Chapter 3—System Desigr S
Page 3-
Rev.
CHAPTER III
System Design
f(4 oô((
This section will cover the proper design of the Pyro Chem Res-
taurant Fire Suppression System. It is divided into four (4) sections:
Nozzle Coverage and Placement.
Cylinder Sizing.
Piping Limitations.
Detector Requirements.
Each of these sections must be completed before
attempting any installation.
SECTION 1
Nozzle Coverage and Placement
This section will provide guidelines for determining nozzle
type, positioning, and quantity for duct, plenum, and
appliance protection.
A. Duct Protection
The following three (3) nozzles have been developed for
the protection of exhaust ducts:
Model NL-R
Model NL-D2.
Model NL-D3.
Each nozzle is approved for use with the exhaust fan dampered,
undampered with -tfie fan on, or undampered with the fan off. It
is not required that the fan be shut down or the exhaust duct be
dampered for the system to operate properly. Each nozzle is
approved to protect exhaust ducts of unlimited length.
1. Model NL-P.
The Model NL-P nozzle is a one (1) flow point nozzle
designed for the protection of exhaust ducts. One (1) or
two (2) Model NL-P nozzles can be used on a single duct
branch.
A single Model NL-P exhaust duct nozzle can protect a square
or rectangular duct with a maximum perimeter of 50 inches
and a maximum one-side length of 17 inches. It can also
protect a round duct with a maximum circumference of 50
inches and a maximum diameter of 16 inches (see Figure 3-1).
The nozzle must be installed on the centerline of the duct and
aimed directly into the duct opening (see Figure 3-2).
Two (2) Model NL-P exhaust duct nozzles can protect a
square or rectangular duct with a maximum perimeter of
84 inches and a maximum one-side length of 34 inches.
They can also protect a round duct with a maximum
circumference of 84 inches and a maximum diameter of
26.5 inches. When two (2) Model NL-P nozzles are used to
protect a single duct, the cross sectional area of the duct
must be divided into two equal symmetrical areas. The
nozzle must then be installed on the center line of the area
it protects and aimed directly into the duct opening (see
Figure 3-2.1).
Model NL-D2.
The Model NL-D2 nozzle is a two (2) flow point nozzle
designed for the protection of exhaust ducts. Only one (1)
Model NL-D2 nozzle can be used on a single duct branch.
A single Model NL-D2 exhaust duct nozzle can protect a
square or rectangular duct with a maximum perimeter of
75.5 inches and a maximum one-side length of 25 inches.
It can also protect a round duct with a maximum circum-
ference of 75.5 inches and a maximum diameter of 24
inches (see Figure 3-1). The nozzle must be installed on
the centerline of the duct and aimed directly into the duct
opening (see Figure 3-2).
Model NL-D3.
The Model NL-D3 nozzle is a three (3) flow point nozzle
designed for the protection of exhaust ducts. One (1) or two
(2) Model NL-D3 nozzles can be used on a single duct branch.
A single Model NL-D3 exhaust duct nozzle can protect a
square or rectangular duct with a maximum perimeter of
100 inches and a maximum one-side length of 33 inches.
It can also protect a round duct with a maximum circum-
ference of 100 inches and a maximum diameter of 31.75
inches (see Figure 3-1)
The nozzle must be installed on the centerline of the duct
and aimed directly into the duct opening (see Figure 3-2).
Two (2) Model NL-D3 exhaust duct nozzles can protect a
square or rectangular duct with a maximum perimeter of 150
inches and a maximum one-side length of 66 inches. They
can also protect a round duct with a maximum circumference
of 150 inches and a maximum diameter of 47.5 inches. When
two (2) Model NL-D3 nozzles are used to protect a single duct,
the cross sectional area of the duct must be divided into two
equal symmetrical areas. The nozzle must then be installed
on the centerline of the area it protects and aimed directly
into the duct opening (see Figure 3-2.1).
NL-P M-02 M-D3
3 (37LX)
2L+2W-5OMAX a+2W-75SMAX X).+2W100MAX
I I Li I I Li Lii LI
..-L 425 MAX) - L-L 33 MAX)
HrJ HrJ
il..
X).5 MAX -4-- -()-- —4- l8S MAX -4-----1- 25 MAX
MAX 18.5 MAX -....-2 -4
Figure 3-1. Duct Nozzle Coverage Limitations.
ULEX 3830
November 1, 1994
hapter 3w-System Design
age 3-2
ev.1
Figure 3-2. Single Nozzle Placement In Duct.
4 MAX
I5X MAX
Figure 3-2.1. Dual Nozzle Placement In Duct.
MAXIMUM MAXIMUM
NOZZLE SIDE PERIMETER FLOW POINTS
NL-P 17" 50"
2xNL-P 34" 84" 2
NL-D2 25" 2
NL-D3 33 ioo"
2xNL-D3 66" 150'
r NOTE: A SINGLE DUCT BRANCH CAN ONLY SUPPORT.
A Single NI-P
A Single NI-D2
A Single NL-D3
Two NL-P's
Two NL-D3's
B. Plenum Protection
The Model NL-A nozzle is a one (1) flow point nozzle that 61 MAX
XX' MAX has been developed to protect the plenum section of the
exhaust hood. Only one (1) Model NL-A nozzle can be
used on a single plenum branch. A single Model NL-A can
protect a plenum (with single or V-Bank filters) with
rectangular dimensions of 8 x 4' or less. Larger plenums
can be protected by dividing the hazard area so that each
nozzle protects an area of 8' x 4 or less (see Figure 3-3).
The nozzle(s) must be located at the center of the V-Bank
width or centered between the filter width when used with
a single bank filter plenum. It must be within 4 of the wall
it is mounted against (see Figure 3-4), or within 4" of the
edge of the protected zone.
) MAX Duct Nozzle Coverage Chart
'SS MAX
00 MAX
Figure 3-3. Plenum Coverage Limitations, Model NI-A Nozzle.
JLEX 3830
Jovember 1, 1994
7Pyr
Pre-Engineered Fire
Number 95-005 .- Date:6-23-95
To: Authorized Pyro Ch&n Restaurant Pre-Engineered Fire Suppression System
Distributors.
Pyro Chem has developed two new nozzles for protecting range tops. They may be
used in addition to the range top' protection currently q.iaIified for the PCL-Series
systems.
A. The Model NL-RH2 is a two (2) flow point nozzle that can be used for range top
protection. The maximum range top area that can be protected by a single NL-RH2
nozzle is 28" by 28. The nozzle must be located within 5 of the center of the
protected zone and aimed at the center of the protected zone. The nozzle must be
mounted 32 to 45 above the cooking surface.
Øiary
Note:
Nozzle must be located anywl
within the shaded area and aimec
11 center of the protected zon.
Enclosed with this bulletin is Revision 2 of Page 3-4a and Page 3-4b of the Technical
Manual which illustrates this coverage. This new page can be inserted in the Technical
Manual for easy reference by removing and discarding Revision 1 of Page 3-4a. All
other system parameters and limitations are listed in the Technical Manual.
Nqte: Any branch that utilizes the NL-RH2 for range top protection must comply with
the limitations listed in the Technical Manual for an Appliance Branch of the appropriate
number of nozzles on the branch (one; two, or three). Four nozzle range branch piping
Pyro Chem, Inc. 8005261079
- 301 Division Street 201.3359750
Boonton, New Jersey 07005 FAX 201.3350253
p
2. Griddle Coverage.
The Model NL-R nozzle is a one (1) flow point nozzle that
is used for griddle protection. The maximum griddle area
that can be protected by a single NL-R nozzle is 30' x 30".
The nozzle must be located over the griddle cooking
surface, no more than six (6) inches from the edge of the
protected zone. The nozzle must be aimed at the center of
the protected zone. The nozzle must be mounted 24" to
50" above the cooking surface. See Figure 3-7.
NOTE
Nozzle shall be located anywhere in the shaded area
and aimed at the center of the protected zone.
Figure 3-7. Model NL-R Nozzle Placement, Griddle.
54-
1
INC
Figure 3-8. Model NL-F2 Nozzle Placement, Deep Fat Fryer.
LONGEST SIDE
If
SHORTEST SIDE
Figure 3-8.1. Model NL-F2 Nozzle Aiming.
LONGEST SIDE
apter 3—System Design
ge 3-4
VA
Nozzle Height:
The nozzle must be mounted 40" to 500 above the cooking
surface.
b. Nozzle Aiming.
The tip of the Model NL-F1.25 nozzle has two flat areas
designed to assist aiming. The nozzle must be positioned
so that these flat areas are parallel to the longest side of
the protected zone. See Figure 3-6.
The tip of the Model NL-F2 nozzle has two flat areas
designed to assist aiming. The nozzle must be positioned
so that these flat areas are parallel to the longest side of
the protected zone. See Figure 3-8.1.
NOTE
Nozzle shall be located anywhere in the shaded area
and aimed at the center of the protected zone.
3. Deep Fat Fryer Coverage.
The Model NL-F2 nozzle is a two (2) flow point nozzle that
is used for the protection of a single vat of a deep fat
fryer. The maximum area that can be protected by a single
NL-F2 nozzle is:
Cooking Area: 14.75" x 14.00"
Integral Drip Board: 14.75" x 7.5'
The nozzle must be located over the cooking surface and
aimed at the center of the protected zone. The nozzle must
be mounted 30" to 50" above the top surface of the deep
fat fryer (see Figure 3-8).
LEX 3830.
ovember 1, .1994
Chapter 3- System Desk'
Page 3-
3.1. Deep Fat Fryer Coverage.
The Model NL-F2 nozzle isat o(flowpoint nozzle that is
used for the protection of a single vat of a deep fat` fryer. The
maximum area that can be protected by a single NL-F2
nozzle is:
Cooking Area: 18" x 18"
Integral Drip Board: 1.8" x 9.75"
The nozzle must be located within 11.875" of the center of the
longest side, and within 7" of the center of the shortest side 01
the cooking surface and.aimedatthe center of the protected.
zone. • The nozzle must be mounted 30" to 42" above .thetop
surface of the deep fat fryer (see,Flgure 34.Z).
The tip of the Model NL.-F2 nozzle has two fiat areas
designed to assist aiming. The nozzle must be positioned so
that these flat areas are parallel to the Iongst side of the
protected zone. See Figure 3-8.1.'
N)T
Nozzle shall be located anywhere in the shaded area and
aimed at the center of the protected zone.
NOTE
For installations that require the use of the Model NL-F2
nozzle to protect a deep fat fryer in accordance with Deep
Fat Fryer Coverage 3.1 shown here (See Figure 3-8.2), the
following additional restrictions apply to the main supply
line piping:
Minimum length, linear: 8 feet
Miminum length, equivalent: 14.1 feet
Minimum system.f low points: 4
Minimum branches (total): 3
2775"
?'c— ,- >n-<-.. -'.--.
ir
INTEGRAL OF
FAN COOKING,,'
AREA
Figure 34.2. Model NL-F2 Nozzle Placement, Deep Fat Fryer.
ULEX 38Z
June 1, 1 BE
NOTE
Nozzle shall be located anywhere in the shaded area
and aimed at the center of the protected zone.:
0°
Figure 3-10. Model NL-F2 Nozzle Placement, Synthetic Rock
Charbroiler.
6. Natural Class "A" Charbroiler Coverage.
0
naper i—ysem LJeSl9fl
Page 3-5
Rev.1 4. Radiant Charbroiler Coverage.
NOTE
A radiant charbroiler is distinguished by the use of
gas or electrically heated metal strips (radiants) that
are used for cooking.
The Model NL-R nozzle is a one (1) flow point nozzle that
is used to protect either gas or electrically fueled radiant
charbroilers. The maximum area that can be protected by
a single NL-R nozzle is 25° x 25°.
The nozzle must be located over the cooking surface and
aimed at the center of the protected zone. The nozzle must
be mounted 24" to 50" above the cooking surface. See
Figure 3-9.
depth shall not exceed two (2) layers of lava, pumice, or
synthetic rocks. The maximum area that can be protected
by a single NL-F2 nozzle is 25" x 25".
The nozzle must be located over the cooking surface and
aimed at the center of the protected zone. The nozzle must
be mounted 30" to 50" above the cooking surface (see
Figure 3-10).
The tip of the Model NL-F2 nozzle has two flat areas
designed to assist aiming. The nozzle must be positioned
so that these flat areas are parallel to the longest side of
the protected zone. See Figure 3-8.1.
NOTE
Nozzle shall be located anywhere in the shaded area
and aimed at the center of the protected zone.
Figure 3-9. Model NL-R Nozzle Placement, Radiant Charbroiler.
5. Synthetic Rock Charbroiler Coverage.
NOTE
Asynthetic rock charbrôiler is distinguished by the
use of Java, pumice, or synthetic rocks that are used
for cooking.
The Model NL-F2 nozzle is a two (2) flow point nozzle that
is used for the protection of either gas or electrically
fueled synthetic rock charbroilers. The maximum fuel
NOTE
A Class "A" charbroiler is distinguished by the use of
charcoal, mesquite chips, chunks, and/or logs that
are used for cooking.
The Model NL-A nozzle is used for the protection of Class
"A" charbroilers with a maximum fuel depth of six (6)
inches. The maximum area that can be protected by a
single NL-A nozzle is 20° x 24°.
The nozzle must be located over the cooking surface and
aimed at the center of the protected zone. The nozzle must
ULEX 3830 November 1, 1994
Chapter 3—System DesiCr
Page 37
Re
Figure 3-13. Model NL-UB Nozzle Placement, Closed Top Chain Broiler.
b. Open Top Chain Broiler Coverage.
The Model NL-A nozzle is a one (1) flow point nozzle that is
used for open top chain broiler protection. The maximum
area that can be protected by an NL-A nozzles is 32" x 34".
The nozzle must be located over the opening and aimed at
the center of the protected zone. The nozzle must be mounted
10" to 22" above the cooking surface. See Figure 3-14.
9. Wok Coverage.
The Model NL-R nozzle is a one (1) flow point nozzle that
is used for wok protection. A single NL-R nozzle can cover
a single wok of 14" to 24" in diameter.
The nozzle must be mounted 40" to 50" above the cooking
surface at a radius of 12" from the center of the wok,
regardless of wok diameter. The nozzle must be aimed at
the center of the protected zone. See Figure 3-14.1.
NOTE
Nozzle shall be located anywhere in the shaded area
and aimed at the center of the protected zone.
24 Dia, -
241 Dia. Max. -,. I iO
40"
NOTE
Nozzle shall be located anywhere in the shaded area
and aimed at the center of the protected zone.
Figure 3-14.1. Model NL-R Nozzle Placement, Wok.
Figure 3-14. Model NL.A Nozzle Placement, Open Top Chain Broiler.
ULEX 383(
November 1, 199
Figure 3-12. Model NL-UB Nozzle Placement, Upright Broiler.
8. Chain Broiler Coverage.
Two types of chain broilers are commonly used; open and
closed top. Each is protected in a different manner.
a. Closed Top Chain Broiler Coverage.
The Model NL-UB nozzle is a one-half (V2) flow point
nozzle that is used for closed top chain broiler protection.
Two (2) Model NL-UB nozzles are commonly used for this
application. The purpose of using two nozzles is to
distribute the chemical evenly between the cooking
surface (on top) and the drip pan (below). For closed top
chain broilers that have no drip pan, a single Model NL-
UB nozzle can be used. The maximum area that can be
protected by a pair of NL-UB nozzles (or a single NL-UB
nozzle when no drip pan is present) is 30" x 34".
One nozzle must be positioned in the front entrance of the
broiling chamber and aimed at the diagonal corner. The
nozzle will be positioned above the cooking surface. The
second nozzle (if necessary) must be installed above the
front edge of the grease drip pan and aimed at its
midpoint. See Figure 3-13.
Chapter 3—System Design Page 34
Rev.,
be mounted 15" to 35" above the cooking surface. See
Figure 3-11'
NOTE
Nozzle shall be located anywhere in the shaded area
and aimed at the center of the protected zone.
S.
Figure 3-11. Model NL-A Nozzle Placement, Class A"
Charbroiler.
7. Upright Broiler Coverage.
The Model NL-UB nozzle is a one-half (1/2) flow point
nozzle that is used for upright broiler protection. Two (2)
Model NL-UB nozzles are commonly used for this
application. The purpose of using two nozzles is to
distribute the chemical evenly between the cooking
surface (on top) and the drip pan (below). For upright
broilers that have no drip pan, a single Model NL-UB
nozzle can be used. The maximum area that can be
protected by a pair of NL-UB nozzles (or a single NL-UB
nozzle when no drip pan is present) is 30" x 34".
One nozzle must be positioned in the front entrance of the
broiling chamber and aimed at the diagonal corner. The
nozzle will be positioned above the cooking surface. If
necessary, the second nozzle must be installed above the
front edge of the grease drip pan and aimed at its
midpoint. 'See Figure 3-12.
ULEX 3830
November 1, 1994