tqco F/re & Building
IProducts
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series TY-FRB - 5.6 K-factor
Horizontal and Vertical Sidewall Sprinklers
Quick Response, Standard Coverage
General
Description
The Series TY-FRB, 5.6 K-Factor,
Horizontal and Vertical Sidewall Sprin-
klers described in this data sheet are
quick response - standard coverage,
decorative 3 mm glass bulb type spray
sprinklers designed for use in light and
ordinary hazard, commercial occupan-
cies such as banks, hotels, shopping
malls, etc. They are designed for in-
stallation along a wall or the side of a
beam and just beneath a smooth ceil-
ing. Sidewall sprinklers are commonly
used instead of pendent or upright
sprinklers due to aesthetics or building
construction considerations, where
piping across the ceiling is not desir-
able.
The recessed version of the Series
TY-FRB Horizontal Sidewall Sprinkler
is intended for use in areas with a
finished wall. It uses a two-piece Style
10 Recessed Escutcheon with 1/2 inch
(12,7 mm) of recessed adjustment or
up to 3/4 inch (19,1 mm) of total adjust-
ment from the flush sidewall position,
or a two-piece Style 20 Recessed Es-
cutcheon with 1/4 inch (6,4 mm) of
recessed adjustment or up to 1/2 inch
(12,7 mm) of total adjustment from the
flush sidewall position. The adjust-
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
ment provided by the Recessed Es-
cutcheon reduces the accuracy to
which the fixed pipe nipples to the
sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY3331 - Horizontal
TY3431 - Vertical
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A for complete ap-
proval information including corrosion
resistant status.)
Maximum Working Pressure
Refer to Table B.
Discharge Coefficient
K =5.6 GPM/psi1/2 (80,6 LPM/barl'2)
Temperature Ratings
Refer to Table A.
Finishes
Sprinkler: Refer to Table A.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated.
Page 1 of 6 APRIL, 2006 TFPI76
Page 2 of 6 TFPI76
SPRINKLER FINISH (See Note 11)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED
WHITE
POLYESTER
LEAD
COATED
5.6
HORIZ.
SIDEWALL
(TY3331)
135°F/57°C Orange
1/2
1,2,3,4,9,10 1,2,3,9 1,2,3,9
155F/68°C Red
175°F/79°C Yellow
200°FI93C Green
286°F/141°C Blue
NPT RECESSED
HORIZ.
SIDEWALL
(TY3331)*
Figure 3
135°F/57°C Orange
1,2,4,9,10 1,2,9 N/A
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
RECESSED
HORIZ.
SIDEWALL
(TY3331)
Figure 4
135°F/57°C Orange
1, 2, 3,4,9 N/A
155°F168°C Red
175F/79°C Yellow
200°F/93°C Green
5.6
1/2'
NPT
-
VERTICAL
SIDEWALL
(TY3431)
Installed
Pendent
or
Upright
135°F/57°C Orange
5,6,7,8,9 5,6,7,9
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
286°F/141°C Blue
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a
4 to 12 inch (100 to 300 mm) top of deflector to ceiling distance.
Listed by Underwriters Laboratories Inc. for use in Canada (C-UL) as Quick Response Sprinklers for use in Light and Ordinary
Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deflector to ceiling distance.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers for use in Light Hazard Occupancies at a
4 to 12 inch (100 to 300 mm) top of deflector to ceiling distance.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007a/04) at a 4 to 6 inch (100 to 150 mm) top of
deflector to ceiling distance. The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers.
Listed by Underwriters Laboratories, Inc. as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies.
Listed by Underwriters Laboratories for use in Canada (C-UL) as Quick Response Sprinklers for use in Light and Ordinary Hazard
Occupancies.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers for use in Light Hazard Occupancies.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06 & 007a/04) as Quick Response Sprinklers.
Approved by the City of New York under MEA 354-01 -E.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) at a 4 to 6 inch (100 to 150 mm) top of
deflector to ceiling distance. The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers.
Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed
as Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) 3/4" Total Adjustment Recessed Escutcheon.
** Installed with Style 20 (1/2' NPT) 1/2' Total Adjustment Recessed Escutcheon.
Frame and deflector only. Listings and approvals apply to color (Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS
Physical Characteristics
Frame .............Bronze
Button .........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflont
Bulb ...............Glass
Compression Screw .....Bronze
HSW Deflector ........Bronze
VSW Deflector ........Copper
Patents
U.S.A. 5,810,263
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
.4—
TFPI76 Page 3 of 6
SPRINKLER FINISH
K TYPE NATURAL CHROME WHITE LEAD BRASS PLATED
I
POLYESTER COATED
HORIZONTAL SIDEWALL 250 PSI (17,2 BAR)
(TY3331) OR 175 PSI (12,1 BAR)
175 PSI (12,1 BAR)
RECESSED HORIZ.
SIDEWALL (TY3331) N/A F
5.6
1/2" (SEE NOTE 1)
NPT VERTICAL SIDEWALL
(TY3431) 175 PSI (12,1 BAR)
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories, Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C-UL); and, the Approval by the City of New York.
TABLE B, MAXIMUM WORKING PRESSURE
* Temperature rating is DEFLECTOR
indicated on deflector or HAT -----... adjacent to orifice seat
on frame.
**Pipe thread
connections per ISO 7/1
can be provided on
special request.
6* 4 2 3
9/16" WRENCH 1/2" **
(14,3 mm) FLATS NPT
1-13/16' 7/16" 46,0 mm) (11,1 mm)
CENTERLINE NOMINAL I
OF SPRINKLER MAKE-IN I
WATERWAY 1-1/2"
(38,1 mm)
2-3/16"
(55,6 mm)
1 - Frame
2 - Button STYLE ESCUTCHEON
10 or 20 —-_- PLATE SEATING
Assembly RECESSED SURFACE
4-Bulb I ESCUTCHEON 5 - Compression I Screw I 6 - Deflector I
2-7/8" DIA.
(73,0 mm)
FIGURE 1
5.6 K-FACTOR QUICK RESPONSE
SERIES TY-FRB HORIZONTAL SIDEWALL (TY3331) SPRINKLERS
Design
Criteria
The Series TY-FRB Horizontal and
Vertical Sidewall Sprinklers are in-
tended for fire protection systems de-
signed in accordance with the stand-
ard installation rules recognized by the
applicable Listing or Approval agency
(e.g., UL Listing is based on the re-
quirements of NFPA 13, and FM Ap-
proval is based on the requirements of
FM's Loss Prevention Data Sheets).
Only the Style 10 or 20 Recessed Es-
cutcheon, as applicable, is to be used
for recessed horizontal installations.
ARROW MUST
7/16' FROM AND BE
(11,1 mm)
POINT AWAY
_rg
PERPENDICULAR
1/2" ** NOMINAL TO THE BACK
MAKE-IN WALL SURFACE NPT
I I
Page 4 of 6 TFPI76
Installation
The Series TY-FRB Sprinklers must
be installed in accordance with the fol-
lowing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 1350F/57°C to 3/32
inch (2,4 mm) for the 286°F/141°C
temperature ratings.
A leak tight 1/2 inch NPTsprinklerjoinf
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. Higher levels of
torque may distort the sprinkler and
cause leakage or impairment of the
sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Horizontal and
Vertical Sidewall Sprinklers must be
installed in accordance with the follow-
ing instructions.
Step 1. Horizontal sidewall sprinklers
are to be installed in the horizontal
position with their centerline of water-
way perpendicular to the back wall and
parallel to the ceiling. The word "TOP"
on the Deflector is to face towards the
ceiling.
Vertical sidewall sprinklers are to be
installed in the pendent or upright po-
sition with the arrow on the Deflector
pointing away from the wall.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 5),
With reference to Figure 1 or 2, the
W-Type 6 Sprinkler Wrench is to be
applied to the wrench flats.
The Series TY-FRB Recessed Hori-
zontal Sidewall Sprinklers must be
installed in accordance with the follow-
ing instructions.
Step A. Recessed horizontal sidewall
sprinklers are to be installed in the
horizontal position with their centerline
of waterway perpendicular to the back
wall and parallel to the ceiling. The
word "TOP" on the Deflector is to face
towards the ceiling.
ESCUTCHEON
PLATE SEATING
SURFACE
7
2-J16,,
6mm)
(55,6 mm)
1
(38,
SHOWN
PENDENT
1 - Frame 3-Sealing 2 - Button Assembly
Step B. After installing the Style 10 or
20 Mounting Plate over the sprinkler
threads, hand tighten the sprinkler into
the sprinkler fitting.
Step C. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 6). With reference to Figure 1,
the W-Type 7 Recessed Sprinkler
Wrench is to be applied to the sprinkler
wrench flats.
Step D. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 10 or 20 Clo-
sure over the Series TY-FRB Sprinkler
and push the Closure over the Mount-
ing Plate until its flange comes in con-
tact with the ceiling
SHOWN CROSS
UPRIGHT SECTION
4 - Bulb 6 - Deflector
5 - Compression 7- Ejection Spring
Screw
Care and
Maintenance
The Series TY-BFR Sprinklers must
be maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down
the affected fire protection system
must be obtained from the proper
authorities and all personnel who may
be affected by this action must be no-
tified.
The owner must assure that the sprin-
klers are not used for hanging of any
objects; otherwise, non-operation in
the event of a fire or inadvertent opera-
tion may result.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
* Temperature rating is indicated on deflector or adjacent to orifice seat on frame.
**Pipe thread connections per ISO 7/1 can be provided on special request.
FIGURE 2
5.6 K-FACTOR QUICK RESPONSE
SERIES TY-FRB VERTICAL SIDEWALL (TY3431) SPRINKLERS
TFPI76 Page 5 of 6
5/8±1/4'
(15,9±6,4 mm)
FACE OF
MOUNTING SURFACE __ SPRINKLER
FITTING
CLOSURE
2-7/8"DIA.
(73,0 mm)
TY-FRB 2-1/4" DIA.
(57,2 mm)
SERIES
-
MOUNTING
PLATE
1/8"
(3,2 mm)
1-1/4(31,8mm)
-_-
3/4(19,1 mm) H 3/4(19,1 mm) 1/4(6,4mm)
FIGURE 3
SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
1/2±1/8"
(12,7±3,2 mm)
MOUNTING FACE OF
SURFACE —1 - SPRINKLER I FITTING
CLOSURE
2-7/8" DIA.
(73,0 mm) SERIES
TY-FRB 2-1/4" DIA.
(57,2 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
1-1/4(31,8mm) 1/2(12,7mm)
1" (25,4 mm) 1/4(6,4 mm)
FIGURE 4
SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
WRENCH RECESS
(END "A' USED FOR 1/2' NPT MODELS)
FIGURE 5
W-TYPE 6 SPRINKLER WRENCH
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 6
W-TYPE 7 RECESSED
SPRINKLER WRENCH
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
Page 6 of 6 TFPI7G
PIN 57-XXX-X-XXX
I L
SPRINKLER I
135
155
175
200
286
TEMPERATUR
RATING
1 NATURAL BRASS 135°F/57°C
4 WHITE POLYESTER 155°F/68°C
3 WHITE RAL9010)* 175°F/79C
9 CHROME PLATED 200°F/93°C
7 LEAD COATED 286F/141°C
MODEL/SIN
378 I HORIZONTAL SIDEWALL I 1Y3331
375 I VERTICAL SIDEWALL I 1Y3431
TABLE C * Eastern Hemisphere sales only.
PART NUMBER SELECTION
SERIES TY-FRB HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship "en paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Refer to the Price
List for complete listing of Part Num-
bers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Horizontal Sidewall or Vertical
Sidewall) Sprinkler with (specify type
of finish or coating), P/N (specify from
Table C).
Recessed Escutcheon:
Specify: Style (10 or 20) Recessed
Escutcheon with (specify*) finish, P/N (specify*).
* Refer to Technical Data Sheet TFP770.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446