Permit No: FPC2023-0018
Status: Closed - Finaled
High-Piled Storage
Applied: 02/01/2023
Issued: 02/14/2023
Finaled Close Out: 07/17/2024
Final Inspection:
INSPECTOR: Cheung, Nathaniel
Project Title:
Description: CAMSTON WRATHER -HIGH PILE STORAGE PHASE 2 & 3
Applicant: FPContractor:
QUALITY MATERIAL HANDLING INCORPORATE QUALITY MATERIAL HANDLING INC
JULIE DARR 10156 SHARON CIR
10156 SHARON CIR RANCHO CUCAMONGA, CA 91730-5300
RANCHO CUCAMONGA, CA 91730-5300 (626) 812-9722
(626) 812-9722
FEE AMOUNT
FIRE High Piled Storage $895.00
Total Fees: $895.00 Total Payments To Date: $895.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 442-339-2665 1 Inspections: 442-339-2660 1 www.carlsbadca.gov
ATTACHMENT 9
High Pile Storage (HPS) Required Information
The following information shall be completed and copied onto the HPS plans for
all projects within the city of Carlsbad:
Commodity Classification:
[] I 0 II [] III 0 IV 0 High Hazard 0 Group A plastic
Commodity detailed
description: scrap steel, scrap aluminum, ferrous and non-ferrous metal concentrates, polymer
poweder (ground FR-4)
For Group A Plastics where the commodity classification is not High Hazard complete the following:
Expanded plastic: Percent by volume:_%. Percent by weight %
Non-expanded plastic: Percent by weight:%
Packaging consist of
1 Cartoned 0 Free flowing 0 Non-expanding 0 Encapsulated KI Non-encapsulated
IJOther SUPER SACK
The maximum storage height (solid pile rack 25-0'
The following storage methods are employed at this facility (mark all that apply):
OSolid pile storage OPalletized [Single row rack J@Double row rack DMulti-row rack
DOther
Rack storage shelf 0 N/A 0 Load beam only J Wre mesh DWood slates 0 Plywood
0 Other (Describe):_______________________________________________
The area designated in the building and used for high piled storage is 18,890 square feet.
CLASS Ill commodity, 16.400 sq ft UNDER PERMIT NUMBER FPC2022-0010
CLASS ii commodity, 4,039 sqft
CLASS commodity, sq ft
Smoke vents required [@ No [:]Yes Fusible link degree F.
Draft Curtains Required? 0 Yes D NO
The overhead fire sprinkler system utilizes the following heads:
J ESFR: K 25.2 at 25 PSI with 205 F° heads
[:]Standard Coverage Heads: K 0 Pendant 0 Upright _____ degree with a density of gpm over
square feet spaced at a maximum of square feet per fire sprinkler.
NFPA 13 Design Table:23.3.1 Curve:
Minimum distance between top of storage and sprinkler deflector: 3 Feet
In-rack sprinklers required 0 Yes JK1 No
0 There is/are __level(s) of in-rack fire sprinkler protection.
Aisle width: 8+ feet.
O Fire access doors required? J Yes (Maximum distance of 100 lineal feet) ONo
0 Flue spaces required? 91 Yes [--]No
i:i Flue space between racks shall be maintained a minimum of
Transverse 3" "clear. 0 Must be vertically aligned (for storage >25')
Longitudinal 6" "clear
C] Column protection required? 0 Yes )No
E] Pallet Stops Required? I]Yes DNo Longitudinal pallet stop configuration:
O Chain Link 0 Roll Form J "C" Channel j Other DIVIDERS (WORLDSTOP)
Transverse Flue Pallet Stop configuration:
C] Mechanical means (flue keepers, etc.) 91 Load beam markings "Keep Clear"
Hand Stack? [@ No []Yes # of tiers: Chain link required EKI No 0 Yes
DOUBLE ROW RACK SHALL USE "KEEP CLEAR" STICKERS AND PALLET STOPS. SINGLE ROWS SHALL USE ONLY "KEEP CLEAR" STICKERS
19
DocuSign EnveIop ID.: C9130F97-0146-48F2-A40A-123D7FC5B1 B2
***CAMSTON WRATHER RESOURCE RECOVERY FACILITY
LETTER OF INTENTED USE
RE: 2856 WHIPTAIL LOOP EAST CARLSBAD CA 92010
Project No:
To Whom This May Concern:
The following information is in answer to your request regarding the intended business operation to be conducted
at the above address.
Operation conducted in the building are as follows - Storing Printed Circuit Boards.
The description of the product to be stored and high piled combustible storage details are as follows:
> The storage racks Type B will be housing the following products: Scrap steel, scrap aluminum, ferrous and
non-ferrous metal concentrates, polymer powder (ground FR-4). Commodities are stored either on
cardboard boxes or super sacks, non-encapsulated and no open-tops.
The storage racks Type A and C will be housing the following products: Equipment spare parts and bulk
bags.
> All commodities shall be treated as Class Ill commodities per Section 3203 of the 2019 California Fire Code.
) The approximate square footage for high pile storage area is 4,039 square feet.
Actual Storage height shall not exceed 25'-0" for the high pile storage area.
There shall be no solid shelving in the high pile storage area that exceeds 20 square feet between approved
flue space per CFC 3208.2.2
For racks B (double-row racks), the transverse flue space of 3" will be maintained by providing "keep clear"
labels, and longitudinal flue space of 6" will be maintained with pallet stops.
> For Type A and C (single-row racks), the transverse flue space of 3" will be maintained by providing "keep
clear" labels. No longitudinal flue space requirement.
> Shelving Type S is not part of the high-pile, and it is considered low pile storage. Maximum storage height
shall not exceed 12 feet.
The approval for high piled combustible storage analysis will be maintained on site for the duration of the high piled
combustible storage operation.
If you have any further question regarding the High Pile Plans and commodities in our facility, feel free to contact
Quality Material Handling (626) 812-9722. They have been contracted as our fire prevention consultant for the
project.