Chapter 3 - System Design
CHAPTER III
SYSTEM DESIGN
GENERAL
This section will cover the proper design of the Protex Series
II Restaurant Fire SuppressiQn System. It is divided into four
(4) sections:
Cylinder Sizing
Nozzle Coverage and Placement
Piping Limitations
Detector Requirements
Each of these sections must be completed before attempting
any installation.
SYSTEM CYLINDER SIZING
Each of the nozzles in the section, "Nozzle Coverage and
Placement" has its own flow point value. Each of the three
different agent tanks can support a maximum number of
flowpoints, based on the volume of the pipe used. Select the
system tank(s) by calculating the total number of flow points
associated with the appliances(s), plenum, and ducts, plus
the total piping volume.
' CAUTION
Do not exceed the maximum number of flowpoints as
shown on the Tank Chart, page 46. If the number of flow
points or the pipe volume required exceeds the amounts
shown, additional tank(s) or changes in piping design are
required.
NOZZLE COVERAGE AND PLACEMENT
This section will provide guidelines for determining nozzle
type, positioning, and quantity for duct, plenum, and
appliance protection.
A. DUCT PROTECTION
It is not required that the fan be shut down or the exhaust
duct be dampered for the system to operate properly. Each
nozzle is approved to protect exhaust ducts of unlimited
length.
Duct protection requires that a nozzle by positioned to dis-
charge up, into the duct. The nozzle is a Part No. NL2D.
The NL2D duct nozzle is a two (2) flow nozzle. A single
6 IN.
INTO DUCT
2D NO LE
Figure 3-1
NL2D nozzle is capable of protecting square or rectangular
duct with a maximum of 100 in. perimeter, with the longest
side being a maximum of 34 in. It can also protect a round
duct with a maximum diameter of 31 7/8 in.
Two (2)NL2D duct nozzles can protect a square or rec-
tangular duct with a maximum of 150 in. perimeter, with the
longest side being a maximum of 51 in. They can also pro-
tect a round duct with a maximum diameter of 47 1/2 in.
When two (2) NL2D duct nozzles are used to protect a single
duct, the cross sectional area of the duct must be divided into
two equal symmetrical areas. The nozzle must then be
installed on the centerline of the area it protects and aimed
directly into the duct opening.
The nozzle(s) must be installed on the centerline of the duct,
with the tip located 0 to 6 in. into the opening, and aimed
directly into the duct opening. See Figure 3-1.
TRANSITION DUCTS
The protection of non-standard ducts should be reviewed by
the authority having jurisdiction. Protex Series II recommends
that transition ducts be protected as follows:
A. TRANSITION DUCTS - LARGER TO SMALLER
In cases where the duct/plenum interface opening is larger
than the final exhaust duct, measure the perimeter/diameter
UL XXXX January 15, 2002 11 Part # PMAN2 rev 0
V-BANK
Chapter 3 - System design
B. PLENUM PROTECTION
The NL1H nozzle is a one (1) flow nozzle used for plenum
protection. A single NL1H nozzle can protect a plenum (with
single or V-bank filters) 10 ft. long by 4 ft. wide. Dividing the
length into sections equal to or less than 10 ft. in length and
positioning a nozzle at the start of each section can be done
to protect longer plenums.
On V-bank plenums, the nozzle(s) must be located at the
center of the V-bank width, 1/3 of the vertical height of the
'filters. On single filter bank plenums, the nozzle must be
located 2 in. from the back edge of the filter, 1/3 down from
the vertical height. For either application, the nozzle must be
located within 6 in. of the end of the plenum (or module) and
aimed directly down the length of the plenum. See Fig. 3-2.
I
SINGLE BANK
Figure 3-2.
a
UL XXXX January 15, 2002 13 ?act # PMAN2 rev 0
Chapter 3 - System Design
C. APPLIANCE PROTECTION
Note: When protecting appliances which are larger than sin-
gle nozzle coverage, multiple nozzles can be used.
Larger appliances can be divided into several modules, each
equal to or smaller than single nozzle coverage. Exception:
Fryers must not exceed a maximum of 864 sq. in. For
modularizing fryers, refer to "Protecting Large Fryers by
Dividing Their Area Into Modules," page 22.
Design Index Chart and Nozzle Coverage Summary Sheet
Area/ Mm. Max
Nozzle Flow Width Length Height Height
Appliance Mount Figure Type Points (in) (in2lin) (in) (in)
Deep Fat Fryer Vat H 3-31 NL2H 2 19-.1/2 19 24 48
Deep Fat Fryer - Vat L 3-4 NL2L 2 19-1/2 19 13 24
Deep Fat Fryer wl drip board H 3-5 NL2H 2 24 48
Deep Fat Fryer wl drip board L 3-6 NL2L 2 13 24
Tilt Skillet/Braising-Pan. H 377 NL2H 2 27-3/4 500 24 48
Tilt Skillet/Braising Pan L 3-8 NL2L 2 27-3/4 500 13 24
Four Burner Range 3 9 NL2L 2 28 28 34 48
Two Burner Range H 3-10 NL1H 1 12 28 40 50
two. Burner Range L 311 NL1L 1 12 28 13 213-1/2
Small Wok H 3-12 NL1H 1 24" dia. 6' depth 24 48
Small Wok L .3-13 NL1L 1 24 dia 6 depth 13 24
Large Wok H 3-14 NL2H 2 30" dia. 8" depth 24 48
Large Wok L 3-15 NL2L 2 30 dia 8 depth 13 24
Small Griddle H 3-16 NL1H 1 36 1080 24 48
Small Griddle L &17 NL1L 1 36 1080 10 24
Large Griddle H 3-18 NL2H 2 48 1440 24 48
Large Griddle L 3 19 NL2L 2 48 1440 13 24
Gas Radiant Char-Broiler H 3-20 NL1 H 1 26 624 24 48
Gas Radiant Char Broiler L 3 21 NL1L 1 26 624 13 24
Large Gas Radiant Char-Broiler H 3-22 NL2H 2 36 864 36 48
Large Gas Radiant Char Broiler L 323 NL2L 2 36 864 13 36
Lava Rock Char-Broiler H 3-24 NL2L 2 26 624 24 35
Lava Rock Char Broiler L 325 NL2L 2 26 624 15 24
Natural Charcoal Char-Broiler H 3-26 NL1H 1 24 480 24 35
(max. fuel depth 6")
Natural Charcoal Char Broiler L 327 NL1L 1 24 480 15 24
Mesquite Char-Broiler H 3-28 NL1 H 1 24 480 24 35
(max. fuel depth 6')
Mesquite Char Broiler L 329 NL1L 1 24 480 15 24
Upright/Salamander Broiler 3-30 NL1L 1 36W 28 D Front Edge
above the chain
Chain Broiler (Internal Chamber) .3-31 -Nu L1 1 27W 38 D Fr ont Edge
1-3.1 above the chain
ULXXXX January 15, 2002 15 Part # PMAN2 rev 0
* Chapter 3 - System Design
Fryers with Drip Board (High Mount Nozzle)
Compulsory Nozzle NL2H
Flow Points Per Nozzle 2 (Two)
Number of Nozzles Required 1 (One)
Maximum Area of Protection
Condition 1
Deep Vat Cooking Area 324 square inches with a maximum longest side dimension of 18 inches.
(excludes drip board)
Overall Cooking Area 500 square inches with a maximum longest side dimension of 27-3/4 inches.
(includes drip board)
Condition 2
Deep Vat Cooking Area 371 square inches with a maximum longest side dimension of 19-1/2 inches.
(excludes drip board)
Overall Cooking Area 495 square inches with a maximum longest side dimension of 25-3/8 inches.
(includes drip board)
Nozzle Location Anywhere over the protected area.
Nozzle Height 24 inches to 48 inches above the cooking surface.
Nozzle Aiming Aimed at the center of the cooking area.
Graphic Representation See Figure 3-5
L bo1e must be located anywhere within the shaded area and aimed at the center of the protected zone
OVERALL
COOKING AREA
LONGEST SIDE
DIMENSION
27-3I4
500 SQUARE
INCHES
MAXIMUM
COOKING
AREA
- I
OVERALL
COOKING AREA
LONGEST SIDE
DIMENSION
495 SQUARE
INCHES
MAXIMUM
COOKING
AREA
324 SQUARJ
INCHES
MAXIMUM
DEEP VAT
AREA
Part # PMAN2 rev 0
371 SQUA
INCHES
MAXIMUM
DEEP VAT
AREA
18"
LONGEST
SIDE DRIPBO
-. DIMENSION
(DEEP VAT)
Condition 1
Figure 3-5
18
Condition 2
law,
LONGEST
SIDE
DIMENSION
(DEEP VAT)
UL XXXX January 15, 2002
Chapter 3 - System Design
S
J
Four Burner Range
Compulsory Nozzle NL2L
Flow Points Per Nozzle 2 (Two) -
Number of Nozzles Required 1 (One)
Maximum Area of Protection 28 inches x 28 inches
Nozzle Location On both the front to back centerline and side to side centerline.
Nozzle Height 34 inches to 48 inches above the cooking surface.
Nozzle Aiming Directly down.
Graphic Representation See figure 3-9
Nozzle must be located anywhere within the shaded area on the intseötionof the center lines
and aimed at the center of the protected zone.
Figure 3-9
Part # PMAN2 rev 0 23 UL XXXX January 15, 2002
Chapter 3 7 $ystem Design
Small Griddle (High Mount Nozzle)
Compulsory Nozzle NL1H
Flow Points Per Nozzle 1 (One)
Number of Nozzles Required 1 (One)
Maximum Area of Protection 1080 square inches with a longest side dimension of 36 inches
Nozzle Location Above any corner of the protected area.
Nozzle Height 24 inches to 48 inches above the cooking surface.
Nozzle Aiming At a point 12 inches in and 12 inches over from the corner below the nozzle.
Graphic Representation See figure 3-16
Ni zz1e must be located anywhere within the shaded area and aimed at the center of the protected zoi
I - L /1
NOZZLE CAN BE .----.
MOUNTED ABOVE
A ':-- ANY CORNER
1080 SQUARE
INCHES
MAXIMUM
COOKING AREA
Figure 3-16
Part # PMAN2 rev 0 30 UL XXXX January 15, 2002
Chapte 3 - System Design
Large Griddle (High Mount Nozzle)
Compulsory Nozzle NL2H
Flow Points Per Nozzle 2 (Two)
Number of Nozzles Required 1 (One)
Maximum Area of Protection 1440 square inches with a longest side dimension of 48 inches
Nozzle Location Above any corner of the protected area.
Nozzle Height 24 inches to 48 inches above the cooking surface.
Nozzle Aiming At a point 12 inches in and 12 inches over from the corner below the nozzle.
Graphic Representation See figure 3-18
[Nozzle must be located anywhere within the shaded area and aimed at the center of the protecte zone.1
<•1-
________
:.
T I NOZZLE CAN BE
MOUNTED ABOVE
A ANY CORNER
\
1440 SQUARE
INCHES
MAXIMUM
COOKING AREA
Figure 3-18
Part # PMAN2 rev 0 32 UL XXXX January 15, 2002