Description: CAMSTON WRATHER -REVISIONS TO HIGH PILE STORAGE
Applicant: FPContractor:
QUALITY MATERIAL HANDLING QUALITY MATERIAL HANDLING INC
LISA RISNER 10156 SHARON CIR
10156 SHARON CIR RANCHO CUCAMONGA, CA 91730-5300
RANCHO CUCAMONGA, CA 91730-5300 (626) 812-9722
FEE AMOUNT
FIRE High Piled Storage $831.00
FIRE Plan Review (per hr - Regular Office Hours) $223.50
Total Fees: $1,054.50 Total Payments To Date: $1,054.50 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1442-339-2665 1 Inspections: 442-339-2660 1 www.carlsbadca.gov
Quality Material Handling Inc.
10156 Sharon Circle.
Rancho Cucamonga, California 91730
Contractor's License Number 731100
HIGH PILE AMENDMENT LETTER
CAMSTON WRATH ER RESOURCE RECOVERY
Project Name: FACILITY
Project Address: 2856 WHIPTAIL LOOP EAST
Plan Permit #: FPC2022-0010
City of Issuance: CITY OF CARLSBAD
Plan Reviewer: D LOCATI
1. High pile plans are approved. We are making an amendment to these plans since
floor plan layout changed to accommodate for forklift. Please see sheet HP213 for new floor plan
layout. Only type I and Type ci changed. They were previously proposed as double-row racks
that were going to use deep-reach forklift. Type I and Type 0 are now proposed as single-row
racks highlighted with a revision cloud and delta Al on sheet HP213. A new elevation sheet was
added, HP3C, to show compliance of the flue space for the single-row racks. A 3" transverse flue
space shall be maintained by using "keep clear" stickers. Please note that changes were only
made to type I and Type 0. racks. Compliance for the other rack types remain the same.
Another change that was made was the maximum storage height was increased from 24'-2" to
25'. Please note that the existing sprinkler system is able to protect up to 25 feet storage height
and this is why height are been amended.
Per building corrections, a note was added to the building plans stating that this facility will
storage hazardous materials. They will not be stored on the racks and will not be part of the high
pjj, but they will be stored elsewhere inside the facility.
Thank you,
Karla Garcia
Permit Technician
Quality Material Handling Inc.
May 2 Id , 2022
***CAMSTON WRATHER RESOURCE RECOVERY FACILITYtm
LETTER OF INTENTED USE
RE: 2856 WHIPTAIL LOOP EAST CARLSBAD CA 92010
Project No:
To Whom This May Concern:
The following information is in answer to your request regarding the intended business operation to be conducted
at the above address.
Operation conducted in the building are as follows -Storing Printed Circuit Boards.
The description of the product to be stored and high piled combustible storage details are as follows:
> The storage racks will be housing the following products: Printed Circuit Boards whole or partially sized. All
cartoned, non-encapsulated and no open-tops.
> All commodities shall be treated as Class Ill commodities per Section 3203 of the 2019 California Fire Code.
> The approximate square footage for high pile storage area is 16,400 square feet.
Actual Storage height shall not exceed 25'-0" for .the high pile storage area.
> There shall be no solid shelving in the high pile storage area that exceeds 20 square feet between approved
flue space per CFC 3208.2.2
For racks Type R and Type 55 (double-row racks), except the ones indicated on the floor plan, the transverse
flue space of 3" will be maintained by providing "keep clear" labels, and longitudinal flue space of 6" will be
maintained with pallet stops.
> For Type R and SS (double-row racks) marked on floor plan with note 5, the transverse flue space of 6" will
be maintained by providing "keep clear" labels and mechanical enforcement devices.
' For Type I and Type Q (single-row racks), the transverse flue space of 3" will be maintained by providing
"keep clear" labels. No longitudinal flue space requirement.
The approval for high piled combustible storage analysis will be maintained on site for the duration of the high piled
combustible storage operation.
If you have any further question regarding the High Pile Plans and commodities in our facility, feel free to contact
Quality Material Handling (626) 812-9722. They have been contracted as our fire prevention consultant for the
project.
Sincerely,
Aaron Kamenas
COO
ATTACHMENT 9
High Pile Storage (HPS) Required Information
The following information shall be completed and copied onto the HPS plans for
all projects within the city of Carlsbad:
Commodity Classification:
0 I 0 If El III 0 IV 0 High Hazard 0 Group A plastic
Commodity detailed
description: PRINTED CIRCUIT BOARDS, WHOLE OR PARTIALLY SIZED.
For Group A Plastics where the commodity classification is not High Hazard complete the following:
Expanded plastic: Percent by volume:_%. Percent by weight%
Non-expanded plastic: Percent by weight:%
Packaging consist of
gj Cartoned 0 Free flowing 0 Non-expanding 0 Encapsulated El Non-encapsulated
DOther
The maximum storage height (solid pile rack 25-0"
The following storage methods are employed at this facility (mark all that apply):
[]Solid pile storage OPalletized []Single row rack Double row rack DMulti-row rack
[]Other
Rack storage shelf. 0 N/A 0 Load beam only I] Wre mesh DWood slates 0 Plywood 0 Other (Describe):___________________________________________
The area designated in the building and used for high piled storage is 16,400 square feet.
CLASS III commodity, .16.400 sq ft
CLASS commodity, sq ft
CLASS commodity, sq ft
El Smoke vents required No DYes Fusible link degree F. O Draft Curtains Required? 0 Yes gj NO
The overhead lire sprinkler system utilizes the folling heads:
El ESFR: K 25.2 at 25 PSI with 205 P heads
OStandard Coverage Heads: K 0 Pendant 0 Upright _____ degree with a density ofppm over
square feet spaced at a maximum of square feet per fire sprinkler.
NFPA 13 Design Table:16.2.3.1 Curve:
Minimum distance between top of storage and sprinkler deflector: 3 Feet
In-rack sprinklers required 0 Yes Z1 No 0 There is/are ___level(s) of in-rack fire sprinkler protection.
Aisle width: 8+ feet.
Fire access doors required? J Yes (Maximum distance of 100 lineal feet) DNo
O Flue spaces required? El Yes []No
0 Flue space between racks shall be maintained a minimum of
Transverse 3" 6"" clear. 0 Must be vertically aligned (for storage >26)
Longitudinal 6" 011 " clear
Column protection required? 0 Yes No O Pallet Stops Required? 93Yes []No
Longitudinal pallet stop configuration:
O Chain Link 0 Roll Form 0 "C" Channel 1XI Other. DIVIDERS (WORLDSTOP)
Transverse Flue Pallet Stop configuration: (Z Mechanical means (flue keepers, etc.) J Load beam markings "Keep Clear"
Hand Stack? l No 0 Yes # of tiers: Chain link required f3 No DYes
NOTE: A FEW TYPE R, SS (SEEPLANS) SHALL USE FLUE KEEPERS AND "KEEP CLEAR" LABELS. ALL OTHERS SHALL USE
"KEEP CLEAR" STICKERS AND PALLET STOPS.
TYPE I AND Q CHANGED TO SINGLE-ROW RACKS. A 3' TRANSVERSE FLUE SPACE IS REQUIRED AND SHALL BE
MAINTAINED WITH "KEEP CLEAR" LABELS.
NOTE: BOTH OPTION 1 AND 2, TABLE
3208.3 ARE PROPOSED TO MAINTAIN
FLUE SPACES. SEE PLANS FOR RACKS
THAT USE OPTION 1. ALL OTHER
RACKS SHALL USE OPTION 2.
19