HomeMy WebLinkAbout7720 RANCHO SANTA FE RD; ; AS160061; Permit12/6/24, 10:54 AM AS160061 Permit Data
City of Carlsbad
Sprinkler Permit
7720 RANCHO
Job Address:
SANTA FE RD
Permit Type: SPRINK
Parcel No: 2230602800
Lot #: 0
Permit No: AS160061
Status: ISSUED
Applied 3/8/2016
Approved: 3/8/2016
Reference No.: Issued: 3/8/2016
PC #: Inspector:
Project T1tIe: DIGITAINMENT T.I. INSTALL NEW QUICK RESPONSE PENDENT
IN NEW TI CEILINGS
Applicant:
INNOVATIVE FIRE PROTECTION INC
STE 101
8779 COTTONWOOD AV
SANTEE CA
(619) 593-8200 (619)593-9133
Owner:
SANTA FE LA COSTA L L C
9404 GENESEE AVE #330
LA JOLLA CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
303 0 303 0
about:blank 1/1
Bulletin 014 Rev. K
Model Fl FR Series
Quick Response
Standard Spray
Model Fl FR56 Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
Model Fl FR56 Recessed Sprinkler Types
Standard Pendent/F1/F2/FP
Horizontal Sidewall
Model Fl FR56 Concealed Sprinkler Types
Standard Pendent
Model 171FR42, F1FRXLH & F1FR28 Sprinkler
Types
Standard Upright
Standard Pendent
Model Fl FR42, Fl FRXLH & Fl FR28 Recessed
Sprinkler Types
Standard Pendent
Model Fl FR56LL & Fl FR42LL Low Lead Sprinkler
Types*
Standard Pendent
Less than 025% Lead Content
Listing & Approvals
1, Underwriters Laboratories Inc. and Certified for
Canada (cULus).
Factory Mutual Approvals (FM)
Loss Prevention Council (LPCB, UK)
4, VdS SchadenverhUtung GmbH
5 *NSF Certified to NSF/ANSi Standard 61 Annex G
UL Listing Category
Sprinklers, Automatic & Open (VNIV)
Quick Response Sprinkler
Product Description
Reliable Models F1FR56, F1FR56LL, F1FR42, F1FR42LL,
F1FRXLH & F1FR28 Series Sprinklers are quick response
sprinklers which combine the durability of a standard sprin-
kler with the attractive low profile of a decorative sprinkler.
The Models F1FR56, F1FR56LL, F1FR42, F1FR42LL,
F1FRXLH & F1FR28 Series Recessed automatic sprinklers
utilize a 3.0 mm frangible glass bulb. These sprinklers have
demonstrated response times in laboratory tests which are
five to ten times faster than standard response sprinklers.
This quick response enables the Model Fl FR56, Fl FR56LL,
F1FR42, F1FR42LL, F1FRXLH & F1FR28 Series sprinklers
Upright Pendent Conventional
IF
Vertical Sidewall Horizontal Sidewall Recessed
PendentjFl/F2
I
Recessed Concealed Recessed
Horizontal Sidewall Pendent Pendent/FP
XLH Upright XLH Pendent XLH Recessed
Pendent F1/F2
to apply water to a fire much faster than
standard sprinklers of the same tem-
perature rating.
The glass bulb consists of an accu-
rately controlled amount of special fluid
hermetically sealed inside a precisely
manufactured glass capsule. This glass XLH Recessed bulb is specially constructed to provide Pendent FP
fast thermal response.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid
expands, forcing the bubble smaller and smaller as the liq-
uid pressure increases. Continued heating forces the liquid
to push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Application
Quick response sprinklers are used in fixed fire protection systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflector style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection Association or the approving Authority Having Jurisdiction. Quick
response sprinklers are intended for installation as specified in NFPA 13. Quick response sprinklers and standard re-
sponse sprinklers should not be intermixed.
*jf tie
XLH Only)
Deflector
Load Screw
Washer Bulb
Cup Frame
1
0 14FGQ6A
Model F1FR42, F1FRXLH Uoriaht
Technical data:
Models Discharge Coefficient Response Thread Max.
Working
Mm.
Working Temperature Finish Size Pressure Pressure Rating
F1FR56
**F1 FR56LL11t K 5.6
Quick 1/2' NPT See See F1FR42
**F1FR42LL(l) K 4.2 Response (R1/2) 175 PSI 7 PSI "Temperature 'Finish Table"
F1FRXLH Ratings" Table.
F1FR28 K2,B
1) Low Lead Sprinklers available only with Temperature Rating 200"F!93°C
Material Data:
Frame Deflector I Load Screw *pintle Cup Washer Bulb
DZR Brass CDA Alloy 260,
CDA Alloy 220 CDA Alloy 360 CDA Alloy 360 CDA Alloy 651 Nickel Alloy 440 or Alloy 360
GM Brass I or or or coated with FIFE Adhesive Glass
**Low Lead Brass or
CDA Alloy510 CDA Alloy 544 CDA Alloy 544 CDA Alloy 693 Tape
2,
Model Fl FR56, Upright, Pendent & Conventional Sprinklers
Model Fl FR42, Fl FRXLH & Fl FR28 Upright & Pendent Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread Nominal K Factor Sprinkler Approval Sprinkler Identification Number
'SIN
Size US Metric Height Organization Upright Pendent
Standard-Upright (SSU) and Pendent Deflectors Marked to Indicate Position
1/2' (15mm)'1) 1/2" NPT(R1/2) 5.6 80 2.25" (57mm) 123,4 RA14250(2X3))4) RA1414(1)0(3)(4)
7/16" (10mm) 1/2' N P T (R1/2) 4.2 60 2.25" (57mm) 1 RA1423(4) RA14134
3/8"(10mm) 1/2" NPT(R1/2) 2.8 40 2.25" (57mm) 1 RA1421 4 RA 1(41
Conventional-Install in Upright or Pendent Position
15mm 1/2" NPT (A 1/2) 5.6 80 57mm j 3,4 RA14753
cULus listed corrosion resistant (Polyester coated) sprinkler.
Polyester coated FM approved sprinkler.
Polyester coated LPCB & VdS approved sprinkler RA1425, RA1414 & RA1475.
14) Electroless Nickel PTFE (Teflon')' Plated - cULus listed Corrosion Resistant
Upright Pendent Conventional
Model Fl FR56LL & Fl FR42LL Pendent Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Nominal [ Thread
_______ Orifice -------
Nominal K Factor
_________________
Sprinkler
___________
Approval
___________
Sprinkler Identification Number
(SIN)
Size US
__________________
I Metric
____________
Height
____________
Organization
____________________________
Pendent
Standard-Pendent Deflectors Marked to Indicate Position
1/2(15mm)l) 1/2" NPT(R1/2) ] 5.6 80 2.25" (57mm) 1,5 RA1415
7/16(11mm) 1 1/2" NPT(R1/2) j 4.2 60 2.25" (57mm) 1,5 RA1410
11 cULus listed corrosion resistant (Polyester coated) sprinkler.
"DuPont Registered Trademark
3.
'/2 REDUCER
2 5/8' 057 166 7mm1 NOSE IN CEUNO ,
25/76 OR '587271,'J -- 7 USE
CEIL.MIS._\
-j—
TACT OF RFTUIG M FACE Or CEALANG DIWISI-1
"7 AT 71415/MUM RECESS 9/75794.3mm] 15772.7mm] ADJUSTMENT 7" AT MINIMUM - RECESS - 7725.4mm]
/777 47 57:71,5757,, '7;U:ss - 2/779
1/572751571
,,,,. J 7.44_I,,
277145777171,1, SECTS: 7/8(22 715757557;, RCCSS - -5/874; 5,,,,)
47 71221575757 9'CCCSS .. 7-7/9 7257 947577 47 711575771 575255 S 7-5/874;
Model Fl FR56, Fl FR42, Fl FRXLH & Fl FR28 Quick Response Recessed Pendent Sprinkler0>
Installation Wrench: Model GFR2 Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread K Factor
Size US 1 Metric
Sprinkler
Height
Sprinkler Identification Number
(SIN)
1/2" (15mm) 1/2 NPT(R½) 5.6 80 2.25" (57mm) RA1414
7/16(10mm) 1/2' NPT(R1/2) 4,2 60 2,25' (57mm) RA1413
3/8"(l0mm) 1/2" NPTRh/2j 2.8 40 2.25': (57mm) RA1411
Refer to escutcheon data table for approvals & dimensions
Model Fl FR56LL & Fl FR42LL Quick Response Recessed Pendent Sprinkler(1)
Installation Wrench: Model GFR2 Sprinkler Wrench
Installation Data:
Nominal Thread K Factor Sprinkler Sprinkler Identification Number
Orifice Size US Metric Height (SIN)
1/2" (15mm) 1/2" NPT(R1/2) 5.6 80 2.25" (57mm) RA1415
7/16" (10mm) 1/2" NPT (R1/2) 4.2 60 2.25" (57mm) RA1410
meter to escutcneon data table tor approvals & dimensions
Mode' Hl-H56, 1-1EH561-L, F1FR42, F1FR42LL, F1FRXLH &
F1FR28 Fl or F2
Model F1 FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH &
F1FR28 FR
Model Fl FR56 Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
Nominal 1 Nominal K Factor
. Thread Size
. Sprinkler I Sprinkler I Approval
Orifice . US Metric Height I . . 7 Identification Organizations Numbers (SIN)
½"(lsmm) ½" NPT(R1/2) 5.6 80 2.25(57mm) 1,2,3
15mm ½NPT(R1/2) 56 80 225 57mrn RA1485(2)( 31
31
[PC Approval is for pendent position only.
(2/ cULus Listed corrosion resistant (Polyester coated) sprinkler,
Electroless Nickel RIFE (Teflon®)' Plated - cULus listed Corrosion Resistant
Sprinkler Type Deflector to Ceiling Distance
(Mm. - Max.)
Upright 4" (102mm) - 12" (305mm)
Pendent 4" (102mm) - 12" (305mm)
Vertical Sidewall
DuPont Registered Trademark ri
Horizontal Sidewall
Model Fl FR56 Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW
Installation Wrench: Model D Sprinkler Wrench
Installation Data: Horizontal Sidewall
Nominal Orifice Thread Size
1/2"(15mm) ½" NPT (R1/2)
Sprinkler Nominal K Factor Height
Approval Organizations
and Type of Approval Sprinkler
Identification Ordinary Numbers (SIN) Light Hazard Hazard
12 1 RA1435021°1
US
5.6
Metric
80 1 2.63" (67mm)
cULus Listed corrosion resistant (Polyester coated) sprinkler,
Polyester coated FM approved sprinkler.
i Electroless Nickel PTFE (Teflon®)* Plated - cULus listed Corrosion Resistant
FACE OF FITTING
iO FACE OF CEILING O'MFN'IEN
El ESCUTCHEON
AT MAXIMUM RECESS 1"[25.4-1
AT MINIMUM RECESS ,:, 3/5'I[?9.5mm]
52 ESCLiTCHEQfV
AT MAXIMUM RECESS
AT MINIMUM RECESS = 3/879.5mm/
r 2 1/4 HOLE CIA
[57.2mm]
X 1/2" REDUCER -
I /5/16" oIA.\JJL,: [49.2mm] 752. '- -
TURN COLLAR UNTIL -
liGHT 90411151 SPRINKLER
WRENCH BOSS.
/.A............................
Fl FSCUTGHEON
AT MAY/MUM RECESS
AT MINIMUM RECESS
F2 ESCUTCHEON
AT MAXIM/lU RECESS
1/8" AT MINIMUM RECESS 2- 1/15752.4mm]
[3,2mm]
2 27/32OIA.
SHEO1J
3/4 '[19mm] ADJUSTMENT
F2 .ESCUTCHEON
1/2'[I2.7mm] ADJUSTMLNI
Y (I)
4"- 12"
[101.6mm -304.8mm)
CE,LING TO
DEFLECTOR
RECESSED HSW W/F'l OR F2 ESCUTCHEON
(1) FM APPROVED FOR 4" - 6" [101.6MM - 152.4MM] CEILING TO DEFLECTOR WITH 52 ONLY.
Note: 1-or Hecessed HSW Sprinklers use installation wrench GFR2.
cULus permits use with Fl, F2 or FP escutcheons for "Light Hazard"
only. While FM limits use for the same hazard with the F2 escutcheon
only,
Model Fl FR56 Quick Response Concealed Pendent Sprinklers
Installation Wrench: Model RC1 Sprinkler Wrench
Technical Data:
Nominal
Orifice
"K" Factor I Thread
Size Model
Temp. Rating Max.
Ambient
Temp
Bulb
Color Approvals
Sprinkler
Identification
Number(SIN) US Metric
_________
Sprinkler i Cover
1/2" (15mm) 5.6 80 ½' NPT F1FR 135'F/57' 1! 1351F/571C 1001F1381C Orange 1 RA1414
1/2" (15mm) 5.6 I 80 ½" NPT F1FR 155°F/681C 135°F/57°C 1001F/381C Red 1 4(1) RA1414
1/2" (15mm) 5.6 80 1/2" NPT F1FR 175°F/79°C I 165°F/74°C 100°F/38°C Yellow 1 RA1414
/2" (15mm) 5.6 [ 80 1/2" NPT F1FR 200°F/930C 165°F/740C 150°F/65°C Green 1 RA1414
r-or vab only = 1b5ThIbdU NorDuIb and 1/ [12,1mm] adjustment,
Model Fl FR56LL Quick Response Concealed Pendent Sprinklers
Installation Wrench: Model RC1 Sprinkler Wrench
Technical Data:
Nominal "K" Factor Temp. Rating
--_ Thread Max. Bulb Sprinkler
Orifice . Model US Metric Size Sprinkler Cover Ambient Color Approvals Identification
Temp I Number(SIN)
½" (15mm) 5.6 80 ½" NPT 1-11-R561-1-1 200°F/93°C 165°F/74°C 150°F/65°C Green 1,5 RA1414
'DuPont Registered Trademark
7 / 1/2" RLOUC1?./O.
TEE QO ELBOW"_1
IF
2 _5116"Di S
En in
- 0 iVG
1/2" MAE I
CQL1,' ALJUS!MENJ
COVET PLATE —r--
VS 0/A
SPP,NKLEP ......................../
CONCEALED, 1 /2" ADJUSTMENT
Figure 1
Installation Aid
A protective cap is included for use during installation.
Important: The F1FR56 Sprinkler with Model CCP cover
plate is not an FM Approved combination.
Installation
Quick response sprinklers are intended for installation as
specified in NFPA 13. Quick response sprinklers and stan-
dard response sprinklers should not be intermixed.
The Model F1FR56, F1FR56LL, F1FR42, F1FR42LL,
F1FRXLH & F1FR28 Recessed Quick Response Sprin-
klers are to be installed as shown. The Model Fl or F2 Es-
cutcheons illustrated are the only recessed escutcheons
to be used with the Model F1FR56, F1FR56LL, F1FR42,
F1FR42LL, F1FRXLH & F1FR28 Sprinklers. The use of any
other recessed escutcheon will void all approvals and ne-
gate all warranties.
When installing Model F1FR56, F1FR56LL, F1FR42,
F1FR42LL, F1FRXLH & F1FR28 Sprinklers, use the Model
D Sprinkler Wrench. Use the Model GFR2 Wrench for install-
ing F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH &
F1FR28 Recessed Pendent Sprinklers. Any other type of
wrench may damage these sprinklers.
NOTE: A leak tight 112" NPT (R112) sprinkler joint can be
obtained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do
not tighten sprinklers over maximum recommended torque.
It may cause leakage or impairment of the sprinklers.
The Models F1FR56/CCP & F1FR56LL/CCP Concealed
Sprinkler use the /" orifice, V2" NPT (R1/2), Model F1FR56
& F1FR56LL Pendent Sprinkler with a threaded Model CCP
cup which is factory attached to the sprinklers. The Model
F1FR56 Pndent is available in temperature rating of 135°F
(57°C), 155°F (68°C), 175°F (79°C) or 200°F (930C). The
Model Fl FR56LL Pendent is available only in a rating of
200°F (930C). The concealed sprinkler assemblies are com-
pleted by the installation of the attractive low profile Model
CCP push on cover plate assembly, rated 135°F (57°C) or
165°F (74°C) for the Fl FR56 and 165°F (74°C) for the FlFR56
LL. The cover plate and sprinkler cup assemblies are joined
using a cover plate skirt with flexible tabs for threaded en-
1/2" RECLE/NG
TEE2TE90w
/
2
/8 DIA
/ MAX
rACE Of- CEILING
MIE
COVE' ACJUMC'JT
COVET °LATE—' I
ASSLESO(
SFO'Oi"LER /
CONCEALED. 5/76" ADJUSTMENt
Figure 2
gagement. A choice of two cover plate assemblies provide
either 1/2" (13mm) or 5/8" (8mm) of cover adjustment,
Do not install these sprinklers in ceiling which have positive
pressure in the space above.
After a 2/e" (67mm) diameter hole is cut in the ceiling, the
sprinkler is easily installed with the Model RC1 Wrench. A
Teflon* based thread sealant should be applied to the sprin-
kler threads only. The Model RC1 Wrench is then used to
engage the sprinkler wrenching surfaces and to install
the sprinkler in the fitting. When inserting or removing the
wrench from the sprinkler/cup assembly, care should be tak-
en to prevent damage to the sprinkler. DO NOT WRENCH
ON ANY OTHER PART OF THE SPRINKLER, The cover
plate is then pushed onto the cup. Final adjustment is made
by hand turning the cover plate until the skirt flange makes
full contact with the ceiling. Cover plate removal requires
turning in the counter clockwise direction.
After installation, inspect all sprinklers to ensure that there
is a gap between the cover plate and ceiling and that the
four cup slots are open and free from any air flow impedi-
ment to the space above.
Concealed cover plate/cup assemblies are listed only for
use with specific sprinklers. The use of any other concealed
cover plate/cup assembly with the Model Fl FR56 Pendent
Sprinkler or the use of the Model CCP Concealed cover
plate assembly on any sprinkler with which it is not specifi-
cally listed my prevent good fire protection and will void all
guarantees, warranties, listings and approvals.
Glass bulb sprinklers have orange bulb protectors to
minimize bulb damage during shipping, handling and in-
stallation. REMOVE THIS PROTECTION AT THE TIME THE
SPRINKLER SYSTEM IS PLACED IN SERVICE FOR FIRE
PROTECTION. Removal of the protectors before this time
may leave the bulb vulnerable to damage. RASCO wrench-
es are designed to install sprinklers when covers are in
place. REMOVE PROTECTORS BY UNDOING THE CLASP
BY HAND, DO NOT USE TOOLS TO REMOVE THE PRO-
TECTORS.
15/
*DuPont Registered Trade Mark
6.
&
Temperature Ratings Finishes (1)
Classification
Sprinkler Max Ambient Ternperature +ern Bulb Color
°C °F
Ordinary 57 135 100°F (38°C) Orange
Ordinary 68 155 100°F (38°C) Red
Intermediate 79 175 150°F(66°C) Yellow
Intermediate 93 1 200 150°F(66°C) Green
Hiah (1) 141 1 286 225'F (107'C) Blue
(1) Not available for recessed sprinklers
Escutcheon Data (1)
SIN RA1435 cULus permits use with Fl. F2 or FP escutcheons for light
hazard only, while FM limits use for same hazard with [2 escutcheon only.
Maintenance
The Model F1FR56, F1FR56LL, FIFR42, F1FR42LL,
F1FRXLH and Model F1FR56, F1FR56LL, F1FR42,
Fl FR42LL, Fl FRXLH & Fl FR28 Recessed Sprinklers should
be inspected and the sprinkler system maintained in accor-
dance with NFPA 25. Do not clean sprinklers with soap and
water, ammonia or any other cleaning fluids, Remove dust
by using a soft brush or gentle vacuuming. Remove any
sprinkler which has been painted (other than factory ap-
plied) or damaged in any way. A stock of spare sprinklers
should be maintained to allow quick replacement of dam-
aged or operated sprinklers. Prior to installation, sprinklers
should be maintained in the original cartons and packaging
to minimize the potential for damage to sprinklers that would
cause improper operation or non-operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Recessed Pendent
Vertical Sidewall
Horizontal Sidewall
Recessed Horizontal sidewall
Concealed pendent
Maximum Working Pressure
175 psi (12 bar)
100% Factory tested hydrostatically to 500 psi (34.5 bar)
Standard Finishes ___________
Sprinkler Escutcheon Cover p..ate°t
Bronze Brass Chrome
Chrome Plated i Chrome White
Polye..gr .Plated .......
Coated 4i)2'(° . White Painted
.............................
Special Application Finishes
Sprinkler Escutcheon Cover plateti)
Electroless Nickel i. Electroless Nickel Bright Brass PTFE(Tefion®17' PTFE (TefIon)°
Bright Brass Bright Brass Black Plating I
Black Plated Black Plated Black Paint
Black Paint' 2K,3) Black Paint Off White
Off White)2))6)Off White Satin Chrome l
Chrome Dull Chrome Dull
Other finishes and colors are available on special order, Consult the
factory for details. Custom color painted sprinklers may not retain their
UL Corrosion resistance listing. Coverplate custom paint is semi-gloss,
unless specified otherwise.
2) cuLus Listed only.
0) 200°F (93°C) maximum.
4) cuLus listed corrosion resistance" applies to SIN Numbers RA1435
(HSW), RA1485(VSW). RA1425 (Upright), RA1414 (Pendent) and
RA1415 (Pendent) in standard black or white. Corrosion resistance in
other polyester colors is available upon request.
FM Approvals finish as "Polyester coated" applies to SIN Number
RA1414, RA1435 and RA1 425 in standard black or white.
(6; _PCB and VdS Approved finish applies onlyto RA1425, RA1414 and RA1475.
(7) cULus listed Corrosion Resistant
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
3, Orifice Size
Deflector Type
Temperature Rating
Sprinkler Finish
Escutcheon Type
Escutcheon Finish (where applicable)
Cover plate Model
Cover plate Thread size
Cover plate Temperature
Cover plate Adjustment
13, Cover plate Finish
Note: When Model Fl FR56 Recessed sprinklers are ordered, the sprinklers
and escutcheons are packaged separately.
*DuPont Registered Trademark
7.