HomeMy WebLinkAbout5781 VAN ALLEN WAY; ; FPC2021-0190PERMIT REPORT
4rLpZ" of
Carlsbad
Print Date: 06/17/2024
Job Address: 5781 VAN ALLEN WAY, CARLSBAD, CA 92008-7321
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel #: 2121304400 Track #:
Valuation: $316,545.52 Lot #:
Occupancy Group: Project #:
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #:
Plan Check#:
Permit No: FPC2021-0190
Status: Closed - Finaled
Applied: 10/06/2021
Issued: 10/29/2021
Finaled Close Out: 06/26/2023
Final Inspection:
INSPECTOR: Salcedo, Felix
Project Title:
Description: THERMO FISHER -REVISION FOR SPRINKLER TI FOR DISTRIBUTION CENTER WAREHOUSE STORAGE (1330 HEADS) (TWO
AM&MS APPROVED FOR THIS PROJECT, SEE FPC2021-0003 & 0109) (REV 1)
Applicant: FPContractor:
WESTERN FIRE PROTECTION INC WESTERN FIRE PROTECTION INC
MARIO MACK 13630 DANIELSON ST
13630 DANIELSON ST POWAY, CA 92064-6830
POWAY, CA 92064-6830 (858) 513-4949
(858) 513-4949
FEE AMOUNT
FIRE Hourly Services (each additional hour) $170.00
FIRE Hourly Services (first hour) $200.00
FIRE Hourly Services (first hour) $188.00
FIRE NFPA 13 or 13R System > 100 heads $719.00
FIRE Plan Review (per hr - Regular Office Hours)
-
$255.00
Total Fees: $1,532.00 Total Payments To Date: $1,532.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 442-339-2665 1 Inspections: 442-339-2660 1 www.carlsbadca.gov
Thermo Fisher Scientific - 5781 Van Allen Way - Ambient Racking
High Pile Storage (HPS) Required Information
The following information shall be completed and copied onto the HPS
plans:
Commodity Classification: 0 1 0 Ii 0 in 0 lv 0
Commodity detailed
description:Various Laboratc
Paperboard, Stored In Larger Boxes Or Plastic Bins. Plastic Tubes And Bottles Filled With Liquids/Solut
(Product). Large Plastic Bags In Open Plastic Bins Or Packed In Larger Corrugated Boxes For Transport
For Group A Plastics where the commodity cisslicatlon is not High Hazard complete the
following:
Expanded plastic: Percent by volume: Q%. Percent by weight: -% (if cartoned)
Non-expanded plastic: Percent by weight: -% (uncartoned Group A plastics in dedicated racks)
Packaging consist of: Cartoned and uncartoned Group A plastics, in bottles, plastic bins, plastic bags, etc.
El Cartoned 0 Free flowing 0 Non-expanding El Encapsulated U Non-encapsulated El Other In addition to uncartoned Group A plastics, in bottles, plastic bins, plastic bags, etc.
The maximum storage height (solid pile N/A rack Ambient Warhouse: 25 ft
The following storage methods are employed at this facility (mark all that apply):
High Hazard R1 Group A plastic
Product In Finished Packaging. Finished Product Packaged In Cardboard Or
ons or Powders
And Storage.
OSolid pile storage OPalletized ElSingle row rack ElDouble row rack OMulti-row rack see high-piled storage report
UOther
Rack storage shelf: 0 N/A 0 Load beam only El Wire mesh []Wood slates 0 Plywood 0 Other (Describe):_______________________________
The area designated in the building and used for high piled storage is 35,000 square feet.
CLASS I-IV, GAP commodity, 35,000 sq ft. GAP: Group A Plastics
CLASS commodity, sq ft.
CLASS, commodity, sq ft.
El Smoke vents required 0 No El Yes Fusible lInk degree F. see high-piled storage report I Draft Curtains Required? 0 Yes Iii NO
The overhead fire sprinkler system utilizes the following heads:
El ESFR: K at PSI with .F° heads Warehouse density
ElStandard Coverage Heads: K 16.8 0 El Pendant Upright 212 degree with a density 12@11 psi per FM Global: see
of _gpm over square feet spaced at a maximum of _______ square feet per fire sprinkler, high-piled storage
NFPA 13 Design Table:N/A (FM Global DS 8-9) Curve:' report
Minimum distance between top of storage and sprinkler deflector: .. 9 Feet (see HPS report for more details: Warehouse)
In-rack sprinklers required El Yes 0 No per FM Global DS 8-9: see high-piled storage report El There Is/are 2_(uncartoc)(s) of in-rack fire sprinkler protection. (see HPS report for more details: Warehouse)
Aisle width: 8 feet.
El Fire access doors required? El Yes (Maximum distance of 100 lineal feet) ONo LJ Flue spaces required? El Yes ONo El Flue space between racks shall be maintained a minimum of: per FM Global DS 8-9: see Transverse 3 - 6 "clear, 0 Must be vertically aligned (for storage >25')
Longitudinal 6 clear high-piled storage report "
El Column protection required? 0 Yes hi No
El Pallet Stops Required? DYes hiNo
Longitudinal pallet stop configuration: 0 Chain Link 0 Roll Form 0 "C" Channel 0 Other:see rack plans
Transverse Flue Pallet Stop configuration: El Mechanical means (flue keepers, etc.) 0 Load beam markings "Keep Clear"
Hand Stack? 0 No lJ Yes # of tiers: 2 (10 ft) Chain link required El No 0 Yes