HomeMy WebLinkAbout961 PALOMAR AIRPORT RD; ; FA1300939/16/2020 FA130093 Permit Data
City of Carlsbad
Fire Alarm Permit
Permit No: FA130093
961 PALOMAR
Job Address: Status: PENDING
AIRPORT RD
Permit Type: FALARM Applied 12/4/2013
Parcel No: 2110403400 Approved:
Lot #: 0
Reference No.: Issued:
PC #: Inspector:
Project Title: BURGER LOUNGE TI—ADDITION OF KITCHEN HOOD
SUPPRESSION SYSTEM MONITORING. PROVIDE
MONITORING MODULES FOR UNIT DUCT DETECTORS THAT
ARE BEING PROVIDED BY OTHERS.
Applicant:
JJJ ENTERPRISES
533 S VINEWOOD ST
ESCONDIDO CA
760-747-3050
Owner:
M E R I PALOMAR PLACE L L C
C/O MISSION EQUITIES REAL ESTATE
12838 STEBICK CT
SAN DIEGO CA
[ Fees ($) Add'l Fees ($)Total ($)iBalance ($)
L 286 0 I6 1 a
1/1
! PISES
FIRE ALARM - SECURITY - LOW VOLTAGE SYSTEMS
Palomar Place Tenant Improvement
for
Burger Lounge
961 Palomar Airport Road Suite 116
Carlsbad, CA 92011
FIRE ALARM SYSTEM
FA130093
Palomar Place Tenant Improvement
for
Burger Lounge
961 Palomar Airport Road Suite 116
Carlsbad, CA 92011
FIRE ALARM SYSTEM BILL OF MATERIALS
NOTIFIER N?-100P ADDRESSABLE MINI MODULE
CSFM# 7300-0028:0230
Monitor Modules
NMM-100(A), NMM.IOOP(A),
KIII RA.InniAl sand tJflM.1flfl1A
DN-6999:C
fl@,'HOTIFIER'
I
for FireWarden Series Panels by Honeywell
General
Four different monitor modules are available for Notifier's Fire-
Warden Series intelligent control panels for a variety of appli-
cations. Monitor modules supervise a circuit of dry-contact
input devices, such as conventional heat detectors and pull
stations, or monitor and power a circuit of two-wire smoke
detectors (NZM-100(A)).
NMM-100(A) is a standard-sized module (typically mounts to a
4" [10.16 cm] square box) that supervises either a Style D
(Class A) or Style B (Class B) circuit of dry-contact input
devices.
NMM-100P(A) is a miniature monitor module a mere 1.3"
(3.302 cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D that
supervises a Style B (Class B) circuit of dry-contact input
devices. Its compact design allows the NMM-100P(A) to be
mounted in a single-gang box behind the device it monitors.
NZM-100(A) is a standard-sized module that monitors and
supervises compatible two-wire, 24 volt, smoke detectors on a
Style D (Class A) or Style B (Class B) circuit.
NDM-100(A) is a standard-sized dual monitor module that
monitors and supervises two independent two-wire Style B
(Class B) dry-contact initiating device circuits (lDCs) at two
separate, consecutive addresses in intelligent, two-wire systems.
NMM-100(A) Monitor Module
Built-in type identification automatically identifies this device
as a monitor module to the control panel.
Powered directly by two-wire SLC loop. No additional power
required.
High noise (EMF/RFI) immunity.
SEMS screws with clamping plates for ease of wiring.
Direct Decade entry of address: 01 - 99 on FireWarden-
100-2, 01 —50 on FireWarden-50.
LED flashes during normal operation and latches on steady
to indicate alarm.
The NMM-100(A) Monitor Module is intended for use in intelli-
gent, two-wire systems, where the individual address of each
module is selected using the built-in rotary switches. It pro-
vides either a two-wire or four-wire fault-tolerant Initiating
Device Circuit (IDC) for normally-open-contact fire alarm and
supervisory devices. The module has a panel-controlled LED
indicator.
NMM- 100(A) APPLICATIONS
Use to monitor a zone of four-wire smoke detectors, manual
fire alarm pull stations, waterflow devices, or other normally-
open dry-contact alarm activation devices. May also be used
to monitor normally-open supervisory devices with special
supervisory indication at the control panel. Monitored circuit
may be wired as an NFPA Style B (Class B) or Style D (Class
A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor
(provided) terminates the Style B circuit. No resistor is
required for supervision of the Style D circuit.
NMM-100(A) (Type H)
NMM-100'A) OPERATION
Each NMM-100(A) uses one of the available module
addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and the status (open/nor-
mal/short) of its Initiating Device Circuit (IDC). A flashing LED
indicates that the module is in communication with the control
panel. The LED latches steady on alarm subject to current
limitations on the loop).
NMM-100(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 '/DC.
Maximum current draw: 5.0 mA (LED on).
Average operating current: 350 pA LED flashing), 1 com-
munication every 5 seconds, 47k EOL.
Maximum IDC wiring resistance: 40 ohms.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
DN-6999:C .10/0312010 - Page 1 of 4
NMM-IOOP(A) Mini Monitor Module
Built-in type identification automatically identifies this device
as a monitor module to the panel.
Powered directly by two-wire SLC loop. No additional power
required.
High noise (EMF/RFI) immunity.
Tinned, stripped leads for ease of wiring.
Direct Decade entry of address: 01 - 99 on FireWarden-
100-2, 01 —50 on FireWarden-50.
1415 0 1 ADDRESS
11 4 LOOP 1~4
10 5
TENS ONES
I. —
-J LU :
11 1~4
LU
0
The NMM-100P(A) Mini Monitor Module can be installed in a
single-gang junction directly behind the monitored unit. Its
small size and light weight allow it to be installed without rigid
mounting. The NMM-100P(A) is intended for use in intelligent,
two-wire systems where the individual address of each module
is selected using rotary switches. It provides a two-wire initiat-
ing device circuit for normally-open-contact fire alarm and
security devices. NMM-100P(A)
NMM-100P(A) APPLICATIONS
Use to monitor a single device or a zone of four-wire smoke
detectors, manual fire alarm pull stations, waterf low devices, or
other normally-open dry-contact devices. May also be used to
monitor normally-open supervisory devices with special super-
visory indication at the control panel. Monitored circuit/device
is wired as an NFPA Style B (Class B) Initiating Device Circuit.
A 47K ohm End-of-Line Resistor (provided) terminates the cir-
cuit.
NMM-100P(A) OPERATION
Each NMM-100P(A) uses one of the available module
addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and the status (open/nor-
mal/short) of its Initiating Device Circuit (IDC).
NMM-100P(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Average operating current: 350 pA, 1 communication every
5 seconds, 47k EOL; 600 pA Max. (Communicating, IDC
Shorted).
Maximum IDC wiring resistance: 40 ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 400 pA.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x
0.65" (1.651 cm) deep.
Wire length: 6" (15.24 cm) minimum.
NZM.100(A) Interface Module
Supports compatible two-wire smoke detectors.
Supervises IDC wiring and connection of external power
source.
High noise (EMF/RFI) immunity.
SEMS screws with clamping plates for ease of wiring.
Direct Decade entry of address:, 01 - 99 on FireWarden-
100-2, 01 —50 on FireWarden-50.
LED flashes during normal operation.
LED latches steady to indicate alarm on command from
control panel.
The NZM-100(A) Interface Module is intended for use in intelli-
gent, addressable systems, where the individual address of
each module is selected using built-in rotary switches. This
module allows intelligent panels to interface and monitor two-
wire conventional smoke detectors. It transmits the status (nor-
mal, open, or alarm) of one full zone of conventional detectors
back to the control panel. All two-wire detectors being moni-
tored must be UL compatible with the module.
NZM-100(A) APPLICATIONS
Use the NZM-100(A) to monitor a zone of two-wire smoke
detectors. The monitored circuit may be wired as an NFPA
Style B (Class B) or Style D (Class A) Initiating Device Circuit.
A 3.9 K ohm End-of-Line Resistor (provided) terminates the
end of the Style B or D (class B or A) circuit (maximum IDC
loop resistance is 25 ohms). Install ELR across terminals 8
and 9 for Style D application.
NZM-100(A) OPERATION
Each NZM-100(A) uses one of the available module
addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and the status (open/nor-
mal/short) of its Initiating Device Circuit (IDC). A flashing LED
indicates that the module is in communication with the control
panel. The LED latches steady on alarm (subject to current
limitations on the loop).
NZM-100(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Maximum IDC wiring resistance: 25 ohms.
Average operating current: 300 pA, 1 communication and 1
LED flash every 5 seconds, 3.9k eol.
EOL resistance: 3.9K ohms.
External supply voltage (between Terminals T3 and T4):
DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms
maximum. Current: 90 mA per module maximum.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4' (10.16 cm) square x
2.125" (5.398 cm) deep box.
Page 2 of 4— DN-6999:C • 10/06/2010
NDM.100(A) Dual Monitor Module
The NDM-100(A) Dual Monitor Module is intended for use in
intelligent, two-wire systems. It provides two independent two-
wire initiating device circuits (lDCs) at two separate, consecutive
addresses. It is capable of monitoring normally open contact fire
alarm and supervisory devices. The module has a single panel-
controlled LED.
NOTE: The NDM- 100(A) provides two Style B (Class B) IDC cir-
cuits ONLY Style 0 (Class A) IDC circuits are NOT supported in
any application.
NDM- 100(A) SPECIFICATIONS
Normal operating voltage range: 15 to 32 VDC.
Maximum current draw: 6.4 mA (LED on).
Average operating current: 750 pA (LED flashing).
Maximum IDC wiring resistance: 1,500 ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 240 pA
EOL resistance: 47K ohms.
Maximum SLC Wiring resistance: 40 Ohms.
Temperature range: 320 to 120°F (0° to 49°C).
Humidity range: 10% to 93% (non-condensing).
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
2.125" (5.398 cm) deep.
NDM-100(A) AUTOMATIC ADDRESSING
The NDM-100(A) automatically assigns itself to two address-
able points, starting with the original address. For example, if
the NDM-100(A) is set to address "26", then it will automati-
cally assign itself to addresses "26" and '27".
NOTE: "Ones" addresses on the NDM-100(A) are 0, 2, 4, 6, or 8
only. Terminals 6 and 7 use the first address, and terminals 8 and
9 use the second address.
CAUTION:
Avoid duplicating addresses on the system.
Installation
NMM-100(A), NZM-100(A), and NDM-100(A) modules mount
directly to a standard 4" (10.16 cm) square, 2.125" (5.398 cm)
deep, electrical box. They may also be mounted to the
SMB500 surface-mount box. Mounting hardware and installa-
tion instructions are provided with each module. All wiring
must conform to applicable local codes, ordinances, and regu-
lations. These modules are intended for power-limited wiring
only.
The NMM-100P(A) module is intended to be wired and
mounted without rigid connections inside a standard electrical
box. All wiring must conform to applicable local codes, ordi-
nances, and regulations.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.
UL: S635
ULC: S635
FM Approved
CSFM: 7300-0028:0230 (NMM-100, NMM-100P, NZM-
100); 7300-0028:0237 (NDM-100)
MEA: 72-01-E Vol. 2 (NMM-100, NMM-100P, NZM-100);
227-03-E Vol. 3 (NDM-100)
Product Line Information
NOTE: "A" suffix indicates ULC-listed model.
NMM-100(A): Monitor module.
NMM-100P(A): Monitor module, miniature.
NZM-1 00(A): Monitor module, two-wire detectors.
NDM-100(A): Monitor module, dual, two independent Class B
circuits.
SMB500: Optional surface-mount backbox.
NOTE: See installation instructions and refer to the SLC Wiring
Manual, PN 52304.
DN-6999:C • 10/06/2010 - Page 3 of 4
Notifier® and Fire Warden® are registered trademarks and FireWatchTM is a
trademark of Honeywell International Inc.
02010 by Honeywell International Inc. All rights reserved, Unauthorized use
of this document is strictly prohibited.
I So ooi
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
T33 We cannot cover all specific applications or anticipate all requirements.
MCINIERINS 9 MANUFACTUMNS All specifications are subject to change without notice.
QUALITY SYSTEMS Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 4 of 4— DN-6999:C • 10/06/2010
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No.
CATEGORY
LISTEE:
DESIGN:
7300-0028:0230 Page 1 of 1
7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
NotifierOne Fire-Lite Place, Northford, CT 06472-1653
Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309
Email: vladimir.kireyev@honeywell.com
Models NMM-100P, NMM-100, and NZM-100 monitor modules; Models NC-100R and
NC-100 control modules; and *NzM1006 six zone interface signaling device module. Refer
to listee's data sheet for additional detailed product description and operational
considerations.
RATING: 15-32 VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listees name, model number, electrical rating, and UL label.
APPROVAL: Listed as control unit accessories for use with listee's separately listed electrically
compatible fire alarm control units. Refer to listee's Installation Instruction Manual for details.
XLF: 7300-0075:0185
08-23-11 rev. mt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
RV% operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2013 Listing Expires June 30, 2014
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division