HomeMy WebLinkAbout381 TAMARACK AVE; ; FA1300387/15/24, 2:00 PM FA130038 Permit Data
City of Carlsbad
Fire Alarm Permit
Permit No: FA130038
Job Address: 381 TAMARACK AV
Permit Type: FALARM
Parcel No: 2060200807
Lot #: 0
Reference No.:
Status: APPROVED
Applied 6/4/2013
Approved: 6/4/2013
Issued: 6/4/2013
PC #: Inspector:
Project Title: SEA BREEZE VILLAS NEW R-2 FIRE SPRINKLER MONITORING
SYSTEM
Applicant: Owner:
BAY ALARM COMPANY TONY SFREDDO
4883 RONSON CT SUTE C
SAN DIEGO, CA 92111
714-719-9334 11LIsIrnI;I;B]
Fees ($) Add'I Fees ($)
I
Total ($) Balance ($)
286 0
-
286 0
about:blank 1/1
-:f--A ~ ~~g
F,-
4883 Ronson Court, Suite C
San Diego, CA 92111 1 (800) 470-1000
Contractor License # 880138
I. PROTECTED PREMISE
Sea Breeze Villas Group
381 Tamarack Ave.
Carlsbad, CA 92008
H. MONITORING COMPANY
Bay Alarm Company
60 Berry Drive
Pacheco, CA 94553
800-470-1000
California Alarm Operating License
Number: ACO28
EQUIPMENT SUPPLIER & INSTALLER
4883 Ronson Court, Suite C
San Diego, CA 921111(800)470-1000
Contractor License # 880138
_•SLLWQi
6.8 XR100FC Series Power Requirements
During AC power failure, the XR100FC Series panel and all connected auxiliary devices draw their power from the battery.
All devices must be taken into consideration when calculating the battery standby capacity. The following table lists the
XR100FC Series panel power requirements. You must add the additional current draw of keypads, zone expansion modules,
smoke detector output, and any other auxiliary devices used in the system for the total current required. The total is then
multiplied by the number of standby hours required to calculate the total ampere-hours required.
Standby Battery Power Calculations Standby Current Alarm Current
XR100FC Series Control Panel Qty 1 Qty 1 - 180mA 180 mA
Relay Outputs 1-2 (ON) Qty 180mA 180 mA
30mA Qty 30m
Switch Grounds 3-6 (ON) Qty Qty _______ 5mA 5mA Active Zones 1-8 Qty x _______ Qty x *2mA
Active Zones 9-10 Qty 1.6mA Qty _______ 30mA
2-Wire Smoke Detectors Qty 4A Qty _______ 0.1mA 0 imA Panel Bell Output ______
- 1500mA mA
893A Dual Phone Line Module Qty _______ x 12mA Qty _______ x 50mA
462N Network Interface Card Qty x 50mA Qty _______ x SOmA
463G Digital Cellular Communicator Card Qty _______ x 22mA Qty x 22mA
463C CDMA Cellular Communicator Card Qty _______ x 22mA Qty _______ x 22mA
481 Expansion Interface Card Qty _______ x 15mA Qty x 15mA
CellComRT Digital Cellular Communicator Qty _______ x 21mA Qty x 21mA
630F Remote Fire Command Center Qty _______ x 63mA Qty _______ x 92mA
733 Wiegand Interface Module Qty x 30mA
Active Zones (EOL Installed) Qty x 30mA Qty x _______ *2mA
Annunciator (ON) Qty x 1 6mA Qty _______ x 20mA
734 Wiegand Interface Module Qty _______ 15mA Qty _______ x 15mA
Active Zones (EOL Installed) Qty 1.6mA Qty x *2mA
Annunciator (ON) x Qty _______ x 20mA
734N Wiegand Interface Module Qty x 146mA Qty x _______ 148mA
Active Zones (EOL Installed) Qty _______ x 1.6mA Qty _______ x *2mA
Annunciator (ON) Qty _______ x 20mA
Wiegand Reader Qty _______ x 200mA Qty _______ x 200mA
734N-WiFi Wiegand Interface Module Qty _______ x 146mA Qty _______ x 148mA
Active Zones (EOL Installed) Qty _______ x 1.6mA Qty x *2mA
Annunciator (ON) Qty _______ x 20mA
Wiegand Reader Qty _______ x 200mA Qty :x 200mA
860 Relay Output Module (one relay active) 34mA 34mA
All four relays active Qty x 138mA Qty x 138mA
865 Style W or X Notification Module Qty x 26mA Qty x 85mA
866 Style W Notification Module Qty x 45mA Qty x 76mA
867 LX-Bus Style W Notification Module Qty x 30mA Qty x 86mA
869 Dual Style D Initiating Module Qty x 25mA Qty x 75mA
1100X Wireless Receiver Qty x 46mA Qty x 46mA
1100XH Wireless High Power Receiver Qty x 160mA Qty x 160mA
7060/7160 Thinline/7060A Aqualite Keypad Qty x 72mA Qty x 80mA
7063/7163 Thinhine/7063A Aqualite Keypad Qty x 85mA Qty x lOOmA
7070/7170 Thinline/7070A Aqualite Keypad 72mA Qty x 87mA
Active Zones (EOL Installed) Qty x 1.6mA Qty x *2mA
7073/7173 Thinline/7073A Aqualite Keypad 85mA Qty x lOOmA
Active Zones (EOL Installed) Qty x 1.6mA Qty x *2mA
7760 Clear Touch Keypad Qty x 65mA Qty x 115mA
Copy Sub-Totals to next page Sub-Total Standby ______mA Sub-Total Alarm mA
*Based on 10% of active zones in alarm.
Digital Monitoring Products - - XR100FC Series Installation Guide
10
Standby Battery Power Calculations Standby Current Alarm Current
736P POPIT Interface Module Qty x 25mA Qty x 25mA
Radionics Popex, POPITs, OctoPOPITs Qty _______ x __mA Qty _______ x _mA
738A Ademco Wireless Interface Module Qty x 75mA Qty _______ x 75mA
710 Bus Spl itter/ Repeater Module Qty x 32mA Qty x 32mA
711 Zone Expansion Module Qty x ilmA Qty _______ x limA
Active Zone (EOL Installed) Qty x 1.6mA Qty _______ x *2mA
714 Zone Expansion Module Qty x 7mA Qty _______ x 7mA
Active Zones (EOL Installed) Qty x 1.6mA Qty _______ x *2mA
712-8 Zone Expansion Module Qty x 17mA Qty _______ x 17mA
Active Zones (EOL Installed) Qty x 1.6mA Qty _______ x *2mA
714-8, 714-16 Zone Expansion Module Qty x 20mA Qty _______ x 20mA
Active Zones (EOL Installed) Qty x 1.6mA Qty _______ x *2mA
715 Zone Expansion Module Qty x 7mA Qty - x 7mA
Active Zones (EOL Installed) Qty x 4mA Qty _______ x *30mA
2-Wire Smokes Qty _____ x .1mA Qty _____ x .1mA
715-8, 715-16 Zone Expansion Modules Qty x 20mA Qty x 20mA
Active Zones (EOL Installed) Qty x 4mA Qty _______ x *30m
2-Wire Smokes Qty x .1mA Qty. ______ x .1mA
716 Output Expansion Module Qty x 13mA Qty : x 13mA
Active Form C Relays Qty ______ x 12mA
717 Graphic Annunciator Module Qty x lOmA Qty _______ x lOmA
Annunciator Outputs Qty _______ x imA
521LX, 521LXT Smoke Detectors Qty x 8 8mA Qty _______ x *28mA
Aux. Powered Devices on Terminals 7 and 11 mA mA
Other than Keypads and LX-Bus Modules
This page only Sub-Total Standby _mA Sub-Total Alarm mA
Sub-Totals from previous page Sub-Total Standby mA Sub-Total Alarm mA
*Based on 10% of active zones in alarm Total Standby mA Total Alarm mA
Total StandbymA x number of Standby Hours needed = mA-hours
Total Alarm mA +mA-hours
Total mA-hours
X .001
= __Amp-hrs Required
Refer to section 6.9 for standby battery selection.
XR100FC Series Installation Guide Digital Monitoring Products
11
I t SI4JLL4 MIL J OI
6.9 Standby Battery Selection
To choose the type and number of batteries needed for 24, 60, or 72 hours of standby power based on the Amp Hours
Required calculation from section 6.8 XR100 Series Power Requirements, perform the following:
Select the desired standby hours required from the table below: 24, 60, or 72 hours
Select the desired battery size: Model 368 (12 VDC 4.5 Ah), Model 369 (12 VDC 7 Ah),
Model 367 (12 VDC 7.7 Ah), Model 365 (12 VDC 9 Ah), Model 366 (12 VDC 18 Ah).
Select a Max. Ah Available number that is just greater than the number calculated in Amp Hours Required.
Install the number of batteries shown in the corresponding No. of Batteries required column.
Example: If the Amp Hours Required calculation equals 22 Ah for 24 hours of standby time and 4.5 Ah batteries
are desired, install six (6) Model 368 (12 VDC, 4.5 Ah) batteries.
For listed installations, all batteries shall be installed in a DMP Model 341, 349, 350 or 352S enclosure and all wiring shall
run through conduit. The enclosure shall be installed to the left of the XR100FC Series enclosure to ensure Battery and AC
wire separation.
24 hours of standby power
4.5 Ah Batteries
Max. Ah No. of
Available Batteries
8 2
12 3
I 16 I 4 I
24
28
32
36
7 Ah Batteries
Max. Ah No. of
Available Batteries
6 1
12 2
18 3
24 4
31 5
37 6
43 7
7.7 Ah Batteries
Max. Ah No. of
Available Batteries
6 1
13 2
20 3
27 4
34 5
41 6
9 Ah Batteries
Max. Ah No. of
Available Batteries
8 1
16 2
24 3
32 4
40 5
18 Ah Batteries
Max. Ah No. of
Available I Batteries
16 1
32 2
48 3
Note: 48 hours is the typical battery recharge time for any of the Number of Batteries shown in
this section.
60 hours of standby power
7 Ah Batteries
Max. Ah No. of
Available Batteries
13 2
20 3
27 4
33 5
47
54
60
67
7.7 Ah Batteries
Max. Ah No. of
Available Batteries
14 2
22 3
29 4
37 5
44 6
52 7
59 8
67 9
9 Ah Batteries
Max. Ah No. of
Available Batteries
17 2
26 3
34 4
43 5
52 6
61 7
69 8
18 Ah Batteries
Max. Ah No. of
Available I Batteries
17 1
34 2
52 3
69 4
Note: 48 hours is the typical battery recharge
time for any of the Number of Batteries shown
in this section.
72 hours of standby power
9 Ah Batteries
Max. Ah I No. of
Available I Batteries
16 2
25 3
33 4
42 5
50 6
59 7
18 Ah Batteries
Max. Ah No. of
Available Batteries
16 1
33 2
50 3
67 4
Note: 72 hours is the typical battery recharge time required for any of the Number of Batteries
shown in this section.
Note: If the Amp Hours Required calculation is greater than any Max. Ah Available number shown on a table, then add
power supply(s) to power some system devices allowing the Amp Hours Required calculation to be reduced. See the 710
Bus Splitter! Repeater Installation Guide (LT-0310).
Digital Monitoring Products XR100FC Series Installation Guide
12
11,2 Compatible 2-Wire Smoke Detector Chart
Manufacturer Model Detector Base Base DC # of Zone Panel
ID ID Voltage Detectors Expansion Zones
Range (12V/24V) Modules
Detection Systems DS230, DS230F B/A MB2W, MB2WL A 8.5-33 10 725
Detection Systems D5250, DS2SOTH B MB2W MB2WL A 8.5-33 10/12 9 & 10, 715,715-8,
715-16,725
Detection Systems DS25OHD B MB2W, MB2WL A 8.5-33 10 715 , 715-8,
715-16
9 & 10
Detection Systems DS260 B/A MB2W, MB2WL A 8.5-33 17 725
DS282, DS282TH, 715, 715-8, Detection Systems DS282THC, B 8.5-33 10/12 715-16, 725 9 & 10
DS282THS
Hochiki SLR-835B-2 HD-6 N/A 8-35 14 725 SLR-835BH-2
Hochiki SLR-24, SLR-24H HD-3 NS4-220 HB-3 15-33 15 725
Hochiki SIJ-24, DCD-190, HD-3 NS4-220 HB-3 15-33 15 725 DCD-135
Hochiki SLR-24, SLR-24H HD-3 NS6-220 HB-3 15-33 15 725
Hochiki SIJ-24 HD-3 NS6-220 HB-3 15-33 20 725
Hochiki DCD-190, DCD-135 HD-3 NS6-220 HB-3 15-33 16 725
429AT, 521B, 715, 715-8, Sentrol/ESL 521B 521NB, SO9A 71XT, 6.5-20 12 5-16 9 & 10
521NBXT
Sentrol/ESL 429C, 429CT S10A 8.5-33 12 725 52113/13XT
Sentrol/ESL 429CRT, 429CST, S11A 8.5-33 12 725 429CSST, S21CRXT
711U, 712U, 713- 701E, 70-lu, Sentrol/ESL 5U, 713-6U, 721U, S10A 702E, 702U SOO 8.5-33 12 725
721uT
701E, 701U,
Sentrol/ESL 731U, 723U S11A 702E, 702u, SOO 8.5-33 12 725
702RE, 702RU
System Sensor 1400 A 8.5-35 10 715, 715-8,
715-16
9 & 10
System Sensor 1151, 2151 A B110PL, B401 8.5-35 10/10 715, 715-8,
715-16,725 9 & 10
System Sensor 1451, 2451TH A B401, B40113 8.5-35 10 715,715-8,
715-16
9 & 10
System Sensor 1451DH A DH400 8.5-35 10 715 , 715-8,
7i5-16
9 & 10
2100T, 21008, 715, 715-8, System Sensor 2100TB, 2100D, A 8.5-35 10 7 1 5-16 9 & 10
2100TD
System Sensor 2400, 2400AT A 8.5-35 10 715, 715-8, 9 & 10 2400A1T, 2400TH 715-16
System Sensor 2451 A B401, B4O1B, . 85-35 10 715, 715-8, 9 & 10 DH400 715-16
System Sensor 2W-13, 2WT-B A 8.5-35 10 715, 715-8,
715-16
9 & 10
System Sensor 2WTA-B, 2WTR-B A 8.5-35 10 715, 715-8,
715-16
9 & 10
System Sensor DH100P, DH100LP A 8.5-35 10 715,715-8,
715-16,725
15,715-8,
715-16,725 9 & 10
Compatible 2-Wire Smoke Detectors
XR100FC Series Installation Guide Digital Monitoring Products
15
Photoelectric
Smoke Detectors
System Sensor's /3 series smoke detectors represent
significant advancement in conventional detection.
The i3 family is founded on three principles: installation
ease, intelligence, and instant inspection.
Features
Plug-in detector line, mounting base included
Large wire entry port
In-line terminals with SEMS screws
Mounts to octagonal and single-gang backboxes, 4-square
backboxes, or direct to ceiling
Stop-Drop 'N Lock attachment to base
Removable detector cover and chamber
Built-in remote maintenance signaling
Drift compensation and smoothing algorithms
Simplified sensitivity measurement
Wide angle, dual color LED indication
Loop testing via EZ Walk feature
Built-in test switch
Installation ease. The i3 line redefines installation ease with its
plug-in design. This allows an installer to pie-wire the bases included
with the heads.The large wire entry port and in-line terminals
provide ample room for neatly routing the wiring inside the base.
The base accommodates a variety of back box mounting methods,
as well as direct mounting with drywall anchors. To complete the
installation, il heads plug in to the base with a simple Stop-Drop 'N
Lock action.
Intelligence. il detectors offer a number of intelligent features
to simplify testing and maintenance. Drift compensation and
smoothing algorithms are standard with the i3 line to minimize
nuisance alarms. Two-wire i3 detectors needing cleaning can
generate a remote maintenance signal, when connected to the
2W-MOD2 loop test/maintenance module, or to a panel equipped
with the i3 protocol.This signal is indicated by LEDs located at the
module and the panel. The SENS-RDR,a wireless device, displays the
sensitivityof i3 detectors in terms of percent per-foot-obscuration.
Instant inspection. The j3 series provides wide-angle red and
green LED indicators for instant inspection of the detector's
condition: normal standby, out-of-sensitivity, alarm, or freeze trouble.
When connected to the 2W-MOD2 loop test/maintenance module
or a panel with the i3 protocol, the EZ Walk loop test feature is
available on two-wire il detectors.This feature verifies the initiating
loop wiring by providing LED status indication at each detector.
Agency Listings
&
LISTED
5911
Cj) Smoke Detector
Smoke detector shall be a System Sensor i3 Series model number listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems. The
detector shall be a photoelectric type (Model 2W-B, 4W-B) or a combination photoelectric/thermal (Model 2WT-B, 4WT-B) with thermal sensor rated at 135°F
(57.2°C). The detector shall include a mounting base for mounting to 31/2-inch and 4-inch octagonal, single gang, and 4-inch square back boxes with a plaster
ring, or direct mount to the ceiling using drywall anchors. Wiring connections shall be made by means of SEMS screws.The detector shall allow pre-wiring of
the base and the head shall be a plug-in type.The detector shall have a nominal sensitivity of 2.5 percent-per-foot nominal as measured in the UL smoke box.
The detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms. The detector shall provide
dual color LED indication which blinks to indicate power up, normal standby, out of sensitivity, alarm, and freeze trouble (Model 2WT-B, 4WT-B) conditions. When
used in conjunction with the 2W-MOD2 module, 2-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control
panel, and shall provide a loop testing capability to verify the circuit without testing each detector individually.
Operating Voltage Nominal: 12/24V non-polarized
Minimum: 8.5V
Maximum: 35V
Maximum Ripple Voltage 30% peak to peak of applied voltage
Standby Current 2-wire: 50 hA maximum average; 4-wire: 50 pA maximum average
Maximum Alarm Current 2-wire: 130 mA limited by control panel; 4-wire: 20 mA @12V, 23mA @ 24V
Peak Standby Current 2-wire: 100 VA, 4-wire: n/a
Alarm Contact Ratings 2-wire: n/a; 4-wire: 0.5 A @ 30V AC/DC
Dimensions (including base) 5.3 inches (127 mm) diameter; 2.0 inches (51 mm) height
Weight 6.301(178 grams)
Operating Temperature Range 2W-Band 4W-B: 32°F-1 20°F (0°C-49°C); 2WT-B and 4WT-B: 32°F-100°F (0°C-37.8°C)
Operating Humidity Range 0 to 95% RH non-condensing
Thermal Sensor 135°F (57.2°C) fixed
FreezeTrouble 2WT-B and 4WT-B only: 41°F (5°C)
Sensitivity 2.50/o/ft. nominal
InputTerminals 14-22 AWG
Mounting 31/2-inch octagonal back box
4-inch octagonal back box
Single gang back box
4-inch square back box with a plaster ring
Direct mount to ceiling
LED Mode Green LED
s -
Red LED Condition Duration
Power up Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds
Normal (standby) Blink every 5 seconds off
Out of sensitivity off Blink every 5 seconds
Freeze trouble off Blink every 10 seconds
Alarm off Solid
Ordering Information
2W-B No 2-wire 130 mA max. limited by control panel
2WT-B Yes 2-wire 130 mA max. limited by control panel
4W-B No 4-wire 20mA@ 12V,23mA@24V
4WT-B Yes 4-wire 20 mA @ 12V, 23mA @ 24V
Accessories
2W-MOD2 2-wire loop test / maintenance module RT Removal / replacement tool
SENS-RDR Sensitivity reader A77-AB2 Retrofit adapter bracket, 6.6 in. (16.76cm) diameter
155TEIff 02006 Sys em SenSOL 3825 Ohio Avenue. St. Charles, IL 60174
Phone: 800-SENSOR2. Fax: 630-377-6495 A05-0318-006-7/06. P1676
OTT IOU
SECUR
SIGNAuNG
Powerful UL Listed
addressable fire system
Proven reliability suitable for commercial and
industrial installations
Network ready option with on-board Ethernet
connection
Full range of zone expansion, communication, and
relay output capability
Flash Updateable
XR1 OOFCIXR500FC with network & the 463G
approved as primary communication by the
New York Fire Department (FDNY)
DMP XR1 OOFCIXR500FC panels deliver true flexibility
and expandability to cover all your fire needs.
XR100FC/XR500FC SERIES COMMERCIAL FIRE PANELS
SYSTEM FEATURES
UL listed for Fire Protective Signaling UL 864 Fire Warning
Up to 562 two-wire smoke detector or fire initiating zones
Up to .5 Amps 12 VDC smoke and auxiliary output with OVC
protection
Up to .7 Amps 12 VDC supervised bell output
Up to 506 fully-programmable Form C relays
Serial 3 Digital Dialer or CID reporting to multiple receivers
Eight communication paths between the panel and Central Station
Built-in DB-9 RS-232 (XR500FC/XR50ONFC) or LX-Bus (Selectable)
Built-in remote or on-site feature upgrade capability
Flash updateable: No more firmware chips to replace
2.000 event buffer
Multi-lingual menus available
Multiple on-board status LEDs
Up to 100 output schedules to control relays and panel outputs
32 individual reporting areas, with common areas
Output Groups: Maximum functionality—Minimum programming
XR100NFC/XR500NFC SYSTEM FEATURES
All above listed System Features
On-board Ethernet connection for Network MonitoringTM
Customizable check-in time and retry time
Suitable for multi-site applications where the Internet or
LAN/WAN is available
I
I
Digital SLC
Loop 2 I Any expansion device
can operate on SLC Loop
1 or2
FC SERIES FIRE PANELS
The XR100FC/XR500FC Series provides basic fire monitoring for any single site application. The XR100NFC/XR500NFC panels provide all
I the same basic fire monitoring as the XR100FCIXR500FC enhanced by the on-board Ethernet connection that allows the use of Network
MonitoringTM. Both panels come fully assembled from the factory with the following components:
CONTROL PANEL
I The XR1 ODFCIXR500FC Series addressable fire panel provides complete system control for local NAC operation and DACT or NET communication
to the central station. The microprocessor based panel also provides input for Class A zone expansion, conventional and addressable smoke
detectors, pull stations, and heat detectors.
I ENCLOSURE
The enclosure is comprised of cold rolled steel in Red to distinguish it for fire operation. For added security, the enclosure comes with a lock
and key.
I KEYPAD ANNUNCIATOR
The Fire Command Center mounted in the door offers a 32-character full text LCD readout that displays system events and menu prompts,
making it efficient and easy-to-use.
I TRANSFORMER AND ENCLOSURE
The 16 VAC. 56 VA wire-in transformer is factory installed and features a built-in PlC for power circuit protection.
I XR100FC/XR500FC TYPICAL NOTIFICATION/ANNUNCIATION
. 12or24VDC
NAC1
j, or Sync 12 24VDCI am I
Module Strobe Mini-Horn
NA
R _4V 12
Power Supply
12DC
Sync Module
24VDC
Motor Bell 505-12 or other 12/2INDC UL
Commercial Fire Approved Digital
Power Supplies. Annunciator Bus
Digital SLC Additional 630F
Loop 1 Fire Command
Centers
630F Fire
Command Center
FLEXIBLE COMMUNICATION
The XR100NFC/XR50ONFC has transitioned
from dialer-focused communications to a
true network and cellular communications
approach by providing stronger, multi-layered
panel communications that ensure a constant
link between the panel and Central Station.
Installers have the ability to create, configure
and manage up to eight communication
paths.
The unique DMP Serial 3 format supports 16
or 32-character user, zone and area names
to decrease the central station response time
and limit dependence on automation literal
tables for message conversion.
NETWORK OR CELLULAR
COMMUNICATION
Built-in Ethernet Communications enhance
network options and provide Standard and
Encrypted Line Security. Both UDP and TCP
are supported. The network option can be
used as the primary or backup path to the
digital dialer or cellular option.
The XR1 OOFCIXR500FC Command Processor
Panel used with the 4636 Digital Cellular
Communicator has earned the UL 864 listing
when used as the primary path (no backup
required) for commercial fire installations per
NPFA 72. The check-in and fail time settings
are programmed for five minutes. As the
backup path. the 4636 provides the security
of a communication link that continues to
function. even when land lines are cut or
compromised. This interface works on digital
cellular GSM/GPRS data networks over a
variety of carriers in the USA and Canada.
For XR100FC/XR500FC Series Fire Panels,
the 4636 plug-in Digital Cellular Communicator
can be used as the primary path, providing
installation flexibility where no land lines
are available. Can be used as a stand-alone
communicator without the need for a backup.
Used as the backup path. the 4636 provides the
security of a communication link that continues
to function, even when Land lines are cut or
compromised. This interface works on digital
Cellular GSM/GPRS data networks over a variety
of carriers in the USA and Canada.
I
I
I
I
1
.JI I
EIGHT COMMUNICATION PATHS
Create, configure, and manage up to eight
communication paths between the panel and
Central Station. Each path has its own panel
communication programming parameters,
and can be identified as either primary or
backup. This enables installers to configure a
reliable communication link, offering greater
confidence that the panel will always be
connected to the Central Station.
COMMUNICATION FUNCTION
DIAGNOSTICS
The enhanced diagnostic menu enables
technicians to check network and cellular
communication status, cell signal strength.
and email status from the keypad.
FIRE ZONE PROGRAMMING
Program zones for fire, fire verify, fire retard,
presignal. cross zoning, or fire supervisory.
This flexibility allows the ability to match
individual zone characteristics to the needs
of any area in the fire installation.
ZONE EXPANSION
The FC Series provides up to 562 zones.
programmable fora variety of fire applications.
The system provides Class B 12 VDC powered
zones, two on-board and four on the 715
Module, plus eight panel burglary zones.
Up to 60 zones are available on 15 keypad
addresses and up to 100 zones are available
on the built-in LXBusTM. Add up to 500 zones
using Expansion Modules,
FIRE VERIFY
Used primarily for smoke detector circuits to
verify the existence of an actual fire condition.
When a Fire Verify zone initiates an alarm,
the panel performs a Sensor Reset. If any
Fire Verify zone initiates an alarm within 120
seconds after the reset, an alarm is indicated.
If an alarm is initiated after another 120
seconds, the cycle is repeated.
NOTIFICATION CIRCUIT EXPANSION
Easily add NAC outputs to the XR100FC/
XR500FC system. Up to three CLass B modules
can be mounted within the FACP. ModeL 865 or
866 Class B NAC Modules may be combined
with a power supply to provide additional 4
Amp NAG outputs. Use an 867 on the SLC
Loop to further expand NAC circuits.
any DMP LCD keypad.
FLASH UPDATEABLE
The XR1 OOFC/XR500FC Series panel accepts
software updates from a remote Location
using Remote LinkTM software. When new
XR1 OOFC/XR500FC feature updates release.
perform the flash update remotely.
STATUS LIST
To provide maximum system flexibility, fire
zones may be programmed to display at a
specific keypad. In this manner. all fire zones
can be monitored in one location and other
zones can be programmed to display and be
monitored at different keypad Locations.
2,000 EVENT MEMORY
The Display Events feature allows users
to view up to 2.000 stored fire events, zone
events, user code and-schedule changes, and
supervisory events.
REMOTE LINK
The Remote Link programming software
takes advantage of the easy-to-use simplicity
of Microsoft® WindowsTM. The XR100FC/
XR500FC Series include an interface
connection for installers to use to connect a
laptop computer.
oulPuts
The XR100FC/XR500FC series allows the -
use of two SPDT relay outputs and four open
collector outputs, that may be activated by
zone or system events, by schedule, through
the User Menu or when a card is presented.
Output Groups allow multiple outputs to
activate with a single event and/or can be
assigned to a particular user profile up to 500
FIRE DRILL AND ONE-MAN outputs on the LX-Bus when optional output
WALK TEST expanders are used.
Users can test fire notification bells using
the Fire Drill feature. A special code is also OUTPUT SCHEDULES
available for installers to test the system. The Achieve maximum system flexibility with
one-man walk test feature allows a single 100 programmable schedules that simplify
technician to check the panel response to planning and operations. Control any
fire, burglary. panic and supervisory zones. contact-activated device with schedules that
automatically regulate relays and switched-
BUILT-IN PROGRAMMER ground outputs.
AND DIAGNOSTICS
No programming device is required. enabling MULTI-LINGUAL DISPLAYS
installers and service technicians to fully For additional flexibility, keypads attached
program the system and run diagnostics from to the XR100FC/XR500FC Series panels can
any DMP LCD keypad. Check the electrical display keypad Status List and User Menu text
state of zones. find individual zone numbers, using multiple languages. The user has the
check the LX-Bus for Missing. Overlapping option to select the language to use.
and/or Extra zones, and much more, all from
INTERFACE CARDS
461 Interface Adaptor Card I 462N Network Interface Card
462P Printer Interface Card I 463G Cellular Communicator
481 Expansion interface Card
AUXILIARY MODULES I .860 Relay Output Module
865 Style W/X Notification Circuit
Module ' 866 Style W Notification Circuit
Module
867 LX-Bus Notification Circuit
Module
869 Style 0 Class A Initiating Circuit I Module
893A Dual Phone Line Module
vii
- I
-
KEYPADS
630F LCD Remote Fire Command
EXPANSION MODULES
710 Bus Splitter/Repeater
711 Single Zone Expansion
714 4-zone Class-B Expansion
714-8 8-zone Class-B Expansion
714-16 16-zone Class-B Expansion
715 4-zone 2-wire smoke Expansion
715-8 8-zone 2-wire smoke Expansion
715-16 16-zone 2-wire smoke Expansion
716 Output Expansion,
4 Form C relays.
4 open collector outputs
717 Graphic Annunciator: 20 open
collector outputs
POWER SUPPLIES
505-12/LX 5 Amps @ 12 VDC
505-12L 5 Amps @ 12 VDC
505-12A 5 Amps @12VDC
PULL STATIONS
850 Series Pull Stations
SMOKE/HEAT DETECTORS
SLR-835B Smoke/Heat
5218/BXT Conventional Smoke. CleanMe
521 LX/LXT Addressable Smoke/Heat.
CleanMe
ACCESSORIES
300 Four-wire Harness
303 Silence/Reset Push-Button
305 Plug-in Output Relay
306 Tamper Harness
307-S Screw-On Tamper Switch
3012 Clip-On Tamper Switch
335 Intrusion Siren
370 Lightning Suppressor
374 Surge Voltage Suppressor
431 Output Harness
861 Power Distribution Module
CENTRAL STATION RECEIVERS
SCS-1 R Network Enabled Receiver
Compatable with Central Station
Receivers that accept Standard CID,
DD. or DMP Serial 3 messaging
SCS-VR (Virtual Receiver) Software only
solution that runs on a server for network IP
and cellular communications
DMP WIRELESS Two,, 1100X Receiver Way 1100XH High Power Receiver
1100R Repeater
1103 Universal Transmitter,
External Contact
1165 Commercial Smoke
Detector
1165H Commercial Smoke/Heat
Detector
1165H5 Commercial Smoke/Heat
Detector with Sounder
1181 Post Indicator Valve (UL)
1182 Outside Screw and Yoke Valve
Supervisory Switch (UL)
1183-135F Heat Detector
1183-135R Heat Detector
1184 Carbon Monoxide Detector
COMPUTER SOFTWARE
Remote Link Upload/Download
Programming Software
System Link End-User Management
Software
Alarm Monitoring Module
Command Center Module
Advanced Reporting Module
Account Groups Module
Link Server Application
1
I
I]
1
• SYSTEM SPECIFICATIONS
Primary Power (included) 16 VAC 56 VA transformer
Secondary Power 12 VDC Battery
Models 365, 366, 367. 368 or 369 I Output Rating
Bell Up to .7 Amps at 12 VDC
Smoke and Auxiliary Up to .5 Amps at 12 VDC
For UL installations, total bell, smoke, and auxiliary cannot I exceed 1.2 Amps using a 56 VA transformer.
Current Draw 180mA
Enclosure: 1 Material Cold-rolled steel (Red)
ORDERING INFORMATION
XR100FC-R
XR100NFC-R
XR100 Fire Control Panel
XRIOO Fire Control Panel with
Network
XR500FC-R XR500 Fire Control Panel
—_.XR500NFC-R XR500 Fire Control Panel with
--- Network
- —j
LISTINGS AND APPROVALS
Refer to the XR100FC and XR500FC Series Installation Guides (LT-1087.
LT-1088). XR100FC and XRSOOFC Series Programming Guides (LT-0896.
LT-0679) and specific compliance listings for installation and programming
requirements necessary to meet a particular approval.
California State Fire Marshall (CSFM)
FCC Part 15
FCC Part 68 Registration ID CCKALOOBXR500
New York City (FDNY COA #6123)
Underwriters Laboratories (UL) Listed
ANSI/UL 864 Fire Protective Signaling
For additional information, access www.dmp.com and select Compliance
- - SECURITY
SIGNALING
FDNY
LISTED
t u i
- Search dmpatarms
UL Listed Digital Cellular
Communication for
Fire Alarm Control Panels
The 4636/463C. when installed with a DMP
XR1 00/ XR1 OOFC or XR500/XR500FC Panel.
is UL approved as a primary (standalone)
fire communicator with no backup, and is
approved as a fire slave communicator,
compatible with any FACP. The 4636/463C
provides a dependable communications Link
between your alarm system panel and Central
Station.
Compared to a diaLup communication Link,
cellular can save significantly in annual
telecommunication costs
UL Listed as the Primary Communicator and
Fire Slave Input for the XR1 00/XR500 in Fire
Applications under ANSI/UL 864 Commercial
Fire (Meets NFPA 72)
Works on digital cellular data networks over a
variety of carriers
XR1 OON/XR500N with the 4636 approved
as primary communication by the New York
Fire Department (FDNY)
DIGITAL CELLULAR FIRE COMMUNICATORS
FEATURES
463G/463C enhances system security that conforms with • 4636/463C uses power from panel with low current draw
NFPA and UL requirements for Long standby battery life
Direct reporting to the DMP Central Station receiver, with • Can be equipped with local or remote antenna, offering
no relaying of alarm signals more flexibility when installing
Fire Slave Input option of the XR1 00/XR500 with • Ability to check signal strength indication at the keypad
4636/463C approved for any FACP • Messaging features transmit alarms/alerts to users via
Modular solution means easily updated for newer SMS text messages, and allow users to remotely control
technologies their panel via text commands
Eight-path redundancy with multiple message delivery
available
DMP Adaptive TechnoLogyTM switches communication
paths while maintaining supervision if the current path
I
I
Li
F]
UL LISTED
Install the DMP 46361463C Digital
Cellular Communicator in an XR100/
XR500 Series panel to create a UL
Listed, primary communication path
for commercial fire installations. The
Fire Slave Input option of the XR500
has also been approved under ANSI!
UL 864 (NFPA 722007 & 2010). allowing
it to be used as a Stave Communicator
for any FACP.
DIRECT REPORTING
The digital cellular communicators
transmit IP data packets directly from
the panel's processor over the wireless
data network. ALL of the messages
that are capable of being sent by the
control panel are received directly
by the DMP Central Station receiver.
There are no intermediary servers
or network operation centers, and no
retransmission or reinterpretation of
the information. Direct reporting means
faster response, with no concerns about
signals not being properly relayed or
intermediate communication Links
failing.
ADD-ON TO XR100/XR500
PANEL
The 463G!463C works as an easy-to-
install. XR100/XR500 expansion card,
with plug-and-play ease of installation.
No extra programming is required.
It provides full data delivery of DMP
Zones. Areas, and Users, with all names
and details included.
The remarkably compact 463G!463C
won't take up a lot of space in your
communications closet. The unit directly
installs in the panel expansion card slot,
which is mounted inside a sturdy UL-
Listed metal cabinet. Tamper protection
is also available for added security.
FULLY SUPERVISED
You're kept fully informed of system
status. The unit sends full reporting
messages including Zones. Areas.
and Users, with all names and details
included. Full supervision ensures that
the cellular communication path is
intact and functional.
EIGHT-PATH REDUNDANCY
Feet more secure with up to eight
paths of communication redundancy.
Select from ICR UDP. RS232. GPRS,
CDMA. Single Line Dialer, Dual Line
Dialer with multiple IP numbers, and
multiple telephone numbers. You
identify and configure your redundant
communication links via Remote Link.
A DACT (digital alarm communicator
transmitter) system may be
configured as:
Path 1 Type DD Primary and Path 2
Type DO Backup
Path 1 Type DD Primary and Path 2
Type CELL Backup
Path 1 Type DD Primary and Path 2
Type NET Backup
A NET or CELL system may be
configured as:
Path 1 Type NET Primary with no
Backup
Path 1 Type CELL Primary with no
Backup
Path 1 Type NET Primary and Path 2
Type DD Backup
Path 1 Type NET Primary and Path 2
Type CELL Backup
Path 1 Type CELL Primary and Path 2
Type NET Backup
ADAPTIVE TECHNOLOGYTM
If the primary communication path is
compromised or becomes unavailable.
Adaptive Technology almost instantly
switches to a designated backup path.
Where multiple backups are available.
communications can be programmed
to switch to another path as necessary.
The checkin frequency and programming
for a backup path adapt to the checkin
programming of the primary path.
When the primary path becomes
available, normal communications are
restored. Adaptive Technology provides
additional confidence in the integrity of
your system, while protecting you from
unexpected cellular service charges.
REDUCED EQUIPMENT NEEDS
With other cellular backup equipment,
you need to purchase additional
enclosures, power supplies, batteries,
cabling, and conduit connections. The
463G!463C reduces the number of pieces
of equipment you have to purchase.
It comes ready to mount, reducing
your initial costs and simplifying both
installation and ongoing operation.
REDUCED COMMUNICATION
COSTS
Adding the cellular communicator to the
DMP XR100/XR500 fire alarm control
panel can lower costs significantly
compared to dial-up connections.
Fire systems typically require two
dial-up tines that can be eliminated
and replaced with a single cellular
connection.
ANTENNA PLACEMENT
The unit includes both local and remote
SMA (S-band multiple access) antenna
connections, giving you added freedom
and flexibility during installation.
LOW CURRENT DRAIN
With its extremely low current drain
and long standby battery life, the
46313!463C will continue to provide a
communications Link for an extended
period of time, even during a power
failure. It draws half the current of other
comparable units.
SIMPLE TO INSTALL AND
PROGRAM
Connect the 463G or 463C to your panel,
attach the antenna and power, and
installation is complete. Programming
the 463G/463C is fast and simple,
accomplished within the panel itself.
After programming the 4636/463C
cellular communications path via
Remote Link. you will be presented with
the Activate SIM/MEID window to activate
your cellular plan. Once activated.
the wireless backup connection is
immediately online protecting your
communications link. No separate
programming utility is required.
SECURECOM CELLULAR
SERVICES
The 463G comes standard with a SIM
(Subscriber Identity Module) card ready
to use SecureCom Wireless Cellular
Service from DMP. The 463C does not
include a SIM Card and is activated with
the MElD number. With the 463G1463C
and SecureCom, you have a one-stop
resource for both hardware and cellular
service.
ENHANCED FIRE PROTECTION
Compared to dial-up connections, a
digital cellular communication link
provides greater reliability, protection
from sabotage. and is less prone
to being knocked out by weather.
Unlike mobile cellular connections.
the 463G/463C creates a fixed network
connection that minimizes hand-offs
and the chance for dropped connections.
When trouble conditions occur, they can
be more quickly diagnosed and often
corrected remotely.
The NFPA 72 code requires a test of
the entire communications path every
five minutes. The DMP Model XR100/
XR500 Command Processor Panel used
with DMP 46313/463C Digital Cellular
Communicator meets this requirement
when check-in and fail time settings
are programmed for five minutes. The
net result is a higher level of system
reliability in comparison with traditional
systems that rely on redundant phone
lines and the substantially less frequent
24-hour supervision reports associated
with that approach.
UPDATEABLE
In addition to being able to change
cellular carriers, you will also be
ready to take advantage of technical
improvements as they occur. The unit's
modular architecture enables seamless
upgrades as improved technology
becomes available.
MOBILE PLATFORMS
DMP mobile platforms provide you
with the tools
you need to build strong connections
with your customers.
MyAccessTM enables end users to
monitor and manage their systems
remotely from any mobile phone using
simple SMS texting.
The Virtual Keypad1M App puts a
keypad on the user's Apple iPhone®,
iPadTM. or Android compatible devices.
The ePadTM puts a Mobile Keypad on
any browser or mobile device.
Dealers can offer these much-
appreciated services to their customers
and realize the benefits of additional
recurring revenue.
MYACCESS
Your customers can send many of the
most common system commands to
their residential or commercial systems
via text messages. They can also choose
to have alerts sent to them each time
there's an arm/disarm, an alarm, or
other selected events.
Alerts can be transmitted by the panel
as text messages to up to three phones.
Users can also use MyAccess to interact
with any Z-Wave devices programmed
through their DMP panel, enabling them
to control lights, thermostats, and more
via text commands.
- Use any model
of cell phone
for Messaging 8yamMsb.o, Features
THE VIRTUAL KEYPAD APP --
Dealers can invite their customers to
begin using their APP to give them
control of their security system. The
Virtual Keypad allows them to arm or
disarm, and to check the status of their
cellular connected DMP security system
from anywhere they have cell service.
They can also access any Z-Wave home
control devices programmed through
their DMP panel and DMP cameras.
EPAD
This technology delivers the full function
and feel of a traditional LCD keypad
connected to any DMP panel.
)
Cftiiijr 9 M~W_ 00 ca~_G
DMP WIRELESS DEVICES FOR ANSI/UL 864 COMMERCIAL FIRE
Complete your fire system with other DMP wireless devices that are ANSI/UL 864 Listed for Fire Protective Signaling Systems.
TWO-WAY COMMUNICATION
Superior to traditional wireless
devices that just broadcast until the
zone is restored, DMP 1100 Series
require an acknowledgement from
the 1100 Series Receiver, indicating
successful communication. This smart
technology ensures that each and
every communication is received and
efficiently processed at the panel.
With the 900MHz frequency-hopping
spread-spectrum technology, clear
and accurate signal transmissions
without interference in practically any
environment is to be expected.
1100 SERIES RECEIVERS
The 1100 Series
Receivers: 1100X and
1100XH altowyoutoadd
up to 500 transmitters
and is required for
Wireless capability in
both regular and harsh
environments.
1103 UNIVERSAL TRANSMITTER
Model 1103 Universal Transmitter is
typically used in commercial fire or
burglary door/ window applications. It
offers the same look and features as
the 1101 transmitter, with the addition
of a 470k end-of-tine resistor and wall
tamper switch.
1165/1165H/1165H5 COMMERCIAL
SMOKE DETECTORS
be Model 1165 Smoke
Detector. 1165H Smoke!
Heat Detector, and
1165HS Smoke! Heat
\ Detector with Sounder
-' ncLudea tamper switch
that sends a trouble signal
if the detector is removed from the
mounting base.
1181 POST INDICATOR VALVE
The model 1181 PIV is a weather proof
and tamper resistant wireless switch
for monitoring the open position of fire
sprinkler control values of the post
indicator, butterfly and other types.
1182 OS&Y
The 1182 OS&Y Switch is used to monitor
the open position of an OS&Y (Outside
Screw and Yoke) type gate valve. The
1182 mounts conveniently to most OS&Y
valves ranging in size from /2" to 12". The
switch operates the external contacts of
the wireless transmitter when the valve
position is altered from an open state.
I
I
I
I
I
I
I I
I
I
SPECIFICATIONS
I Primary Power 12 VDC from panel
Current Draw (463G)
Standby 22 mA
Alarm 45 mA
I Current Draw (463C)
Standby 22 mA
Alarm 22 mA
COMPATIBILITY
I DMP XR1 00/XR500 Series using Software Version 202
or higher
ORDERING INFORMATION
I 463G 2G Digital Cellular Communicator (AT&T. T-Mobile.
Rogers)
463C 3G CDMA Cellular Communicator (Verizon)
ACCESSORIES
I 380-400 Replacement Level 400 SIM Card
381-12 12 Coax Extension
- 381-25 25 Coax Extension
383 Rubber Duck Antenna
,__ 386 —WatLMount Antenna Bracket
ACCESSORIES CONT,
387-1 3dB Fiberglass Antenna w/bracket
387-2 2dB Attack Enclosure Antenna
387-3 3dB MEG Antenna
387-25 SMATO N CABLE, 25FT. LMR195
387-50 SMATO N CABLE. 50FT. LMR195
LISTINGS AND APPROVALS
463G
California State Fire Marshal (CSFM)
FCC ID: MIVGSM0308
Industry Canada: 4160AGSM0308
New York City (FDNY COA#6123)
463C
FCC ID: MIVCNNO301
Industry Canada: 4160ACNN0301
Underwriters Laboratories (UL) Listed (463G/463C)
ANSI/UL 365 Police Station Connect Burglar Alarm Systems
ANSI/UL 985 Household Fire Warning System Units
ANSI/UL 1023 Household Burglar Alarm System Units
ANSI/UL 1076 Proprietary Burglar Alarm Units & Systems
ANSI/UL 1610 Central Station Burglar Alarm Units Ill
Simple Expansion
Solutions
-I_
SECURITY
SIGNALING
LISTED
Expand your DMP Command Processor panel options
with a wide array of expansion modules.
Add supervised Class B burglary zones.
Connect non-powered burglary or fire type
devices for intrusion, glassbreak, and motion
detection.
Add 12 VDC zones for addressable 2-wire smoke
detectors with 715 moduels.
ZCD NE EXPAKSUCK MODULES:
ZONE EXPANSION NODULE FEATURES
Provides Class B zones for burglary and fire
Compatible with DMP Command Processor Panels that allow
zone expansion
Suitable for mounting near protection devices
Connect devices using 4-wire bus
Easily mount attractive cases on wall or 3-gang box
Compatible with all panel zone types
Easy connection to 4-wire keypad or LX-Bus
Proven design ensures stability and performance
Data LED on zone expander indicates good panel
communication
Durable and attractive plastic or metal housing
Low current draw
Can be powered from panel or auxiliary power supply
' r_'-::''•--:/ :- ' c •: r
708 BUS EXTENDER MODULES 710 USE ON THE DMP LXBUSTE
The modules can be used on the LX-Bus'
of DMP Command Processor" Panels. The
modules connect to the 4-wire bus and
use only one zone address. To assign an
additional zone expander use the next
available zone address.
CONNECT TO KEYPAD BUS
You can also use the modules as an
addressed device on the keypad data
bus of DMP Command Processor panels.
Simply set the module to an available
keypad address and connect the wiring
to the appropriate screw terminals.
SIMPLE ADDRESSING
Address the 711, 714, 714-8, 714-16,
715, 715-8, 715-16, and 725 modules by
setting two on-board rotary switches with
a small screwdriver. The 712-8 uses slide
dip switches.
EASY INSTALLATION
Zone Expansion Modules are mounted in
a decorative plastic housing suitable for
installing outside the panel enclosure,
such as on walls or single gang boxes.
After all wiring connections are made,
the cover snaps on to form tight-fitting
protection against incidental contact or
tampering.
714-8, 714-16, 715-8, and 715-16 Zone
Expanders are housed in a rugged,
20-gauge, cold- rolled steel enclosure.
You may also mount the 708, 710, 710F,
and 725 modules inside a DMP enclosure
using the 3-hole configuration and the
provided standoffs. The 712-8 only
mounts using the 3-hole configuration
and provided standoffs.
ZONE PROGRAMMING
Program the zone on the modules with
any of the panel's available zone types
for use in burglary applications including
Arming type zones when used with
keyswitches.
The expansion zones are programmable
for annunciation on DMP keypads
connected to the panel. Each zone
can also be individually programmed to
report alarms, troubles, and restorals to
remote DMP SCS-1R Receivers.
The 708 Bus Extender Modules allow you
to increase the length of wire used to run
an LX-Bus or keypad bus by a maximum of
4,000 feet, while providing immunity to
noise on the wires. The 708 Bus Extenders
are received from the factory as a pair of
modules that connect between the panel
and LX-Bus or keypad bus devices.
Use the 708 Modules for applications
that include running wire over long
distances, through noisy environments,
or where the bus is bundled with other
wires, such as telephone company wire.
The 708 Extender can be used on all DMP
panels.
708 FEATURES
Extends Keypad Bus or LX-Bus by
4000 feet with one pair of modules
Connects to an auxiliary power
supply for added power
Uses existing wire: No need to run
additional wire
Allows twisted pair and/or shielded
wire between the 708 modules
7101710F BUS SPLIT TER!
REPEATER MODULES
The 710 and 710F Bus Splitter/Repeater
Modules allow you to expand the typical
LX-Bus or Keypad bus installation both
in the number of devices and the length
of the wire used. Each 710/710F Module
provides three bus connections each
up to 2,500 feet. When using multiple
modules, the total distance of all circuits
can be an incredible 15,000 feet!
As a splitter, the 710 provides superior
mechanical wire connecting capability for
up to three additional 12 VDC LX-Bus or
keypad bus circuits. This makes the 710
module an excellent junction box when
terminating multiple LX-Bus/keypad bus
runs at one location. As a repeater, the
710 module can be installed at the end of
an LX-Bus or keypad bus circuit to allow
an additional circuit to be added, thus
increasing the total wire length.
TI OF
As well as providing all of the functions
of the 710 listed above, the 710F also
allows you to use the 725 Zone Expander
to expand the number of 24 VDC zones.
The 710F Bus Splitter/Repeater allows
the connection of a 24 VDC power supply
to the 725 to power smoke detectors and
isolate the 24 Volt source from the panel.
Therefore, the 710F must be used when
using the 725 Zone Expander.
72-8 ZONE EXPANSION
MODULE
Expand your system at an affordable
price! You can connect non-powered
burglary devices to DMP Command
Processor panels using the 712-8 Module.
The 712-8 Module is compatible with
many intrusion contacts, glassbreak
detectors, motion detectors, and
intrusion detectors.
7E 1-8 FEATURES
Eight grounded, addressable burglary
zones
Set jumper for LX-Bus or Keypad bus
operation
Compatible with all DMP Command
Processor panels
Expand systems by daisy chaining a
second 712-8
Easily address using dip switches
Snaps into panel enclosure using
3-hole pattern
Separate zone 1K End-of-Line
resistors included
714/7I5 ZONE EXPANDERS
The 714 contains four Class B burglary
zones and is suitable for use with burglary
and fire devices that are normally opened
or normally closed. Individual zones are
supervised with 1k Ohm EOL resistors and
can be programmed with any burglary or
fire zone type.
The 715 contains four Class B powered
zones and is suitable for use with 12 VDC,
2-wire smoke detectors and non-powered
fire or burglary devices. Individual zones
on the 715 are supervised with a 3.3k
Ohm EOL resistor and can be programmed
with any burglary or fire zone type.
OPTIONAL ACCESSORIES
The standard wiring harness can be
replaced with the optional 7181 Plug-in
Screw Terminal.
The enclosure can also accommodate the
7191 Terminal Boards for the 714 or the
7201 Terminal Boards for the 715, which
pass through the wiring of the panel's
LX-Bus. 1K EOL resistors are included
with the 7191 and 3.3K resistors are
included with the 720T.
7141715 FEATURES
Four protection zones on each
module
Comes with 12-conductor wire
harness
Optional 12-position screw terminal
7-8. 714.-k 6,71 5-6, AND
715-16 DESCRIPTIOt
The expanders are housed in a Model
340 locking metal enclosure suitable
for mounting in a remote location.
Each expander provides screw terminal
strips for zone inputs and data bus
connections, a two position jumper to
designate connection to the keypad bus
or the LX-Bus, and an LED to indicate
communication with the panel. Separate
zone End-of-Line resistors are included
with each expander.
714-8/714-16 EXPANDERS
The 714-8 Expander contains 8 Class B
zones. The 714-16 Expander contains 16
Class B zones. Both are suitable for use
with normally open or normally closed
burglary and fire devices. Individual
zones are supervised with a 1k Ohm EOL
zone type.
715-8/715-16 EXPANDERS
The 715-8 Expander contains 8 Class B
powered zones. The 715-16 Expander
contains 16 Class B powered zones.
Both are suitable for use with 12 VDC
2-wire devices, such as smoke detectors
or with non-powered fire or burglary
devices. Individual zones are supervised
with a 3.3k Ohm EOL resistor and can be
programmed as any zone type.
714-8,714-16, 715-6, AND
715-16 FEATURES
8 or 16 protection zones per
expander
Durable metal enclosure housing
with lock and key
Individual screw terminals
accommodate 14 to 22 gauge wire
for easy connection
Suitable for mounting in a remote
location
725 2VDC EXPANSIOt
MODULE
The 725 provides four 24 VDC powered
zones that enable you to connect
2-wire smoke detectors to the XRSOO
Series, XR2500F, XR200, and XR200-485
Command Processor Panels. As a result,
the 725 provides you the flexibility to
retrofit a 24 Volt system without the need
to run more wire or change to 12 Volt
smoke detectors.
7S FEATURES
Provides four 24 VDC zones
Sensor reset performed through
panel relay or 716 Output Expander
Powered from 24 VDC power supply
Supervised operation
24 Volt surge protection from 710F
Provides ability to use 24 VDC 2-wire
smoke detectors
ill DESCRIPTION
The 711 Zone Expansion Module connects
to the panel's 4-wire keypad bus or
LX-Bus and are set to an address that
determines the reporting zone number.
The 711 provides one Class B zone for the
connection of detection devices.
711 FEATURES
Single-zone expander
Rugged screw terminals
accommodate 14 to 22 AWG
Board fits in Radionics POPIT housing
resistor and can be programmed as any • Easily mounted in 3-hole pattern
Easy rotary switch addressing
NOW
- Digital Monitoring Producto
:--
ZONE EXPANSION MODULE COMPARISONi CHART
Refer to the chart below for a comparison of the features for each DMP Zone Expansion Module.
Module Address Number of
Zones 3-Hole Plastic Case Operating
Voltage Compatible Panels
708 N/A N/A Yes Yes 12 VDC
ALIDMP
12 VDC
710 N/A N/A Yes Yes 12 VDC
710F N/A N/A Yes Yes
712-8 Dip Switch 8 Yes No 12 VDC
XT Series, XR100/XR500 Series, XR2500F
12 VDC
711 Rotary 1 No Yes 12 VDC
714 Rotary 4 Class B No Yes 12 VDC
714-8 Rotary 8 Class B No Metal Enclosure 12 VDC
714-16 Rotary 16 Class B No Metal Enclosure 12 VDC
715 Rotary 4 Class B No Yes 12 VDC
715-8 Rotary 8 Class B No Metal Enclosure 12 VDC
715-16 Rotary 16 Class B No Metal Enclosure
725 Rotary 4 24 VDC Class B No Yes 24 VDC XR500 Series, XR2500F
MODULE SPECIFICATIONS 714/715 SPECIFICATIONS
708 SPECIFICATIONS (NONE UL) Operating Voltage 8.8 to 15.0 VDC
Operating Voltage 8.8 to 15.0 VDC Operating Current
Operating Current 20mA Per Pair 714 Average 7mA + 1 .6mA per zone
Dimensions 4.5" X 2.75" X 1.75" Alarm 7mA + 2mA per zone
Maximum Distance 4,000 feet between the two 715 Average 7mA + 4mA per zone + 0.1 per 2-wire smoke
708 Modules Alarm 7mA + 58mA per shorted zone + 01 per
2-wire smoke + 30mA per smoke in alarm 710/71 OF SPECIFICATIONS Dimensions 45" X 2.75" X 1.75" Operating Voltage 8.8 to 15.0 VDC
Operating Current -
714-85, 714-16, 715-8, AND 71 5-16 SPECIFICATIONS
710 30mA Operating Voltage 8.8 to 150 VDC
710F 40mA Operating Current
Dimensions 4.5" X 2.75" X 1.75" 7148/16
Distance 2,500 feet (one module), Average 20mA + 1.6mA per zone
15,000 feet maximum Alarm 20mA + 2mA per zone
71 t SPECIFICATIONS 715-8/16
Average 20mA + 4mA per zone + 0.1 per 2-wire smoke Operating Voltage 88 to 15.0 VDC Alarm 20mA + 58mA per shorted zone + 0.1 per Operating Current 2-wire smoke 30mA per smoke in alarm ,+ Average 11 mA + 1 .6mA per active zone Enclosure 20-Gauge cold-rolled steel Alarm 11 mA + 2mA per zone in alarm
Zone Voltage 5 VDC (1.6mA across EOL) Dimensions 12.5" W x 11.5" H x 3.5" D
Dimensions 4.5" X 2.75" X 1.75" 714-8/-16 Color Gray
715-8/-16 Color Red
712-8 SPECIFICATIONS LISTINGS AND APPROVALS Operating Voltage 8.8 to 15.0 VDC Refer to the appropriate panel programming and installation guide
- Current Draw 17mA + 1 .6mA per active zone for specific compliance listings for installation and programming 17mA + 2mA per zone in alarm requirements necessary to meet a particular approval. Dimensions 4.5" H x 2.5"
Underwriters Laboratories (UL) Listed - 725 SPECIFICATIONS California State Fire Marshall (CSFM) Operating Voltage 24 VDC Nominal New York City MEA accepted (711, 714, 715 only) Average Current 8mA + 4mA per active zone -
Alarm Current 8mA + 4mA per active zone For additional information, access www.dmp.com and select + 30mA per smoke in alarm
+ 47mA per shorted device Compliance.
EOL Resistor Model 316 6.8k EOL
moot, -
2500 North Partnership Boulevard
M
-
[Tj . Springfield, Missouri 65803-8877 DigitIMonito.ingPrnthcte
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL -
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7165-1157:0123 Page 1 of 2
CATEGORY: 7165-- FIRE ALARM CONTROL UNIT (COMMERCIAL)
LISTEE: Digital Monitoring Products2500 N. Partnership Blvd, Springfield, MO 65803
Contact: Terry Shelton (417) 831-9362 Fax (417) 831-1325
Email: tshelton@dmp.com
DESIGN: Models XR500, XR500N, XRSOOE, XR100 XR100N, XR500FC, XRSOONFC, XR100FC, and
XR100NFC combination fire and burglary alarm control units. Local, remote station (PPU),
proprietary (PPU), and central station (PPU) services. Refer to listees data sheet for
additional detailed product description and operational considerations. System components:
XR500, XR500N, XR100 XR100N; Main Board
XR500FC, XR500NFC, XR100FC, XR100NFC; Main Board
349, 350, 350A, 352P, 352X; Enclosure
341; Battery Enclosure
630F, 690, 690F, 693, 790, 790F, 791, 793; Supervised LCD Keypads
7060, 7060A, 7063, 7063A, 7064, 7070, 7070A; LCD Keypads
7073, 7073A, 7074, 7760, 7160, 7160A; LCD Keypads
7163, 7163A, 7170, 7170A, 7173, 7173A; LCD Keypads
7560, 7560A, 7563, 7563A, 7570, 7570A, 7573, 7573A; LCD Keypads
325; Transformer Bracket
322, 327, 323; Transformer Adaptor
481, 462N, 462P, 462FM, 472; Interface Card
461; Interface Adaptor
714, 714-8, 714-16, 715, 711, 711E; Zone Expanders
715-8, 715-16, 725; Zone Expanders
Output Expander
Annunciator Module
860; Relay Module
865, 866, 867; Indicating Modules
869; Initiating Module
893A; Dual Phone Line Module
733, 734; Wiegand Interface
736P; Interface Module
710,710F; Bus Splitter
303; Reset/Silence Switch
iCOM, iCOM-E; Internet Alarm Router
1100X, 1100XH; RF (Wireless) Receiver
1100R; Wireless Repeater
1103; Wireless Transmitter
*463C,463G; Digital Cellular Communicator (may be used as the stand alone primary
*Rev. 10-22-12 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2012 Listing Expires June 30, 2013
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
Listing No. 7165-1157:0123
I Page 2 of 2
communicator)
RATING: 120 VAC, 0.5 A, 60 Hz primary, 12 VDC secondary
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as combination fire and burglary alarm control units for use with separately listed
electrically compatible initiating and indicating devices. Refer to listee's Installation
Instructions Manual for details.
These control units can generate a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
This control unit meets the requirements of UL Standard 864, 9th Edition.
NOTE: 1. The Fire Alarm Verification Feature (delay of fire alarm signal), the maximum
Retard/Reset/Restart period shall not exceed 30 seconds.
2. Burglary and other non-fire functions were not examined.
*Rev. 10-22-12 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2012 Listing Expires June 30, 2013
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7272-1653-.0152 Page 1 of 1
CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC
LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l Inc.3825 Ohio Ave, St. Charles, IL
60174
Contact: Trish Linhart (630) 377-6580 Fax (630) 377-7245
Email: trish.linhart@systemsensor.com
DESIGN: Models 2W-B, 2WT-B, 4W-B and 4WT-13 photoelectric type smoke detectors. Models 2W-B
and 2VVT-B are 2-wire and model 4W-B and 4WT-B are 4-wire detectors. Models 2WT-B and
4WT-B employ a thermistor type heat sensor (135°F). The heat sensor is are supplemental
to the detector and is not intended for use as a required heat detector. Refer to listees
printed data sheet for additional detailed product description and operational considerations.
RATING: 8.5-35 VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction. For vertical wall or ceiling
mount.
MARKING: Listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as photoelectric smoke detectors for use with separately listed compatible fire alarm
control units. Suitable for installation in open areas with air velocity range from 0-1000 ft/min.
NOTE: Formerly 7272-1209:210
06-20-05
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria Refer to listee s data sheet installation instructions and/or other
Date Issued: July 01, 2012 Listing Expires June 30, 2013
Authorized By: JASON DEWITT, Deputy State Fire Marshal
Fire Engineering Division