HomeMy WebLinkAbout2793 ELMWOOD ST; ; AS1401589126/24, 8:26 AM AS140158 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address: 2793 ELM WOOD ST
Permit Type: SPRINK
Parcel No: 1562316700
Lot #: 0
Reference No.:
Permit No: AS140158
Status: ISSUED
Applied 6/27/2014
Approved: 7/1/2014
Issued: 7/1/2014
PC #: Inspector:
Project Title: HOLLERAN RESIDENCE SPRINKLER SYSTEM FOR NEW
SINGLE FAMILY RESIDENCE W/ ATTACHED GARAGE, RAISED
DECKS, SPIRAL STAIR AND DETACHED CARPORT
Applicant:
ALPHA FIRE PROTECTION
500 HACIENDA DR #180
VISTA, CA
760-727-6993
Owner:
HOLLERAN FAMILY TRUST 07-15-97
2793 ELM WOOD ST
CARLSBAD CA
Fees ($) Add'l Fees ($) Total ($) Balance ($)
404 0 404
about:blank ill
ALPHA FIRE PROTECTION Mio5-g
RESIDENTIAL FIRE SPRINKLER SYSTEM
DATA BLOCK: DATE: 6119114
JOB ADDRESS: 2793 ELMW000 STREET CARLSBAD, CA.
ASSESSOR'S PARCEL NUMBER: 156-231-67
OWNER'S NAME: WILLIAM & MARY HOLLERAN
OWNER'S ADDRESS: SAME
OWNER'S PHONE NUMBER:
GENERAL CONTRACTOR'S NAME: MIRA BEu..A DESIGN
GENERAL CONTRACTOR'S ADDRESS:
GENERAL CONTRACTOR'S PHONE NUMBER:
SPRINKLER CONTRACTOR'S NAME: ALPHA FIRE PROTECTION
SPRINKLER CONTRACTOR'S ADDRESS: 4203 GENESEE AVE #103-424 SAN DIEGO, CA 92117
SPRINKLER CONTRACTOR'S PHONE NUMBER: (760) 727-6993
CALIFORNIA STATE LICENSE #582853 EXPIRES 12-31-2015
HYDRAULIC NOTES:
WATER METER SIZE: 1"
METER ELEVATION: - 150 AMSL
PRESSURE AT METER: 45 PSI
FLOW (GPM): HOUSE SIDE OF METER: 50 GPM
PAD ELEVATION: 144'
PRESSURE AT PAD: 48 PSI
PIPE LENGTH: METER To PAD: 45'
Pipe Type/Size: PVC - 2"
SPRINKLER TABLE:
CARLSBAD WATER DEPT. (760) 438-2722
DATE: 6-18-14 3PM
SYMB COMPANY & MODEL ORF TYPE TEMP K-FAT CANOPY QT
• Tyco LF-ll 1/2 SSP RR Sin#_2524
165 Degree 4.9 White Concealed 21
o Tyco -FRB
Sin # 3231 1/2 SSP 200 Degree 5.6 flute
Recessed/none 6 I
Total 1 27
PIPE TABLE:
TYPE MFG MODEL AREA OF USE
CPVC Tco BLAZEMASTER SYSTEM
STEEL ALLIED SCHEDULE 40 NONE USED
COPPER MULLER TYPES M & L SUPPLY
PVC SPEARS SCHEDULE 40 SUPPLY
NOTE: PIPE MUST BE U.L. OR F.M. LISTED FOR RESIDENTIAL FIRE SPRINKLER USE.
PLANS MUST STATE:
"PIPE WILL BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS"
"A COPY OF PIPE MANUFACTURER'S INSTALLATION INSTRUCTION PAMPHLET MUST BE KEPT ON-SITE."
Alpha Fire- Hydraulic Cakulations
Contract Name: IOU, 1Z,O Sheet / of
'Calculafion for: 2- I1I2 Pt) W6' Date:
Nozzle
Type &
Location
Flow
In
GPM —
Pipe
Size
Inches
Fittings
And
Devices
Pipe
Fittings
Total
Friction
Loss
psi/ft
Required
Pressure
psi
Elevation
Node
Notes
jtco q
Q
1 3
Type4O/(
Diameter 3
C-Factors 'O
. Ln /
0q 1/L/
Pt - 6
16V
773 Ft I0 Pf /1 (C)1/
Tot // Pe
q
Q
Type
Diameter
C-Factor
La ptg(,ot/
Ft Pf
Tot Pe / (I
q
Q 12
Type CPVC
Diameter
C-FactorJ$6
it, Ln 2 a q t, LI
Pt -7--- 4
-1i3 Ft 10 Pf
Tot I' Pe
q
Q
13,
Type cP Li C
Diameter
C-Factor! V
71 La 9
05o?
Pt (0 L( c, 7"'
/ 2-
Ft I Pf 3 /
Tot / (f) Pe t(D LI
q
Q
'j
Type C.j°V C.
Diameter (
C-Factor I $)
i-f . e/v Ln 4 Pt , 3 ~ ) 70 P.
I LI 7
q-3 - Ft
-'fl. Tot Pe 7,3(o
q
Q , (ç
Type M c
Diameter I
C-Factor I D
V( Ln ..j
3 I
Pt
/45
I Th Ft 1 3.5 Pf
Tot 17, 5 Pe , 7
q
Q
'2 L
Type 1,1
Diameter /
C-Factor 10
ç- La (p
'ii'
Pt 7,S. o F A4 10
'' 6•1' 's" IV Ft L. $ Pf 2. ..Z-
Tot /0,5 Pe (27 / L/ 3
q
Q 31
Type put
Diameter 4,
C-Factor 150
La Lj5
00 -75
Pt3g,q5
Ft - Pf L(
Tot 11 Pe+347 3 150
q
Q 3f Diameter"!
Type
C-Factor
Ln
If /
Pt 2-, H M[Z2
/ O
Ft 1
Tot Pc
q
Q
3 /
Type }(CL)
Diameter )•
C-Factor /50
2lC La 17,
50G
Pt32-(P .1
Ft Pf i.j /
Tot 1 6' Pe 1 ,30 / L./ 7
q
Q
Type
Diameter
C-Factor
Ln Pt3O7
Ft Pf
Tot Pe
q
Q
Type
Diameter
C-Factor
La Pt
Ft Pf
Tot Pe
4 AS 14-o [5-F
tqCJ7 Fire Suppression
& Building Products
Technical Services 800-381-9312 I +1-401-781-8220
www.tyco-fire.com
11
papid esponse
HOME FIRE SPRINKLER SYSTEM
Series LFII Residential Sprinklers
Flat-Plate Concealed Pendent
49 K-Factor
General
Description
The TYCO RAPID RESPONSE Series
LFII Residential Flat-Plate Concealed
Pendent Sprinklers (TY2524) are decora-
tive, fast response, fusible solder sprin-
klers designed for use in residential oc-
cupancies such as homes, apartments,
dormitories, and hotels.
The Cover Plate/Retainer Assembly con-
ceals the sprinkler operating compo-
nents above the ceiling. The flat profile
of the Cover Plate provides the optimum
aesthetically appealing sprinkler design.
Additionally, the concealed design of the
Series LFII Residential Flat-Plate Con-
cealed Pendent Sprinklers provides 1/2
inch (12,8 mm) vertical adjustment. This
adjustment provides a measure of flex-
ibility when cutting fixed pipe drops.
The Series LFII Residential Flat-Plate
Concealed Pendent Sprinklers are in-
tended for use in the following systems:
per NFPA 13D, wet pipe residential
sprinkler systems for one- and two-
family dwellings and mobile homes;
per NFPA 13R, wet pipe residential
sprinkler systems for residential oc-
cupancies up to and including four
stories in height; and
per NFPA 13, wet pipe sprinkler sys-
tems for the residential portions of
any occupancy.
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
The Series LFII Residential Flat-Plate
Concealed Pendent Sprinkler has a 4.9
(60,5) K-factor that provides the required
residential flow rates at reduced pres-
sures, enabling smaller pipe sizes and
water supply requirements.
This sprinkler has been designed with
heat sensitivity and water distribution
characteristics proven to help in the con-
trol of residential fires and to improve
the chance for occupants to escape or
be evacuated.
The Series LFII Residential Flat-Plate
Concealed Pendent Sprinklers are
shipped with a Disposable Protective
Cap. The Protective Cap protects the
sprinkler during ceiling installation or
finish. After ceiling installation is com-
plete, the Protective Cap is removed
and the Cover Plate/Retainer Assem-
bly is installed. Removing the Protec-
tive Cap is required for proper sprinkler
performance.
L(.1tL.I
The Series LFII Residential Flat-Plate
Concealed Pendent Sprinklers (1-Y2524)
described herein must be installed and
maintained in compliance with this doc-
ument and with the applicable standards
of the National Fire Protection Associa-
tion, in addition to the standards of any
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
Owners are responsible for maintaining
their fire protection system and devices
in proper operating condition. The in-
stalling contractor or sprinkler manu-
facturer should be contacted with any
questions.
Model/Sprinkler
Identification
Number (SIN)
TY2524
Technical
Data
Approvals
UL and C-UL Listed
NSF-61 Certified
The Series LFII Residential Flat-Plate
Concealed Pendent Sprinklers are only
listed with the Series LFII Concealed
Cover Plates having a factory-applied
finish.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=4.9 GPM/psi° (70,6 LPMJbar1 )
Temperature Rating
Sprinkler: 160°F (71°C)
Cover Plate: 139°F (59°C)
Vertical Adjustment
1/2 inch (12,7 mm)
Finishes
Refer to the Ordering Procedure
section.
Physical Characteristics
Cover Plate/Retainer Assembly:
Cover Plate .............Copper
Ejection Spring .... Stainless Steel
Retainer ................Brass
Page 1 of 6 OCTOBER 2010 TFP443
TFP443
Page 2 of 6
Horizontal Ceiling Sloped Ceiling Sloped Ceiling Minimum Flow0'tand Minimum Flow(b) and Minimum Flow(b) and Residual Pressure Residual Pressure Residual Pressure
Maximum Maximum (Maximum 2-inch rise (Greater than 2-inch rise (Greater than 4-inch rise Coverage Spacing for 12-inch run) up to maximum 4-inch up to maximum 8-inch Area N rise for 12-inch run) rise for 12-inch run)
160°F (71°C) 160°F (71°C) 160°F (71°C) Sprinkler Sprinkler Sprinkler
12' x 12' 12' 13 GPM (49,2 LPM) 17 GPM (64,3 LPM) 17 GPM (64,3 LPM) (3,7 m x 3,7 m) (3,7 m) 7.0 psi (0,48 bar) 12.0 psi (0,83 bar) 12.0 psi (0,83 bar)
14'x 14' 14' 13 GPM (49,2 LPM) 17 GPM (64,3 LPM) 17 GPM (64,3 LPM) (4,3 m x 4,3 m) (4,3 rn) TO psi (0,48 bar) 12.0 psi (0,83 bar) 12.0 psi (0,83 bar)
16 x 16' 16' 13 GPM (49,2 LPM) 17 GPM (64,3 LPM) 17 GPM (64,3 LPM) (4,9 m x 4,9 m) (4,9 m) 7.0 psi (0,48 bar) 12.0 psi (0,83 bar) 12.0 psi (0,83 bar)
18'x 18' 18' 17 GPM (64,3 LPM) 22 GPM (83,3 LPM) 22 GPM (83,3 LPM) (5,5 m x 5,5 m) (5,5 m) 12.0 psi (0,83 bar) 20.2 psi (1,39 bar) 20.2 psi (1,39 bar)
20' x 20' 20' 20 GPM (75,7 LPM) 24 GPM (90,8 LPM) 24 GPM (90,8 LPM) (6.1 m x 6,1 m) (6,1 m) 16.7 psi (1,15 bar) 24.0 psi (1,65 bar) 24.0 psi (1,65 bar)
For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage
area for which Hydraulic Design section under the Design Criteria are stated.
The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures
are calculated using the nominal K-factor. Refer to "Hydraulic Design' in the Design Criteria section for details.
TABLE A
SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER (TY2524)
NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA
WET PIPE SYSTEMS
Sprinkler/Support Cup Assembly:
Body ...................Brass
Cap ...................Bronze
Saddle ..................Brass
Sealing Assembly .......Beryllium
Nickel w/ Teflon'
Soldered Link Halves ......Nickel
Lever ..................Bronze
Compression Screw .......Brass
Deflector ...............Bronze
Guide Pin Housing........Bronze
Guide Pins .............Bronze
Support Cup ..............Steel
Operation
When exposed to heat from a fire, the
Cover Plate, which is normally soldered
to the Retainer at three points, falls away
to expose the Sprinkler/Support Cup As-
sembly. At this point, the Deflector, sup-
ported by the Guide Pins, drops down
to its operated position.
The Solder Link Element of the Sprinkler/
Support Cup Assembly is comprised of
two (ink halves that are soldered togeth-
er with a thin layer of solder. When the
rated temperature is reached, the sol-
der melts and the two link halves sepa-
rate, allowing the sprinkler to activate
and flow water.
1 Registered trademark of Dupont
Design
Criteria
The TYCO RAPID RESPONSE Series
LFII Residential Flat-Plate Concealed
Pendent Sprinklers (TY2524) are UL
and C-UL Listed for installation in ac-
cordance with the following criteria.
When conditions exist that are outside
the scope of the provided criteria, re-
fer to the Residential Sprinkler Design
Guide TFP490 for the manufacturer's
recommendations that maybe accept-
able to the Authority Having Jurisdiction.
The Series LFII Residential Flat-Plate
Concealed Pendent Sprinklers must
not be used in applications where the.
air pressure above the ceiling is greater
than that below. Down drafts through
the Support Cup can delay sprinkler op-
eration in a fire situation.
System Type
Only wet pipe systems may be utilized.
Hydraulic Design
Table A provides the minimum required
sprinkler flow rate for systems designed
to NFPA 13D or NFPA 13R as a function
of temperature rating and the maximum
allowable coverage areas. The sprinkler
flow rate is the minimum required dis-
charge from each of the total number of
"design sprinklers" as specified in NFPA
13D or NFPA 13R.
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is to be the greater of the following:
flow rates given in Table A for NFPA
13D and 13R as a function of tem-
perature rating and the maximum al-
lowable coverage area
minimum discharge of 0.1 GPM/
sq. ft. over the "design area" com-
prised of the four most hydraulically
demanding sprinklers for actual cov-
erage areas protected by the four
sprinklers
Obstruction To Water Distribution
Locate sprinklers in accordance with the
obstruction rules of NFPA for residential
sprinklers as well as obstruction criteria
described within TYCO technical data
sheet TFP490.
Operational Sensitivity
Install sprinklers relative to the ceiling
mounting surface as shown in Figure 3.
Sprinkler Spacing
The minimum spacing between sprin-
klers is 8 feet (2,4 m).
The maximum spacing between sprin-
klers cannot exceed the length of the
coverage area (Table A) being hydrau-
lically calculated; for example, a maxi-
mum of 12 feet for a 12 ft. x 12 ft. cov-
erage area or 20 feet for a 20 ft. x 20 ft.
coverage area.
TFP443
Page 3 of 6
BODY
(1/2" NP
CAP
SADDLI
EALING
SEMBLY
INKLER
ENCHING
ASREA
PRESSION
CREW
EVER
DER LINK
EMENT
SUPPOF
CUP Wfl
ROLL FOR
THREAC
GUIDE
PIN
GUIDE F
HOUSIt'
rRI irrr
THREAD INTO
SUPPORT CUP
UNTIL MOUNTING
SURFACE IS
FLUSH WITH
CEILING
LECTOR
ERATED
I JSITION)
SPRINKLER/SUPPORT CUP
ASSEMBLY
RETAINER
WITH THREAD
DIMPLES
CD C) fl EJECTION
H SPRING
WRENCH
RECESS
PUSH WRENCH
INTO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 2
W-TYPE 18
SPRINKLER WRENCH
SOLDER -' COVER PLATE/RETAINER -_. COVER
TAB ASSEMBLY PLATE
FIGURE 1
FLAT-PLATE CONCEALED PENDENT SPRINKLER (TY2524)
ASSEMBLY
2-1/2' DLA. SPRINKLER-
&-l
i ,
.12,7 mm) FACE OF (63,5 mm) SUPPORT CUP
v 14
ASSEMBLY 1/2'EADED SPRINKLER
/ OPERATE
NPT STMENT FIfiNG
SPRINKLE
COVER
(47,6 mm RETAINEF /8 GAP ±3,2 mm)
(3,2 mm)
PLATE
7/8' (22,2 COVER- SPRINKLER- MOUNTING
RETAINER SUPPORT CUP 3/16" j SURFACE ,
1-1/8' (28,6
ASSEMBLY ASSEMBLY I (4,8 mm)
3-3/16' DIA. DISPOSABLE
(81,0 mm) TIP PROTECTIVE CAP
DEFLECTOR IN
OPERATED POSITION
FIGURE 3
PROTECTIVE CAP AND ACTIVATED DEFLECTOR
INSTALLATION DIMENSIONS
TFP443
Page 4 of 6
.1
Installation
The TYCO RAPID RESPONSE Series
LFli Residential Flat-Plate Concealed
Pendent Sprinklers must be installed
in accordance with the following
instructions.
Damage to the Solder Link Element dur-
ing installation can be avoided by han-
dling the sprinkler by the Support Cup
only; that is, do not apply pressure to the
Solder Link Element (Figure 1).
Obtain a leak-tight 1/2 inch NPT sprinkler
joint by applying a minimum-to-maxi-
mum torque of 7 to 14 ft.-tbs. (9,5 to 19,0
Nm). Higher levels of torque can distort
the sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in the Cover Plate!
Retainer Assembly by under- or over-
tightening the sprinkler. Re-adjust the
position of the sprinkler fitting to suit.
Install pendent sprinklers in the
pendent position, with the center-
line of the sprinkler perpendicular
to the mounting surface.
Remove the Protective Cap.
With pipe-thread sealant applied
to the pipe threads, and using the
W-Type 18 Wrench shown in Figure
2, install and tighten the Sprinkler!
Support Cup Assembly into the fit-
ting. The W-Type 18 Wrench ac-
cepts a 1/2 inch ratchet drive.
Replace the Protective Cap by
pushing it upwards until it bottoms
out against the Support Cup. The
Protective Cap helps prevent dam-
age to the Deflector and Guide
Pins during ceiling installation and/
or during application of the finish
coating of the ceiling.
As long as the protective Cap re-
mains in place, the system is con-
sidered "Out Of Service".
After the ceiling has been com-
pleted with the 2-1/2 inch (63 mm)
diameter clearance hole and in
preparation for installing the Cover
Plate/Retainer Assembly, remove
and discard the Protective Cap,
and verify that the Deflector moves
up and down freely.
If the Sprinkler has been damaged
and the Deflector does not move up
and down freely, replace the entire
Sprinkler assembly. Do not attempt to
modify or repair a damaged sprinkler.
6. Screw on the Cover Plate/Retainer
Assembly until its flange contacts
the ceiling.
Do not continue to screw on the
Cover Plate/Retainer Assembly such
that it lifts a ceiling panel out of its
normal position.
If the Cover Plate/Retainer Assembly
cannot be engaged with the Mounting
Cup or the Cover Plate/Retainer As-
sembly cannot be engaged sufficiently
to contact the ceiling, the Sprinkler
Fitting must be repositioned.
Care and
Maintenance
The TYCO RAPID RESPONSE Series
LFII Residential Flat-Plate Concealed
Pendent Sprinkler (TY2524) must be
maintained and serviced in accordance
with the following instructions.
Before closing a fire protection system
main control valve for maintenance work
on the fire protection system that it con-
trols, obtain permission to shut down the
affected fire protection system from the
proper authorities and notify all person-
nel who may be affected by this action.
When properly installed, there is a nomi-
nal 1/8 inch (3,2 mm) air gap between
the lip of the Cover Plate and the ceil-
ing, as shown in Figure 3. This air gap
is necessary for proper operation of the
sprinkler by allowing heat flow from a
fire to pass below and above the Cover
Plate to help assure appropriate release
of the Cover Plate in a fire situation. If the
ceiling needs repainting after sprinkler
installation, exercise care to ensure that
the new paint does NOT seal off any of
the air gap. Failure to do so may impair
sprinkler operation.
Absence of a Cover Plate can delay the
sprinkler operation in a fire situation.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Exercise care to avoid damage to sprin-
klers before, during, and after installa-
tion. Never paint, plate, coat, or other-
wise alter automatic sprinklers after they
leave the factory.
Never repaint factory-painted Cover
Plates. When necessary, replace cover
plates with factory-painted units. Non-
factory applied paint can adversely de-
lay or prevent sprinkler operation in the
event of afire.
Replace sprinklers that:
were damaged by dropping, striking,
wrench twisting, wrench slippage, or
the like.
were modified or over-heated.
are leaking or exhibiting visible signs
of corrosion.
Responsibility lies with owners for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards of
the National Fire Protection Association
(for example, NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or sprinkler manufacturer
regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Worldwide www.tyco-fire.com Contacts
Series TY-FRB - 28, 42, 56, and 80 K-Factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The TYCO Series TY-FRB, 2.8, 4.2,
5.6, and 8.0 K-factor, Upright, Pen-
dent, and Recessed Pendent Sprin-
klers described in this data sheet are
quick response, standard coverage,
decorative 3 mm glass bulb-type spray
sprinklers designed for use in light or
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
ping malls.
The recessed version of the Series TY-
FRB Pendent Sprinkler, where applica-
ble, is intended for use in areas with a
finished ceiling. This recessed pendent
sprinkler uses one of the following:
A two-piece Style 10 (1/2 inch NPT)
or Style 40 (3/4 inch NPT) Recessed
Escutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a
A two-piece Style 20 (1/2 inch NPT)
or Style 30 (3/4 inch NPT) Recessed
Escutcheon with 1/4 inch (6,4 mm) of
recessed adjustment or up to 1/2 inch
(12,7 mm) of total adjustment from the
flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Corrosion-resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be obtained
when exposed to corrosive atmo-
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and
installation of sprinkler systems and
components. Improper handling and
installation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
spheres. Although corrosion-resistant
coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently,
it is recommended that the end user
be consulted with respect to the suit-
ability of these coatings for any given
corrosive environment. The effects of
ambient temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level of the Series TY-
FRB Pendent Sprinklers is detailed
in Technical Data Sheet TFP356, and
Sprinkler Guards are detailed in Tech-
nical Data Sheet TFP780.
IL'L•)1DI
The Series TY-FRB Concealed Pendent
Sprinklers described herein must be
installed and maintained in compliance
with this document and with the appli-
cable standards of the National Fire
Protection Association, in addition to
the standards of any authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
- —
0-121
i Ii "1l
i •i jLJ
,•,
-
- -.-.
Sprinkler
Identification
Number (SIN)
TY1131: Upright 2.8K, 1/2- NPT
1Y1231: Pendent 2.8K, 1/2NPT
TY2131: Upright 4.2K, 1/2- NPT
1Y2231: Pendent 4.2K, 1/2" NPT
TY3131: Upright 5.6K, 1/2" NPT
TY3231: Pendent 5.6K, 1/2- NPT
TY4131: Upright 8.0K, 3/4" NPT
TY4231: Pendent 8.0K, 3/4" NPT
1Y4831: Upright* 8.0K, 1/2" NPT
TY4931: Pendent* 8.0K, 1/2" NPT
"Eastern Hemisphere Sales Only
MARCH 2OI TFPI7I
Alpha Fire Protection
Submittal Package
Job: 2793 Elrnwood Street
Carlsbad, Calif
Scope: Provide Fire Sprinklers to a
New Residential House
To: Greg Ryan @ Carlsbad Fire Prevention
From: Alpha Fire Protection
4203 Genesee Ave. #103-424
San Diego Calif. 92117
Cell (760) 917-9058
e-mail: alphafireprotection@hotmail.com
Submitted By: Don Riley
Cal. Lic. # 582853
AS140158