DESIGN, INSTALLATION,
MAINTENANCE & RECHARGE
MANUAL
NO. 12385 REV. A
AMEREX KP
RESTAURANT
FIRE SUPPRESSION SYSTEM
TESTED AND LISTED BY
UNDERWRITERS LABORATORIES
TO UL STANDARD 300
and
UNDERWRITERS LABORATORIES OF CANADA
ULC/ORD 1254.6-1995
AMEREX CORPORATION
Post Office Box 81
Trussville, Alabama 35173-0081
Phone: (205) 655-3271 Fax: (205) 655-5112
e-mail: sales @amerex-fire.com web page: www.amerex-fire.com
No part of this manual may be reproduced or transmitted in any form or by any means electrical or
mechanical, including photocopying or by any storage and retrieval system without the expressed
permission in writing from Amerex Corporation.
A Factory Trained and Authorized Distributor must perform the installation and service of any Amerex KP
Restaurant Fire Suppression System in strict accordance with this manual.
Printed in U.S.A. October 2003 • MM#12385A-10/2003
SECTION 3
DESIGN
MANUAL PIN 12385 Rev. A
AMEREX
RESTAURANT
FIRE SUPPRESSION SYSTEM
Tested and Listed by
Underwriters Laboratories, Inc.
to UL Standard 300
EX 4658
Tested and Listed by
Underwriters Laboratories of Canada
To ULCIORD 1254.6-1995
October 2003
October 2003 Section 3 Design Page 3 - I
Amerex KP Wet Chemical System (EX 4658)
DUCT PROTECTION
DUCT PROTECTION LIMITATIONS
SINGLE NOZZLE (PIN 16416)
The Amerex duct nozzle (PIN 16416) is listed to protect restaurant cooking ducts of unlimited length up to 50
perimeter inches (127 cm) or 16 diameter inches (40.6 cm) using one nozzle. The nozzle has one flow point
and must be centered within the duct, placed 2 - 8 inches (5.08 - 20.32 cm) into the duct opening and aimed
at the center of the cross section of the duct.
NOTE: In no case shall the diagonal
dimension of the duct exceed 18.8 inches
without additional duct nozzles.
OF VERTICAL DUCT
-
- -Q OF HORIZONTAL DUCT
/ AIM POINT
VERTICAL / HORIZONTAL DUCT
TRANSITIONS
Special Note: For ducts with vertical/horizontal
transitions reference the diagram above with respect
to nozzle aim.
TRANSITION LIMITATIONS - SINGLE NOZZLE (PIN 16416)
A transition is a section found on some exhaust systems between the hood and the duct. One Amerex
duct nozzle (PIN 16416) will protect a transition at the point where the transition is 50 perimeter inches
(127 cm) or less or a diameter of 16 inches (40.6 cm) or less. The nozzle has one flow point and must be
placed in the center of the opening at the point where the perimeter inches are 50 (127 cm) or less or
where the diameter inches are 16 (40.6 cm) or less and aimed at the center of the cross section on the
duct. Additional duct protection is not required when using this method.
October 2003 Section 3 Design Page 3 - 2
Amerex KP Wet Chemical System (EX 4658)
DUCT PROTECTION LIMITATIONS -
TWO NOZZLES (2 x P/N 16416)
Two Amerex duct nozzles (PIN 1 641 6) will protect ducts with
51 inches to 82 inches (129.5 - 208.3 cm) or a maximum c
inches (66 cm). To correctly position the nozzles a rectangul
be divided along its longest side into four equal distances. I
should be divided along a centerline into four equal distancE
should be placed at one quarter of the duct's width (or diamE
nozzles on the centerline, paced 2-8 inches (5.08 - 20.3 cm
opening and aimed at the center of the cross section of th
nozzle has one flow point.
NOTE: In no case can the diagonal dimension of
each module exceed 18.8 inches (46 cm).
DUCT PROTECTION LIMITATIONS 100 IN. PERIMETER
TWO - 11/2 FLOW POINT NOZZLES (PIN 11983)
The Amerex solid fuel appliance/duct nozzle (P/N 11983) is listed to
protect a restaurant cooking exhaust duct of unlimited length and up
to 100 perimeter inches (254 cm) or 32 inch diameter (81.2 cm)
using two nozzles. The nozzles total three flow points and to
properly position the nozzles, a rectangular duct should be divided
along its longest side into four equal distances. A circular duct
should be divided along its center line into four equal distances. The
nozzles are to be placed at one quarter and three quarters position
of the duct width (or diameter) with both nozzles on the center line,
placed 2 - 8 inches (5.08 - 20.3 cm) into the duct opening and aimed
straight up in a vertically run duct.
NOTE: In no case can the diagonal dimension of
the duct exceed 37.2 inches (94.4 cm)
without adding additional duct nozzles.
NOTE: The use of one duct nozzle P/N 11983 is
permitted for duct 50 perimeter inches or
less in the same manner as duct nozzle
16416.
32' MAX
October 2003 Section 3 Design Page 3-3
Amerex KP Wet Chemical System (EX 4658)
DUCT PROTECTION LIMITATIONS 150 IN. PERIMETER
THREE 1/2 FLOW POINT NOZZLES (3 x P/N 11983)
The Amerex solid fuel appliance/duct nozzle
(PIN 11983) is listed to protect restaurant
cooking exhaust ducts of unlimited length
and up to 150 perimeter inches (381 cm) or
48 diameter inches (122 cm) using three
nozzles. The nozzles total four and one-half
flow points and to properly position the
nozzles, a rectangular duct should be
divided along its longest side into six equal
distances. A circular duct should be divided
along its center line into six equal distances.
The nozzles are to be placed at one sixth,
one half and five sixths positions of the duct
width (or diameter) on the center line, placed
2-8 inches (5.08 - 20.3 cm) into the duct
opening and aimed straight up for vertically
run duct.
NOTE: In no case can the diagonal dimension
55.9 inches (142 cm) without addin
nozzles.
TRANSITION LIMITATIONS—TWO NOZZLE (PIN 11983)
A transition is a section of some exhaust systems between the hood and the duct. Two Amerex solid fuel
appliance/duct nozzles (P/N 11983) will protect a transition at the point where the transition is 100 perimeter
inches (254 cm) or less or a diameter of 32 inches (94.4 cm) or less. The nozzles total three flow points and
to properly position the nozzles, a rectangular duct should be divided along its longest side into four equal
distances. A circular duct should be divided along its center line into four equal distances. The nozzles are to
be placed at one quarter and three quarters position of the duct width (or diameter) with both nozzles on the
center line, placed 2 - 8 inches (5.08 - 20.3 cm) into the duct opening and aimed straight up in a vertically run
duct. Additional duct protection is not required when using this method.
NOTE: In no case can the diagonal dimension of the duct exceed 37.2 inches (94.4 cm)
without adding additional duct nozzles.
(REFER TO PAGE 3-2 FOR PICTORIAL REPRESENTATION)
October 2003 Section 3 Design Page 3-4
Amerex KP Wet Chemiccil System (EX 4658)
NOZZLE LOCATION AND AIMING FOR
HORIZONTALLY RUN DUCTS PROTECTED BY DUCT NOZZLE 11983
The nozzles are to be located on the centerline of the
vertically run duct, 2-8 inches (5.08-20.3cm) into the
duct. The aiming point is to be a point 3 (7.6cm) inches
above the base of the horizontally run duct and in the
same vertical plane of the nozzle. See illustration.
(j. OF VERTICAL DUCT
_____ - OF HORIZONTAL DUCT
FAIM POINT
DUCT
NOZZLE
VERTICAL / HORIZONTAL
DUCT TRANSITIONS
DUCT PROTECTION LIMITATIONS -
MULTIPLE NOZZLES (P/N 16416)
Protecting ducts larger than 100 perimeter inches (254 cm) utilizing the single flow point nozzle (P/N 16416)
the perimeter is divided by 50 (126.9 cm). The resulting number must be rounded up to the next whole
number. This equals the minimum number of duct nozzles that must be used. The cross sectional area of
the duct is then divided into the same number of equally sized modules. The duct nozzle is then located in
the center of each
module.
Note: In no case can the
diagonal dimension of each
module exceed 18.8 inches
(46 cm) without adding
additional duct nozzles.
2A + 213 = PERIMETER
OR
(A + B) 2 = PERIMETER
PLENUM PROTECTION - MULTIPLE NOZZLES
Plenums exceeding 10 feet (3.048 m) in length may be
protected by using multiple plenum nozzles. Each nozzle must
be protecting an area of no more than 10 feet in length.
Nozzles may be positioned facing each other or facing the
same direction as long as the entire plenum area is being
covered. Nozzles may not face in opposite directions from a
common tee.
October 2003 Section 3 Design Page 3 - 5
Amerex KP Wet Chemical System (EX 4658)
PLENUM PROTECTION
PLENUM 'PROTECTION LIMITATIONS -
SINGLE FLOW POINT NOZZLE (P/N 11982)
The Arnerex appliance, plenum nozzle (P/N 11982) is capable of protecting plenums up to 10 feet (3.048m)
long with either a single inclined filter bank or a "V" bank filter arrangement. The filter height cannot exceed
24 inches (60.96 cm). Each plenum nozzle uses one flow point. The nozzle must be positioned 4 inches
(10.16) maximum from the wall, aimed horizontally and positioned down 1/3 the filter height from the top of
the filter.
"V" Bank Protection
I 1/3FILTERHEIGHT
DOWN FROM THE
TOP OFThE FILTER,
CENTERED INTHE
"V" BANK
c
co NOUTOBE
LOCATED 4
FROM END WALL
CENTERED INThE
V" BANK
Single Bank Protection
V3 HEIGHT
½tY2
- T FROM
THETOP OF
THE FILTER,
ON CENTER
BETWEEN
SIDEWALL
AND FILTER
NIZI
OFROMENDWALL,- 4"
ENTERED ON THE
FILTER
FULL VAT FRYER
WITH DRAINBOARD
NOZZLE I80 APART 36'
AIMING POINT
October 2003 Section 3 Design Page 3— 6
Amerex KP Wet Chemical System (EX 4658)
FRYER PROTECTION (FULL VAT)
TWO FLOW POINT NOZZLE (P/N 13729)
MAXIMUM AREA: 191/2 in. (50 cm) x 25-3/8 in. (65 cm) including drainboard interface area
191/2 in. (50 cm) x 19 in. (48 cm) not including drainboard interface area
The Amerex fryer nozzle (PIN 13729) uses two flow points and will protect a
full vat fryer. If the fryer does not include a drainboard, the maximum fryer
dimensions for single nozzle coverage are 19" x 191/2" (48 x 50 cm) and the
maximum protected area is 2.53 ft2 (2350 cm2). If the fryer does contain a
drainboard the maximum fryer dimensions for single nozzle coverage are 25-
3/8" x 19W (65 x 48 cm) and the maximum protected area is 3.44 ft2
(3195 cm2). However, the maximum hazard area must not exceed 19" x 19
%" (48 x 50 cm). The nozzle must be located along or anywhere within the
protected area. Nozzle heights must be within 36 to 48 inches (91.44
- 121.92 cm) above the appliance surface and aimed to the center of the
hazard area of the appliance.
Locate nole within shad
(above the pretested
AIM POINT
(CENTER OF HAZARD
Front
WITHOUT DRAIN8OARI
Note: Maximum & minimum heights must be
measured vertically from the tip of
nozzle to the top of the appliance.
FULL VAT FRYER
WiTH DRAINBOARD
LOW PROXIMITY APPLICATION
FRYER PROTECTION (FULL VAT)
TWO (2) SINGLE FLOW POINT NOZZLE (PIN 11982)
MAXIMUM AREA: 191/2 in. (50 cm) X 25 3/8 in. (65 cm) (including drainboard interface area)
19/2 in. (50 cm) x 19 in. (48 cm) (not including drainboard interface area)
A pair of Amerex single flow point nozzles
(P/N 11982) will protect a full vat fryer. The
nozzles must be used in pairs located on the
perimeter of the appliance, 1/2" back from the
inside edge of the appliance and within a
zone extending 6" in both directions of the
center of the hazard. The nozzles are to be
located 180° apart (directly across from one
another). They are to be aimed at a point 3"
below the top of the appliance and directly
below the opposing nozzle. If the fryer does
not include a drainboard, the maximum fryer
dimensions are 191/2" x 19" (50 x 48 cm) and
the maximum protected area is 2.53 ft2 (2530
cm2). If the fryer does contain a drainboard,
the maximum fryer dimensions are 25 3/8" x
19 %" (65 x 50 cm) and the maximum
protected area is 3.44 ft2 (3195 cm2).
However, the maximum hazard area must
not exceed 19 /2 " x 19" (50 x 48 cm). The
nozzle's height must be within 171/2" to 36"
(45 - 92 cm) above the appliance surface.
25-3/8
MAX.
October 2003 Section 3 Design Page 3 - 7
Amerex KP Wet Chemical System (EX 4658)
FRYER PROTECTION (SPLIT VAT)
TWO FLOW POINT NOZZLE (PIN 13729)
MAXIMUM AREA: 14 in. (35.5 cm) X 21 in. (53.5 cm) (including drainboard interface area)
14 in. (35.5 cm) x 15 in. (38.1 cm) (not including drainboard interface area)
The Amerex fryer nozzle (PIN 13729) uses two flow points and will
protect a split vat fryer. If the fryer does not include a drainboard, the
maximum fryer dimensions for single nozzle coverage are 15" x 14"
(38.1 x 35.5 cm) and the maximum protected area is 1.46_ft2 (1356
cm2). If the fryer does contain a drainboard, the maximum fryer
dimensions for single nozzle coverages are 21" x 14" (53.5 x 35.6 cm)
and the maximum protected area is 2.0422 (1897 cm2). However, the
maximum hazard area must not exceed 15" x 14" (38.1 x 35.5 cm).
The nozzle must be located within the protected area on a line
perpendicular to the longest side of the fryer passing through the
center of the hazard area. Nozzle heights must be within 40 to 50
inches (101.6— 127 cm) above the appliance surface and aimed to the
center of the hazard area of the appliance.
SPLIT VAT FRYER
WITH DRAINBOARD
Locate note within shaded area
(above the protected area)
AIM POINT
(CENTER OF HAZARD AREA)
— -
SPLIT VAT FRYER
i&iI!PUT DRAINBOARD
NOTE: Maximum and minimum heights
must be measured vertically from the tip
of nozzle to the top of the appliance.
SPLIT VAT FRYER
WITH DRAINBOARD
FRYERS EXCEEDING SINGLE NOZZLE PROTECTION:
Multiple Amerex fryer nozzles (PIN 13729) may be used to
protect single vat fryers with maximum protected areas
exceeding single vat coverages up to a maximum protected
area of 6 ft2 The fryer must be divided into modules for
single nozzle coverages and the nozzle located and aimed for
each module as indicated for single nozzle coverages. For
modules that do not include drainboards, the maximum
module dimensions for single nozzle coverages is 19 ½" x
19" (50 x 48 cm) and the maximum protected area is 2.53 ft2
(2350 cm2). If the module does contain a drainboard, the
maximum module dimensions for single nozzle coverage is
25 3/8' x 19 1/2? (65 x 50 cm) and a maximum protected area
is 3.44 ft2 (3195 cm2). However, the maximum frying area of
a module must not exceed 19 ½" x 19" (50 x 48 cm).
AIM POINTS
October 2003 Section 3 Design Page 3 —8
Amerex KP Wet Chemical System (EX 4658)
SINGLE BURNER RANGE PROTECTION
ONE -1/2 FLOW POINT NOZZLE (P/N 11984)
The Amerex half (1/2) flow point nozzle (P/N 11984) will protect a single
burner with a surface area of 18" x 18" (46 x 46 cm). The nozzles must
be located on the perimeter of the burner and 20 to 24" (51 - 61 cm)
above the burners surface. The nozzle is aimed at a point 7" above the
center of the burner.
SINGLE BURNER RANGE PROTECTION - OVERHEAD
ONE - 1/2 FLOW POINT NOZZLE (PIN 11984)
The Amerex half (%) flow point nozzle (P/N 11984) will protect a
single burner with a surface area of 18" x 18" (46 x 46 cm). The
nozzles must be located directly above the center of the burner
and 24 to 42" (61 - 107 cm) above the burners surface. The
nozzle is aimed at the center of the burner.
TWO BURNER RANGE PROTECTION -
SINGLE FLOW POINT NOZZLE (P/N 11982)
18'
24"
0.1
18"
24
The Amerex appliance, plenum nozzle (PIN 11982) has
one flow point and will protect a range surface area of
14" x 28" (36 x 71 cm). The center to center distance
between burners must not exceed 14" (36 cm). The
nozzle must be located 44 - 48" (112 - 122 cm) above
the range surface and centered between the two
burners. The range surface area is measured from the
outside of the burner to the outside of the burner.
NOTE: Maximum and minimum heights
must be measured from the tip of nozzle
to the surface of the appliance.
October 2003 Section 3 Design Page 3 - 9
Amerex KP Wet Chemical System (EX 4658)
RANGE PROTECTION
SINGLE FLOW POINT NOZZLE (P/N 11982) 12"
nan' mY
The Amerex appliance plenum nozzle (PIN 11982) has
one flow point and will protect a range surface area of
12" x 24" (31 x 61 cm). The center to center distance
between burners must not exceed 12" (31 cm). The
nozzle must be located 36 - 50" (91 - 127 cm) above the
range surface and centered between the two burners.
The range surface area is measured from the outside of
the burner to the outside of the burner.
Note: Maximum & minimum heights
must be measured from the tip of nozzle to
the surface of the appliance.
RANGE PROTECTION
MULTIPLE NOZZLES (P/N 11982)
For ranges that have a surface area exceeding the
capabilities of a single appliance nozzle, multiple
nozzles must be used provided that the surface area
of the range is divided into equally sized modules.
Each module must be equal to or less than 12" x 24"
(31 x 61 cm).
Note: Maximum & minimum heights must be
measured from the tip of nozzle to the surface of
the appliance.
PROTECTION OF BACK SHELVES
Confronted with a back shelf that obstructs the spray pattern of
the protecting nozzle? Locate the nozzle so that it is below the
shelf and still within its listed minimum. When the shelf
interferes with the proper nozzle orientation it may be
necessary to route the pipe under the shelf or provide a hole in
the shelf for the nozzle. Always receive agreement on shelf
alterations before performing the work.
NOZZLE PN14178 rl-i BACK SHELF
18" MINIMUM
NOZZLE HEIGHT
L_
FOUR BURNER RANGE
August 2004 Section 3 Design Page 3 - 9A
Amerex KP Wet Chemical System (EX 4658)
RANGE PROTECTION
TWO - HALF FLOW POINT NOZZLE (P/N 11984)
The Amerex appliance nozzle (P/N 11984) has one-half flow point value and when used as a pair as illustrated
below will protect a range surface area of 12" x 36" (31 x 92 cm). The nozzle must be located 20 - 30" (50.8 -
76.2 cm) above the range surface, on the burner centerline, 2 inches (5 cm) outboard of the burner and aimed
at the center of the hazard area. The nozzles are to be at the same height and on opposite sides of the range
hazard area.
36" H
OWN I'll ME
N '7-4 I
~14§ L_ rNMIN
g4,4
_.A,
TOP VIEW
t
Note: Maximum & minimum heights
- must be measured from the tip of nozzle to
20"-30" the surface of the appliance.
-... -
I I I
PLAN VIEW
RANGE PLUS BACK-SHELF PROTECTION
OVERHEAD APPLIANCE NOZZLE (P/N 11982)
20
The Amerex appliance nozzle (P/N 11982) has a one flow
point value and will protect a range burner area of 12" x 24"
(31 X 61 cm) from an overhead position. The back shelf
must be at least 20" high (51 cm) and must not cover more
than 11" (28 cm) of the back burners. The nozzle must be
located 40 -47" (102 - 119 cm) above the range surface, on
the burner centerline, 4-6 inches (10- 15 cm) forward of the
center of the two burners and aimed at the center of the
hazard area.
Note: Maximum & minimum heights
must be measured from the tip of nozzle to
the surface of the appliance.
24"
12"
!IT OP VIEW
EDGE
4"-6"
11"
40"-47"
r I
MIN. MAX,
PLAN VIEW
TOP VIEW
KI
OPPOSITE CORNER OF THE
BROILING AREA.
August 2004 Section 3 Design Page 3 - 913
Amerex KP Wet Chemical System (EX 4658)
CLOSED TOP CHAIN BROILER
SINGLE FLOW POINT NOZZLE (PIN 11982)
EXTERNAL The Amerex appliance/plenum nozzle (P/Ni 1982) has one flow • DRIP PAN
point and will protect a closed top chain broiler with a cooking area
of 24 1/2' x 31" (62 X 79 cm). The nozzle is to be located on the
side opposite the external drip pan (when present), positioned in
the middle of the inlet opening and aimed at the opposite rear
corner.
NOZZLE LOCATED IN THE
CENTER OF THE IN-LET
OPENING
S
. FRONT VIEW
EXTERNAL
DRIP PAN
CLOSED TOP
CHAIN BROILER
DRIP PAN
TOP VIEW
OPEN TOP CHAIN BROILER
TWO FLOW POINT NOZZLE (PIN 13729)
The Amerex fryer nozzle (PIN 13729) has two flow
points and will protect an open top chain broiler with a
cooking area of 24%" x 31" (62 x 79 cm). The minimum
opening is 10" x 10" (25.4 x 25.4 cm) and the nozzle is
to be positioned 2" behind the edge of the opening, at a
height of 12" - 36" (30.5 - 91 cm)above the appliance
and aimed at the center of the opening.
"- NOZZLE LOCATED 2" BEHIND
THE EDGE OF THE OPENING
AIMED TO THE CENTER OF THE
OPENING - 10' x 10" MINIMUM OPENING
L
\ 12-36' NOZZLE
HEIGHT ABOVE
\ APPLIANCE
N
N
Note: Maximum & minimum heights
must be measured from the tip of nozzle to
the surface of the appliance.
FRONT VIEV
EXTERNAL
DRIP PAN
October 2003 Section 3 Design Page 3-10
Amerex KP Wet Chemical System (EX 4658)
FOUR (4) BURNER RANGE PROTECTION
TWO (2) FLOW POINT NOZZLE (PIN 14178)
The Amerex 4 burner range nozzle (P/N 14178) has two (2) flow points
and will protect a range surface area of 24" x 24" (61 x 61 cm). The center
to center distance between burners must not exceed 12 inches. The
nozzle must be located 18 - 50" (46 - 127 cm) above the range surface
and centered between the burners. The nozzle is aimed straight down at
the center of the appliance.
NOTE: Maximum and minimum
heights must be measured from
the tip of nozzle to the surface of
the appliance.
RANGE PROTECTION—MULTIPLE NOZZLES (P/N
14178)
For ranges that have a surface area exceeding the
capabilities of a single nozzle, multiple nozzles must be
used provided that the surface area of the range is
divided into equally sized modules. Each module must
be equal to or less than 24" x 24" (61 x 61 cm).
NOTE: When using this nozzle to protect a two
(2) burner range the aiming point is where an
8.50" radius from the center of each burner
crosses one another
50"
WOK PROTECTION
SINGLE FLOW POINT NOZZLE (P/N 11982)
The Amerex appliance plenum nozzle (P/N 11982)
has one flow point and will protect a wok with
dimensions between a minimum diameter of 14" (36
cm) and a maximum diameter of 24" (61 cm)
inclusive. The wok must have a height dimension
between a minimum of 4" (10 cm) and a maximum of
7" (18 cm) inclusive. The nozzle must be centered
over the center of the wok and located at a height
between 40 (102 cm) and 50" (127 cm) from the
bottom of the inside of the wok and aimed at the
center of the wok.
24
14 max.
Mm. Size
Max. Size
\_____,/ 4- min.
max.
Aim POint
,
11" Square Centered
on Griddle Perimeter of Griddle
of Intersection
lM POINT
11" square centered
on griddle center
mar. max
mm.
max,
'•' '••1. iisguaze
N. 4' Centered on
'\ Griddle Module
October 2003 Section 3 Design Page 3 - 11
Amerex KP Wet Chemical System (EX 4658)
GRIDDLE PROTECTION -
SINGLE FLOW POINT NOZZLE (PIN 11982)
The Amerex griddle nozzle (PIN 11982) has one flow ! —480 max.
point and will protect a griddle surface of 36 inches
wide (91 cm) x 30 inches deep (76 cm). The nozzle
must be located along the perimeter of the appliance
and within a vertical height range from 30" to 48" (76
- 122. cm) above the surface of the appliance. The Xt aiming point for the nozzle is the "point of
intersection" of a straight line from the nozzle location
to the center of the appliance, with an 11" (28 cm)
square, generated about the center point of the max.
griddle. Centered on
Griddle Center
Note: Maximum & minimum, heights
must be measured from the tip of nozzle
to the surface of the appliance.
Nozzle Location
GRIDDLE PROTECTION -
MULTIPLE SINGLE FLOW POINT NOZZLES (P/N 11982)
Multiple Amerex griddle nozzles (PIN 11982 -
one flow point) may be used to protect a griddle
surface area greater than 30 inches (76 cm) X 36
inches (91 cm). The griddle must be divided into
modules for single nozzle coverage and the
nozzles located and aimed for each module as
indicated for single nozzle coverage.
11' square centered
on griddle center -
Perimeter of Griddle
.-'Modules
Note: Maximum & minimum heights
must be measured from the tip of
nozzle to the surface of the appliance.
Point of Intersection
Izz!e Location AIM POINT for nozzle
protecting this module
are centered
lie center
October 2003 Section 3 Design Page 3 - 12
Amerex KP Wet Chemical System (EX 4658)
GRIDDLE PROTECTION - OVERHEAD
TWO FLOW POINT NOZZLE (PIN 13729)
The Amerex fryer and griddle nozzle (PIN 13729) has two
flow points and will protect a griddle surface of 42 inches
wide (107 cm) X 30 inches deep (76 cm). The nozzle
must be located within 6 inches (15 cm) of either side of
the appliance centerline, placed 38 inches (97 cm) to 50
inches (127 cm) above the cooking surface and aimed
straight down.
Note: Maximum & minimum heights
F F must be measured from the tip of
I I nozzle to the surface of the appliance.
I I
iFFI 50"
38
12" square centered
on griddle center
30'
GRIDDLE PROTECTION - OVERHEAD
MULTIPLE TWO FLOW POINT NOZZLES (P/N 13729)
Griddles exceeding 30 inches (76 cm) X 42 inches
(107 cm) may be protected using multiple two flow
point nozzles by dividing the surface area into equal
modules. Each module requires one nozzle and
cannot exceed an area larger than 42 inches length
(107 cm) X 30 inches deep (76 cm).
12" square centered
on griddle center
Note: Maximum & minimum heights
must be measured from the tip of
nozzle to the surface of the appliance.
30" max.
rt
42n max.
842 max 42' max. >C1
N
of Intersection
%IM POINT
11 Square Centered
on Griddle
Perimeter of Griddle
Nole Location
Oôtober 2003 Section 3 Design Page 3 - 13
Amerex KP Wet Chemical System (EX 4658)
GRIDDLE PROTECTION - LARGE
TWO (2) FLOW POINT NOZZLE (P/N 14178)
The Amerex Range Nozzle (P/N: 14178) has two (2)
flow points and will protect a griddle surface of 48
inches wide (122 cm) x 30 inches deep (76 cm). The
nozzle must be located along the perimeter of the
appliance and within a vertical height range from 24"
(61 cm) to 5011 (127 cm) above the surface of the
appliance. The aiming point for the nozzle is the
"Point of Intersection" of a straight line from the
nozzle location to the center of the appliance, where
the line crosses the outer edge of an 11 inch square
(28 cm sq.), centered over the center point of the
griddle.
11 Square Centered
on Griddle
Note Maximum & minimum
heights must be measured
from the tip of nozzle to the
surface of the appliance.
Perfrneter of Griddle
11 square
centered on
griddle's
center
of Intersection
%IM POINT
Nozzle Location
GRIDDLE PROTECTION - LOW PROXIMITY
TWO (2) FLOW POINT NOZZLE (P/N 14178)
The Amerex Range Nozzle (P/N: 14178) has two (2) flow points
and will protect a griddle surface of 48 inches wide (122 cm) x 30
inches deep (76 cm). The nozzle must be located at any one of the
four corners of the appliance and within a vertical height range
from 15" (38 cm)to 24" (61 cm) above the surface of the appliance.
The aiming point for the nozzle is the "Point of Intersection" of a
straight line from the nozzle location to the center of the appliance,
where the line crosses the outer edge of an 11 inch square (28 cm
sq.), centered over the center point of the griddle.
1* _
i - 24" max.
15" min.
<N
I '
- I
48 max. 11'Square
Centered on
Gnddle Center
Note: Maximum & minimum
heights must be measured
from the tip of nozzle to the /
surface of the appliance. 24"
15°
11' square
centered on
module center
October 2003 Section 3 Design Page 3 - 14
Amerex KIP Wet Chemical System (EX 4658)
UPRIGHT BROILER PROTECTION
TWO HALF FLOW POINT NOZZLES (P/N 11984)
Two Amerex upright broiler nozzles are required for this application. Each upright broiler nozzle (P/N 11984)
equals a ½ flow point. These nozzles must always be used in pairs equaling one flow point and will
protect an internal broiler chamber measuring 30 1/2" X 28 ½" (77 x 72 cm). The nozzles must be positioned
at the front opening of the broiler with the top nozzle located above the grate, aimed toward the opposite rear
corner and the lower nozzle located the grate and aimed toward the center of the drip pan.
UPRIGHT BROILER
ARMING
HAMBER
R CHAME
DRIP PAN
FRONT VIEW
SIDE VIEW
NOTE: PROTECTION FOR SALAMANDERS AND
CHEESE MELTERS UP TO 38" (96.5cm) IN LENGTH
SHOULD BE ACCOMPLISHED USING A SINGLE
FLOW APPLIANCE NOZZLE P/N 11982 LOCATED IN
THE MIDDLE OF THE OPENING AND AIMED AT THE
REAR OPPOSITE CORNER.
OPTIONAL : PROTECTION MAY ALSO BE
ACCOMPLISHED BY USING TWO HALF FLOW POINT
NOZZLES PN11984 , BOTH NOZZLES LOCATED ON
THE SAME SIDE OF THE SALAMANDER,
POSSITIONED IN THE MIDDLE OF THE UPPER AND
LOWER OPENING, AIMED TO THE REAR OPPSITE
CORNER.
r\.
0
Nate: Max. & Mm. heights ws1 be
measured from the tip at nozzle
to the top of the 0004dng
surface
October 2003 Section 3 Design Page 3— 15
Amerex KP Wet Chemical System (EX 4658)
GAS RADIANT CHARBROILER PROTECTION
SINGLE FLOW POINT NOZZLE (P/N 11982)
One Amerex plenum nozzle (PIN 11982)
will protect a gas radiant charbroiler with a
cooking surface measuring 24 inches X 24
inches (61 x 61cm) maximum. The nozzle
uses one flow point. It must be located 18
to 48 inches (46 - 122 cm) above the
cooking surface and anywhere along or
within the perimeter aimed towards the
center.
ELECTRIC RADIANT CHARBROILER
PROTECTION SINGLE FLOW POINT
NOZZLE (P/N 11982)
Note: Electric charbroilers with a non-grated
surface or a solid ribbed surface may be
protected using the same limitations as a
griddle.
Electric charbroilers with an open grate may
be protected with one Amerex appliance,
plenum nozzle (PIN 11982) provided that the
area is no larger than 24 inches X 24 inches
(61 x 61 cm). The nozzle uses one flow point
and must be located within 18 - 48 inches
(46 - 122 cm) above the grate surface,
anywhere along or within the perimeter of the
protected area, aimed towards the center.
LAVA ROCK (CERAMIC/SYNTHETIC)
CHARBROILER
SINGLE FLOW POINT NOZZLE (P/N 11983)
A single Amerex solid fuel appliance plenum
nozzle (P/N 11983) will protect a lava rock
charbroiler with a maximum cooking surface
of 24 inches wide (61 cm) by 24 inches deep
(61 cm). The appliance nozzle uses 1 1/2 flow
point and for this application must be located
between 18 to 44 inches (46 to 122 cm)
above the cooking surface anywhere along
or within the perimeter of the appliance
aimed toward the center.
I
All
6" -*
Max.
Solid Fuel - Charcoal
6"
Max.
Solid Fuel - Mesquite Chips & Chunks
it, --P.
Max.
Solid Fuel - Mesquite Logs
October 2003 Section 3 Design Page 3- 16
Amerex KP Wet Chemical System (EX 4658)
SOLID FUEL APPLIANCES
NATURAL AND MESQUITE CHARCOAL
CHARBROILER PROTECTION ONE AND
ONE HALF (11/2) FLOW POINT NOZZLE (P/N 11983)
One Amerex solid fuel appliance nozzle (P/N 11983) will
protect a charcoal charbroiler with a cooking surface
measuring 281/2 inches x 24 inches (72 cm x 61 cm)
maximum. The nozzle uses one and one half flow points.
It must be located 16 to 42 inches (41 cm - 107 cm) above
the cooking surface and anywhere along or within the
perimeter aimed at the center. The fuel depth is limited to 6
inches (15 cm) maximum.
MESQUITE CHIPS & CHUNKS CHARBROILER
ONE AND ONE HALF (1/2) FLOW POINT NOZZLE
(P/N 11983)
A single Amerex solid fuel appliance nozzle (PIN 11983) will
protect a mesquite charbroiler with a maximum cooking
surface of 28% inches X 24 inches (72 cm X 61 cm). The
nozzle uses one and one half (11/2) flow points and for this
application must be located between 16 to 48 inches (41 cm
to 122 cm) above the cooking surface anywhere along or
within the perimeter of the appliance aimed at the center of
the appliance. The fuel depth is limited to 6 inches (15 cm)
maximum.
MESQUITE LOG CHARBROILER
ONE AND ONE HALF (11/2) FLOW POINT NOZZLE
(P/N 11983)
A single Amerex solid fuel appliance nozzle (PIN 11983) will
protect a mesquite log charbroiler with a maximum cooking
surface of 281/2 inches X 24 inches (72 cm X 61 cm). The
nozzle uses one and one half (11/2) flow points and for this
application must be located between 19 to 44 inches (48 cm to
112 cm) above the cooking surface anywhere along or within
the perimeter of the appliance aimed at the center of the
appliance. Solid fuel is limited to three (3) layers of logs or 11
inch (28 cm) maximum stacked height.
July 2006 Section 3 Design Page 3— 16A
Amerex KP Wet Chemical System (EX 4658)
NIECO MODEL 9025 - BURGER KING CHAIN BROILER
TWO - SINGLE FLOW POINT NOZZLE (P/N 11982)
The Nieco Chain Broiler Model 9025 is a unique appliance and when fitted with two catalysts it requires the
use of two Amerex nozzles (P/N 11982) to protect each half of the appliance. Total appliance protection
therefore, requires the use of a total of four Amerex nozzles (P/N 11982). This unique appliance is actually
two chain broilers put together to accommodate the cooking of two different products at the same time. This
appliance can be fitted with two catalysts (18" x 24" overall) one for each cooking side.
The protection of the appliance is accomplished by using two nozzles PIN 11982 positioned two inches
outside of the catalyst perimeter aimed at the center point of the catalyst. The nozzles are to be located on
opposite ends of the catalyst, 1800 apart and are to be 13" to 36" above the top surface of the catalyst. This
configuration is repeated for both cooking sides of the appliance. If no catalyst is used the same protection is
required for the unit.
Note: Maximum & minimum heights
must be measured from the tip of nozzle
to the top surface of the catalyst or
appliance (if no catalyst is used).
71 --
TOP VIEW
-- --
NOZZLE LOCATED 2" BEHIND
THE EDGE OF THE CATALYST
AIMED TO THE CENTER OF THE
CATALYST - 18' x 24
Ak A
12"-36NOZZLE
HEIGHT ABOVE
CATALYST
\\\ •// \\ 1,1
FRONT VIEW
I14IL,L tlu4o
CHAIN BROILER
Nozzle PIN Flow
£ rOifli.S
. Width Length Mm.
. , neigiiu.
Max.
Height
FFDeepFateFryer—without Drip Pan 13729 2 19 1/2 in. 19 in. 36 in. 48 in.
yer—with Drip Pan 13729 2 19% in. 253/8 in. 36 in. 48 in.
yer—with Drip Pan Low Proximity 2-11982 2 19 1/2 in. 253/8 in. 17 1/2 1n. 36 in.
Range - Single Burner 11984 % 18 in. 18 in. 20 in. 42 in.
Range —Two Burner 11982 _1_ 14 in. 28 in. 44 in. 48 in.
Range —Two Burner 11982 _1_ 12 in. 24 in. 36 in. 50 in.
Range-Two Burners w/Back Shelf 11982 1 12 in. 24 in. 40 in. 47 in.
Low Back-Shelf/Salamander— BS Manifold 17461 1 14 in. 42 in. 14 in. 19 in.
Range — ThreeBurners 2-11984 1 12 in. 36 in. 20 in. 30 in.
Range - Four Burners _14178 2 24 in. 24 in. 18 in. 50 in.
Wok 11982 1 14-24 dia. 4-7 depth 40 in. 50 in.
Griddle 11982 1 30 in. 36 in. 30 in. 48 in.
Griddle 13729 2 30 in. 42 in. 38 in. 50 in.
Griddle 14178 2 30 in. 48 in. 15 in. 50 in.
Upright Broiler 2-11984 1 30% in. 28 1/2 in. - -
Charbroiler (Lava Rock) 11983 1% 24 in. 24 in. 18 in. 44 in.
Charbroiler (Gas Radiant & Electric Radiant) 11982 1 24 in. 24 in. 18 in. 48 in.
Chain Broiler - Closed Top 11982 1 241/2 in. 31 in. - -
Chain Broiler — Open Top _13729 2 241/2 in. 31 in. 12 in. 36 in.
Chain Broiler— Nieco Model 9025 /Catalyst (2) 4-11982 2 18 in. 24 in. 12 in. 36 in. Natural & Mesquite Charcoal Charbroiler _11983 1 % 24 in. 28 % in. 16 in. 42 in. Mesquite Chips & Chunks Charbroiler 11983 1 % 24 in. 28 % in. 16 in. 48 in. Mesquite Log Charbroiler =11983 1 % 24 in. 28 % in. 19 in. 44 in.
Plenum Nozzle PIN Flow
Points Width Length
10 ft. Single BankN-Bank 11982 1 4ft.
Duct Nozzle PIN Flew
Points
Max.
Perimeter Diameter Length Max.
Diagonal Rectangular 16416 1 50 in. - Unlimited 18.8 in. Circular 16416 1 - 16 in. Unlimited - Rectangular 2-11983 3 .100 in. - Unlimited 37.2 in. Circular 2-11983 3 - 32 in. Unlimited - Rectangular 3-11983 4 1/2 150 in. - Unlimited 55.9 in. Circular 3-11983 1 4 1/2 - 48 in. Unlimited -
Protection is not limited to the items listed on this chart. Madulizing larger appliances is an acceptable practice.
See your Amerec KP Manual for additional information.
C-C
I\)
Q 0)
B
AMEREX KP RESTAURANT SYSTEM NOZZLE APPLICATION CHART
pw-~~
Section 3 Design Page 3— 18
Amerex KP Wet Chemical System (EX 4658)
AGENT QUANTITY AND CYLINDER SELECTION:
After reviewing the hazards and determining the number and type of nozzles that will be required, the
quantity of agent and the number and type of cylinders must be selected. Adding the number of flow
points that are needed for the system will determine the agent quantity and cylinder options. ONE 2.75
GALLON CYLINDER (PIN 16921) WILL SUPPLY SUFFICIENT AGENT FOR UP TO AND INCLUDING 8
FLOW POINTS. ONE 3.75 GALLON CYLINDER (PIN 13334) WILL SUPPLY SUFFICIENT AGENT FOR
UP TO AND INCLUDING 11 FLOW POINTS. ONE 4.75 GALLON CYLINDER (P/N 17379) WILL
SUPPLY SUFFICIENT AGENT FOR UP TO AND INCLUDING 14 FLOW POINTS. Cylinders may be
used together for multiple cylinder systems with one MRM or PRM. A MAXIMUM OF 10 KP 275/375/475
AGENT CYLINDERS MAY BE USED PER MECHANICAL RELEASE MECHANISM OR PNEUMATIC
RELEASE MODULE. ONE 6.14 GALLON CYLINDER (P/N 15196) WILL SUPPLY SUFFICIENT AGENT
FOR UP TO AND INCLUDING 18 FLOW POINTS. A MAXIMUM OF 6 KP 600 AGENT CYLINDERS
MAY BE USED PER MRM or PRM. ANY COMBINATION OF CYLINDERS INVOLVING THE KP600
CYLINDER IS LIMITED TO A TOTAL OF 6 CYLINDERS PER MRM or PRM.
ACTUATION NETWORK LIMITATIONS - MRM OR PRM
The actuation network for the Amerex KP Restaurant Fire Suppression System consists of factory
supplied hose, installer supplied copper tubing or pipe that connects the MRM or PRM to each cylinder
discharge valve. A single MRM or PRM is capable of actuating up to ten (10) 3.75/2.75 gallon agent
cylinder discharge valves or six (6) 6.14 gallon agent cylinder discharge valves by discharging a single 10
in nitrogen cylinder (P/N 12856) through the actuation network. If the network is a
combination of 2.75/ 3.75/ 4.75 & 6.14 gallon cylinders, then maximum number of
cylinders is six (6).
N5 Note: A vent plug (P/N 10173) must be placed in an accessible location
anywhere in the actuation line to aid in releasing pressure after the
system has discharged. See the RECHARGE Section 7.
LIMITATIONS (SINGLE OR MULTIPLE CYL SYSTEMS)
Copper tubing - 1/4" O.D. refrigeration type with a minimum wall thickness of .049 inches. Use with brass or
steel compression style fittings (with brass or steel sleeves or ferrules). Maximum length (including all fittings)
100 feet (30.48 m)
High Pressure Hose - 1/4" I.D. wire braid hose that is factory supplied. Maximum length (including all fittings)
54 feet (16.46 m) or a maximum number of 40 hose assemblies P/N 12854, 20-hose assemblies P/N 16448,
or any combination that does not exceed a total of 54 feet (16.56 m)
Pipe - ¼" NPT schedule 40 made of stainless steel,
galvanized, chrome plated or black iron pipe.
Maximum length - 22.2 feet (6.77m)
Maximum tees - 9
Maximum elbows - 9 (note: 2 -
450 elbows = 90°)
Note: Different methods of constructing the actuation network
may be mixed provided that the shortest limitations are followed,
Example: A mix of ¼" copper tubing and 1/4" high pressure hose
requires that the hose limitations be followed (no more than 54
feet [16.46m]) for the complete network. A mix of 1/4" high
pressure hose and 1/4" pipe requires that the pipe limitations be
followed (no more than 22.2 feet [6.77m]) for the complete work.
Nitrogen Cylinder 10 cu. in.
Maximum Total Length for: Feet Meters
1/4" Copper tubing 100 30.48
1/40 ID Hose 54 16.46
¼" Schedule 40 Pipe 22.2 6.77
- Mechanical Release Module Possible location for (whO in cyl)
Vent Plug P/N 10173 /
Mechanical Relp—o MM ilô
(whO In3 cyl)
Up to ten (10) KP 275/375/475
Cylinders - maximum or
up to six (6) KP 600
Cylinders - maximum
July 2006 Section 3 Design Page 3 —19
Amerex KP Wet Chemical System (EX 4658)
A Supply Line is the
distribution piping that
runs from the distributor
outlet or discharge fitting
to the first splitting tee. MANUAL ACTUATOR
PLENUM NOZZLE
/ DUCT NOZZLE
/ LINEAR DETECTOR ( 1UBING . N
PPLIANCE NOZS
(P375 C'YIJNOER AS?-' /
PNEUMATIC RELEASE-' MODULE GAS I/Al
A Supply Branch Line
(including the last nozzle
branch) is the distribution
piping that runs from the
first tee atY the hood to the
last nozzle in the system
including all fittings used to
exit the supply branch line. MANUAL
ACTUATOR
NOZZLE
DUCT NOZZLE
LINEAR DETECTOR
- TUBING
-APPLIANCE NOZZLES
(5375 CYLINDER ASY.-I/
PNEUMATIC RELEASE-'
MODULE
GAS VALVE
A Nozzle Branch Line is
the distribution piping that
runs from the supply
branch tee splitting to the
nozzles including all
fittings used to exit the
supply branch line. MANUAL
ACTUATOR
NOZZLE
DUCT NOZZLE
LINEAR DETECTOR
TUBING
NOZZLES
<P375 CYLINDER AS?.-'
PNEUMATIC RELEASE
MODULE
GAS VALVE
GENERAL PIPING REQUIREMENTS:
All pipe used for the distribution network must be schedule 40 (black, chrome or
stainless steel) pipe.
Piping limitations are expressed in linear length of pipe. Linear piping is the actual
length of straight pipe used throughout the system.
WARNING: GALVANIZED PIPE IS N01 ALLOWED
Maximum flow point per cylinder: KP 275 = 8 flow points
KP 375 = 11 flow points
KP 475 = 14 flow points
KP 600 = 18 flow points
Twin KP 375 = 22 flow points
NOTE: THESE ARE EXAMPLES ONLY - OTHER CONFIGURATIONS CAN BE DESIGNED I
ru
Plenui
10 Feet
Supply Branch
October 2003 Section 3 Design Page 3 —20
Amerex KP Wet Chemical System (EX 4658)
TYPICAL DISTRIBUTION NETWORK FOR SINGLE CYLINDER SYSTEM
Duct
Fryer Griddle Range
Distributo
STRAIGHT PIPING SYSTEM
Duct Suoolv Branch
4 Feet Max.
A
10 Feet Max.
V Nozzle1
Wok Branch
Fryer
enum Nozzle
Branch
Griddle
(Overhead)
Range
1 Distributor
SPLIT PIPING SYSTEM
NOTE: The schematics above do not represent the only configurations possible - they are
informational only.
October 2003 Section 3 Design Page 3 - 21
Amerex KP Wet Chemical System (EX 4658)
TYPICAL DISTRIBUTION NETWORK FOR TWIN (KP 375) CYLINDER SYSTEM
&Øy Bath
We
ti (Re-Lim
I I 1I
iI
ii
F1 GicUe pales wd<
4
ftr2ies
STRAIGHT PIPING SYSTEM
Duct
_________ ' Supply Branch
4 Feet Max.
14" Supply Line
Wok
Fryer
lOFeetMax. Plenum
-
I Distributors Range
Manifolded
4 Feet
Max.
/8' Nozzle
Brunch
Fryer
--
Griddle 3/a° Nozzle
Branch
Gas Radiant Charbroiler
SPLIT PIPING SYSTEM
[NOTE: The schematics above do not represent the only configurations possible they are __7 informational only.
July 2006 Section 3 Design Page 3 - 22 Amerex KP Wet Chemical System (EX 4658)
KP DISTRIBUTION PIPING
DESIGN LIMITS FOR ALL CYLINDER SIZES
When designing a KP system to protect a kitchen containing a Fryer, Wok or Range, the
f
o
l
l
o
w
i
n
g
MINIMUM TOTAL SYSTEM PIPING must be used in accordance with the chart below:
SUPPLY LINE LIMITATIONS:
All pipe and fittings running from the distributor block or the discharge fitting to the first tee.
CYLINDER
FLOW POINTS
- - MAXIMUM
PIPE SIZE
;YI;
LINEAR
FEET OF PIPE
Zi
MAX. QTY.
TEES
MAX. QTY.
ELBOWS
MAX. QTY.
BUSHINGS
s
r1, 1I
NOTE: 1. Use 3/8" supply line only when all piping is to be 3/8" pipe.
- 2. The supply line has a maximum vertical rise above the distributor of 10 feet.
SUPPLY BRANCH LINE (including last nozzle branch) LIMITATIONS: All pipe and fittings leaving the first splitting tee in the system and ending with the last nozzle in the las
t
b
r
a
n
c
h
line. While the last nozzle branch is included in the piping limitations for the supply branch line, the limitati
o
n
(pipe size and maximum length) for nozzle branch lines apply to this portion of the supply branch line.
CYLINDER
FLOW
POINTS I KP275
PIPE SIZE
3/8
MAX. FEET OF
PIPE STRAIGHT
20
MAX. FEET OF
PIPE SPLIT
25
MAX.
QTy-
TEES
I 7
MAX. MAX.
QTY. REDUCING
ELBOWS BUSHINGS
I 8
OTY.,
0 I KP375-11 I 3/80R1/2 27 30 10 8 I 2 I bKP475-14 I 3/8 27 I 30 I 12 I 8 I 2 I KP600 - 18 I AS NOTED 35' OF 3/8' OR 1/2" 50'3/8" PIPE ONLY ( 14 I 8 I 2 I 2-KP375-22 I 1/2* 40 45 I 18 I 8 I 0 NOTE: 1. In a sinale 3.75 Gallon Straiaht Pioe System. 5' of DiDe may be transferred from the surrnlv line to the supply branch line.
- * 2. The use of 3/8" pipe with two manifold KP375s is only permitted when the SUPPLY LINE length
i
s
equal to or less than 20'.
NOZZLE BRANCH LINE LIMITATIONS:
All pipe and fittings leading from the supply branch tee to a system nozzle.
'A • I. .1-I - t. i - •i. I II .! V%'. 1. r'M.' 'LL%M.1. FLOW POINTS PIPE SIZE Ii i I I:fI KP275-8 3/8 32 5 10 0 KP375-11 3/80R1/2 32 8 12 11 KP475-14 3/8 32 10 15 0 KP600-18 3/8 32 11 18 15 2-KP375-22 3/8 32 18 18 20 MAX. PER NOZZLE BRANCH 7 3 6 4 -- -- GENERAL SYSTEM LIMITATIONS:
No 1/2 pipe nozzle branches shorter than 12" long.
Nozzle types may not be mixed on any nozzle branch line and a maximum of 4 flow points.
The discharge fitting, distributor and distribution hose are not to be included in any calculations.
No mixing of pipe sizes is allowed within pipe categories. Example: if one nozzle branch is to be 1/2 pipe then all must be %" pipe. h/2 pipe for nozzle branch lines is allowed only in an 11 flow point system.
Duct nozzle has a maximum vertical rise above the supply branch line of 4'0".
October 2003 Section 3 Design Page 3 - 23
Amerex KP Wet Chemical System (EX 4658)
DETECTION NETWORK LIMITATIONS: MRM
Optimum fire suppression system performance relies on proper detection network design. This section
discusses the type of detectors used, their selection, placement and design limitations.
The Amerex KP Restaurant Fire Suppression System MRM uses a continuous cable, corner pulleys, detector
bracket, detector linkage, fusible links, conduit offset, terminal link connector and a temperature-measuring
device.
The quantity of detectors to be used in a system will depend on the number of ducts, number of appliances
and the location of the appliances under the hood.
DETERMINING DETECTOR LOCATION AND NUMBER OF DETECTORS
In order to detect a fire in the duct, a detector is required to be placed within the duct opening or up to 12
inches into the duct. If it is mounted into the duct, the bracket cannot shield the fusible link from the hot
vapors moving through the duct.
Every appliance under the hood that is being
protected by the suppression system must
have a detector placed over it and positioned
within the path of exhaust vapors.
WARNING: DO NOT LOCATE DETECTORS
DIRECTLY IN THE PATH OF GAS APPLIANCE
EXHAUST FLUE GASES. DOING SO COULD
RESULT IN UNNECESSARY DISCHARGE OF
THE SYSTEM.
GENERAL LIMITATIONS OF DETECTION
NETWORK:
Maximum of 24 corner pulleys. (either style)
Maximum of 20 detectors (any combination of temperature settings).
Maximum of 120 feet of cable on the detection network.
No pulley tees are allowed.
Remote manual pulls are not allowed on the detection network.
Maximum of I conduit offset (must be located at mechanical release module when chosen).
ATTACH DETECTION NETWORK
TO ANY ONE OF THREE SIDES.
12 O'CLOCK /
POSITION / V CONDUIT OFFSET /
P/N 12508 DETECTOR BRACKET
ASSEMBLY MAXIMUM QUANTITY AS
SPECIFIED.
I I'JI'llL)
CK
POSITION
6 O'CLOCK CABLE LENGTH AND CORNER
POSITION PULLEY MAXIMUMS AS INSTALL IN CONDUIT CONNECTOR SPECIFIED OF LAST DETECTOR BRACKET
ASSEMBLY.
October 2003 Section 3 Design Page 3 —24
Amerex KP Wet Chemical System (EX 4658)
FUSIBLE LINK SELECTION
To assure that the appropriate temperature is selected, the temperature sensing device must be used at each
detector location while the cooking line and exhaust fan is operating. Temperatures found at each detector
should be recorded and placed with other documentation in the job file for future reference. Selection of
fusible links should be made according to the temperature measured:
Globe Type "K" Standard Response Links
Temperature Measured Link Rated Temp. Part No.
70° to 150°F (21° to 65°C) 212°F (100°C) 12326
151° to 225°F (66° to 107°C) 280°F (138°C) 12327
226° to 300°F (21° to 65°C) 360°F (182°C) 12328
301° to 375°F (21° to 65°C) 450°F (232°C) 12329
376° (192°C) & above consult factory consult factory
Job Quick Response Links
Temperature Measured Link Rated Temperature
Job Link
Part Number
700 to 150°F (210 to 65°C) 200°F (93°C) Quick Response 16225
151° to 225°F (66° to 107°C) 286°F (141°C) Quick Response 16226
226° to 300°F (108° to 149°C) 360°F (182°C) Quick Response 16227
DETECTION NETWORK LIMITATIONS: PRM
Select a suitable location for the pneumatic release module (PRM) that has access for installation, service,
recharge and where both the nitrogen actuation cylinder pressure gauge and the system status indicator can
be viewed. The PRM has provisions for a single, continuous section of detection tubing. No splicing or
"tee's" are allowed. There shall be only two tubing terminations - one at the accumulator cylinder inside the
PRM and the other at the opposite end of the tubing, with the use of an End of Line fitting (P/N 16506). Install
in areas where the maximum expected ambient temperature does not exceed 375°F.
SEE SECTION 4 "INSTALLATION" FOR ROUTING INFORMATION ON DETECTOR TUBING PAGE 5
July 2006 Section 3 Design Page 3 - 24A
Amerex KP Wet Chemical System (EX 4658)
LINEAR FUSIBLE LINK DETECTION NETWORK
LINK TO LINK
CABLE SEGMENT
24" MAX. DIST. 24" MAX. DIST. / LINK TO MRM FROM END OF HOOD LUNK TO LINK CABLE SEGMEI 4 11, 4/
LU
/ DUCT
C)
PLENUM
TERMINAL CABLE CABLE EYE BOLT SUPPORT
24" MAX. DIST. SEGMENT REQUIRED O N EACH SIDE FROM END OF HOOD OF THE DUCT TERMINAL CONNECTOR
& EMT FITTING
HANDY CONDUIT BOX
21/8"X4" HOOD
The Linear Fusible Link Detection System provides complete hood fire detection by placing thermal
links at maximum 24" intervals the entire length of the hood. Installing the links in this manner
allows the appliances to be placed anywhere under the hood without having to locate links directly
over each appliance.
A unique system of cable segments, pre-fabricated, has been developed to make the installation of
this system simple and easy. It eliminates the use of conduit, link holders and mounting brackets under the hood in the plenum area.
The limitations of the Linear Fusible Link Detection System are as follows:
Maximum of 20 detection links and (19) Link to Link Cable Segments.
Maximum of 30 feet of cable used in the Link to MRM Cable Segment.
Maximum of 20 corner pulleys. (either style)
Maximum unsupported detection cable length is 8'-0".
Refer to Fusible Link Selection section, page 3-24 of this manual for proper selection
process. The higher setting links are to be used when higher temperatures are encountered
with appliances such as char-broilers.
The Linear Fusible Link Detection System is for use in single hood applications, or where
multiple hoods are connected "end to end" only. It can not be used for "back to back" hood arrangements or multiple hoods that are mounted in separate locations and are part of a
single KP Fire Suppression System.
October 2003 Section 3 Design Page 3 - 25
Amerex KP Wet Chemical System (EX 4658)
MANUAL PULL STATION NETWORK LIMITATIONS
Every Amerex KP Restaurant Fire Suppression System installation must have at least one manual pull
station. The manual pull station network consists of cable, corner pulleys, pulley tee, manual pull station(s)
and optional conduit offset.
GENERAL LIMITATIONS OF MANUAL PULL STATION NETWORK
Maximum of 20 corner pulleys per manual pull station
Maximum of 130 feet of cable per manual pull station
Maximum of I pulley tee per network (counts as one corner pulley for each manual pull station)
Maximum of I conduit offset per network (must be attached to the MRM and before tee pulley when chosen)
NOTE: Manual pull stations should be installed no higher than 48 inches from the floor and must be
along a path of egress. Consult the local Authority Having Jurisdiction (AHJ) for the final
approval for manual pull station quantity, locations and mounting height and other
considerations prior to finalizing manual pull station mounting details.
ATTACH MANUAL PULL STATION
NETWORK TO ANY ONE OF THREE SIDES.
12 OCLOCK
POSITION
CONDUIT OFFS - ( SINGLE STATION (OPTIONAL)
NETWORK
MRM
or
POSITION
6 O'CLOCK !
POSITION
DENOTES SINGLE PATH FOR CABLE LENGTH
& PULLEY QUANTITY CALCULATiON. r - - -
FMRM mp.mj
,
Ji DUAL STATION
or NETWORK
PULLEY TEE
NOTE: The manual pull station(s) are the only MANUAL means of activating the Amerex KP
Restaurant Fire Suppression System.
SINGLE GAS
VALVE
NETWORK MRM
OR
PRM
CONDI
(OPTIC
D "OlkIfli
CABLE LE
QUANTITI
AS
RK
October 2003 Section 3 Design Page 3 - 26
Amerex KP Wet Chemical System (EX 4658)
MECHANICAL GAS VALVE APPLICATIONS
The PRM or MRM closes the mechanical gas valve immediately upon system discharge. A pneumatic and
mechanical action in the gas trip assembly pulls on a cable attached to the mechanical gas valve, unlatching
the valve and allowing an internal spring within the valve body to provide the closing force. Connection of the
cable from the valve to the PRM or MRM under tension maintains the gas valve in an open position.
MECHANICAL GAS VALVE
A mechanical gas valve trip assembly must be used with any
mechanical gas valve. The gas valve trip assembly (P/N
12740) is included with all Amerex manufactured gas valves
but must be ordered separately for use with gas valves listed -EREX PART NO. 12740 in this manual supplied by other manufacturers.
See Section 3 "System Components" for all mechanical gas valves that
are suitable for use with the Amerex Restaurant Fire Suppression
System. The use of any other mechanical gas valves will avoid the UL
listing for the system installation. All of the listed valves have female NPT
threads. The location of the gas valveshould be accessible and approved
by the local Authority Having Jurisdiction. A contractor licensed and
qualified for such work should perform installation of the mechanical gas
valve into the gas line.
MECHANICAL GAS VALVE ACTUATION NETWORK LIMITATIONS
The mechanical gas valve actuation network consists of cable, corner pulleys, pulley tee, gas valve and
conduit offset.
GENERAL LIMITATIONS OF MECHANICAL VALVE NETWORK
Maximum of 20 corner pulleys per mechanical gas valve of any listed type in KP Manual
Maximum of 130 feet (39.6m) of cable per mechanical gas valve of any listed type in KP Manual
Maximum of I pulley tee per network (counts as one corner pulley for each mechanical gas valve)
Maximum of I conduit offset per network (must be located at pneumatic release module and before tee pulley
when chose)
October 2003 Section 3 Design Page 3— 27
Amerex KP Wet Chemical System (EX 4658)
ELECTRICAL GAS VALVE APPLICATIONS
110 VAC electrical gas valves may be used in place of the mechanical gas valves. The electric shut off valve
used with the Amerex KP Restaurant Fire Suppression System must be UL listed for use with natural gas or
propane, be held open by energizing an electric solenoid and be wired through a microswitch and manual
release relay. A qualified electrician must do any field wiring and connections involving the shut down of
electrical cooking equipment or an electric gas valve.
P/N Size Manufacturer
12870 3/4"
Asco
12871
_12872 11/4
12873 1%"
12874
12875 2W
12876
ELECTRIC GAS VALVE OPERATION
Power to the electric gas valve is run through the normally closed contact on a microswitch located in the
pneumatic release module (PRM) or mechanical release module (MRM) to the manual reset relay and from
the manual reset relay to the electric gas valve. In a normal (non fire) condition, current is allowed to flow to
the solenoid on the electric gas valve, holding the valve open. In a fire condition, when the release module
actuates the suppression system, the microswitch contacts will transfer, opening the normally closed contacts
in the manual reset relay, interrupting current to the gas valve and cause it to close.
Resetting the MRM or PRM and transferring the contacts back to a normal (normally closed) position will not
cause the electrical gas valve to open. The manual reset relay must reset before current will flow to the valve
and cause it to open. A loss in electrical power, even temporary or momentary, will require someone to
manually reset the relay before the electrical gas valve will open again.
NOTE: SEE WIRING SCHEMATICS NEXT TWO PAGES
October 2003 Section 3 Design Page 3 —28
Amerex KP Wet Chemical System (EX 4658)
POWER SOURCE MANUAL RESET RELAY
ERM
MRM or
ELECTRIC GAS
VALVE
7
"MICROS WITCH
INSTALLER PROVIDED JUNCTION BOXES
BASIC WIRING DIAGRAM
POWER SOURCE
MANUAL RESET RELAY
RED (COMMON) Ll
-
YELLOW (N.
1661
GAS VALVE
NOTE: DO NOT USE YELLOW WIRE ON MICROSWITCH IN NORMAL
MICROSAITCH INSTALLATION. THE YELLOW WIRE IS TO BE USED ONLY FOR EXTINGUISHER
ALARM, LIGHT CIRCUITS, ETC.
BASIC WIRING DIAGRAM MANUAL RESET RELAY
H RED (COMMON) I 20V/6OHZ Li
—+--o Ka -
YELLOW (N PUSHBPUSHBUTTON
I SWITCH
M ICR OS WI TCH >1<
CURRENT DRAW MAX: BA GAS VALVE RESISTIVE, BA INDUCTIVE, NOTES: 12OvAC SEE NOTE 3 DENOTES FIELD INSTALLATION
---- DENOTES FACTORY INSTALLATION
GAS VALVE: UL LISTED ELECTRICALLY—OPERATED SAFETY VALVE FOR NATURAL OR LP GAS AS NEEDED OF
APPROPRIATE PRESSURE AND TEMPERATURE RATING, 11OV/60HZ OR AMEREX GAS VALVES, P/N 12870, 12871,
12872, 12873, 12874, 12875 AND 12876.
Kla AND KTb ARE N.O. WHEN Ki IS DE—ENERGIZED.
October 2003 Section 3 Design Page 3 - 29
Amerex KP Wet Chemical System (EX 4658)
INSTALLATION OVERVIEW
C CAS VM.%
BASIC WRING DIAGRAM
MA1SJ.L ftic=7 I.AY
Flamm PAMEP= PIt1
-
MICRO
NOTE: DO NOT USE BLACK WIRE ON MICRO SWITCH IN NORMAL
INSTALLATION. BLACK WIRE TO BE USED ONLY FOR EXTRANEOUS ALARM,
LIGHT CIRCUITS, ETC.
WIRING SCHEMATIC
*KI CL AND K1b ARE N.O. WHEN K1 IS DE—ENERGIZED.
U
OLACK
L L.
FAD r—
1iLJiJT --j
-®— H
NOTE
I. DENOTES FIELD INSTALLATION.
------DENOTES FACTORY INSTALLATION-
GAS VALVE - UL LISTED ELFCTRlCALLY—OPERA1 SAFETY VALVE FOR NATURAL OR LP GAS
AS NEEDED OF APPROPRIATE PRESSURE AND TEMPER1URE RATING, 11OV/60HZ OR AMEREX
GAS VALVES, PART NUMBERS 12870,12871, 12872, 12873, 12874, 12875 AND 12876.
INSTALLATION OVERVIEW