HomeMy WebLinkAbout2555 EL CAMINO REAL; ; FA100020; Permit12/5/24, 2:09 PM FA1 00020 Permit Data
City of Carlsbad
Fire Alarm Permit
2555 EL CAM INO
Job Address:
REAL
Permit Type: FALARM
Parcel No: 1563021000
Lot #: 0
Reference No.:
Permit No: FAI 00020
Status: ISSUED
Applied 5/3/2010
Approved: 5/3/2010
Issued: 5/3/2010
PC #: Inspector:
Project Title: JC PENNEY TWO FIRE ALARM INSPECTIONS @ $65/EA
Applicant:
ADT SECURITY SERVICES, INC.
3830 CALLE FORTUNADA
SAN DIEGO, CA
(858) 654-3224
Owner:
NEW MARJORAM ASSOCIATES
C/O JCPENNY CO INC #566-0
P0 BOX 10001
DALLAS TX
Fees ($) Add'l Fees ($) Total ($) Balance ($)
130 0 130 0
about:blank 1/1
tiittFfl1TiIIWI1
Prepared for
JCPenney
2555 EL CAMINO REAL
CARLSBAD, CA 92008
Submitted By
ADT Tyco Fire & Security
3830 Calle Fortunada
San Diego, CA 92123
(858) 654-3200
Prepared By
ADT Tyco Fire & Security
National Accounts Group
120 West Park Drive
Birmingham, AL 35211
Jody Cong leton
Phone 205-943-6518
FAX 205-942-4943
NICET SET 108686
04/08/10
These plans have been reviewed for apparent coiiiphaiice.
with the ciii ciii applicable codes and itandards in force
in li ui'idii_tion. The owner or contractor ina\' uiili,.c
ew in support of an application for a huildinir
ic iiii ss 11h The eprcss understaiidiiig thai this review
no way relieves ihe owner or contractor or their
pistessii inal engineer or architect for sole responsibility
or full compliance with said codes and standards.
including the building code or for any responsihilty for
deficiencies. c rrors. omissions or negligence in these
plans whether or not noted in this review.
l)aie:1f3// Reviewer:
RECOMMEND APPROVAL
RECOMMEND APPROVAL. AS NOTED
Standby Battery Calculations
FireLite MS9600
JCPenney
CARLSBAD CA 92008
Standby Curr8nt Alanft Cutient
Part Number Description Qua(itlty Per Device Alt Devices PeDe t ViCG All Devtces
MS9600 Fire Alarm Control 1 0.120000 0.120000 0.170000 0.170000
DACT-UD Dual Line Dialer 1 0.100000 0.100000 0.132000 0.132000
LCD-80F Annunciator LCD 1 0.025000 0.025000 0.064000 0.064000
SD355 Smoke Detector Photo 1 0.000300 0.000300 0.000300 0.000300
BG-12LX Manual Pull Station Addressable 0 0.000230 0.000000 0.000200 0.000000
MDF-300 Monitor Module Dual Input 2 0.000750 0.001500 0.000400 0.000800
MMF-300 Monitor Module Single input 2 0.000400 0.000800 0.000400 0.000800
MMF-301 Montior Module Small 2 0.000380 0.000760 0.000375 0.000750
D350PL Duct Smoke Detector 14 0.000300 0.004200 0.000300 0.004200
1300 Isolator Module 2 0.000400 0.000800 0.000400 0.000800
CRF-300 Control Module Relay 9 0.000270 0.002430 0.000270 0.002430
H355R Heat Detector Rate of Rise 0 0.000300 0.000000 0.000300 0.000000
Total Aux currrent Max 3 Amps 0.256 Alarm 0.376
Signal Circuits
Citcuit Device Ouantity Per Device AltDevices
Circuit 1 0.000
0.000
0.000
0.000
Total 1 Maximum 2.5 Amps . 0.000
Circuit 2 0.000
0.000
0.000
0.000
Total 2 Maximum 2.5 Amps 0.000
Circuit 3 0.000
0.000
0.000
0.000
Total 3 Maximum 2.5 Amps 0.000
Circuit 4 0.000
0.000
0.000
0.000
Total 4 Maximum 2.5 Amps 0.000
Totals Maximum 6 Amps 0.000
Circuit 1 Circuit 2 Circuit 3 Circuit 4
Max Wire Run Distance For AWG 14
Actual Wire run Distance
Voltage Drop for 14 AWG wire
Voltage Drop 2 * Wire Run Distance * 3.07 Ohms Per 1000 ft 14 AWG * Total Current for Circuit I 100C
Standby Hours 60
Standby Battery Draw 0.256
Standby Amp Hrs 15.347
Alarm Current 0.376
Alarm Current 5 Mm 0.031
Size Required
l
Battery
with 5 Mm. Alarm Time
and 20% Reserve 18.454
IBattery Size Supplied 26 A. H. I
System Outline
1. Location
JCPenney 0566
2555 EL CAMINO REAL
CARLSBAD , CA 92008
Codes
2002 NFPA 72 Chapters 1-10 as Applicable(Remote Station)
2002 NEC Articles 250, 725, 760
Local, City, State
Ill. Control
1 M59600 Fire Alarm Control
1 DACT-UD Dual Line Dialer
IV. Fire Alarm Initiating Devices
1 5D355 Smoke Detector Photo
2 Water Flow Connection Only, Provided by Others
4 Tamper Switch Connection Only, Provided by Others
14 D350PL Duct Smoke Detector
H.
V. Fire Alarm Indicating Devices
1 LCD-80F Annunciator LCD
H
1.
J.
VI. Zones
All devices are addressable with there own adddress
1-159 detector addresses
1-159 module addresses
SLC Loop is style 4
VII. Wiring
All Circuits and Wiring Shall be "Power Limited"
SLC Circuits Shall be 16/2 Shellded U.L. FPLP Cable
Initiating Zones Shall be 18/2 or 18/4 U.L. FPLP Cable
Indicating Circuits Shall be 14/2 U.L. FPLP Cable
System Ground Shall be 14THWN Green Conductor
Under Ground and Outside Wire shall be 14 THWN in Approved Raceway
VIII. Listings
A. All Equipment Shall Be U.L. Listed and Compatible
IX. Power Supply
Primary - 110 VAC Dedicated 20 Amp Circuit
Secondary - 26 Amp Hour Battery
X. Alarm Supervision
Human
Remote Station Installing Branch/Contractor
ADT Fire & Security ADT Tyco Fire & Security
14200 E Exposition Blvd. 3830 CaIle Fortunada
Aurora, CO 80012 San Diego, CA 92123
(303) 338-8200 (858) 654-3226
5994-183UUFX 0
Sequence of operation
Remote Station Local
Alarm Supervisory
_____
Device Trouble Annunciator Horn/strobes Relay
Water Flow x
Switch x
x _____
Tamper
Detector x
x ____
Smoke
KUnit Detector x
x _____
Duct x Shutdown
System Trouble x x ____________
Standard Fire Alarm Zoning
FireLite_MS9600
Reporting
Zone #
Address
Number Device
Software Software
Zone Zone
Software
Zone
Software
Zone
Software
Zone
NAC #1 System sensor Sync - 2
NAC #2 System sensor Sync 1 2
NAC #3 System sensor Sync - 2
NAC #4 System sensor Sync - 2
Relay #1 Alarm - 2
Relay #2 Trouble 4
Relay #3 Supervisory 3
Loop #1 Module Addresses
001 1 Box Tampers Control 3
002 2 Box Tampers Battery Box 3
005 5 Water flow #1 1
006 6 Sprinkler Tamper Switch #1 3
007 7 Water flow #2 1
008 8 Sprinkler Tamper Switch #2 3
010 10 S prinkler Tam per Switch #3 3
012 12 Sprinkler Tamper Switch #4 3
157 93 HVAC #1 Shutdown 41
158 94 HVAC #2 Shutdown 42
159 95 HVAC #3 Shutdown 43
160 96 HVAC #4 Shutdown 44
161 97 HVAC #5 Shutdown 45
162 98 HVAC #6 Shutdown 46
163 99 HVAC #7 Shutdown 47
Detector Addresses
321 1 Smoke Detector at panel 2
341 21 AHU #1 Supply Duct Detector 3 41
342 22 AHU #1 Return Duct Detector 3 41
343 23 AHU #2 Supply Duct Detector 3 42
344 24 AHU #2 Return Duct Detector 3 42
345 25 AHU #3 Supply Duct Detector 3 43
346 26 AHU #3 Return Duct Detector 3 43
347 27 AHU #4 Supply Duct Detector 3 44
348 28 AHU #4 Return Duct Detector 3 44
349 28 AHU #5 Supply Duct Detector 3 45
350 30 AHU #5 Return Duct Detector 3 45
351 31 AHU #6 Supply Duct Detector 3 46
352 32 AHU #6 Return Duct Detector 3 46
353 33 JAHU #7 Supply Duct Detector 3 47
354 34 JAHU #7 Return Duct Detector 3 47
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-0075:205 Page 1 of 1
CATEGORY: Misc. Devices/Control Unit Accessories
LISTEE: Fire-Lite Alarms, Inc., One Fire-Lite Place, Northford, CT 06472-1653
Contact: Brian Reynolds *(203) 484-7161 FAX (203) 484-7309
DESIGNS Models CRF-300-6 relay module, CMF-300-6 supervising control module and MMF-300-
10 input monitor module. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING: 30VDC -
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING: Listees name, model designation, electrical rating, and UL label.
APPROVAL: Listed control unit accessories for use with listee's separately listed compatible fire alarm
control units.
*Rev. 05-06-05BH
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 16, 2009 Listing Expires June 30, 2010
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL -
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
:RATING:
INSTALLATION
MARKING:
APPROVAL
7300-0075:205 Page 1 of 1
Misc. Devices/Control Unit Accessories
Fire-Lite Alarms, Inc., One Fire-Lite Place, Northford, CT 06472-1653
Contact: Brian .Reynolds *(203) 484-7161 FAX (203) 484-7309
Models CRF-300-6 relay module, CMF-300-6 supervising control module and MMF-300-
10 input monitor module. Refer to listee's data sheet for additional detailed product
description and operational considerations.
30 VDC
In accordance with listées printed: installation instructions, applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction.
Listees name model designation electrical rating and UL label
Listed control unit accessories for use with listee s separately listed compatible fire alarm
control units
*Rev. 05-06-05BH
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
; recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 16, 2009 Listing Expires June 30, 2010
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
S
LISTING No.
CATEGORY:
LISTEE:
-
'DESIGN:
7300-0075:205 Page 1 of 1
Misc. Devices/Control Unit Accessories
Fire-Lite Alarms, Inc., One Fire-Lite Place, Northford, CT06472-1653
Contact: Brian Reynolds *(203) 484-7161 FAX (203) 484-7309
Models CRF-300-6 relay module, CMF-300-6 supervising control module and MMF-300-
10 input monitor module. Refer to listee's data sheet for additional detailed product
description and operational considerations.
In accordance with listee's printed installation instructions, applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction.
Listee's name, model designation, electrical rating, and UL label.
Listed control unit accessories for use with listee's separately listed compatible fire alarm
control units.
*Rev. 05-06-05BH
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
; recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 16, 2009 Listing Expires June 30, 2010
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division