HomeMy WebLinkAbout6191 EL CAMINO REAL; ; FA1500597/10/24, 2:50 PM FA150059 Permit Data
City of Carlsbad
Fire Alarm Permit
6191 ELCAMINO
Job Address:
REAL
Permit Type: FALARM
Parcel No: 2131002300
Lot #: 0
Permit No: FA150059
Status: ISSUED
Applied 9/8/2015
Approved: 9/9/2015
Reference No.: Issued: 9/9/2015
PC #: Inspector:
Project Title: VIA SAT BLDG 4 REMOVE AND RELOCATED EXISTING
DEVICES CONSISTING OF THE EQUIPMENT SHOWN IN THE
DEVICE LEGEND, TO ACCOMMODATE NEW TI.
Applicant:
JJJ ENTERPRISES
533 5 VINEWOOD ST
ESCONDIDO CA
760-747-3050
Owner:
LEVINE INVESTMENTS LIMITED
PARTNERSHIP
1702 E HIGHLAND AVE #310
PHOENIX AZ
Fees ($) Add'I Fees ($) Total ($) Balance ($)
290 0 290 0
about:blank 1/1
FIRE ALARM - SECURITY - LOW VOLTAGE SYSTEMS
ViaSat Bldg 4
Tenant Improvement
6191 El Camino Real
Carlsbad, CA 92011
FIRE ALARM SYSTEM
MATERIAL DATA SHEETS
FAIS0059
FIRE ALARM SYSTEM BILL OF MATERIALS
WHEELOCK RSS-24MCC MULTICAIWELA CEILING STROBES
CSFM# 7125-0785:0141
WHEELOCK AS-24MCC MULTICAIWELA CEILING HORN /STROBES
CSFM# 7125-0785:0131
Series RSS and RSSP Strobes and Strobe Plates
Series RSS Series RSS Series RSSWP
t. Description
The Wheelock patented Series RSS Strobe Appliances and
Series RSSP Strobe Plates have lower current draw while
maintaining outstanding performance, reliability and cost
effectiveness. These versatile appliances will satisfy virtually all
requirements for indoor, wall or ceiling mount applications.
Strobe options for wall mount models include 1575 or the
Wheelock Patented MCW multi-candela strobe with field
selectable candela settings of 15/30/75/110cd or the high
intensity MCWH strobe with field selectable 135/185cd.
Ceiling mount models include the patented MCC multi-candela
ceiling strobe with field selectable intensities of 1 5/30/75/95cd
or the high intensity MCCH strobe with field selectable
115/177cd.
All models may be synchronized using the Wheelock DSM Sync
Modules, Wheelock Power Supplies or other manufacturers
panels incorporating the Wheelock Patented Sync Protocol.
Synchronized strobes can eliminate possible restrictions
on the number of strobes in the field of view. Wheelock's
synchronized strobes offer an easy way to comply with ADA
recommendations concerning photosensitive epilepsy as well
as meeting the requirements of NFPA 72.
The Wheelock Series RSS Strobes employ a Patented Integral
Strobe Mounting Plate that can be mounted to a single gang,
double gang, 4" square, 1 00m European backboxes or the
SHBB surface backbox. If the flush backbox has side or top
space between it and the finished wall, the NATP (Notification
Appliance Trimplate) may be used. It provides an additional .65"
of trim for the Appliance. An attractive cover plate is provided
for a clean, finished appearance on all models.
The Series RSSP Multi-Candela Strobe Plates are a cost
effective way to retrofit required wall strobe appliances to
bells, horns, chimes, multitones or speakers and easily mounts
to standard 4" backboxes or for surface mount use with the
Wheelock SBL2 surface backbox.
D OU L M EA APPROVED
S5391 151-92-E 7125-0785:141
Features
Approvals include: UL Standard 1971, New York City (MEA),
California State Fire Marshal (CSFM), Factory Mutual (FM), and
Chicago (BFP) See approvals by model in Specifications and
Ordering Information
ADNNFPNUFC/ANSI compliant. Meets OSHA 29 Part
1910.165
Wall mount Multi-Candela models are available with Field
Selectable Candela Settings of 15/30/ 75/110cd or 135/185cd.
Single Candela models are available in 1575cd
Ceiling mount Multi-Candela models are available with field
selectable candela settings of 15/30/75/95cd or 115/177cd.
(Square)
Strobes produce 1 flash per second over the regulated voltage
range
12 and 24 VDC models with wide UL "Regulated Voltage" us-
ing filtered (DC) or unfiltered VRMS input voltage
Synchronize using the Wheelock sync modules or panels with
built-in Wheelock Patented Sync Protocol
Fast installation with IN/OUT screw terminals using #12 to #18
AWG wire
For Weatherproof Series RSS See Datatsheet S9004
SERIES RSSIRSSP APPLIANCES SYNCHRONIZED
WITH MULTIPLE DSM MODULES
DSM #1
Sync Strobe NAC Cir.Z:, RSSRSS F
r DSM #2
A sYflC ; Strobe NAC Cir.I C DSM #3
P RSS nRS S' Strobe NAC Cir. I
DSM Interconnecting wiring shown. Maximum of
twenty (20)
NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters.
A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR
APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS.
FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU
AND/OR OTHERS.
General Notes:
Strobes are designed to flash at 1 flash per second minimum over their Regulated Voltage Range. Note that NFPA-72 specifies a flash rate of I
to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.
All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.
'Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the
terminology "Listed Voltage Range".
Table 1: Average RMS Current*
RSS/RSSP - Wall Mount I Ceiling Mount
RSS/RSSP 241575W 24MCW 24MCWH 24MCC I 24MCCH
24VDC ___________
I I
Models I I I I I
I I
I
1575cd l5cd 30cd 75Cd ll0cd I 135cd l85Cd I l5cd 30Cd 75cd 95cd I 115Cd I 177cd
UL max* 0.090 0.060 10.092 10.165 10.220 10.300 10.420 10.065 10.105 10.189 10.2491 0.300 I 0.420
RSS/RSSP
RSS/RSSP Wall Mount 4VDC * RMS current ratings are per UL average RMS method. UL max Current Models 121575W rating is the maximum RMS current within the listed voltage range (16-33v
for 24v units). For strobes the UL max current is usually at the minimum
12 vdc 0.152 listed voltage (16v for 24v units). For audibles the max current is usually at
UL max 0.255 the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, * see installation instructions.
Table 2: AudibleslSpeakers for RSSP Strobe Plate
Product Series
Multitone Appliances AMT, MT
Horns AH, NH, HS
Motor Bells MB-G6/G10
Speakers ET-1010/1080, E70, ET70
Chimes CH70
Wiring Diagrams
SERIES RSS/RSSP APPLIANCE
FROM +___ _______ TO NEXT
PRECEDING - APPLIANCE
APPLIANCE, SYNC OR EOLR MODULE, POWER
SUPPLY OR FACP
+ H
SERIES RSS/RSSP APPLIANCES SYNCHRONIZED
WITH DSM MODULE SINGLE CLASS "A" NAC CIRCUIT
DSM STROBE
NAC + SYNC CIRCUIT
—OUT--F-
=RSS
RSS
SS
ROBEL
NAC
CIRCUIT
RETURN
STROBE/PLATE ASSEMBLY
AUDIBLE & VISIBLE APPLIANCE OPERATE IN UNISON
TO NEXT
FROM _____ _______ ______
+ APPLIANCE
PRECEDING II II - OR EOLR
APPLIANCE, SYNC
MODULE, POWER
SUPPLY OR FACP +
- + -
STROBE AUDIBLE
STROBE/PLATE ASSEMBLY
AUDIBLE & VISIBLE APPLIANCE OPERATE INDEPENDENTLY
FROM + + TO NEXT PRECEDING APPLIANCE APPLIANCE OR - __________________ __________ - OR EOLR FACP
FROM - 1 1 - - + TO NEXT
PRECEDING STROBE OR
STROBE. SYNC — - - •1I 1 1 - - EOLR - —
MODULE, POWER
SUPPLY OR FACP
STROBE APPLIANCE
SERIES RSS/RSSP APPLIANCES SYNCHRONIZED
WITH WHEELOCK POWER SUPPLIES
Series PS Power Supplies
rHS
nRS S j OUTPUTS ire EOLR
4
- 4-CLASS
A OR RSS
C 2-CLASS
P
HS r•;_ I IRSS
PS Power
11 For detail using DSM Sync Module refer to Data Sheet
S3000 or Installation Instructions P83177 for DSM. For
wiring information on the power supplies refer to Wheelock
Power Supplies.
Specifications and Ordering Information
Model Order
Code
Wall
Mount
Ceiling
Mount
Non-
Sync
Strobe
Candela
24
VDC
12
VDC
Color
RED
Color
WHITE Mounting
Square
or
Round
Agency Approvals
-
UL MEA CSFM FM BFP
RSS-24MCW-FR 940 X - X 15/30/75/110 X - X - B,DE,F,G,HJN,OR,X Square X X X X X
RSS-24MCW-FW 9401 X I - X 15/30/75/110 X - - X B,DE,FG,H,J,N,O,R,X Square X X X X X
RSS24MCWAR**** 9773 X - X 15/30/75/110 X - - X BDE,FG,HJN,O,R,X Square X X X X X
RSS-241575W-FR 7471 X - X 15(75onAxis) X - X - B,DE,F,G,HJ,NOR,X Square X X X X X
RSS-241575W-FW 7788 X - X 15(75onAxis) X - - X BD,E,FG,H,J,NO,R,X Square X X X X X
RSS-121575W-FR 7476 X - X 15(75onAxis) - X X - B,D,E,F,G,F-IJ,N,O,R,X Square X X X X X
RSS-121575W-FW 7468 X - X 15(75onAxis) - X - X B,DEF,G,HJ,NOR,X Square X X X X X
RSS-24MCC-FW 3158 - X X 15/30/75/95 X - - X BD,EFG,H,J,NOR,X Square X X X X -
RSS-24MCC-FR 3157 - X X 15/30/75/95 X - X - B,D,EFGH,J,N,O,R,X Square X X X X -
RSS-24MCCH-FW 3461 - X X 115/177 X - - X BD,E,F,G,I-IJN,O,R,X Square X X X X -
RSS-24MCWH-FR 3465 X X 135/185 X X BD,E,FQH,J,N,OR,X Square X X X X -
RSS-24MCWH-FW 3464 X X 1 135/185 X X B,DE,F,G,HJN,O,R,X Square X X X X -
RSSWP2475WFR** 9013 X - X 180@ 77-F X - X - BD,EFGH,J,N,OR,X Square X X X X -
RSSWP2475WFW** 3034 X - X 180@ 77-F X - - X B,DE,F,G,HJ,N,O,R,X Square X X X X -
RSSP-121575W-FR 7798 X - X 115(75onAxis) - X X - DE,Z Square X - X X X
RSSP-24MCW-FR 9402 X - X 15/30/75/110 X - X - D,E,Z Square X X X X X
RSSP-241575W-FR 7793 X - X 15 (75 on Axis)j - - X - D,E,Z Square X X I X X X
RSSP-24MCWH-FR 9482 X X 135/185 X X BD,E,F,GH,J,N,O,R,X Square X X I X - -
All models sync with Wheelock DSM or Wheelock Power Supplies.
# Models are available in either Red or White. Call Customer Service for Order Code & Delivery.
**For Weatherproof Series RSS Strobe specifications see data sheet S9004.
***Refer to data sheet S7000 for mounting options.
- **** "A stands for Agent Lettering.
S0410 RSS/RSSP 07/11
Cooper Notification is Wheelock* (MEDC) SAFEPATH WAV
Architects and Engineers Specifications
The visual notification appliances shall be Wheelock Series RSS Strobe Appliances or approved equals. The Series RSS shall meet
and be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired) for Indoor Fire Protection Service. The strobe shall
be listed for indoor use and shall meet the requirements of FCC Part 15 Class B. The strobe appliances shall produce a flash rate of
one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens.
All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP). When
Strobe Plates are to be installed, they shall be the Wheelock Series RSSP Strobe Plate and shall have the same electronic circuitry
as the Wheelock Series RSS.
The Series RSS Strobe shall be of low current design. Where Multi-Candela appliances are specified, the strobe intensity shall have
field selectable settings and shall be rated per UL Standard 1971 at 15130175/110cd or 135/185cd for wall mount and 15/30/75/95cd or
115/177cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 1575 candela strobe shall be
specified when 15 candela UL Standard 1971 Listing with 75 candela on axis is required (e.g. ADA compliance).
When synchronization is required, the appliance shall be compatible with Wheelock's DSM Sync Modules, Wheelock Power Supplies
or other manufacturers panels with built-in Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any
time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a
non-synchronized flash rate. The strobes shall be designed for indoor surface of flush mounting.
The Series RSS Strobe Appliances shall incorporate a Patented, Integral Strobe Mounting Plate that shall allow mounting to single-
gang, double-gang, 4-inch square, 1 00m European type backboxes, or the SHBB Surface Backbox. If required, an NATP (Notification
Appliance Trimplate) shall be provided. An attaching cover plate shall be provided to give the Appliance and attractive appearance. The
Appliance shall not have any mounting holes or screw heads visible when the installation is completed.
The Series RSSP Multi-Candela or single candela Strobe Plate shall mount to either a standard 4 inch square backbox for flush mounting,
or the Wheelock SBL2 backbox for surface mounting.
All notification appliances shall be backward compatible.
NOTE; Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock, Inc. standard terms and conditions.
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7125-0785:0141 Page 1 of 2
CATEGORY: 7125 -- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: Cooper Wheelock lnc.7246 16th St. E., Ste. 105, Sarasota, FL 34243
Contact: Tom Conover (941) 487-2336
Email: thomas.conover@cooperindustries.com
DESIGN: Synchronized or non-synchronized Strobe Lights. Models are as follows:
RSS-##W RSSP-W RSS-##C RSSP-##C RSS-#CR RSSP-##CR
2415 2415 2415 2415 2415 2415
2475 2475 2430 2430 2430 2430
241575 241575 2475 2475 2475 2475
2430 2430 *2495 *2495 *2495 *2495
24110 24110
1215 1215
121575 121575
Also, Models RSS-24MCW and RSSP-24MCW, RSS-24MCC, RSS-24MCCR,
• RSSP-24MCC, RSS-24MCWH, RSS-24MCWHR, RSSP-24MCWH, RSS-24MCCH,
RSS-24MCCHR, RSSP-24MCCH, *ZRS..MCC *ZRSMCW *ZRSMCCH and *ZRSMC\
Model numbers may be followed by any two alpha/numeric character indicating lens
orientation, lettering and color. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING: Electrical 12 = 8-17.5VDC/FWR OR 24 16-33VDC/FWR
Candela 155cd,157515/75cd on axis, 30=30cd,7575cd, 110=110cd(WaIl)
RSS-24MCW, RSSP24MCW,*ZRSMCW: Selectable 15cd,30cd ,75cd
orll0cd
RSS-24MCC, RSS24MCCR,RSSP24M CC, *ZRSM CC: Selectable
15cd,30cd,75cd and 95cd
RSS24MCWH,RSS24MCWHR,RSSP24MCWH,*ZRSMCWH:Selectable
135cd, 1 85c
RSS24MCCH,RSS24MCCHR,RSSP24MCCH,*ZRSMCCH:Selectable
115cd,177cd
Flash rate 60 flashes/minute
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction. Models with suffix -W, wall
mount only. Models with suffix -C, ceiling mount only. All models are for indoor use only.
MARKING: Listee's name, model number, electrical/candela rating, and UL label.
APPROVAL: Listed as strobe light suitable for the hearing impaired when used with separately listed
electrically compatible fire alarm control units. For synchronization strobes, Models
*Rev. 12-13-2006 jw
r' This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2015 Listing Expires June 30, 2016
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
Listing No. 7125-0785:0141
Page 2 of 2
SM-12/24, SMX-12/24, DSM-12/24 or DSMX-12/24 Sync Control Module (CSFM Listing No.
7300-0785:132) must be used. Refer to listee's Installation Instruction Manual for details.
Rev. 12-13-2006 jw
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to Iistee's data sheet, installation instructions and/or other
Date Issued: July 01, 2015 Listing Expires June 30, 2016
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
Series AS Audible Strobe Appliances and Series AH Audibles
U']
SERIES AS SERIES AH
Description
The Wheelock patented 2-wire Series AS Audible Strobe
Appliances and Series AH Audibles offer more features with
low current draw.
Strobe options for wall mount models include 1575cd or the
Wheelock patented MCW multi-candela wall strobes with field
selectable candela settings of 15/30/75/110cd, or the high
intensity MCWH strobe with field selectable 135/185cd.
Ceiling mount models incorporate Wheelock's patented MCC
multi-candela ceiling strobe with field selectable intensities of
15/30175/95cd or the high intensity MCCH strobe with field
selectable 115/177cd.
The audible provides a selectable choice of either a
continuous horn or temporal pattern (Code 3) when
constant voltage from a Fire Alarm Panel (FACP) is
applied. Each tone has 3 dBA settings to choose from.
When used with the Wheelock Series DSM Sync Modules,
Wheelock Power Supplies or other manufacturers panels
incorporating the Wheelock Patented Sync Protocol,
synchronization of the continuous horn tone provides the
temporal (code 3) tone (mandated by NFPA72) simultaneously
for all audible appliances. This ensures a distinct temporal
(code 3) pattern when 2 or more audibles are within hearing
distance. If not synchronized the temporal sound could overlap
and not be distinctive. At the same time the strobes will be
synchronized. This provides the ability to comply with ADA
guidelines concerning photosensitive epilepsy and the NFPA
standards when installing 2 or more visual appliances within
the field of view all of this plus the ability to silence the audible
is achieved by using only 2 wire.
Features
Approvals include: UL Standard 1971, UL Standard 464
New York City (MEA), California State Fire Marshal (CSFM),
Factory Mutual (FM), and Chicago (BFP). See approvals by
model in Specifications and Ordering Information
ADA/NFPA/UFC/ANSI Compliant
Wall mount models are available with Field Selectable
Candela Settings of 15/30/75/110cd or 135/185cd (Multi-
Candela models) or 1575cd (single candela model)
Ceiling mount models are available with field selectable
candela settings of 15/30/75/95cd or 11 5/1 77cd (multi-candela
ceiling models)
Selectable Continuous Horn or Temporal (Code 3).
3 Selectable dBA settings (99, 95 and 90 dBA) in both tones
Patented 2-Wire Audible Strobe Appliance.
Patented Universal Mounting Plate
Weatherproof models are available for outdoor use
Strobes produce I flash per second over the regulated
voltage range
12 and 24 VDC models with wide UL "Regulated Voltage
Range" using filtered DC or unfiltered FWR input voltage
Synchronize using the Wheelock Sync Modules or panels with
built-in Wheelock Patented Sync Protocol
Fast installation with IN/OUT screw terminals using
#12 to #18 AWG wires
For Weatherproof Series AS, See Datasheet 590Q4
® MEA X <~@>
APPROVED
E5946 151-92-E 7125-0785;131
S5391
24 VDC Models
Audible
AH-24 AS-241575W
1575cd
High (99)
dBA
24 vdc 0.062 0.100
UL max* 0.080 0.121
Med (95)
dBA
24 vdc 0.033 0.080
UL max* 0.043 0.107
Low (90)
dBA
24 vdc 0.017 0.072
UL max* 0.021 0.100
12 VDC Models
Audible
Wall Mount
Audible
Strobe
AH-12 I AS-121575W
High (99)
12 vdc 0.163 0.260
UL max- 0.192 0.320 dBA
Med (95)
12 vdc 0.076 0.195
UL max* 0.108 0.275 dBA
Low (90) 12 vdc 0.039 0.175
UL max* 0.058 0.265 dBA
NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters.
A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING SPECIFYING OR
APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS.
.FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU
AND/OR OTHERS.
General Notes:
Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range". Note that NFPA-72 specifies a flash rate of 1
to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.
All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.
"Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the
terminology 'Listed Voltage Range".
Table 2: dBA Ratings for 12 VDC and 24 VDC Series AS/
AH 12 and 24 VDC Audible
Reverberant Anechoic
Description Volume dBA
Per UL 464 dBA
@10 ft.
@10 ft.
High 91 99
Continuous Medium 88 95 Horn
Low 83 90
High 87 99
Medium 84 95 Code 3 Horn
Low 79 90
Table 1: Ratings Per UL 1971
Model
Number
Input
Voltage
VDC
Regulated
Voltage Range
VDC/FWR
Strobe
Candela (Cd)
AS-24MCW 24 16.0 -33.0 15/30/75/110
AS-24MCCH 24 16.0-33.0 115/177
AS-241575W 24 16.0-33.0 15(75onAxis)
AS-121575W 12 8.0 -17.5 15 (75 On Axis)
AS-24MCC 24 16.0 -33.0 15/30175/95
AS-24MCWH 24 16.0 -33.0 135/185
ASWP-2475W 24 16.0-33.0 75 @ -31°F
Table 3: Average RMS Current
ill Mount Audible Strobe Models Ceiling Mount Audible Strobe Models
AS-24MCW AS-24MCWH AS-24MCC AS-24MCCH
1 5c 30cd 75cd hOed 135cd 185cd 15cd 30cd 75cd 95cd hlscd 177cd
0.080 0.102 0.150 0.194 0.250 0.320 0.088 0.114 0.165 0.205 0.250 0.320
0.088 0.125 0.200 0.267 0.355 0.480 0.095 0.138 0.221 0.285 0.355 0.480
0.060 0.084 0.132 0.173 0.230 0.305 0.066 0.092 0.145 0.186 0.230 0.305
0.074 0.110 0.190 0.253 0.340 0.465 0.080 0.122 0.201 0.269 0.340 0.465
0.052 0.076 0.121 0.158 0.220 0.295 0.056 0.082 0.132 0.173 0.220 0.295
0.068 0.105 0.182 0.245 0.335 0.460 0.074 0.113 0.198 0.263 0.335 0.460
Table 4: Average Current* (AMPS) For Series ASWP#
Voltage
High dBA
Setting
(99) dBA
Medium dBA
Setting
(95) dBA
Low dBA
Setting
(90) dBA
24.0 VDC 0.128 0.105 0.098
UL Max* 0.168 0.155 0.150
* RMS current ratings are per UL average RMS method. UL max current
rating is the maximum RMS current within the listed voltage range (16-33v
for 24v units). For strobes the UL max current is usually at the minimum
listed voltage (16v for 24v units). For audibles the max current is usually
at the maximum listed voltage (33v for 24v units). For unfiltered FWR
ratings, see installation instructions.
SERIES AS APPLIANCES SYNCHRONIZED WITH MULTIPLE DSM
MODULES
. DSM #1
Strobe NAC Cir. JAS I
F Hø+_ rH0
Audible NAC Cir DSM #2
I Strobe NAC Cir.
12)
5Ycø AS AS
DKN C +
Audible NAC Cir I DSM #3
F []Sync st Strobe NAC Or
Interconnecting wiring shown. Maximum of DSM
twenty (20)
For detail using DSM Sync Module refer to Data Sheet
S3000 or Installation Instructions P83177 for DSM. For
wiring informationon the power supplies refer to Installation
Instructions P84905 for Wheelock Power Supplies.
Wiring Diagrams
SERIES AS APPLIANCES NON-SYNCHRONIZED
FROM TO NEXT
APPLIANCE - OR EOLR
OR FACP
PRECEDING APPLIANCE
Snecifications and Orderina Information
-
Number Model N b Order
Code
Strobe
Candela
Non-
Sync
Sync DSM
or Wheelock
Power
Supplies
24
VDC
12
VDC
Wall
Mount
Ceiling
Mount MountingOptions***
Agency Approvals
-
UL MEA CSFM
-
FM
-
BFP
AS-24MCW-FR 9024 15/30/75/110 X X X - X - A,B,D,E,FG,H,J,NOR,X X X I X X X
AS-24MCW-FW 9025 15/30/75/110 X X X - X - A,B,D,E,F,G,HJ,N,O,R,X X X X X X
AS-24MCWH-FR 3468 135/185 X X X - X - A,B,DE,F,GH,JN,O,R,X X X X X -
AS-24MCWH-FW 3469 135/185 X X X - X - A,B,D,EFG,H,J,NOR,X X X X X -
AS-241575W-FR 7405 15(75onAxis) X X X - X - A,B,D,E,F,G,H,J,N,O,R,X X X X X X
AS-121575W-FR 7410 15(75onAxis) X X - X X - A,B,DE,F,G,HJN,O,R,X X X X X X
AS-24MCC-FR 3161 15/30/75/95 X X X - - X A,B,D,E,F,G,H,JNO,R,X X X X X -
AS-24MCC-FW 3162 15/30/75/95 X X X - - X A,B,D,EFG,H,J,N,O,R,X X X X X -
AS-24MCCH-FW 3467 115/177 X X X - - X A,B,D,E,F,GH,J,N,O,R,X X X X X -
ASWP2475WFR** 9012 75 @ -31°F X X X - X - I (see Data Sheet S9004) X X X X X
AH-24-R 7892 - X X X - X X A,B,D,E,F,G,H,J,NO,R,X X X X X X
AH-24-W 7893 - X X X - X X A,BD,E,F,G,HJNO,R,X X X X X X
AH-12-R 7891 - X X - X X X A,B,D,EF,GH,JN,O,R,X X X X X X
AH-12-W 7894 - X X - X X X A,B,D,E,F,G,H,JNO,R,X X X X X X
AH24WPR** 7416 - X X X - X X K X X X - X
AH12WPR** 7415 - X X - X X X K X X X - X
**For Weatherproof Series AS/AH specifications see data sheet S9004. *PENDING
***Refer to Data Sheet 57000 for Mounting Options.
Note: Models are available in either Red or White. Contact Customer Service for Order Code and Delivery.
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in
accordance with Wheelock Inc. standard terms and conditions.
S8100 AS/AH 06/11
Notification
-Architects and Engineers Specifications
The notification appliances shall be Wheelock Series AS Audible Strobe appliances and Series AH Audible appliances or approved
equals. The Series AS Audible be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired) for Indoor Fire Protection
Service. The Series AH Audible shall be UL Listed under Standard 464 (Fire Protective Signaling). Both shall meet the requirements
of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm
Control Panel (FACP).
The audible portion of the appliance shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice
of continuous or temporal (Code 3) audible outputs.
The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and
shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series AS shall be of low current design. Where Multi-
Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at
15/30/75/110 or 135/185 candela for wall mount and 15/30175195 or 115/177 candela for ceiling mount. The selector switch for selecting
the candela shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75
candela on-axis is required (e.g. ADA compliance).
When synchronization is required, the appliance shall be compatible with Wheelock's DSM Sync Modules, Wheelock Power Supplies
or other manufacturers panels with built-in Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any
time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a
non-synchronized flash-rate. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe
activation when used with Wheelock synchronization.
The Series AS Audible Strobe and Series AH Audible shall incorporate a Patented Universal Mounting Plate that shall allow mounting
to a single-gang, double-gang, 4-inch square, 1 00m European type backboxes, or the SHBB Surface Backbox. If required, an NATP
(Notification Appliance Trimplate) shall be provided.
All notification appliances shall be backward compatible.
NEit4
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
7125-0785:0131 Page 1 of 2
7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
Cooper Wheelock lnc.7246 16th St. E., Ste. 105, Sarasota, FL 34243
Contact: Tom Conover (941) 487-2336
Email: thomas.conover@cooperindustries.com
Models AS-1215, -2415, -1230, -2430, -121575, -241575, -2475 and -24110 audible/strobes
for the hearing impaired followed by any three alpha/numeric characters indicating lens
orientation, lettering and color.
Models AS-1215W, -2415W, -1230W, -2430W, -121575W, -241575W, -2475W and -24110W
audible/strobes for the hearing impaired followed by any three alpha/numeric characters
indicating lens orientation, lettering and color. These units with suffix -Ware for wall mount
only. *Models AS-1 21575W and AS-241575W lens color may be white, red, blue, green, or
amber.
Models AS-2415C, -2430C, -24750 and -241 OOC audible/strobes for the hearing impaired
followed by two alpha/numeric characters indicating lens lettering, orientation and color.
These units are intended for ceiling mount only.
Model AH-12, -24, AH-12WP, -24WP audible appliances (no strobe), followed by an alpha or
numeric character indicating product color.
Model AS-24MCW and AS-24MCC audible/strobe, followed by any two alpha or numeric
character indicating lettering and product color. *Lens color may be white, red, blue, green,
or amber.
Models ASWP-2475W and *ASWP..2475c audible/strobe with integral private mode
fire/emergency visual signaling for non-hearing impaired applications. Lens color may be
white, red, blue, green, and amber. Both models are suitable for outdoor use when mounted
on the Model WPBB back box.
Models AS-24MCWH, AS-24MCCH, *ASWP24MCWH and *ASv/P24MCCH
audible/strobes for the hearing impaired followed by two alpha/numeric characters indicating
lens lettering and product color. Units with suffix CH are for ceiling mount only. Units with
suffix WH are for wall mount only. *Lens color may be white, red, blue, green, or amber.
Refer to the listee's data sheet for detailed product description and operational
considerations.
*Rev. 10-01-07
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2015 Listing Expires June 30, 2016
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
- Listing No. 7125-0785:0131
Page 2 of 2
RATING: Electrical: 8-17.5/16-33 VDCNFWR
Flash Rate: 60 flashes/minute
Candela: 15:l5cd,1575:15/75cd,30:30cd,75:75cd,95:95cd,100:100cd, 110:ll0cd
MCW: Selectable 15cd, 30cd, 75cd,110cd
MCC: Selectable 15cd, 30cd,75cd,95cd
MCWH: Selectable 135cd,185cd (65cd, 90cd at -40 C)
MCCH: Selectable 115cd,177cd (50cd, 75cd at -40 C)
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction. Models ASWP-2475W,
ASWP-24MCWH, AS-24MCW and AS-24MCWH are for wall mount only. Models
ASWP-2475C, ASWP-24MCCH, AS-24MCCH, AND AS-24MCC are for ceiling mount only.
Models with suffix -w or WH are for wall mount only. Models with suffix -C or -CH are for
ceiling mount only.
MARKING: Listee's name, model number, electrical/candela rating, and UL label.
APPROVAL: Listed as audible and audible/visual signaling devices suitable for the hearing impaired when
used in conjunction with separately listed electrically compatible fire alarm control units. For
indoor use only except Models AH-12WP, AH-24WP, *ASWp..2475w ASWP-2475C,
ASWP-24MCWH, and ASWP-24MCCH audible appliances are suitable for indoor/outdoor.
For synchronization, Models AS Series must be used with Model SM-12/24, SMX-12/24,
DSM-12/24 or DSMX-12/24 sync control module (CSFM Listing No. 7300-0785:132). Refer to
listee's Installation Instruction Manual for details.
These appliances can generate a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
NOTE: Models AH-12, AH-24, -I2WP and -24WP audible devices are not suitable for the hearing
- impaired applications.
*Rev. 10-01-07
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
40
Date Issued: July 01, 2015 Listing Expires June 3O,2016
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division