HomeMy WebLinkAbout3207 GREY HAWK CT; ; FA070046; Permit1/17/25, 3:22 PM FA070046 Permit Data
City of Carlsbad
Fire Alarm Permit
3207 GREY HAWK
Job Address:
CT
Permit Type: FALARM
Parcel No: 2210150100
Lot #: 0
Reference No.:
Permit No: FA070046
Status: ISSUED
Applied 5/9/2007
Approved: 5/17/2007
Issued: 5/17/2007
PC #: Inspector.
Project Title: PALOMAR CONCOURSE ONE TI FIRE ALARM PLAN CHECK &
INSPECTION
Applicant:
STANDARD ELECTRONICS
STEA
2830 VIA ORANGE WAY
SPRING VALLEY CA
619-670-2332
Owner:
CONCOURSE ONE LLC
5330 CARROLL CANYON RD #200
SAN DIEGO CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
117 0 117 0
about:blank 1/1
SUBMITTAL DATA 4/23/2007
Sta=ndard April 23, 2007
Electronics
9340 Stevens Rd. Santee, CA 92071
Ph# 619-596-9950 Fax# 619-596-8850
SUBMITTAL SHEET
PROJECT: PALOMAR CONCOURSE SUITE 150, 3207 GREYHAWK CT. CARLSBAD, CA 92008
CONTR: BILBRO CONSTRUCTION CO., 8954 SAN DIEGO DR., SUITE 102, SAN DIEGO, CA 92108
EQUIPMENT
FIRE NO SECTION
ITEM QTY DESCRIPTION MODEL NO. DATA SHEET
ADDRESSABLE MONITOR MODULE 1 5 AMM-2F FCI SFM #7300-0694:178
REMOTE TEST STATION SYSTEM 2 5 RTS451 SFM 7300-1653:110 SENSOR
16 AWG/ 2 CONDUCTOR - SOLID CONDUCTORS POWER
LIMITED - RED OVERALL JACKETED - FIRE 3 A/R 990 WEST PENN PROTECTIVE SIGNALING CABLE
SFM #7161-0859:101
18 AWG/ 4 CONDUCTOR - SOLID CONDUCTORS POWER
LIMITED - OVERALL JACKETED - FIRE PROTECTIVE 4 A/R 982 WEST PENN SIGNALING CABLE
SFM #7161-0859:101
FIRE CONTROL
LEI INSTRUMENTS
by Honeywell
Description
The FCI VelocitiTM Series, addressable monitor module
AMM-2F is a single Style B, Class B initiating device
circuit (IDC) with a 471V end-of-line resistor. This mod-
ule provides an address for any device or group of de-
vices connected to this circuit on the signaling line circuit
(SLC) of the FCI addressable series fire alarm control
panel. Any initiating device with normally open (NO.) dry
contacts may be made addressable when connected to
the AMM-2F module.
The VelocitilM Series use a communication protocol that
substantially increases the speed of communication be-
tween the sensors and certain FCI analog addressable
fire alarm controls. These devices operate in a grouped
fashion. If one of the devices in the group has a status
change, the panel's microprocessor stops the group poll
and concentrates on the single device. The net effect is
response speed up to five times greater than earlier de-
signs.
The AMM-2F module can be programmed to provide a
wide variety of input functions to the FCI addressable
series fire alarm control panels. It can be identified as a
manual station, heat detector, plenum detector, water-
flow switch, tamper switch, N.O. contact, smoke detector,
projected beam smoke detector, sub loop, remote zone,
etc. It can also serve as a remote system silence, system
reset, system acknowledge or drill switch. It is even pos-
sible to customize its device type to meet specific job
requirements.
The initiating device circuit of the AMM-2F can support a
maximum line resistance of up to 40 ohms allowing the
use of linear heat detection devices. The compact size
facilitates the installation of the module inside manual
stations, or mounting boxes of various types of alarm
initiating devices.
Ordering Information
Model Description
AMM-2F Addressable monitor module, single circuit
Style B, Class B
Velociti" and E3 Series' are trademarks of Fire Control Instruments.
Velocill'"m Series
AMM-2F
Addressable
Monitor Module
.
---- . !
'•
'•" -I.-
AMM-2F
Features
Compact size allows easy installation.
Class B, Style B, initiating circuit
40 Ohm line resistance for each initiating device
circuit
Connects to any normally open dry contact device.
Bicolor LEDs flash green whenever the module
is addressed, and light steady red on alarm.*
*Note: Only the red LED is operative in panels that do not oper-
ate in VelocitlTm mode.
Specifications
An ISO 9001-2000 Company
SIGNALING
®<>MEA
LISTED APPROVEC Approvec
t1941 3023594 2210 EVollV 01300 069 118
Supervisory current:
Alarm current:
Operating temperature:
Relative humidity:
End-of-line Resistance:
Dimensions:
0.0004 amp.
0.0006 amp.
32" to 120" F (0" to 49" C)
10 to 93% (non-condensing)
47K ohms
1.3" Lx2.5"Wx0.5" D
(3.3x5.5x 1.3 cm)
FIRE CONTROL INSTRUMENTS
16 Southwest Park, Westwood, MA 02090—Tel 781-471-3000—Fax: 781-471-3099
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Fire Control Instruments for their use.
@2005 Fire Control Instruments. All nghts reserved. www.flrecontrolinstruments.com 9020-0626 Rev. A page 1 of 1
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-0694:178 Page 1 of 1
CATEGORY: Misc. Devices/Control Unit Accessories
LISTEE: Fire Control Instruments, 16 Southwest Park, Westwood MA 02090
Contact: Anthony J. Shalna (781) 471-3000 FAX (781) 471-3099
19
DESIGN: Models AMM-4, *AMM4F AMM-2 and *AMM.2 monitor modules and Models AOM, AOM-
2, AOM-2R, *AOM..2RF AOM-2S and *AOM..2SF control modules. Refer to listee's data
sheet for detailed product description and operational considerations.
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model designation, electrical rating and UL label.
APPROVAL: Listed as accessories for use with separately listed compatible control units. System Sensor
Model SMB500 surface mount box (CSFM Listing No. 7300-1653:103) may be used as an
enclosure for these modules
XLF: 7300-1653:103
El
Rev 09-07-2005
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 13 2006 Listing Expires June 30, 2007
Authorized By: DIANE K. AREND, Senior Deputy
Program Manager
Models Available
BEAM1224 4 wire conventional beam smoke
detector with 8 reflector
BEAM1224S 4 wire conventional beam smoke
detector with 8 reflector and
integral sensitivity test
Accessories
BEAMLRK Long range accessory kit
(3) additional reflectors
(Required for applications in
excess of 230 ft. [70m])
B EAM MM K
B EA M SM K
RTS45I.
RTS451KEY
BEAM H K
B EAM H KR
Multi-mount kit
(Provides ceiling or wall mount
capability with increased angular
adjustment for either the beam or
the reflector. When installed with the
transmitter/receiver unit, BEAMSMK
must be used as well)
Surface mount kit
Remote test station used to initiate the
NFPA sensitivity test function
Remote test station with key lock
Heater kit for transmitter/receiver unit (See electrical requirements on back)
Heater kit for reflector (See electrical requirements on back)
S
Product Overview
16 to 328 foot protection range
Single-ended, reflective design
User friendly alignment procedure
6 user selectable sensitivity levels
Optional integral NFPA 72 sensitivity test
feature
Removable plug-in terminal blocks
Digital display for easy alignment
Built-In automatic gain control
compensates for signal deterioration from
dust build-up
Remote test station optional
Paintable cover
Easiest alignment in the industry
( DR <jF~M> MEAMSFM LISTED —Rom approved approved
$911 3017888 72601.209.228 5444-0 2165
System Sensor Model BEAM1224 is a 4-wire conventional projected beam smoke
detector. It is uniquely suited for protecting open areas with high ceilings where other
methods of smoke detection are difficult to install and maintain. It is to be used with
UL Listed compatible control panels only. Installation of the single-ended reflective
design is much easier than the dual-ended projected beam detectors. Alignment is
quickly accomplished via an optical sight and a 2-digit signal strength meter incor-
porated into the product. Listed for operation from —22°F to 1310F, BEAM1224 can
be used in open area applications to provide early warning in environments where
temperature extremes exceed the capability of other types of smoke detection.
BEAM1224 consists of a transmitter/receiver unit and a reflector. When smoke enters
the area between the unit and the reflector it causes a reduction in the signal and,
when the smoke level reaches the predetermined threshold, an alarm is activated.
BEAM1224 has four standard sensitivity selections along with two Acclimate set-
tings. When either of the two Acclimate settings are selected the detector will auto-
matically adjust its sensitivity using advanced software algorithms to select the opti-
mum sensitivity for the specific environment.
BEAM1224S is equipped with an integral sensitivity test feature that consists of a
test filter attached to a servo motor inside the detector optics. Using the remote test
station RTS451, the motor is activated and moves the filter in the pathway of the
light beam, thereby testing detector sensitivity. This integral sensitivity test feature
allows the user to quickly and easily meet the annual maintenance and test require-
ments of NFPA 72.
OPTICAL GUNSIGHT
ALiGNM
CGNALENT
- 0 STRENGTH
METER
HORIZONTAL
OP1TCS
ALIGNMENT
KNOB
.AUGNMENT
TEST
VERTICAL
OPTICS
KNOB ALIGNMENT
-
-
RESET
CO27t-01
Activated Test Feature (BEAM1224S only)
BEAMMMK
(detector and surface nit
Operational Specifications
Protection Range
16 ft. to 328 ft.
(5m to lOOm)
Adjustment Angle
+/— 10 Degrees horizontal & vertical
(The optics move independent of the
unit)
Sensitivity Levels
Level 1 — 25%
Level 2 — 30%
Level 3 — 40%
Level 4 — 50%
Acclimate Level 1 — 30-50%
Acclimate Level 2 — 40-50%
Fault Condition (Trouble)
96% or more obscuration blockage
In alignment mode
Improper initial alignment
Self-compensation limit reached
Alignment Aid
Optical gunsight
Integral signal strength indication
2-digit display
Alarm Indicator
Local red LED and remote alarm
Trouble Indicator
Local yellow LED and remote trouble
Normal Indicator
Local flashing green LED
Test/Reset Features
Integral Sensitivity Test Filter
(BEAMI224S only)
Sensitivity filter
(Incremental scale on reflector)
Local alarm test switch
Local alarm reset switch
Remote test and reset Switch
(Compatible with RTS45I and
RTS451KEY test station)
Smoke Detector Spacing
On Smooth ceilings, 30-60 feet
between projected beams and not
more than one-half that spacing
between a projected beam and
a sidewall. Other spacing may be
used depending on ceiling height,
System Sensor Sales and Service
airflow characteristics, and response
requirements. See NFPA 72.
Environmental Specifications
Temperature
—22°F to 131°F (-30°C to 55°C)
Humidity
10-93% RH Noncondensing
Electrical Specifications
Voltage
10.2 to 32 VDC (BEAM1224)
15 to 32 VDC (BEAM1224S)
BEAMI224S should not be used with
12V power sources
AVG. Standby Current (24VDC)
17mA Max
AVG. Current During Testing
500mA Max
AVG. Alarm Current (24VDC)
38.5mA Max
AVG. Fault Current (24VDC)
8.5mA Max
AVG. Alignment Mode Current (24VDC)
28mA Max
Mechanical Specifications
Detector Dimensions
10"H x 7.5"W x 3.3"D
(254mmH x 191mmW x 84mmD)
Reflector Dimensions (16' to 230')
7.9" x 9.1" (200 x 230mm)
Reflector Dimensions for (beyond 230')
15.7" x 18.1" (400 x 460mm)
Electrical Specifications (BEAMHKR)
Voltage
15 to 32V
Current
450mA Max at 32V (per reflector)
Power Consumption (Per reflector)
7.7W @ 24V; 15W @ 32V
Electrical Specifications (BEAMHK)
Voltage
15 to 32V
Current
92mA at 32V
Power Consumption
1.6W @ 24V; 3W @ 32V
System Sensor Headquarters System Sensor Canada System Sensor in Chins System Sensor - Far East system Sensor - India
3825 Ohio Avenue Ph: 905.812.0767 Ph: 86.29.8832.0119 Ph: 85.22.191.9003 Ph: 91.124.237.1770 x.2700
St. Charles, IL 60174 Fx: 905.812.0771 Fx: 86.29.8832.5119 Fx: 85.22.736.6580 Fx: 91.124.237.3118
Ph: 800/5EN50R2 System Sensor Europe System Sensor in Singapore System Sensor - Australia System Sensor - Russia
Fx: 630/377-6495 Ph: 44.1403.891920 Ph: 65.6273.2230 Ph: 613.54.281.142 Ph: 70.95.937.7982
www.systemsensor.com Fx: 44.1403.891921 Fx: 65.6273.2610 Fx: 613.54.281.172 Fx: 70.95.937.7983
0 2005 System Sensor. The company reserves the right to change product specifications without notice.
A05.0365.002.2/05.#1397
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-1653:110 Page 1 of 1
CATEGORY: Misc. Devices/Control Unit Accessories
LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l Inc., 3825 Ohio Ave, St. Charles, IL 60174
Contact: Irish Lin (630) 377-6580 ext. 1185 FAX (630) 377-7245
AN
JV
DESIGN: Models RTS45I and R1S451 KEY remote test switches, and Model RTC remote test station
kit. Refer to listee's data sheet for additional detailed product description and operational
considerations.
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number and UL label.
APPROVAL: Listed as accessory devices for use with separately listed compatible duct smoke detectors.
NOTE: Formerly 7300-0087:129, 7300-1209:129
06-17-05
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 24, 2006 Listing Expires June 30, 2007
Authorized By: DIANE K. A REND, Senior Deputy
Program Manager
Temperature range:
-20° (to 75° C dry locations
Meets 300 volt requirements as
specified in Section 760 of the NEC
APPLICATIONS
Indoor (non-conduit per NEC) for:
Audio circuits
itrol circuits
iiing circuits
Notification circuits
SPECIAL NOTES
Select cables are available in
outdoor and direct burial versions.
See Aquaseol® product line
for details
Orange ripcord under jacket
Catalog No. 980, 982, and 990
are also available with a Blue,
Green, White or Yellow jacket
o UL listed NEC type FPLR __________________________________________
AWG Size & Nom. Insulation
(atolog No. of Strandin Thickness
Norn.
Thickness
Jacket Norn. O.D.
D.C.R.==now=
1084 ' 6 22 Solid .010 .25 .020 .51 i.179 4.55
17.5
1086 8 22 Solid .010 .25 .020 .51 .193 4.90.
17.5 filM
980 1 18 Solid .010 .25 .020 .51 .156 3.96.
Pair 6.5 Q/M
982 4 18 Solid .010 .25 .020 .51 .188 4.78
6.5WM'
984 6 18 Solid 010 25 020 51 224 569
6.5 92/M'
986 8 18 Solid .010 .25 .020 731 .252 6.40
988 .10 18 Solid .010 .25 .020 .51 .294 7.47,
6.5!0/M'
990 1 16 Solid .010 .25 .020 .51 .165 4.19
Pair 4.1Q/M'
992 4 16 Solid .010 .25 .020 .51 .213 5.41
4.1 WM'
994 1 14 Solid .012 .30 .025 .64 .205 5.21
Pair 2.6 WM'
998 1 12 Solid .012 .30 .025 .64 .235 5.97
Pair 1.8c2/M '
Standard spool size 1000 feet
I COLOR CODE
Refer to page 51
JACKET: Red
50 -1I -WEST PENN WIRE /CDT
ower-Limited Multiple Conductor/unshielded DESCRIPTION
ASTM bare copper
PVC insulation • Twisted pair or
cabled construction • PVC fillers as required
IlJL
• Polyester binders as required • Overall 75° (PVC jacket
RATING
Constructed in accordance with
UL Standard 1424
Complies with UL 1666 Vertical
Shaft (riser) Flame Test
V
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7161-0859:101 Page 1 of 1
CATEGORY: Cables-Fire Protective Signaling
LISTEE: West Penn Wire, P0 Box 762, Washington PA 15301
Diane Kelley (724) 222-7060 FAX (724) 2291151*
DESIGN: Types FPL and FPLP power limited fire protective signaling cable. Refer to listee's data
sheet for detailed product description and operational considerations.
INSTALLATION: In accordance with listee's printed installation instructions, NEC Article 760, applicable codes
and ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, type, NEC rating and UL label.
APPROVAL: Listed as power-limited fire protective signaling cable.
Rev. 05-23-2005
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 14, 2006 Listing Expires June 30, 2007
Authorized By: DIANE K. AREND, Senior Deputy
Program Manager