tqCCj /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312 I Fax: (800) 791-5500°
,a
rapid response
HOME FIRE SPRINKLER SYSTEM
Series LFII Residential
Concealed Pendent Sprinklers, Flat Plate
49 K-factor
General
Description
The Series LFlI (1Y3596) Residential
Concealed Pendent Sprinklers are
decorative, fast response, fusible sol-
der sprinklers designed for use In resi-
dential occupancies such as homes,
apartments, dormitories, and hotels.
The cover plate assembly conceals
the sprinkler operating components
above the ceiling. The flat profile of the
cover plate provides the optimum aes-
thetically appealing sprinkler design.
In addition, the concealed design of
the Series lFii (TY3596) provides 1/2
inch (12,7 mm) vertical adjustment.
This adjustment reduces the accuracy
to which the fixed pipe drops to the
sprinklers must be cut to help assure
a perfect fit installation.
The Series LFIl are to be used in wet
pipe residential sprinkler systems for
one- and two-family dwellings and mo-
bile homes per NFPA 13D; wet pipe
residential sprinkler systems for resi-
dential occupancies up to and includ-
ing four stories in height per NFPA
13R; or, wet pipe sprinkler systems for
the residential portions of any occu-
pancy per NFPA 13.
The Series L.Fil (TY3596) has a 4.9
(60,5) K-factor that provides the re-
quired residential flow rates at reduced
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the INSTALLER
WARNING that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can pennanently damage
a sprinkler system or Its compo-
nents and cause the sprinkler to fall
to operate in a fire situation or cause
it to operate prematurely.
pressures, enabling smaller pipe sizes
and water supply requirements.
The Series LFiI (1Y3596) has been
designed with heat sensitivity and
water distribution characteristics
proven to help in the control of residen-
tial fires and to improve the chance for
occupants to escape or be evacuated.
The Series LFli (1Y3596) Residential
Concealed Pendent Sprinklers are
shipped with a Disposable Protective
Cap. The Protective Cap is temporarily
removed for Installation, and then it
can be replaced to help protect the
sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro-
tective Cap can also be used to mark
the center of the ceiling hole into pies-
tar board, ceiling tiles, etc. by gently
pushing the ceiling product against the
Protective Cap. When the ceiling in-
stallation is complete the Protective
Cap is removed and the Cover Plate
Assembly installed.
WARNINGS
The Series LFll (TY3596) Residential
Concealed Pendent Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing Jurisdiction. Failure to do so may
Impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
SprinkleriTvlodel
Identification
Number
SIN TY3596
Aft
Technical
Data
Approvals:
UL and C-UL Listed.
Maximum Working Pressure:
175 psI (12.1 bar)
Discharge Coefficient:
K = 4.9 GPM/ps1112 (70,6 LPM/har112)
Temperature Rating:
160°F/71°C Sprinkler with
135°F/579C Cover Plate
Vertical Adjustment:
1/2 inch (12,7 mm)
Finishes:
Cover Plate:
Fiat White, Bright White, Chrome, or
Custom
Physical Characteristics:
Body .............. Brass
Cap .............. Bronze
Saddle ............. Brass
Sealing Assembly ..........
.:... Beryllium Nickel w/ Teflont
Soldered Link Halves .....Nickel
Leyer ..............Bronze
Compression Screw ......Brass
Deflector ......Copper or Brass r Guide Pin Housing .....Bronze U LJJ_.
Page 1 of 4 JANUARY, 2008 TFP442
These plans have liten reviewed br apparent compliance
with the cuirent applicable codes and standards it) Cotce in I he iuri,cliclion. The owner orcontractor may tit lli/e
this resiess in suppi'rt of all application br a huildin
permit with the express understanding thin this reviess
n no was re eves the ow ncr or con rue or oi their pmlessiiiitat engineer or architect for sole responsibility
for full compliance with said codes and standards. including the building code or for any responsihulty for
deficiencies. errors. omissions or -negligence in these
plans whether or not tinted it) this review.
Dale :/Cy'zc/07 Reviewer
0 RECOMMEND APPROVAL
RECOMMEND APPROVAL. AS NOTED
/
1
I
a
4
I
I
I
/
/
Page 2 of 4
1FP442
Minimum Flow (b) and
Maximum Maximum Residual Pressure
Coverage Spacing For Horizontal Ceiling
Area 1$ Ft. (Max. 2 Inch Rise
Ft. x Ft. (m) for 12 Inch Run)
(m x m)
160°F171°C
Sprinkler
12x12 12 13 GPM (49,2 LPM) (3,7 x 3,7) (3.7) 7.0 psi (0,48 bar)
14x14 14 13 GPM (53,OLPM) (4,3 x 4,3) (4,3) 7.0 psi (0,48 bar)
16x16 16 13 GPM (60,6 LPM) (4,9 x 4,9) (4,9) 7.0 psi (0,48 bar)
18x18 18 17 GPM (64,3 LPM) (5,5 x 5,5) (5,5) 12.0 psi (0,83 bar)
20 x 20 20 20 GPM (75,7 LPM) (6,1x6,1) (6,1) 16.7 psi (1,l5bar)
For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the
next highest coverage area for which hydraulic design criteria are stated.
Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated
using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.
TABLE A
NFPA 130 AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA
FOR THE SERIES LFII (7Y3596) RESIDENTIAL CONCEALED PENDENT SPRINKLER
Guide Pins ......Stainless Steel
Support Cup ..........Steel
Cover Plate ..........Copper
Retainer ............Brass
Cover Plate Ejection Spring .....
.Stainless Steel
tDuPont Registered Trademark
Operation
When exposed to heat from a fire, the
Cover Plate, which is normally sol-
dered to the Support Cup at three
points, falls away to expose the Sprin-
kler Assembly. At this point the Deflec-
tor supported by the Arms drops down
to its operated position. The fusible
link of the Sprinkler Assembly is com-
prised of two link halves that are sol-
dered together with a thin layer of sol-
der. When the rated temperature is
reached, the solder meltsand the two
link halves separate allowing the sprin-
kler to activate and flow water.
Design
Criteria
The Series LFll (1Y3596) Residential
Concealed Pendant Sprinklers are UL
and C-UL Listed for installation in ac-
cordance with the following criteria.
NOTE
When conditions exist that are outside
the scope of the provided criteria, refer
to the Residential Sprinkler Design
Guide TFP490 for the manufacturer's
recommendations that may be accept-
able to the Authority Having Jurisdic-
tion.
System Type. Only wet pipe systems
may be utilized.
Hydraulic Design. The minimum re-
quired sprinkler flow rate for systems
designed to NFPA 130 or NFPA 13R
are given in Table A as a function of
temperature rating and the maximum
allowable coverage areas. The sprin-
kler flow rate is the minimum required
discharge from each of the total
number of design sprinklers" as
specified in NFPA 13D or NFPA 13R.
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
Is to be the greater of the following:
The flow rates given in Table A for
NFPA 13D and 13R as a function of
temperature rating and the maxi-
mum allowable coverage area.
A minimum discharge of 0.1 gpm/sq.'
ft. over the "design area" comprised
of the four most hydraulically de-
manding sprinklers for the actual
coverage areas being protected oy
the four sprinklers.
Obstruction To Water Distribution.
Locations of sprinklers are to be if-, accordance with the obstruction rules
of NFPA 13 for residential sprinklers.
Operational Sensitivity. The sprin-
klers are to be installed relative to the
ceiling mounting surface as shown in
Figure 3.
Sprinkler Spacing. The minimum
spacing between sprinklers is 8 feet
(2,4 m). The maximum spacing be-
tween sprinklers cannot exceed the
length of the coverage area (Ref. Ta-
ble A) being hydraulically calculated
(e.g., maximum 12 feet for a 12 ft. x
12 ft. coverage area, or 20 feet for a 20
ft. x 20 ft. coverage area).
Installation
The Series LFII (TY3596) must be in-
stalled in accordance with the follow-
ing instructions:
NOTES
Damage to the fusible Link Assembly
during installation can be avoided by
handling the sprinkler by the support
cup only (i.e., do not apply pressure to
the fusible link Assembly).
A leak fight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
03/17/2005 09:53 7148792165 FIRE SPEC INC PAGE 03
QUICK RESPONSE fr&.OBJE A UTOMA TIC SPRINKLERS
SPRINKLER GL SERIES
CORPORATION UPRIGHT.FENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
DESCRIPTIONAND Oi'zrnioN CONVENTIONAL (OLD STYLE)
The Glob. Quick Response GL Series Sprinklers are a low
profile yet durable design which utilizes a 3mm frangible glass ampule
as the thermos.nsitive element. Na provides sprinkler operation
approximately six times faster than ordinary sprinklers. While the
Quick Response Sprinkler provides an aesthetically pleasing appear-
ance, it can be installed wherever standard spray sprinklers are specified when allowed by the applicable standards. It offers the
additional feature of greedy Increased safety to life and is available
In various styles, orlflcss, temp.rars ratings and finishes to meet
many varying design requirements. Quick Response Sprinklers QUICK RESPONSE should be used advisedly and under the direction of approving UPRIGHT CONVENTIONAL authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that contains
a precisely measured amount of fluid. When heat Is absorbed, the liquid within the bulb expand; Increasing the internal pressure. At
the prescribed temperature the internal pressure within the ampule
exceeds the strength of the glass causing the glass to shatter. This
results in water discharge which is distributed in an approved
pattern depending upon the deflector style used.
QUICK RESPONSE TECHNICAL DATA PENDENT VERTICAL
See reverse side for Approvals and Specifications.
Temperature Ratings. 135°F (5rC). I 55DF (68°C). 175-F (79°C).
200°F (93°C). 286°F (141 'C).
Water Working Pressure Rating. 175 psi (12 Bars).
* Factory tested hydrostatically to 500 psi (34 Bars).
1(0
Maximum low temperature glass bulb rating Is .67°F (-55°C). * Frame - bronze • Deflector * brass • Screw - brass
a Bulb seat - copper • Spring - nickel alloy • Seal - teflon QUICK RESPONSE Bulb - glass with alcohol based solution. 3mm size. HORIZONTAL SIDEWALl.
4077 AIRPARX DRIVE. SIANDISH. MICHIGAN 4E5S 919446.4583 • FAX 919446.9231
JUNE 2003 A-0 SULLETIN GU l3. REV. #5
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 4.31 - SUBMITTAL.
E1'1GINEERS : PREMIER FIRE PROTECTION. (619)-659-9795.
ADDRESS : 12651 Ridgeton Drive, Lakeside CA 92040.
LICENSE : 772285
DESIGNER : STEVE PETRI
DATE : 10-07-2007
FILE : TAMARACK
JOB NAME : TAMARACK LOFTS TWO HEAD CALC 16 X 16
LOCATION : 245 TAMARACK AVE.
DESIGN DATA.
DESIGN CRITERION:
MIN SPR FLOW
AREA PER SPRINKLER
TOTAL CALCULATED AREA
TOTAL SPRINKLERS CALCULATED
TWO HEAD CALC 16 X 16
13 Gpm
256 Sq Ft
512 Sq Ft
2
FLOW DATA.
TOTAL SPRINKLER FLOW
DOMESTIC DEMAND
TOTAL WATER REQUIRED
BASE OF RISER NODE: B
26.8 Gpm
5.0 Gpm
31.8 Gpm
FLOW: 31.8 Gpm PRESSURE: 33.5 Psi
AUTHORITY HAVING JURISDICTION : CARLSBAD FIRE
PHONE
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 4.31 - SUBMITTAL. Page 1
ENGINEERS : PREMIER FIRE PROTECTION. (619)-659-9795.
ADDRESS : 12651 Ridgeton Drive, Lakeside CA 92040.
Date: 10-07-2007 File: C:\WINDOWS\TAMARACK.RES
JOB : TAMARACK LOFTS TWO HEAD CALC 16 X 16
SOURCE I STATIC : 86.0 Psi RESIDUAL : 85.0 Psi FLOW : 26 Gpm
DESIGN I SPRINKLER MANUF : TYCO MODEL : LF11 4.9
I SPRINKLER Q : 13.0 Gpm VALVE : .0 Psi
I SPRINKLER P : 7.0 Psi METER : 6.0 Psi
NODE ELEVATION K- PRESSURE DISCHARGE
NO. Feet ----------------------------------------------------------- FACTOR Psi Gpm
1 32.0 4.9 7.0 13.0
2 32.0 4.9 7.9 13.8
3 27.0 11.1
4 16.0 19.4
5 8.0 25.5
T 8.0 27.9
B .0 33.5 5.0 DOME
A .0 41.5
M 3.0 46.2
5 3.0 SOURCE 55.9 31.8
SPRINKLERS FLOWING : 2
AREA PER SPRINKLER : 256 Sq Ft
TOTAL DESIGN AREA : 512 Sq Ft
MIN SPRINKLER FLOW : 13 Gpm
REQUIRED DENSITY : .051 Gpm/Sq Ft
COMPUTED DENSITY : .051 Gpm/Sq Ft
TOTAL SPRINKLER FLOW : 26.8 Gpm
TOTAL DOMESTIC FLOW : 5 Gpm
TOTAL WATER REQUIRED : 31.8 Gpm
TOTAL SPRINKLER PRESS : 49.9 Psi
WATER METER LOSS : 6.0 Psi
VALVE FIXED LOSS : .0 Psi
Copyright (2003)
SUPPLY PRESS AVAILABLE : 84.6 Psi by
DEMAND PRESS REQUIRED : 55.9 Psi Hydronics Engineering
PRESSURE CUSHION : 28.7 Psi 34119 Fremont Bi, Suite 609
Fremont, Ca., 94555
MAXIMUM VELOCITY : 12.4 F/S (510) 487-9160
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 4.31 - SUBMITTAL. Page 2
ENGINEER : PREMIER FIRE PROTECTION. (619)-659--9795.
ADDRESS 12651 Ridgeton Drive, Lakeside CA 92040.
Date: 10-07-2007 File: C:\WINDOWS\TANARACK.RES
JOB : TAMARACK LOFTS TWO HEAD CALC 16 X 16
PIPE BEG FLOW K-FACTOR LENGTH C-FACTOR PRESSURE
NO. Gpm FITTING TYPE FTG FR- LOSS Psi
END DIAMETER TOTAL (Psi/Ft)
1 q= 13.0 K=
-------------------------------------------------------------------------------
4.9 L= 30.0 Pt 7.0 Pt 7.0
1 Q= 13.0 F= BBBLLR F'= 30.0 C= 150 Pe 2.2 Pv -.1
Vel= 4.4 D= 1.101 TL= 60.0 .0307 Pf 1.8 Pn 6.9
3 Pt 11.1
2 q= 13.8 K= 4.9
--------------------------------------------------------------------------
L= 10.0 Pt 7.9 Pt 7.9
2 Q= 13.8 F= BLL F= 19.0 C= 150 Pe 2.2 Pv -.1
Ve1= 4.6 D= 1.101 TL= 29.0 .0341 Pf 1.0 Pn 7.8
3 Pt 11.1
3 q= .0 K .0
--------------------------------------------------------------------------
L= 13.0 Pt 11.1 Pt 11.1
3 Q= 26.8 F= BBL F= 17.0 C= 150 Pe 4.8 Pv -.5
Ve1= 9.0 D= 1.101 TL= 30.0 .1168 Pf 3.5 Pn 10.5
4 Pt 19.4
4 q= .0 K= .0
--------------------------------------------------------------------------
L= 13.0 Pt 19.4 Pt 19.4
4 Q= 26.8 F= BB F= 10.0 C= 150 Pe 3.5 Pv -.5
Ve1= 9.0 D= 1.101 TL= 23.0 .1168 Pf 2.7 Pn 18.8
5 Pt 25.5
5 q= .0 K= .0
--------------------------------------------------------------------------
L= 8.0 Pt 25.5 Pt 25.5
5 Q= 26.8 F= LB F= 12.0 C= 150 Pe .0 Pv -.5
Ve1= 9.0 D= 1.101 TL= 20.0 .1168 Pf 2.3 Pn 25.0
T Pt 27.9
T q= .0 K= .0
--------------------------------------------------------------------------
L= 8.0 Pt 27.9 Pt 27.9
6 Q= 26.8 F= SCRR F= 10.0 C= 150 Pe 3.5 Pv -.5
Ve1= 9.0 D= 1.101 TL= 18.0 .1168 Pt 2.1 Pn 27.3
B Pt 33.5
B q= 5.0 DOME
--------------------------------------------------------------------------
L= 10.0 Pt 33.5 Pt 33.5
7 Q= 31.8 F= LLLB F= 26.0 C= 150 Pe .0 Pv -1.0
Ve1= 12.2 D= 1.03 TL= 36.0 .2217 Pt 8.0 Pn 32.4
A Pt 41.5
A q= .0 K= .0
--------------------------------------------------------------------------
L= 190.0 Pt 41.5 Pt 41.5
8 Q= 31.8 F= 4L4ECC F= 34.0 C= 150 Pe -1.3 Pv -.2
Ve1= 5.1 D= 1.59 TL= 224.0 .0268 Pt 6.0 Pn 41.3
M Pt 46.2
N q= .0 K= .0
--------------------------------------------------------------------------
L= 10.0 Pt 46.2 Pt 46.2
9 Q= 31.8 F= BG F= 6.0 C= 150 Pe .0 Pv -1.0
Ve1= 12.4 D= 1.025 TL= 16.0 .227 Pt 3.6 Pn 45.2
S Pt 49.9 --------------------------------------------------------------------------
Meter = 6.0
S Q= 31.8 <<<
--------------------------------------------------------------------------
SOURCE >>> Pt 55.9
E=>45-E1b L=>90-E1b B=>TeeBch R=>TeeRun C=>CouPlg S=>SwgChk G=>GatVlv
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 4.2 - SUBMITTAL.
Vf ENGINEERS : PREMIER FIRE PROTECTION. (619)-659-9795. .01 ADDRESS : 12651 Ridgeton Drive, Lakeside CA 92040.
DATE : 10-07-2007 FILE : C:\WINDOWS\TAMARACK.RES
JOB : TAMARACK LOFTS TWO HEAD CALC 16 X 16
PSI FIRE SPRINKLER HYDRAULIC GRAPH
100
90
80
70
60
50
40
30
20
10
0
10 15 20 25
0 Supply Curve
Static : 86.0
Resid : 85.0
Flow : 26.0
30 35 40 45 50
FLOW - Gpm
S Demand Curve
Avl Pr : 84.6 @ 31
Req Pr : 55.9 @ 31
Pr Cush: 28.7
Copyright: Hydronics Engineering, 2003.
34119 Fremont Bl, Suite 609,
Fremont, CA. 94555.
(510) 487-9160.