/cup assembly with the Model Fl FR56
Pendent Sprinkler or the use of the Model CCP Concealed
cover plate assembly on any sprinkler with which it is not
specifically listed my prevent good fire protection and will
void all guarantees, warranties, listings and approvals.
Glass bulb sprinklers have orange bulb protectors to
minimize bulb damage during shipping, handling and
installation. REMOVE THIS PROTECTION AT THE TIME
THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR
FIRE PROTECTION. Removal of the protectors before this
time may leave the bulb vulnerable to damage. RASCO
wrenches are designed to install sprinklers when covers
are in place. REMOVE PROTECTORS BY UNDOING THE
CLASP BY HAND. DO NOT USE TOOLS TO REMOVE
THE PROTECTORS.
Temperature Ratings
Classification
Sprinkler
Temperature Max. Ambient
Temp. Bulb Color
0 OF
Ordinary 57 135 100°F (38°C) Orange
Ordinary 68 155 100°F (38°C) Red
Intermediate 79 175 150°F (66°C) Yellow
Intermediate 93 200 150°F (66°C) Green
High 141 286 225°F (107°C) Blue
Not available for recessed sprinklers.
Escutcheon Data (1)
Escutcheon "A" FaceofFrthngto
Model Approvals Adjustment Dimension Ceiling or Wall
Dimension
Fl 1,3,4 Max Recess 11/2" (38 lrrni) 3/16" -
Min Recess 3/4 (19.1mm) (5mm - 24rrn)
F2 1,2,3,4 Max Recess 1 'W(38, lrrrn)
________ Min Recess 1" (25rrrn) I (5rm -l7nm)
FP Push-on/ 1,4 Max Recessed 7/s" (llnTn) 1 1Y2" (38.lrrni)
Thread-off Mm Recessed 15/ (24n'rn) 1" (25.4mm)
1) SIN: RA1435 - cULus and FM permits use with Fl or F2 escutcheons for light
hazard only.
Maintenance
The Models FlFR56 and F1FR56 Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or
gentle vacuuming. Remove any sprinkler which has
been painted (other than factory applied) or damaged
in any way. A stock of spare sprinklers should be main-
tained to allow quick replacement of damaged or oper-
ated sprinklers. Prior to installation, sprinklers should be
maintained in the original cartons and packaging to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non-operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Recessed Pendent
Vertical Sidewall
Horizontal Sidewall
Recessed Horizontal sidewall
Concealed pendent
Maximum Working Pressure
175 psi (12 bar)
100% Factory tested hydrostatically to 500 psi (34.5 bar)
Finishes (1)
Standard Finishes
Sprinkler Escutcheon I Cover plate
Bronze Brass
Chrome Plated Chrome Chrome
White Polyester Plated White
Coated (4,5) White Painted
Speci I Application Finishes
Sprinkler Escutcheon Cover plate
Bright Brass (3) Bright Brass Bright Brass
Black Plated Black Plated Satin
Black Paint (2) Black Paint Off White
Off White (2) Off White Black Paint
Satin Chrome Satin Chrome Black Plated
Other finishes and colors are available on special order.
Consult the factory for details.
(2) cULus Listed only.
200°F (93°C) maximum.
(4) cULus listed "corrosion resistance" applies to SIN Numbers
RA1425 (Upright) and RA1414 (Pendent) in standard black or white.
(il) FM Approvals finish as "Polyester coated" applies to SIN Number
RA 1414 (Pendent) in standard black or white.
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
Orifice Size
Deflector Type
Temperature Rating
Sprinkler Finish
Escutcheon Type
Escutcheon Finish (where applicable)
Cover plate Model
Cover plate Thread size
Cover plate Temperature
Cover plate Adjustment
Cover plate Finish
Note: When Model F1FR56 Recessed sprinklers are ordered, the sprin-
klers and escutcheons are packaged separately.
5.
1111111111ft ReliableFor Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
Automatic sprinklers
Flush automatic sprinklers
Recessed automatic sprinklers
Concealed automatic sprinklers
Adjustable automatic sprinklers
Dry automatic sprinklers
Intermediate level sprinklers
Open sprinklers
Spray nozzles
Alarm valves
Retarding chambers
Dry pipe valves
Accelerators for dry pipe valves
Mechanical sprinkler alarms
Electrical sprinkler alarm switches
Water flow detectors
Deluge valves
Detector check valves
Check valves
Electrical system
Sprinkler emergency cabinets
Sprinkler wrenches
Sprinkler escutcheons and guards
Inspectors test connections
Sight drains
Ball drips and drum drips
Control valve seals
Air maintenance devices
Air compressors
Pressure gaugesldentification signs
Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
Reliable The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
- ®
Recycled
Paper
Revision lines indicate updated or new data.