HomeMy WebLinkAbout2501 EL CAMINO REAL; 230; AS150232; PermitCity of Carlsbad
Sprinkler Permit
Permit No: AS150232
2501 ELCAMINO
Job Address: Status: ISSUED
REAL
Permit Type: SPRINK Applied 8/4/2015
Parcel No: 1563020800 Approved: 8/6/2015
Lot #: 0
Reference No.: Issued: 8/6/2015
PC #: Inspector:
Project Title: PEETS COFFEE TI
Applicant:
BRADSHAW ENGINEERING CORP
8645 ARGENT ST
SANTEE CA
619-448-4300
Owner:
CMFPCRLLC
C/O WESTFIELD PROPERTY TAX DEPT
P0 BOX 130940 DEPT WFLD
CARLSBAD, CA
Fees ($)[dd'IFees ($) Total ($) Balance ($)
_____
0 280
____ ____
Bulletin 121 Rev. K
Model G4 Concealed
Automatic Sprinkler
The Concealer®
A Concealed Sprinkler
With ½" (13mm) or
11/2" (38mm) Adjustment
AS150232
Features
Cover plate assembly attachment (Plain
or Perforated) with ½" (13mm) adjustment.
Does not require clips or springs.
11/2" (38mm) Total adjustment provided by
adjustable inlet versions.
Adjustable inlet version available with either
1' NPT male or female threads eliminating
costly reducing coupling.
Smooth aesthetic ceiling profile.
Available in white or other color painted or
brass, chrome, or black plated finishes.
Ordinary and intermediate temperature
ratings.
Multiple orifices for design flexibility.
Approvals & Listings
Underwriters Laboratories Inc. (UL)
Underwriters Laboratories of Canada. (ULC)
N.Y.C. BS&A No. 587-75-SA.
Note: Approvals are for light and ordinary hazard, except for small
orifice sprinklers which are limited to light hazard occupancies.
The cup and skirt are fabricated from plated steel and are in-
tended for interior non corrosive applications.
U.S. Patent No. 4,880,063.
Application
The Reliable Model G4 Conceal-
er® is the most versatile concealed
sprinkler available It provides the
best form of fire protection while
offering an attractive appearance
and ½" (13mm) of cover adjustment for ease of instal-
lation. The adjustable 1" NPT inlet versions have 11/2"
(38mm) of total adjustment and also eliminates the need
for a reducing coupling. The small diameter cover plate
assembly is easily attached and blends into the ceiling,
concealing the most dependable fire protection available,
an automatic sprinkler system.
The Concealer® is designed for use where aesthetic ap-
pearance is important. Offices, hospitals, motels and restau-
rants are but a few of the applications where it can be used.
It is available in different orifice sizes allowing the designer
to optimize system performance, thereby achieving a most
efficient installation.
The Concealer® can eliminate the need for precise cutting
of drop nipples. The cover plate assembly can be adjusted
without tools so it mates accurately with the ceiling. The fire
protection system need not be shut down to adjust or remove
the cover plate assembly.
Product Description
The Reliable Model G4 Concealer® standard response
uses the proven Model G fusible element in a standard style
sprinkler frame with a drop-down deflector. This assembly is
recessed into the ceiling and concealed by a flat cover plate.
This threaded engagement provides ½" (13mm) of cover ad-
justment. The flat cover plate is attached to the skirt using
an ordinary temperature classification solder. This results in
a strong cover plate assembly with an ordinary temperature
rating, and an intermediate temperature sprinkler which can
be installed in 150°F (66°C) environments. When the ceiling
temperature rises, the solder holding the cover plate to the
skirt melts, the flat cover plate released thus exposing the
sprinkler inside to the rising ambient temperature.
The subsequent fusing of the sprinkler element opens the
waterway and causes the deflector to drop into position to
distribute the discharging water. Any secure engagement of
the threads between the cover plate and cup will assure that
the drop-down deflector is properly located below the ceiling
when a sprinkler operates.
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Installation
'o rt ir:lstall The Concealer in ceilings which have posi-
tive pressure in the space in the space above.
After a 2`118 inch diameter hole is cut in the ceiling, the sprin-
kler is to be installed with the Model G4 Wrench. The wrench
has drive tangs which insert into cup slots. When installing
a sprinkler the wrench is first positioned into the sprinkler/
cup assembly until the wrench tangs engage drive slots in
the top of the cup (there are two sets of mating drive slots in
the cup). The sprinkler is then tightened into the pipe fitting.
When inserting or removing the wrench from the sprinkler/
cup assembly care should be taken to prevent damage to
the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF
THE SPRINKLER/CUP ASSEMBLY.
The adjustable inlet versions are similar to the standard
Model G4 except that an addition 1' (25mm) of adjustment is
provided by means of a telescoping inlet section that threads
in or out of a stationary coupling reducer (either 1 male or 1
female) as shown in Fig. 2 or Fig. 3. These sprinklers must be
installed before the ceiling is in place, by wrenching on only
the coupling reducer hex flats. After the ceiling has been in-
stalled with holes for the sprinkler, each telescoping inlet sec-
Temperature Ratings
Classification Sprinkler Cover Plate Max. Ambient
Temp.
Ordinary 135°F/57°c 135°F/57°c 100°F/38=c
Ordinary 165°F/74°C 135°F/57°C 100°F/38°c
Ordinary 165°F/74°C 165°F/74°C 150°F/66°c
Intermediate 2 12°F/i oo°c 165°F174°c r 150°F/66°C
Installation Data
tion is to be adjusted with the G4 Wrench. Install the cover
plate assembly by hand turning it clockwise until it is tight
against the ceiling.
Maintenance
The Model G4 Concealer® should be inspected and the
sprinkler system maintained in accordance with NFPA 25.
Do not clean sprinklers with soap and water, ammonia or any
other cleaning fluids. Remove any sprinkler that has been
painted (other than factory applied) or damaged in any way.
A stock of spare sprinklers should be maintained to allow
quick replacement of damaged Cover Plate Finishest1t
or operated sprinklers. Prior to
installation, sprinklers should
be maintained in the original
cartons and packaging to mini-
mize the potential for damage
to sprinklers that would cause
improper operation or non-op-
eration.
Ordering Information
Sprinkler Model
Temperature Rating
.j. Nominal uruce (1) Other finishes and colors Flat Cover Plate Finish are available on special
Inlet Type order. consult factory for
Note: unless otherwise specified, details. coverplate custom
the 165°F (74°c) sprinkler will paint is semi-gloss, unless
be provided with the 165°F specified otherwise.
(74°c) cover. 2) For the perforated style
coverplate, consult factory Sprinkler for availability on these ci Approvals Identification and other custom finishes Number (SIN) Note: Paint or any other coat- R½) 1.2,3 PT( 82115 ings applied over the factory
8½.) 1,2,3 82113 finish will void all approvals
R½) 1,2,3 R2111 and warranties.
Installation Wrench
Model G4 Sprinkler Wrench
Standard Finishes
Chrome
White Paint
Special Application
Finishes(2)
Bright Brass
Finished Bronze
Black Plating
Black Paint
Off White
Satin Chrome
Sprinkler
Inlet
Total
Adjustment
Nominal
Orifice
Nominal
K Factor Thread
iic
Non-Adiustable ½"(13mm) ½"(l5mm) 6 80 ½" N
Non Adjustable ½"(13mm) 7/t&'(ilmm) 4.2 60 ½ NPT(
Non-Adjustable ½" (13mm) s/B" (10mm) 2.8 40 ½' NPT (
Adjustable 1½"(38mm) ½'(lSmm) 5.6 80 1" NPT Male or Female 1,2,3 R2118
Adjustable 1½"(38mm) 7/16"(llmm) 4.2 60 1" NPT Male or Female 1,2,3 R2113
Adjustable 1½"(38mm) W'(lomm) 2.8 40 1" NPT Male or Female 1,2,3 R2112
- V2 PEOUC/We
ME V.W
-'H
=° CUP
My
2 5/UC TEETh',.,] WaX
IlL
-H ---- —'--
03 d
H
L
Fig. 1 - 1/2' NPT (R½) Non-Adjustable Inlet Fig. 2 - 1" NPT Male-Adjustable Inlet Fig. 3- 1" NPT Female-Adjustable Inlet
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc. Recycled
® (800) 431-1588 Sales Off ices ' Paper
(800) 848-6051 Sales Fax Rellabilm (914) 829-2042 Corporate Offices Revision lines indicate updated or new data.
www.reliablesprinkler.com Internet Address ES. Printed in U.S.A. 10/13 P/N 9999970014