HomeMy WebLinkAbout5781 VAN ALLEN WAY; ; FPC2023-0050(bty of
Carlsbad
Print Date: 06/17/2024
Job Address: 5781 VAN ALLEN WAY, CARLSBAD, CA 92008-7321
Permit Type: FIRE-Construction Commercial Work Class: Fire Alarm
Parcel #: 2121304400 Track #:
Valuation: $316,545.52 Lot #:
Occupancy Group: Project #:
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #:
Plan Check #:
Permit No: FPC2023-0050
Status: Closed - Finaled
Applied: 03/14/2023
Issued: 04/14/2023
Finaled Close Out: 06/27/2023
Final Inspection:
INSPECTOR: Salcedo, Felix
Project Title:
Description: THERMO FISHER -INSTALL NEW ADDRESSABLE FIRE SUPPRESSION CONTROL PANEL FOR RELEASING SERVICE FOR FREEZER
(AM&M FPC2021-0109 ADDENDUM IN LINKED RECORDS)
Applicant: FPContractor:
ADT COMMERCIAL ADT COMMERCIAL LLC
GREGORY COX P0 BOX 310702
920 SAN DREASEN DR, # STE 102 BOCA RATON, FL 33431-0702
ESCONDIDO, CA 92029-1936 (561) 989-7919
(619) 719-2633
FEE AMOUNT
FIRE Hourly Services (each additional hour) $160.00
FIRE Hourly Services (first hour) $188.00
FIRE Sprinkler Monitoring $453.00
Total Fees: $801.00 Total Payments To Date: $801.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 442-339-2665 1 Inspections: 442-339-2660 1 www.carlsbadca.gov
ADT- Commercial Powered by Experience.
Driven by Excellenc&"
Fire Suppression Panel
Product Submittal
FOR
THERMO FISHER
5781 Van Allen Way
Carlsbad, Ca 92008
SUBMITTED BY:
ADT COMMERCIAL
10107 Carroll Canyon Road
San Diego, CA 92111
(760) 233-9787
1501 YAMATO ROAD, BOCA RATON, FL 33431 adt.com/commercial
2020ADr CornmcciILLC.Mrights r&vd.
(E)POTTER C11c -1ob
The Symbol of Protection Fire Alarm Releasing Control Panel
Features
100 addresses available on this analog addressable system
Additional system capacity achieved via multi-point SLC modules
99 software zones
NFPA 72 Compliant Smoke Sensitivity Test Built-In
System Operates as Class A or Class B for SLC, P-Link and NACs
5 Amp Power Supply, Expandable to 310 amps
2 NACS, Regulated, Rated at 3 Amps each, expandable to 188
2 Input/Output (I/O) Circuits for system flexibility rated at I Amp each,
ideal for manual release and abort
Strobe Synchronization and System Wide Sync for Gentex®,
AMSECO®, Cooper Wheelock® and System Sensor® strobes
Dedicated Alarm, Supervisory and Trouble Relays
4,000 Event History Buffer
Optional two line DACT with UD-2000 that can report General, Zone or
Point Information
Built in IP Communicator
Ethernet Port for Programming and Network Connectivity
E-Mail System Status, Reports and Event Information NYC Fire Dept.
Product includes 5 year warranty Certificate of Approval
6256 LISTED
APPROVED 7165-0328:0509 S735
Description
The ARC-100 is an analog/addressable releasing fire alarm system with a
total system capacity of 100 addresses. Additional capacity on the system
is achieved using multi-point SLC modules. The control panel utilizes
the exclusive Potter protocol that includes a complete line of sensors and
modules. Each SLC may be comprised of any combination of smoke
sensor, heat detectors or modules and allows for a total of 50 ohms of
impedance and may use any wire compliant with the National Electrical
Code (NEC).
The ARC-100 has a 5Amp power supply with two Notification Appliance
Circuits (NACs) and two Input/Output (110) circuits. The NACs are rated at
3 Amps each and the I1Os are rated at lAmp each. Each output is regulated
and power limited. In addition, each output is uniquely programmable and
may be configured for steady signal, strobe synchronization, constant
power, door holder power, or releasing. The strobe synchronization
includes Gentex, AMSECO, System Sensor and Cooper/Wheelock and
with the exclusive Quadrasync each output may have a unique brand and
all strobes will flash together. The J1Os are designed for inputs such as
manual release stations and abort switches that will not require polling and
react nearly instantaneously.
The ARC-100 is listed for releasing of fire suppression systems. The
software allows cross zones, counting zones, and timers for suppression.
The system is capable of multiple release outputs across multiple hazards.
In addition, the PSN-1000 may be used to extend releasing capability.
The NACs may be expanded using the PSN-1000 series intelligent power
supplies. Each PSN-1000 adds another 10 Amps of power, 2 additional
input circuits and the ARC-100 will support up to 31 power supplies. The
system will synchronize the strobes system wide. In addition, the PSN-
1000E has space to allow the installation of up to six loop expansion cards.
The cards mount on a stacker bracket that allows access to all SLC circuit
connections.
Technical Specifications
Dimensions 16"W x I711 x 3 "D
AC Mains 3.0 Amps @ 120 VAC 50/60 HZ
2.0 Amps @ 240 VAC 50/60 HZ
Enclosure 16 gauge cold rolled steel with removable locked door with Lexan viewing window
Standby Current-130 mA
Alarm Current-200 mA
5 Amps power for NACs, I/O, and P-Link
Battery 3 Amps per NAC, regulated
1 Amp per I/O circuit, regulated
Battery Charger range 8-55 Ah
Battery Charger voltage 27.3 VDC
P-Link maximum current of! Amp
Temperature and 32° to 120° (0°C to 49°C) with a maximum
Humidity Range humidity of 93% non-condensing.
NFPA, 12, 12A, 13, 15, 16, 17, 17A, 70, 72,
92, 720 ,750, and 2001
ANSI/UL 864 - Local (L), Remote Station
(RS), Central Station (CS), Propriety
(PPU), Auxiliary (AUX). Type of Service:
Standards Automatic (A), Manual (M), Water flow
(WF), Sprinkler Supervisory (SS), Type of
Signaling: Digital Alarm Communicator
(DAC), March Time (March), Non Coded
(NC), Reverse Polarity (Rev P01), Other
Technologies (OT)
IBC (International Building Code)
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 www.pottersignal.com
8830136- REV F • 2/22 PAGE 1 OF 5
(E)POTTER ARC-1 00
The Symbol of Protection Fire Alarm Releasing Control Panel
SLC Loop Accessories
The control panel may be connected with up to 100 addressable devices or modules in any combination. The SLC is not restricted by any special wire
requirements and may be wired with any wire that complies with the NEC.
SLC Loop Devices
Device Description
(PAD200-P Analog Photoelectric Smoke Detector is a smoke detector with a listed obscuration of 1.0 to 3.5%/foot. UL 268 7th Edition.
PAD200-PHD Combination Analog Photoelectric Smoke/Heat Detector - a smoke detector with a listed obscuration of 1.02 to 3.83 percent
obscuration and a fixed temperature range of 135° to 185° F heat detector. Smoke detection compliant with UL 268 7th Edition.
PAD200-PCD Combination Photoelectric Smoke/Carbon Monoxide Detector. Smoke detection compliant with UL 268 7th Edition. Carbon
Monoxide detection compliant with UL 2075.
PAD200-PCHD
Combination Photoelectric Smoke/Heat/Carbon Monoxide Detector. Smoke detection compliant with UL 268 7th Edition. Heat
detection with a fixed temperature range of 135° to 185° F and is UL 268 and UL 521 7th Edition compliant. Carbon Monoxide
detection compliant with UL 2075.
PAD100-HD Analog Fixed Temperature (135° - 185°F) or Rate-of-Rise Heat Detector (software selectable).
PAD200-DUCTR Addressable Duct Smoke Detector with Form C Relay rate at lOAmps @ 250/120VAC or 8 Amps at 30VDC.
PAD200-DUCT Addressable Duct Smoke Detector.
PAD 100-6B 6" round base that is mounted to an electrical box and wired for connection of one of the above sensors.
PAD100-413 4" round base that may be mounted to an electrical box and wired for connection to the above sensors.
PAD 100-TB Isolator base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop.
PAD100-RB Addressable Relay Base that contains one relay controlled by the SLC. Relay is rated at rated at 2 amps at 30 VDC or 0.5A at 125VAC.
PAD 100-SB Addressable Sounder Base that contains an addressable sounder module that may be configured for local, group and all call.
PAD100-CD Addressable CO gas detector.
PAD 100-DD Addressable photoelectric smoke detector for use in DUCT/DUCTR enclosure.
PAD 100-LFSB Addressable Low Frequency Sounder Base that contains an addressable sounder module that may be configured for local, group and all
call. The LFSB complies with the Low Frequency Signal Requirements (520 Hz).
PAD 100-SPKB Speaker base is a wall or ceiling mount speaker capable of 25 or 70.7 VRMS and is field selectable from 1/8W to 4W.
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830136- REV F • 2/22 PAGE 2 OF 5
(E)POTTER ARC-1 00
The Symbol of Protection Fire Alarm Releasing Control Panel
Modules
Device Description
PAD 10O-M1M'1 Micro Input Module provides a small foot print contact module for mounting inside an enclosure.
PAD 100-PSSA Single Action Addressable Pull Station.
PAD 100-PSDA Dual Action Addressable Pull Station.
PAD100-SIM Single Input Module is a standard contact module with an LED that mounts into a 4" square electrical box.
PAD 100-DIM Dual Input Module is a device that can monitor two distinct inputs with a single device or in a Class A mode.
PAD 100TRT1 Two Relay Two Input module provides two form C relays that are individually controlled by the control panel. Each relay is rated for 2
amps at 30VDC or 0.5 amps at 125 VAC. Also provides two contact inputs.
PAD 100-NAC Notification Appliance Circuit module is an addressable remote appliance circuit controlled by the panel.
PADI 00-ZM Zone Module is used to connect conventional 2-wire smoke detectors to the system.
PAD 100-TM Isolater Module interrupts a short on the SLC and prevents the short from affecting protected devices on the loop.
PAD 100-RM Relay Module that provides one form C relay controlled by the control panel. Relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC.
PAD 100-LED Module provides a single addressable LED that is controlled by the control panel.
PAD 100-SM Speaker Module provides switching for two audio channels.
PAD 100-LEDK Addressable LED and key switch that mounts in a single gang box.
PAD 100-DRTS DUCTR Remote Test Switch that mounts in a single gang box and optionally supervised. For use with the PAD 100-DUCTR only.
PAD 100-OROI One Relay One Input Module provides one form C relay and one input. The relay is rated at 2 amps at 30VDC or 0.5 amps at 125 VAC.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830136- REV F • 2/22 PAGE 3 OF
(E)POTTER
The Symbol of Protection
SLC Features
The Potter protocol is a digital protocol with a proven design for
reliability and noise immunity. The system does not require special
cable or conductors for connection of the Signaling Line Circuit
as long as the cable is compliant with NFPA 70 and NFPA 72.
The system allows for Class A or Class B installations as well as
"T-Taps", with a max wiring distance of 10,000 Ft.
Sensor Features
The sensors through the fire alarm control panel provide a real
time status as to the condition of the system. The smoke detector
sensitivity, heat detector temperature level and drift compensation
are all programmable options. The system also allows for a day/night
mode where the panel automatically adjusts the sensitivity depending
on the time of day. To assist in the reduction of false alarms, the
smoke detectors also have a maintenance warning that sends a trouble
signal when a detector is dirty to the point that it can no longer
maintain the programmed sensitivity..
User Interface
The fire alarm control panel has a 2 x 16 LCD display to provide
information to the system status. The keypad has navigation keys
to allow manipulation of the Menu on board the panel. The panel is
shipped standard with the following LEDs:
AC Power - Green
Alarm - Red
Earth Fault - Amber
Supervisory -Amber
Silenced - Amber
Trouble - Amber
Pre-Release - Amber
Release - Red
The common buttons include a Silence, Reset, Acknowledge, and
Drill. All of the buttons are accessible once the locked door is
opened.
P-Link
The AFC-50 has a proprietary communication protocol that
communicates through a RS-485 connection to field devices. Up
to 32 devices may be connected to a single P-Link connection. The
P-Link includes the communication terminals and regulated 24 VDC
connection for the field devices. The field devices may be any of the
following:
SLCE-127 -Nohmi addressable loop expansion module for retrofit
applications.
RA-6075R - 2 x 16 LCD annunciator with a key pad in a locked
metal enclosure.
ARC-1 00
Fire Alarm Releasing Control Panel
RA-6500R(F) —4 x 40 LCD annunciator with a key pad in a locked
metal enclosure. Flush mount version available.
LED-16(F) - 16 LED annunciator with common indicators in a
locked metal enclosure. Flush mount version available.
PSN-1000(E) - 10 amp, remote intelligent power supply with
6 NACs, 2 Inputs and a P-Link repeater. This panel is listed in
conjunction with the AFC-50 as releasing circuits.
CA-6075 - Class A convertor that converts the SLC, NACs and
P-Link connection
UD-2000 - UL listed, Dual line telephone alarm communicator
DRV-50 - LED driver expander, used to connect up to 50 LEDs in a
graphic display
FCB-1000 - Fire communication bridge, provides remote mounting
of the Ethernet connection
FIB-1000 - Fiber interface module, used to extend P-Link to multi-
mode fiber (2 required)
RLY-5 - Relay module, provides 5 form C relay contacts rated at 3.0
amps 24VDC/125AC
SPG-1000 - Serial parallel gateway, allows for the connection to a
serial or parallel printer
The FIB-1000, FCB-1000 and the SPG-1000 may be installed in the
stacker bracket or ordered with the optional rack mount enclosure.
MC-1000 Multi-Connect allows up to sixty-three AFC series panels
to share a single reporting technology.
IDC-6 - Initiating device circuit provides 6 programmable inputs
AE-2 - Two card expansion cabinet
AE-8 - Eight card expansion cabinet
AE-14 - Fourteen card expansion cabinet
Ethernet/I.P. Connection
The AFC-50 is shipped standard with an Ethernet connection.
This connection is the programming port and may be connected
to a building Wide Area Network (WAN) or Local Area Network
(LAN). Once connected to the Internet, the panel may be selectively
programmed to e-mail alarm conditions, trouble conditions,
supervisory conditions, test, Event History and detector status. An
e-mail may be sent to the panel and the panel will e-mail the event
history, detector status, configuration file or server status to an
authorized E-mail account. In addition, reminders may be set to send
an e-mail for service, testing or other conditions.
In addition, the Ethernet connection is UL listed as an IP
communicator. The IP communicator is listed to report to the UI.
listed Sur-Gard III IP receiver. The IP communicator replaces the
traditional less reliable alarm communicator transmitter that utilized
telephone lines. The IP communicator is an active method of
connection and communication to the monitoring station.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830136- REV F • 2/22 PAGE 4 OF 5
(E)POTTER
The Symbol of Protection
ARC-1 00
Fire Alarm Releasing Control Panel
Dimensions
0 of
TOP DEPTH=3.75'
DOOR= 16.07"
BACKBOX= 15.77 DEPTH =3.84
co
oil
LEFT SIDE
BOTTOM L
RIGHT SIDE
DM #593-I
Ordering Information
Model Description Stock No.
ARC-100 Fire Alarm Releasing Control Panel 3992755
Replacement Board ARC-100 3992759
Compatible Releasing Devices
Note: For releasing applications please order the Potter EOLD
(3005012) for circuits connected to a releasing solenoid or actuator.
Brand Description
Skinner 73218BN4UNLVN0C112CZ
732 12BN4TNLVN0C322C2
Victaulic 753-E Series
Mini Max MiX123 & MX200 wl 8876677 & 889323
Viking 11591, 11601, 11602, 13843,& 13844
TLX PA0036
Stat-X 30E, 60E, 100E, 250E, 500E, l000E, 1500E, &
2500E
Potter Electric Signal Company, LLC St. Louis, MO • Phone: 800-325-3936 www.pottersignal.com
8830136 - REV F • 2/22 PAGE 5 OF 5
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION .....
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7165-0328:0509 Page 1 of 2
CATEGORY: 7165-- FIRE ALARM CONTROL UNIT (COMMERCIAL)
LISTEE: Potter Electric Signal Co1609 Park 370 Place, Hazelwood, MO 63042 United States
Contact: Michael Mclsaac (314) 628-2218 Fax (314) 595-6999
Email: michaelm@pottersignal.com
DESIGN: Models AFC-50, AFC-100 and AFC-1000 fire alarm control units. Automatic, Manual,
waterfiow and sprinkler supervisory type device and local, auxiliary, remote station (PPU),
proprietary (PPU) and central station (PPU) services.
*ModeIARC10fire alarm control unit. Automatic, Manual, waterfiow and sprinkler
supervisory type device and local, auxiliary, releasing, remote station (PPU), proprietary
(PPU) and central station (PPU) services.
System components:
PAD 100-DIM Dual Input Module
PADIOO-LED Addressable LED Module
PAD 100-OROI One Relay-One Input Module
PAD 100-RM Relay Module
PAD 100-SIM Single Input Module
PAD 100 TRTI Two Relay-Two Input Module
PAD 100-ZM Zone Module
PAD 100-IM lolator Module
PAD 100- NAC Notification Appliance Circuit Module
PAD 100-SM Speaker Module
AD 100-MIM Micro Input Module'.
PAD 100-LEDK LED Key Switch Module
PAD 100-DRTS Duct Remote Test Switch
PAD 100-SLCE127 Point SLC Expander
MC-1000 Multi-Connect
PAD 100-DUCTR
AE-2 Enclosure
Refer to listee's Installation Instruction Manual for details.
RATING: 24VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
*Rev 12-04-17 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2022 Listing Expires June 30, 2023
Authorized By: VICTOR WONG, Program Coordinator
Fire Engineering Division
Listing No. 7165-0328:0509
Page 2 of 2
MARKING: Listee's name, model designation, rating and UL label.
APPROVAL: Listed as fire alarm control units when use with separately listed electrically and functionally
compatible initiating and indicating devices. Refer to listee's Installation Instruction Manual
for details.
*Rev 12-04-17 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2022 Listing Expires June 30, 2023
Authorized By: VICTOR WONG, Program Coordinator
Fire Engineering Division
(E)POTTER
The Symbol of Protection
Features
UL 268 7th Edition
Low profile, less than 2 inches with the base
Wide selectable sensitivity range of 1.0 to 3.7%/foot
Sensor communicates sensitivity to control panel
UL listed smoke calibration and sensitivity
Optional locking tab to prevent unwanted removal
Simple DIP switch address setting, no programming tool
required
LED alarm indicator
Product includes a 5 year warranty
UUKL Listed for Smoke Control
Description
The Photoelectric Smoke Sensor is a listed Analog Addressable smoke
sensor compatible with fire alarm control panels that utilize the Potter
Addressable Device (PAD) protocol. The PAD200-PD is a low profile
smoke sensor with a wide sensitivity range. The sensor and base (not
included) are made of a durable plastic in an off-white color to blend
in with the ceiling.
The PAD200-PD has a sensitivity range of 1.0 to 3.7 % per foot and
is UL. The PAD200-PD features drift compensation and has built in
dirty detector warning as well as. The PAD200-PD and the control
panel communicate over a proven and robust digital communication
path and the system analyzes the information at the particular device.
The total polling speed is less than five (5) seconds, well under the UL
requirements.
The sensor is compatible with any of the PAD series sensor bases and
simply twists on. The PAD200-PD is addressed using DIP switches
in the rear of the sensor and can be easily programmed in the field
without special tools.
Setting the Address
Each addressable device on the SLC loop must have a unique address
from 1 to 127 to function properly. The address is set using DIP
switches.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to SLC or device. Verify the
following:
'PAD2OO-PD
Photoelectric Smoke Sensor'
LISTED
Technical Specifications
Operating Voltage 24 VDC
Detector Current Draw 300 jiA
Alarm indicator 1 LED
Alarm set-point range 1.0 to 3.7 %/ft 3.6-12 %/m
Installation temperature 32to120°F/ 0to49°C range
Operating relative 0% to 93% (Non-condensing) humidity range
Start-up time Max. 1 sec.
Maximum number of 127 addresses per loop
Maximum number of
lighted indicators in 30
alarm per loop.
Color Eggshell White
Weight (without base) lOig (3.560z)
Dimensions (without Height: 1.35 in (34mm)
base) Diameter: 3.93 in (100 mm)
Power to the device is removed
Field wiring is correctly installed.
Field wiring has no open or short circuits.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 www.pottersignal.com
8830172- REV A • 5/21 PAGE 1 OF 2
(E)POTTER PAD200-PD
The Symbol of Protection Photoelectric Smoke Sensor
Air Velocity Ratings
The PAD200-PD has an Open Area of Protection air velocity rating of 0 to 300 feet per minute.
The system has a maximum of 30 LEDs that can be turned on simultaneously. If the system already has 30 LEDs on, the PAD200-PD will operate even
though the LED may not illuminate.
Operation
The PAD200-PD is an analog addressable sensor that uses one address on the Signaling Line Circuit (SLC) of a compatible fire alarm control panel.
The unit communicates with the control panel as it is polled. The LEDs flash every time the unit is polled and they will flash at a fast rate if the unit is
in an active status. The polling LED can be turned off if desired for less conspicuous operation.
The PAD20 0-PD with the PAD 100-4DB or PAD 100-6DB has a low profile of less than two (2) inches to blend into the surrounding environment. The
sensor includes an insect screen to prevent foreign objects from reaching the chamber and the can be cleaned to restore operation of a dirty detector.
Sensor Sensitivity
The PAD200-PD and the compatible control panel work in tandem to keep the sensitivity consistent. As the sensor is installed over time, the sensor
compensates for the dirt in the unit until it is out of range. At that time, the panel will indicate a dirty sensor. The sensor will then have to be cleaned
or replaced.
The PAD200-PD can be programmed to provide a maintenance alert prior to reaching the dirty sensor level which will allow for intervention prior to
the sensor going into trouble. This allows for sensor replacement or cleaning prior to a nuisance trouble occurs.
NOTE: As required by NFPA, do not install the sensors until all construction is complete and the work area has been thoroughly cleaned. If the sensors
have been installed in a construction environment, they should be cleaned or replaced before the system is placed into service.
Spacing
The PAD200-PD is UL listed with a recommended maximum spacing of 30 feet. Refer to NFPA 72 for specific information regarding detector spacing,
placement and special applications.
Compatible Bases
All bases will mount on a single gang, double gang, octagon, 4" square or mud ring electrical box.
Device Description Stock No.
PAD100-4DB 4" Standard Base 3992731
IPAD100-61)13) (6" Standard Base) 3992732
PAD 100-lB 6" base with an isolator module included. 3992730
PAD 100-RB 6" base with one Form-C relay contact. 2A @ 30VDC, 0.5A @ 125 VAC 3992728
PAD 100-SB 6" base with sounder module included. Sound pattern is provided from external source. 3992729
PAD1 00-SPKB 6" base with speaker included 3992762
Ordering Information
Model Description I Stock No.
PAD200-PD Photoelectric Smoke Sensor 3992770
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 www.pottersignal.com
8830172- REV A • 5/21 PAGE 2 OF 2
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7272-0328:0504 Page 1 of 1
CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC
LISTEE: Potter Electric Signal Co1609 Park 370 Place, Hazelwood, MO 63042 United States
Contact: Michael Mclsaac (314) 628-2218 Fax (314) 595-6999
Email: michaelm@pottersignal.com
DESIGN: ModelsPAD100-PD PAD100-DD and PAD100-PHD photoelectric smoke detector heads.
Model PAD100-PHD has an intergral heat detector. Refer to Listee's data sheet for detailed
product description and operational considerations.
RATING: 24Vdc
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Models PAD100-PD and PAD100-PHD are listed as photoelectric smoke detector heads for
use with listee's detector base Models PAD100-4DB, PAD100-6DB, PAD100-RB,
PAD100-SB (CSFM#7300-0328:502) and Model PAD100-IB (CSFM#7300-0328:501). Model
PAD100-DD is listed as a photoelectric smoke detector head for use with Model
PAD100-DUCT(CSFM#3248-0328:0505). Refer to listee's Installation Instruction Manual for
details.
06-21-2017 dcc
es This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2022 Listing Expires June 30, 2023
Authorized By: VICTOR WONG, Program Coordinator
Fire Engineering Division
(E)POTTER
The Symbol of Protection
I I (\PAD1OO4DB/6DB) \ - 4 /6"Addressable Detector Base
Features
Terminals Marked with Polarity to assist with installation
Duplicate terminals for in and out SLC wiring
Terminals accept 22 to 12 AWG wire sizes
Installs on single gang, double gang, octagon or 4" square box
Locking tab prevents unauthorized detector removal
Product includes 5 year warranty
<~>
APPROVED LISTED
Application
The Potter PAD100-6DB and PAD100-4DB detector bases are used
to install Potter's addressable smoke and heat detectors. The PAD100-
6DB will mount on a single gang, double gang, octagon or 4" square
electrical box.
Description
The PAD100-6DB and PADIOO-4DB are low-profile, surface mount
bases used with Potter's addressable detectors. The base uses screw-
clamp terminals that accept wire ranging from 22 to 14 AWG. When
installed on recessed electrical boxes the PAD 100-6DB is wide enough
to completely cover the back box and the immediate surrounding area.
The base is equipped with a locking tab to deter unauthorized removal
of the attached detector.
Technical Specifications
Mounting Options Single gang, double gang, octagon, and 4"
square box
Terminals Screw-Clamp Type
Wire Guage 22 to 12 AWG
Diameter: 6.3 in (166 mm) Dimensions Height 0.72 in (18 mm)
Shipping Weight 87g (3.07 ox)
Material Durable Plastic
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 www.pottersignal.com
PRINTED IN USA 8830107- REV C • 12/18 PAGE 10F2
(E)POTTER
The Symbol of Protection
Locking Feature
The PAD100-6DB and PADI004DB include a locking feature that
prevents removal of the detector without using a tool.
To eliminate this feature, break off the locking tab (refer to Figure
1), and then install the detector.
Fig. I
To remove the detector from the base when the locking feature has
been enabled, insert a small screw driver into the slot on the base to
push the plastic tab while simultaneously turning the detector head
counter-clockwise.
Fig. 2
PADI 00-4DB/6DB
4 '76" Addressable Detector Base
Wiring Diagram
Fig. 3
To FA(
Loop (l
Ordering Information
Model Description Stock No.
PAD100-6DB 6" Sensor Base 3992732
PAD100-4DB 4" Sensor Base 3992731
Insert small screwdr
into slot to remove
detector from base.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
PRINTED INUSA 8830107- REV C . 12/18 PAGE 2OF2
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM 4
LISTING SERVICE
LISTING No. 7300-0328:0502 Page 1 of 1
CATEGORY: 7300 -- FIRE ALARM CONTROL UNITACCESSORIES/MISC. DEVICES
LISTEE: Potter Electric Signal Co1609 Park 370 Place, Hazelwood, MO 63042 United States
Contact: Michael Mclsaac (314) 628-2218 Fax (314) 595-6999
Email: michaelm@pottersignal.com
DESIGN: Models PAD 100-4DB,6i00-ë5) PAD 100-RB and PAD 100-SB detector bases. Refer to
Listee's data sheet for detailed product description and operational considerations.
RATING: 24Vdc
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as a addressable isolator base for use with separately listed compatible fire alarm
control units and listee's separately listed Models PAD-100-PD and PAD-100-PHD
(CSFM#7272-0328:0504), PAD-100-HD (CSFM#7270-0328:0503) and PAD-100-CD
(CSFM#5278-0328:0506) detector heads. Refer to listee's Installation Instruction Manual
for details.
06-21-2017 dcc
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2022 Listing Expires June 30, 2023
Authorized By: VICTOR WONG, Program Coordinator
Fire Engineering Division
(E)POTTER
The Symbol of Protection
Features
One Class B contact monitoring input
Small size allows mounting in most electrical boxes
SLC Class A, Class X & Class B
6" Pigtail wiring connections
Product includes a 5 year warranty
UUKL Listed for Smoke Control
Description
The PAD100-MIIM is used to monitor the status of an initiating
device(s) that contain a normally open set of dry contacts. The module
is enclosed in a plastic case to protect against inadvertent shorts and
ground faults. The case can be mounted using a single screw. The
PAD 100-MJM has a status indicator LED to indicate communication
and alarm condition. In normal condition, the LED flashes when the
device is being polled by the control panel. When the input is activated,
the LED will flash at a fast rate.
Application
The micro input module (PAD 100-MuM) is compatible with Potter's
IPA and AFC/ARC series addressable fire alarm control panels.
Generally the PAD100-MIM is used to monitor pull stations and
other devices where the module is installed in an electrical box or
enclosure behind the device being monitored.
(PAD I 00-MIM
Micro Input Module 1
124iZ4
M8
*
-
a C6
PAD 100-MIM (SLC Module)'
II H
<S>
APPROVED
Technical Specifications
Operating Voltage 24.0V
Max SLC Standby 200 pA Current
Max SLC Alarm 200pA Current
[DC Input Circuit Class B
Wiring
Max Wiring Resistance 100 92 of IDC
Max Wiring IPF Capacitance of IDC
EOL Resistor 5.lK0
Operating Temperature
Range
32 to 120°F (0 to 49°C)
Operating Humidity
Range 0 to 93% (non-condensing)
Max no. of Module Per 127 units Loop
Dimensions 1.75" (44.5mm)L x 1.36"
(34.5mm)Wx .43" (llmm)D
Mounting Options 2-1/2" (64mm) deep single-gang box
Shipping Weight 0.3 lbs
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830079-REVD • 12/18 PAGE 1 OF 2
(E)POTTER PAD1 00-MIM
The Symbol of Protection Micro Input Module
Setting the Address
Each addressable SLC device must be assigned an address. The address is set using the DIP switch located on the front of the PAD100-MIM. Before
connecting a device to the SLC loop, take the following precautions to prevent potential damage to the panel or device:
Power to the device is removed.
Field wiring is correctly installed.
Field wiring has no open or short circuits.
Wiring Diagram
Fig 1
FROM FACP OR PREVIOUS ---/
DEVICE AND TO NEXT DEVICE
TO NORMALLY OPEN
MONITORED DEVICE
5.1K OHM REQUIRED
Part #3005013
Ordering Information
Model Description I Stock No.
PAD 100-MIM Micro Input Module 3992700
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 . www.pottersignal.com
8830079- REV D • 12/18 PAGE 2 OF 2
I
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION .-...
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM 1
LISTING SERVICE
LISTING No. 7300-0328:0514 Page 1 of 1
CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: Potter Electric Signal Co1609 Park 370 Place, Hazelwood, MO 63042 United States
Contact: Michael Mclsaac (314) 628-2218 Fax (314) 595-6999
Email: michaelmpottersignaI.com
DESIGN: Model PAD100-DIM Dual Input Module
Model PAD100-LED Addressable LED Module
Model PAD100-OROI One Relay-One Input Module
Model PAD 100-RM Relay Module
Model PAD100-SIM Single Input Module
Model PAD100-TRTI Two Relay-Two Input Module
Model PAD100-ZM Zone Module
Model PAD100-IM Isolator Module
Model PAD100-NAC Notification Appliance Circuit Module
Model PAD100-SM Speaker Module
IModel PAD100-10IM Micro Input Module)
Model PAD 1---LEDK Key Switch Module
Model PAD100-DRTS Duct Remote Test Switch
Model SLCE127 Point SLC Expander
Model MC-1000 Multi Connect
Model PAD100-DUCTR
Model AE-2 Enclosure
Refer to listee's data sheet for detailed product description and operational considerations.
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model designation, rating and UL label.
APPROVAL: Listed as fire alarm control unit accessories for use with listee's separately listed fire alarm
control panels. Refer to listee's Installation Instruction Manual for details.
09-11-18 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2022 Listing Expires June 30, 2023
Authorized By: VICTOR WONG, Program Coordinator
Fire Engineering Division
-t