HomeMy WebLinkAbout300 CARLSBAD VILLAGE DR; 124; AS0501058/9/24, 2:17 PM AS050105 Permit Data
City of Carlsbad
Sprinkler Permit
300 CARLSBAD I2-4
Job Address:
VILLAGE DR
Permit Type: SPRINK
Parcel No: 2031730500
Lot #: 0
Reference No.:
Permit No: AS050105
Status: ISSUED
Applied 5/17/2005
Approved: 5/20/2005
Issued: 5/20/2005
PC #: Inspector:
Project Title: SKINSATIONAL FIRE SPRINKLER PLAN CHECK & INSPECTIONS
Applicant: Owner:
COSCO FIRE PROTECTION OREXCIV L L C
STEIO5
10695 TREENA ST 12411 VENTURA BLVD
SAN DIEGO, CA STUDIO CITY CA
858-444-2000
Fees ($) Add'I Fees ($) Total ($) Balance ($)
115 0 115 0
about:blank 1/1
FIRE PROTECTION
San Diego Branch Office
10695 Treena Street., Suite #105
San Diego, CA 92131
(858) 444-2000 fax: 444-2056
Stale License No: C-16-5 77621
www.coscofire.com
MATERIAL SUBMITTAL
Date: May 5, 2005
TO:
Carlsbad Fire Dept.
SKINSATIONAL
300 CARLSBAD VILLAGE DR. #124
CARLSBAD, CA
JOB# CD-3368
All material submitted, may be substituted
by material of equal performance & design, &
shall be deemed acceptable by purchaser.
Submitted By: Justin Shelton
Los Angeles • San Francisco • Orange • Fresno • San Diego • Seattle
NFPA MUBER
0304
FIRE PROTECTION
San Diego Branch Office
10695 Treena Street., Suite #105
San Diego, CA 92131
(858) 444-2000 fax: 444-2056
State License No: C-16-577621
www. coscofi re. corn
TABLE OF CONTENTS
1. HEADS
Imlabii
Bulletin 136 Rev.L
co Model Fl FR
Model F1 FR Recessed
Quick Response
Sprinklers
Model Fl FR Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
— HSW 1 Deflector
Model F1FR Recessed Sprinkler Types
Recessed Pendent
Recessed Horizontal Sidewall
- HSW 1 Deflector
Listings & Approvals
Listed by Underwriters Laboratories, Inc. (UL)
Listed by Underwriters' Laboratories of Canada (ULC)
Certified by FM Approvals
Loss Prevention Council (LPC, UK)
NYC BSM No. 587-75-SA
Meets MIL-S-901C and MIL-STD 167-1
Verband der Schadenversicherer (VdS, Germany)
NYC MEA 258-93-E
UL Listing Category
Sprinklers. Automatic & Open
Quick Response Sprinkler
UL Guide Number
VNIV
Upright Pendent
Vertical Sidewall Conventional
Product Description
awl R
The Models F1 FR and F1FR Recessed autorriatic sprinklers
ute the dischargiing water.
The 'I temperature • of the sprinkler is identified by the color of the glass bulb.
Horizontal Sidewall
HSW 1 Deflector Recessed Pendent
Application -. . Wick response sprinklers are used in fixed fire proteó-tion systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating. defiector. . style and sprinkler type are in accordance with the latest published standards of the National Fire Protection Asso- ciation or the appring Authority Having Jurisdiction.-
Quick response sprinklers are intended for installation as specified in NFPA 13. Quick response sprinklers and stan-
dard response sprinklers should not be intermixed.
The Reliable Automatic Sprinkler Co., inc. 525 North MacQuesten Parkwa% Mcxii Vernon. New Yok 10552
Model F1 FR Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Mode D Sprinrier Virencti
Installation Data:
Sprinkler Type - K Factor I Sprinkler Identification Standard-Upright (SSU) and Pendent (SSP) Sprinkler Approval Detectors Marked to Indicate Position US Metric Height Organization Number (SIN)
ssU Ssp )" (15mm) Standard Orifice wth )" NPT (R,1) Thread 5.6 80 2.2" (56mm) 12,3,45,6,7 R3625 P3615 (20wn) Large Orifice with %" NPT (R3/4)Thread 8.0 115 2.3" (58mm) 1,2,3,4,7,8 R3622 R3612 17mm)SmeiI Orifice with )" NPT (RX)Thread 4.2 60 2.54"(65mm) 1,2,8 P3623 R3613 %"_(1i)SmaJI Orifice with )ç'NPT(ft1)1Thwead 2.8 40 2.54" (65m11) 12,8 P3621 P3611 i(wi Orifice XLH with R% Thread 4.2 60 56. lrrm 4,6.7 P3624 P3614 Conventional-Install in Uptight or Pendent Position
4.2
5.6
8.0
60
80
115
56.lrrrn
56.1mm
58.4mm
-
4.6.7
4,7
P3674
P3675
R3672
10nTn Orifice )QJ-4 wiuil W, Dwead
15mmStandard Orifice with)" NPT (PJ)Uread 2 Large Orifice 4PT(R14)Thread
Upright Pendent Upright Conventional
Model Fl FR Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model RC1 Sprinkler Wrench
Installation Data:
Nominal
Orifice Thread
Size
K Factor Sprinkler
Height Approval
Organization.
Sprinkler identification Number (SIN) us Metric
)"_(15mm) )NPT(RY) 5.6 80 22"(56mm) 1.2.3,4,5.7.8 P3615 %_(2Ckrrn) " NPT (R3A) 8.0 115 2.3" (58mm) 1,2,3 113612 (11mm) )"NPT(RV4 1 4.2 60 1 2.54"(65niTi) 1,2.8 P3613 %_(iQun) )"WT(R) 2.8 40 2.54"(65mi) 1,2.8 113611
4.2 60 56.lrnn 4,7 113614 "I Refer to escutcheon data table for aixovals and duTienslons.
(ft•Z iiI. .l__,
I St/V4 I ( r
Am MUM
(Mt soff
____
cr'nniPa 0_V y/ _ca*rIo
IU
Aww
im
(U W= .( s -_
2.
Model F1 FR Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
Nominal Orifice Thread Size K Factor
Sprinkler Heig ht Approval
Organizations Sprinkler Identification
Number (SIN) US Metric
'If '/1' NPT(RY2) 5.6 80 2.2" (56mm) 1, 2, 3, 6.8
15mm 142- NPT (RV2) 5.6 80 2.2 (56mm) 4
R3685
I LPC Approval is for Pendent position only.
I Orientation I Deflector to CeIling
Dimension (Mm. - Max.) I Upright 4- 12(102mm-305mm) I
Pendent 6- 12"(152rTYn-305mm) I
Vertical Sidewall
0
Model Fl FR Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model 0 Sprinkler Wrench
Installation Data:
I K Factor I e 0 1za43ons
1çreva1 Sprinkler
Identification I Nominal
Orifice Thread
Size
I i US Metric I Sprinkler
Length I Ught I Hazard
Olnay1
Hazard
Number I I (SIN)
r2 ('&=) )NPT(R) 5.6 I 80 I 2.63'(67m) 1.2.3,5.8 j 1.2.5.8 ( R3635 NOTE: UL and ULC Usting permits use with Fl or F2 recessed escutcheon.
Horizontal Sidewall
3.
Finishes (1) (
Standard Finishes
Sprinkler Escutcheon
Bronze Brass
Chrome Plated Chrome Plated (3)
White Polyester Coated White Painted
Special Application Finishes
Sprinkler Escutcheon
Bright Brass Bright Brass
Black Plated Black Plated
Black Paint Black Paint
Off White Oft White
Satin Chrome Satin Chrome
Other finishes and colors are available on special order. Consult the factory for details.
FM Approvals is limited to bronze and brass, chrome or black
plated finishes only.
FP Push-on/Thread-off escutcheon
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
Orifice Size
Deflector Type
Temperature Rating
Sprinkler Finish
Escutcheon Type
Escutcheon Finish (where applicable)
Note: When Model F1FR Recessed sprinklers are
ordered, the sprinklers and escutcheons are packaged .. ., separately.
.• ..
..
Installation
O , -'> rosponse sprnklers are nen:eo for nsaaon
as specified in NFPA 13. Quick response sprinklers and
standard response sprinklers should not be intermixed.
The Model Fl FR Recessed Quick Response Sprinklers
are to be installed as shown. The Model Fl or F2 Escutch-
eons illustrated are the only recessed escutcheons to be
used with the Model F1FR Sprinklers. The use of any other
recessed escutcheon will void all approvals and negate all
warranties.
When installing Model Fl FR Sprinklers, use the Model D
Sprinkler Wrench. When installing Model F1FR Recessed Sidewall Sprinklers, use the Model GFR1 Sprinkler
Wrench. Use the Model RC1 Wrench for installing F1FR Recessed Pendent Sprinklers. Any other type of wrench may damage these sprinklers.
Temperature Ratings
tjo s- Temperature Max. Ambient
Temp.
Bulb
Color c4
Ordinary 57 135 1001F(38'C) Orange Ordinary 68 155 1OY'F(38C) Red Intermediate 79 I 175 150-F (65-C) Yellow Intermediate 93 I 203 150117 (66'C) Green High (1) 141 j 286 225'F(107C) Bk.e
(1) Not available for recessed sprinklers.
Escutcheon Data
Escutcheon 'A FaC(AtIIn
Model Ap3flWalS 4Ustit Dimension n b Cel igor
Wall Dimension
Fl 1Z4 (19mm) (19mm) (5rm-24-rrn)
F2 12,3,4.5,7,8 47 1 X. (13nwn) (25mm) (5r - 17ni'n)
F1' 1.2 FulyReoessed 34,
(11 mm)
1.2 RAy Retracted VIr TlTead-df
(24mm)
Maintenance
The Models F1FR and F1FR Recessed Sprinklers should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gen-tle vacuuming. Remove any sprinkler which has been
painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprin-
klers. Prior to installation, sprinklers should be maintained
in the original cartons and packaging until used to mini-mize the potential for damage to sprinklers that would cause improper operation or non-operation.
Sprinkler Types
Standard Uprigni
Standard Pendent
Conventional
Sidewall (Vertical, Horizontal HSW1)
Recessed Pendent
Recessed Horizontal Sidewall HSW1
The eqtipmerpreserted in this buSetin Is lobe Installed in accordance with die latest pertlient Standards o( the National Fire Protection Association. Factory Mutual Research Corporation, or other wAar 0r9n1zat10ns and also with the provisions Of governmental codes or ordinances whenever applicable.
Products mariufactured and disuted by Reliable have been protecting lifeand property for over 80 years. and are installed and serviced by the most highly qualified and reputa-ble 5Qrider contractors located throughout the United Stales Canada and foreign coist'ies.
Manufactured by
Rellabld
The Reliable AutomatIc Sprinkler Co. Inc.
(831-1588 Sales Offices (800)848-6051 Sales Fax (914)668-3470 Corporate Offices
Internet Address
Revision Ines kidicalle updated or new data
80. F isd Am USA 3 PSe%e70027
- .-.-- - - .