8/g/24,2:12 PM FS070015 Permit Data
City of Carlsbad
Fixed Systems Permit
Permit No: FS070015
300 CARLSBAD
Job Address: Status: ISSUED
VILLAGE DR
Permit Type: FIXSYS Applied 10/1/2007
Parcel No: 2031730500 Approved: 10/17/2007
Lot #: 0
Reference No.: Issued: 10/17/2007
PC #: Inspector:
Project Title: PITA PIT, SUITE 120 HOOD & DUCT TI PLAN CHECK & INSPECTION
Fees ($) Add'I Fees ($) Total ($) Balance ($)
T 130 0 130
-
0
about:blarik 1/1
PERMIT #:
PREMISES NAMEI
ADDRESS: &)() C
CONTRACTOR:
Carlsbad Fire Department
Kitchen Hood Suppression System Testing
Check List
DATE:______________________
\3 \ \ ± \
.1 Dry & Wet Chemical Systems ..' OK CN
A Stamped, Approved Plans On Job Site
B Manual pull station easily accessible in path of egress (Not on sprinkler systems)
C Manual pull station mounted 42" to 60" from floor (Not on sprinkler systems)
D Manual pull station activates system (Not on sprinkler systems) V I
E Manual pull station signage shall read "Pull Station- Emergency Shut Down" (Not on sprinkler systems)
F Building fire alarm sounds upon system activation, if fire alarm system available
G Fuel and exhaust interlocked so that fuel will not flow without exhaust system active
H -Fuel and power shutdown device operates on system activation and all equipment under the hood
shall shutdown when the system activates (electrical outlets & tights included unless listed otherwise)
I Fuel and power shutdown device must be manually reset '
J Operation of fusible test link activates system; also ask if a nitrogen blow off test was completed prior to nozzle installation? (this is optional- not required)
.K Exhaust fan shalt keep running after activation of system, unless other wise listed /
L Make-up air shuts down and HVAC_ system _shuts _down, _if_applicable
M Pipe size and the _configuration _complies _with, _approved _plans
N Piping and nozzles are secured -
O Nozzle types match appliance hazard class and type of use as shown on approved plans (remove &
verify- tech removes)
P Nozzle placement, complies with approved plans
Q Nozzle blow-off caps are in place ' V
R Plenum and duct areas are protected per approved plans ' V
S Deep fat fryers installed a minimum of 16" space between fryer and surface flames from adjacent
cooking equipment (" Exception Steel baffle mm. of 12" height between appliances)
T Deep fat fryers shall be equipped with a separate high-limit control (in addition to reg. control) to shut
'off fuel or energy when temp. reaches 475 degree F below surface
U Chemical container easily accessible, not above ceiling or sitting on the floor
V Pressure gauges in operable range' . .
W Grease filters shall be listed, easily removed for cleaning, drip tray beneath lower edge (shall drain into
metal container not greater than 1 gal)
X Maintenance tao in olace .
Y Fire Extinguisher- Minimum of 2.5 gal. "K" Class mounted in path of egress (kitchen) '7 Z System Supervision- If the suppression system requires electricity to activate the system, then the
system shall required to be electronically monitored by a central monitoring agency "standby power
- supply shall be provided
Z-1 Contractor shall submit "Installation Certificate" for the system per the listing.
1-A Solid Fuel- Cooking appliances constructed of solid masonry or reinforced cement (per NFPA'211)
shall not require fixed automatic fire-extinguishing equipment . . . - 1-B Solid Fuel- Spark arrester screens shalt be located at the entrance of the flue or hood assembly
- 1-C Solid Fuel- Appliances shall be installed on floors of noncombustible construction that extend 3' in all
directions from the appliance
2 '
. Sprinkler Protection
Duct, hood, and appliances configuration(s) match approved plans . .
. B- Sprinkler protection provided for cooking equipment, plenum area, and duct(s) match approved plans
C One sprinkler head (325-375 degree F) located at the top of each vertical duct and at mid-point of each
offset
D One sprinkler head (325-375 degree F) located at entrance of the horizontal duct and at 10' centers
starting at 5' from duct entrance
- E I One sorinkler head (325-375 dnrAA F lnt'tpi1 nt 1"_ 19" nhnva ,4iirf r'nIIr
F One sprinkler head (325-375 degree F) is centered per 10' length of plenum chamber
G The sprinklers listed for protecting the deep fat flyers are provided per approved plans
H
The operation of a sprinkler automatically shutoff all sources of fuel and heat to all equipment
underneath the hood, manual reset is required
I A listed indicating control valve for the water supply is provided with tamper switch
J A listed strainer for the water supply for nozzle orifices less than 3/8" is provided
K A system test connection is provided at the end of the system
L Adequate water pressure is available to operate the system
N Sprinkler heads in ducts are accessible for maintenance
M A 16" separation between deep fat flyer and open flame cooking appliance or a 12" high baffle plate is
provided between the appliances from front to back
0 Listed grease filters are in place and are stamped "Listed Grease Filter on the side
P All penetrations of the hood are properly sealed with fire rated chalking
Q Fire Extinguisher- Minimum of 2.5 gal. "K" Class mounted in path of egress (kitchen)
R
______
System Supervision- If the suppression system requires electricity to activate the system, then the
system shall required to be electronically monitored by a central monitoring agency "standby power-
supply shall be provided
S Solid Fuel- Cooking appliances constructed of solid masonry or reinforced cement (per NFPA.211)
shall not require fixed automatic fire-extinguishing equipment
T
U
,Solid Fuel- Spark arrester screens shall be located at the entrance of the flue or hood assembly
Solid Fuel- Appliances shalt be installed, on floors of noncombustible construction that extend 3' in all
directions from the appliance
V Contractor shall submit "Installation Certificate" for the system per the listing
3 Grease Extractors
A As defined- A system designed for the processing of vapors, gases, and/or air as it is drawn through
devices to collect the airborne grease particles and concentrating them for further action at some
future time
B NFPA 96 allows a listed grease extractor to protect the grease removal devices and hoods of approved
fire extinguishing equipment- Inspector shall specially refer to the approved plans and written fire
review for instruction on approvals and testing -
Site Inspection: Match PIanscr.N Test Pas O-Y r N
Corrections Needed: Y or N If yes, see Correction Notice for further information)
Name:
FD DejiiIjre-MarshaI
Date:______________________________