HomeMy WebLinkAbout1824 MARRON RD; ; AS030146; Permit12/27/24, 11:16AM AS030146 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address: 1824 MARRON RD
Permit Type: SPRINK
Parcel No:
Lot #: 0
Reference No.:
Permit No: AS030146
Status: ISSUED
Applied 8/18/2003
Approved: 9/4/2003
Issued: 9/4/2003
PC #: Inspector:
Project Title: NAVY FEDERAL CREDIT UNION
Applicant: Owner
I—
L Fees ($) I Add'l Fees Total ($) I Balance ($)
H 91 t 0 491
about:blank 1/1
Oea315 _f` O3OkV
WESTERN FIRE PROTECTION, INC.
12232 THATCHER COURT
POWAY, CA 92064
HYDRAULIC CALCULATIONS
FOR
NAVY FEDERAL CREDIT UNION
1824 MARRON RD UNITS B-i & C-3
CARLSBAD, CA.
FILE NUMBER: C-1133-1.SDF
DATE: 7-23-03
-DESIGN DATA-
OCCUPANCY CLASSIFICATION:
DENSITY:
AREA OF APPLICATION:
COVERAGE PER SPRINKLER:
NUMBER OF SPRINKLERS CALCULATED:
TOTAL SPRINKLER WATER FLOW REQUIRED:
TOTAL WATER REQUIRED (including hose)
FLOW AND PRESSURE (@ Base of Riser)
SPRINKLER ORIFICE SIZE:
NAME OF CONTRACTOR:
DESIGN/LAYOUT BY:
AUTHORITY HAVING JURISDICTION:
CONTRACTOR CERTIFICATION NUMBER:
LIGHT HAZARD
.10 gpm sq. ft.
1017 sq. ft.
150 sq. ft.
ii
181.7 gpm
281.7 gpm
181.7 gpm @ 42.0 Psi
1/2" INCH
WESTERN FIRE PROTECTION
D.G.G.
CARLSBAD FIRE DEPARTMENT
588039-C-16
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 50040828)
HRS SYSTEMS, INC.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 8/8/2003 C:\HASS74\C-1133-1.SDF
JOB TITLE: NAVY FEDERAL CREDIT UNION PENDENT CALC
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
SOURCE 110.0 105.0 1635.0 109.8 281.7 44.4
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 281.7 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100.0 GPM
OTHER HOSE STREAM ALLOWANCES 0.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 181.7 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 13.0 - - - - 11.4 - - -
1A 9.0 K= 5.60 11.0 18.6
2 13.0 - - - 11.1 - -
2A 9.0 K= 5.60 10.5 18.1
3 13.0 - - - - 11.1 - - -
3A 9.0 K= 560 10.6 18.2
4 13.0 - - - - 11.3 - - -
4A 9.0 K= 5.60 10.8 18.4
5 13.0 - - - - 7.9 - - -
5A 9.0 K= 5.60 7.8 15.6
5B 10.0 K= 5.60 7.5 15.4
6 13.0 - - - - 7.6 - - -
6A 9.0 K= 5.60 7.5 15.4
7 13.0 - - - - 7.6 - - -
7A 10.0 K= 5.60 7.2 15.0
8 13.0 - - - - 7.7 - -
8A 10.0 K= 5.60 7.4 15.3
8B 9.0 K= 5.60 7.5 15.4
9 13.0. - - - -
8.7
9A 10.0 K= 5.60 8.4 16.3
A 13.0 - - - - 19.1 - - -
B 13.0 - - - - 13.0 - - -
C 13.0 - - - 19.7 - -
D 13.0 - - - - 13.4 - - -
E 15.0 - - - - 22.4 - - -
F 15.0 - - - - 16.1. - -
G 15.0 - - - - 26.3 - - -
H 15.0 - - - - 20.0 - -
TOR 15.0 - - - - 31.5
BOR . 0.5 - - - - 42.0 - - -
UG1 -3.0 - - - - 43.6 - - -
UG2 -3.0 - - - - 46.7 - - -
BF1 2.0 - - - - 41.5 - - -
BF2 2.0 - - - - 44.5 - - -
SOURCE 2.5 SOURCE 44.4 181.7
N
I,
I
0.0
5.6
0.0
5.6
I,
I
0.0
5.6
II
S
nI
0.0
5.6
0.0
5.6
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 8/8/2003 C:\HASS74\C-1133-1.SDF
JOB TITLE: NAVY FEDERAL CREDIT UNION PENDENT CALC
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
PIPE DATA
PIPE TAG
END ELEV. NOZ.
NODES (FT) (K)
Pipe: 1
1 13.0 0.0
1A 9.0 5.
Pipe: 2
1 13.0
2 13.0
Pipe: 3
2 13.0
2A 9.0
Pipe: 4
2 13.0
3 13.0
Pipe: 5
3 13.0
3A 9.0
Pipe: 6
4 13.0
3 13.0
Pipe: 7
4 13.0
4A 9.0
Pipe: 8
B 13.0
4 13.0
Pipe: 9
A 13.0
1 13.0
Pipe: 10
5 13.0
5A 9.0
Pipe: 11
5 13.0
5B 10.0
Pipe: 12
5 13.0
6 13.0
Q(GPM) DIA(IN) LENGTH PRESS.
PT DISC. VEL(FPS) HW(C) (FT) SUM.
(PSI) (GPM) FL/FT (PSI)
18.6 1.080 PL 5.50 PF 2.1
11.4 0.0 6.5 120 FTG 2E2T PE 1.7
11.0 18.6 0.099 TL 21.70 PV
21.4 1.380 PL 8.25 PF 0.3
11.4 0.0 4.6 120 FTG ---- PE 0.0
11.1 0.0 0.039 TL 8.25 PV
18.1 1.080 PL 8.50 PF 2.3
11.1 0.0 6.4 120 FTG 2E2T PS 1.7
10.5 18.1 0.094 TL 24.70 PV
3.3 1.380 PL 8.25 PF 0.0
11.1 0.0 0.7 120 FTG ---- PE 0.0
11.1 0.0 0.001 TL 8.25 LW
18.2 1.080 PL 7.50 PF 2.2
11.1 0.0 6.4 120 FTG 252T PE 1.7
10.6 18.2 0.095 TL 23.70 PV
14.9 1.380 PL 8.25 PF 0.2
11.3 0.0 3.2 120 FTG ---- PE 0.0
11.1 0.0 . 0.020 TL 8.25 PV
18.4 1.080 PL 6.25 PF 2.2
11.3 0.0 6.4 120 FTG 2E2T PE 1.7
10.8 18.4 0.097 TL 22.45 PV
33.3 1.380 PL 11.00 PF 1.7
13.0 0.0 7.2 120 FTG T PS 0.0
11.3 0.0 0.088 TL 19.41 PV
40.0 1.380 PL 53.50 PF 7.6
19.1 0.0 8.6 120 FTG T PE 0.0
11.4 0.0 0.123 TL 61.91 PV
15.6 1.080 PL 9.50 PF 1.8
7.9 0.0 5.5 120 FTG 2E2T PS 1.7
7.8 15.6 0.071 TL 25.70 PV
15.4 1.080 PL 7.50 PF 1.6
7.9 0.0 5.4 120 FTG 2E2T PE 1.3
7.5 15.4 0.069 TL 23.70 PV
19.8 1.380 PL 8.25 PF 0.3
7.9 0.0 4.2 120 FTG ---- PE 0.0
7.6 0.0 0.033 TL 8.25 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 8/8/2003 C:\HASS74\C-1133-1.SDF
JOB TITLE: NAVY FEDERAL CREDIT UNION PENDENT CALC
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 13 15.4 1.080 PL 9.50 PF 1.8
6 13.0 0.0 7.6 0.0 5.4 120 FTG 2E2T PE 1.7
6A 9.0 5.6 7.5 15.4 0.069 TL 25.70 PV
Pipe: 14 4.4 1.380 PL 8.25 PF 0.0
6 13.0 0.0 7.6 0.0 0.9 120 FTG ---- PE 0.0
7 13.0 0.0 7.6 0.0 0.002 TL 8.25 PV
Pipe: 15 15.0 1.080 PL 9.50 PF 1.7
7 13.0 0.0 7.6 0.0 5.3 120 FTG 2E2T PE 1.3
7A 10.0 5.6 7.2 15.0 0.066 TL 25.70 PV
Pipe: 16 10.6 1.380 PL 8.25 PF 0.1
8 13.0 0.0 7.7 0.0 2.3 120 FTG ---- PE 0.0
7 13.0 0.0 7.6 0.0 0.011 TL 8.25 PV
Pipe: 17 15.3 1.080 PL 6.00 FE' 1.5
8 13.0 0.0 7.7 0.0 5.4 120 FTG 2E2T PE 1.3
8A 10.0 5.6 7.4 15.3 0.069 TL 22.20 PV
Pipe: 18 15.4 1.080 PL 10.50 PE 1.9
8 13.0 0.0 7.7 0.0 5.4 120 FTG 2E2T FE 1.7
8B 9.0 5.6 7.5 15.4 0.069 TL .26.70 PV
Pipe: 19 41.3 1.380 PL 8.25 PF 1.1
9 13.0 0.0 8.7 0.0 8.9 120 FTG ---- PE 0.0
8 13.0 0.0 7.7 0.0 0.131 TL 8.25 PV
Pipe: 20 16.3 1.080 PL 4.50 RE' - 1.6
9 13.0 0.0 8.7 0.0 5.7 120 FTG 2E2T FE 1.3
9A 10.0 5.6 8.4 16.3 0.077 TL 20.70 PV
Pipe: 21 . 57.6 1.380 PL 11.00 PF 4.7
D 13.0 0.0 13.4 0.0 12.3 120 FTG T FE 0.0
9 13.0 0.0 8.7 0.0 0.242 TL 19.41 PV
Pipe: 22 50.7 1.380 PL 53.50 PF 11.9
C 13.0 0.0 19.7 0.0 10.9 120 FTG T PE 0.0
5 13.0 0.0 7.9 0.0 0.192 TL 61.91 PV
Pipe: 23 40.0 1.639 PL 12.50 PF 0.7
C 13.0 0.0 19.7 0.0 6.1 120 FTG ---- PE 0.0
A 13.0 0.0 19.1 0.0 0.053 TL 12.50 PV
Pipe: 24 33.3 1.639 FL 12.50 PF 0.5
D 13.0 0.0 13.4 0.0 5.1 120 FTG ---- FE 0.0
B 13.0 0.0 13.0 0.0 0.038 TL 12.50 PV
Pipe: 25 90.8 1.639 PL 10.00 PF 3.5
E 15.0 0.0 22.4 0.0 13.8 120 FTG E PE 0.9
C 13.0 0.0 19.7 0.0 0.243 TL 14.50 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 8/8/2003 C:\HASS74\C-1133-1.SDF
JOB TITLE: NAVY FEDERAL CREDIT UNION PENDENT CALC
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 26 90.9 1.639 PL 10.00 PF 3.5
F 15.0 0.0 16.1 0.0 13.8 120 FTG E PE 0.9
D 13.0 0.0 13.4 0.0 0.244 TL 14.50 PV
Pipe: 27 90.8 1.639 PL 2.75 PF 3.9
G 15.0 0.0 26.3 0.0 13.8 120 FTG ET PE 0.0
E 15.0 0.0 22.4 0.0 0.243 TL 16.15 PV
Pipe: 28 90.9 1.639 PL 2.75 PF 3.9
H 15.0 0.0 20.0 0.0 13.8 120 FTG ET PE 0.0
F 15.0 0.0 16.1 0.0 0.244 TL 16.15 PV
Pipe: 29 90.9 2.157 PL 98.00 PF 6.3
G 15.0 0.0 26.3 0.0 8.0 120 FTG ---- PE 0.0
H 15.0 0.0 20.0 0.0 0.064 TL 98.00 PV
Pipe: 30 181.7 2.157 PL 18.50 PF 5.2
TOR 15.0 0.0 31.5 0.0 15.9 120 FTG L PE 0.0
G 15.0 0.0 26.3 0.0 0.230 TL 22.50 PV
Pipe: 31 181.7 2.157 PL 14.50 PF 4.3
BOR 0.5 0.0 42.0 0.0 15.9 120 FTG L PE -6.3
TOR 15.0 0.0 31.5 0.0 0.230 TL 18.50 PV
Pipe: 32 181.7 4.220 PL 9.00 PF 0.1
UG1 -3.0 0.0 43.6 0.0 4.2 140 FTG ---- PE -1.5
BOR 0.5 0.0 42.0 0.0 0.007 TL 9.00 PV
Pipe: 33 181.7 4.220 PL 5.00 PF 0.0
BF1 2.0 0.0 41.5 0.0 4.2 140 FTG ---- PE 2.2
UG1 -3.0 0.0 43.6 0.0 0.007 TL 5.00 PV
Pipe: 34 FIXED PRESSURE LOSS DEVICE
BF2 2.0 0.0 44.5 0.0 3.0 psi, 181.7 gpm
BF1 2.0 0.0 41.5 0.0
Pipe: 35 181.7 4.220 PL 5.00 PF 0.0
UG2 -3.0 0.0 46.7 0.0 4.2 140 FTG ---- PE -2.2
BF2 2.0 0.0 44.5 0.0 0.007 TL 5.00 PV
Pipe: 36 181.7 4.240 PL 23.00 PF 0.1
SOURCE 2.5 SRCE 44.4 (N/A) 4.1 150 FTG ---- PE 2.4
UG2 -3.0 0.0 46.7 0.0 0.006 TL 23.00 PV
NOTES:
(1) Calculations were performed by the HASS 7.5 computer program
under license no. 50040828 granted by
HRS Systems, Inc.
4792 LaVista Road
Tucker, GA 30084
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 8/8/2003 C:\HASS74\C-1133-1.SDF
JOB TITLE: NAVY FEDERAL CREDIT UNION PENDENT CALC
The system has been calculated to provide an average
imbalance at each node of 0.006 gpm and a maximum
imbalance at any node of 0.198 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 15.9 ft/sec at pipe 30.
PIPE FITTINGS TABLE
Pipe Table Name: STANDARD.PIP
PAGE: A MATERIAL: S40 HWC: 100
Diameter Equivalent Fitting Lengths in Feet
(in) B T L C B G A D
Eli Tee LngEll ChkVlv BfyVlv GatVlv AimChk DPViv
1.380 3.00 6.00 2.00 7.00 6.00 1.00 10.00 10.00
PAGE: B MATERIAL: THNWL HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv
2.157 4.31 10.46 4.00 14.00 7.00 1.00 12.00 12.00
PAGE: D MATERIAL: DIRON HWC: 140
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G
Eli Tee LngEll ChkVlv BfyVlv GatVlv
4.220 18.00 36.00 11.00 39.00 22.00 4.00
PAGE: E MATERIAL: PVC150 HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G
Eli Tee LngEll ChkVlv BfyVlv GatVlv
4.240 19.00 39.00 12.00 43.00. 23.00 4.00
PAGE: H MATERIAL: DYNA-T HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D H
Ell Tee LNGELL CHKVLV BTYVLV GATEVA ALMVLV DPVLV 45
1.080 2.30 5.80 2.30 5.80 6.90 1.20 0.00 0.00 1.00
1.639 4.50 8.90 2.20 10.00 6.70 1.10 0.00 0.00 2.00
WATER SUPPLY ANALYSIS
I I C. C. - _. 2 n - - 2 - 1 n r e% r -- - .-., 120.0
100.0
G
A
U
G
E 80.0
P
R
E
S
S 60.0
U
R
E
40.0
p
S
±
20.0
-14.7
2000 400 600 800 - 1000 1200 1400 1600 1800
FLOW (GPM)
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8
DATE: 8/8/2003 C:\HASS74\C-1133-l.SDF
JOE TITLE: NAVY FEDERAL CREDIT UNION PENDENT CALC
WATER SUPPLY CURVE
120+
110*\0\\\\\\\\\\\\\\\\\\\\
I \\\\\\\\\\\\\\\\\\\\\\
I 105.0 psi 8 1635 gpm-> *
I Flow Test Point
100+
90+
P 80+
R I
E I
S I
5 70+
U I
R I
E
60+
( I
P I
S I
I 50+
Ix
40+
30+
20+ LEGEND
I X = Required Water Supply
I 44.43 psi 8 281.7 gpm
10+
I 0 = Available Water Supply
I 109.81 psi 8 281.7 gpm
I!
0++-+---+----+-----+ ------ + --------+ --------+---------+-----------+
400 600 800 1000 1200 1400 1600 1800 2000
FLOW (GPM)
Bulletin 125 Rev.F
blia Model F4FR
Quick Response
Concealed
Automatic Sprinkler
The Concealer®
A Concealed Sprinkler
With ½" (13mm) or 11/2 " (38-mm)'
Adjustment
Features
½" (13mm) Total adjustment provided by
economical standard inlet version.
1 ½" (38mm) Total adjustment provided by
adjustable inlet versions.
Adjustable inlet version available with either
1" NPT male or female threads
eliminating costly reducing coupling.
Simple sturdy cover attachment.
Smooth aesthetic ceiling profile.
Available in brass, chrome, and black plated
or white or other color painted finishes.
Ordinary temperature rating.
Multiple orifices for design flexibility.
Threaded cover plate does not require clips
or springs.
Listed by Underwriters Laboratories Inc. and
Underwriters' Laboratories of Canada.
NYC BSA 587-75-SA.
U.S. Patent No. 4,880,063.
Application
The Reliable Model F4FR
Concealer is the most versatile quick
response sprinkler available. The
Model F4FR Quick Response Con-
coaled Sprinkler provides the best
form of fire protection by offering an
attractive appearance and /2"
(13mm) cover adjustment for ease of ,..
installation. The adjustable 1" NFl
inlet versions have one and one half
inches of total adjustment, and they
also ejiminaje the need for a reducing coupling. I he small diameter cover plate is easily and positively at-
tached and blends into the ceiling, concealing the most dependable
fire protection available, an automatic sprinkler system.
The Concealer® is designed for use where aesthetic appearance
is important. Offices, hospitals, motels and restaurants are but a few
of the applications where it can be used. It is available in different ori-
fice sizes allowing the designer to optimize system performance,
thereby achieving a very efficient installation.
The Model F4FR Concealer is quick response concealed sprin-
kler intended for use in accordance with NFPA 13.
* .--
-
77.
___ :i 1
The Concealer® can eliminate the need for precise cutting of
drop nipples. The threaded cover plate assembly can be adjusted
without tools to fit accurately against the ceiling. The fire protection
system need not be shut down to adjust or remove the cover plate
assembly.
Product Description
The Concealer® for quick response applications uses a 135°F
(57°C) 3mm diameter glass bulb in a standard style sprinkler frame
with a drop-down deflector. This assembly is recessed into the
ceiling and concealed by a flat cover plate. The cover plate and
sprinkler cup assemblies are attached using a strong threaded en-
gagement. This threaded engagement provides 1/211 (13mm) of
cover adjustment. The cover plate is attached to the skirt using
135°F (57°C) ordinary temperature classification solder. When the
ceiling temperature rises, the solder holding the cover plate fuses,
thus releasing the plate and exposing the sprinkler inside to ambi-
ent temperature. The subsequent shattering of the sprinkler bulb
opens the waterway and causes the deflector to drop into position
to distribute the discharging water. Any secure engagement be-
tween the cover plate and cup will assure that the drop-down de-
flector is properly located below the ceiling.
Installation
Do not install The Concealer® in ceilings which have positive
pressure in the space above. In addition, inspect all sprinklers after
installation to ensure that both the gap between the cover plate and
ceiling and the 4 slots in the cup are open and free from any air flow
impediment.
After a " diameter hole is cut in the ceiling, the sprinkler is to
be installed with the Model G4 Wrench. When installing a sprinkler,
the wrench is first positioned into the sprinkler/cup assembly until
two wrench tangs fully engage drive slots in the top of the cup
(there are two pairs of drive slots in the cup). The sprinkler is then
tightened into the pipe fitting. When inserting or removing the
wrench from the sprinkler/cup assembly care should be taken to
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, MountVernOn, NewYork, 10552
1(1 0* ELgOW 25FGO ,,,,__ /2REOUCtNG
11—.-----------fl
'iTlit
I I II —f'--lftfl ---- + ---1- Rffr--2--
I I stLWJ LY"' . -- -- 25/80L4 CSLINC HOLE
00 V8
I 3 S/H
prevent damage to the sprinkler. DO NOT WRENCH ON ANY
OTHER PART OF THE SPRINKLER/CUP ASSEMBLY.
The adjustable inlet versions are similar to the standard Model
F4FR except that an additional 1" of adjustment is pro'Aded by
means of a telescoping inlet section that threads in or out of a station-
ary coupling reducer (either 11'. NPT male or 1" NFl female) as
shown in Figures 2 or 3. These sprinklers must be installed, before
the ceiling is in place by wrenching on only the coupling reducer hex
flats. After the ceiling has been installed, each telescoping inlet sec-
ton is to be adjusted with the G4 Wrench. Final adjustment of each
cover is made by hand turning the cover in the clockwise direction
until it is fight against the ceiling. THE MODEL F4FR CONCEALER
MUST BE INSTALLED ONLY WITH A 135°F RATED COVER.
Maintenance
The Model F4FR should be inspected quarterly and the sprinkler
system maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other cleaning fluids.
Remove any sprinkler that has been painted (other than factory ap-
plied) or damaged in anyway. A stock of spare sprinklers should be
maintained o allow quick replacement of damaged or operated
sprinklers. Prior to installation, sprinklers should be maintained in the
original cartons and packaging to minimize the potential for damage
to sprinklers that would cause impr'operoperaiton or non-operafion
Ordering Information Approvals
Specify i. Underwriters Laboratories, Inc.
1. Sprinkler Model 2. Underwriters Laboratories
2. Nominal Orifice of Canada
3. Cover Plate Finish NYC BSA 587-75-SA
Inlet Type
Finishes (1). Note: Approvals are ordinary
Standaid Finishes: hazard except for small orifice
sprinklers which are limited to light
Bronze hazard occupancies. The cup and
Bright Brass Plated skirt are fabricated from corrosion
cht -re Plated resistant plated steel and are
Black Rated intended for interior non corrosive
1ite applications.
(1) Other colors and finishes UL Listing Categories
are available. Consult factory Sprinklers, Automatic & Open for details. Quick Response Sprinkler
Note: Paint or any other UL Guide Number
coatings applied over the NV
factory finish will void all Installation Wrench
approvals and warranties: Model G4 Sprinkler Wrench
Temøeratures Ratinas
L Classification Sprinkler Cover Plate Max. Ceiling
I " Ordinary I 135°F/57°C I 135°/57°C I 100°F138°c
InstaIIatiorr Data
Sprinkler
Inlet
Total
_Adjustment Nominal Orifice
Nominal
K Factor
Thread _.Approvals
Sprinkler
Identification
Number (SIN) US Metric
Non-Adjustable /2" (13mn) /2"(l5mm) V415.6 SO NPT (R/2) 12,3 R2512
Non-Adjustable /2"(1iim) 7A6"(llMM) 4.2 80 /2 NPT (Rh/2) 1,2,3 Ff2513
Non-Adjustable /'(13rnii) 3/8"(1rni) 2.8 40 Y' NPT (R½) 1,2,3 Ff2511
Adjustable 1Y2"(38rn1) /2"(15mii) 5.6 80 1"NFT 1,2.3 R2518
Mae orFemste
-
250203
[—
COURING RE-
00 V8
11.E15- 00 V8
I- 1
OLEHS -
0E,L,
NPT (R)) Non Adjustable inlet
Figure 1
1" NPT Male-Adjustable inlet
Figure 2
1" NPT Female-Adjustable inlet
Figure 3
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection ,Association, Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputa-
ble sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
Ie.iablö
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 668-3470 Corporate Offices
www.reiiabIesprinkler.com Internet Address
0 Recycled
Paper
Revision lines indicate updated or new data.
E.G. Printed in U.S.A. 03/01 PIN 9999970018
.,-
rEW
QUICK RESPONSE
HORIZONTAL SIDEWALL
,. '4JICK RESPONSE
VUPRIGHT CONVENTIONAL
QUICK RESPONSE
PENDENT VERTICAL
SIDEWALL
VM41 'so,
10
LOBE®
FIRE SPRINKLER
CORPORATION
QUICK RESPONSE
A UTOMA TIC SPRINKLERS
GL SERIES
4JPRIGHT PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
DESCRIPTIONAND OPERATION CONVENTIONAL (OLD STYLE)
The Globe Quick Response GL Series Sprinklers are a low
profile yet durable design which utilizes a 3mm frangible glass ampule
as the thermosensitive element. This provides sprinkler operation
approximately six times faster than ordinary sprinklers. While the
Quick Response Sprinkler provides an aesthetically pleasing appear-
ance, it can be installed wherever standard spray sprinklers are
specified when allowed by the applicable standards. It offers the
additional feature of greatly increased safety to life and is available
in various styles, orifices, temperature ratings and finishes to meet
many varying design requirements. Quick Response Sprinklers
should be used advisedly and under the direction of approving
authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that contains
a precisely measured amount of fluid. When heat is absorbed, the
liquid within the bulb expands increasing the internal pressure. At
the prescribed temperature the internal pressure within the ampule
exceeds the strength of the glass causing the glass to shatter. This
results in water discharge which is distributed in an approved
pattern depending upon the deflector style used.
TECHNICAL DATA
See reverse side for Approvals and Specifications.
Temperature Ratings - 135°F (57°C), 155°F (68°C), 175°F (790C),
200°F (93°C), 286°F (141 'C).
Water Working Pressure Rating - 175 psi (I 2 Bars).
Factory tested hydrostatically to 500 psi (34 Bars).
Maximum low temperature glass bulb rating is -67°F (-55°C).
Frame - bronze o Deflector - brass o Screw - brass
Bulb seat - copper Spring - nickel alloy e Seal - teflon
Bulb - glass with alcohol based solution, 3mm size.
o SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
I I CLASSIFICATION I
AVAILABLE SPRINKLER BULB I N.F.P.A. MAXIMUM
TEMPERATURES COLOR I CEILING TEMPERATURE
4NOTERMEDIATE
RDINARY 35 F1155°F 57?c68C j ORANGE/RED IOU F • 38°C
I75°F/200 F I 79°CI93 C YELLOW/GREEN 50°F 66°C
HIGH 286°F 141°C BLUE 225°F 107°C
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 517-846-4583 • FAX 517-846-9231
NOVEMBER 2000 A-6 BULLETIN GL5615
QUICK RESPONSE
A UTOMA TIC SPRINKLERS
GL SERIES
,,.-UPRIGHTo PENDENT° VERTICAL SIDEWALL
HORIZONTAL SIDEWALL o CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL "K" FACTOR THREAD SIZE *LENGTH FINISHES
2.8 (39 metric) 112" NPT 2 1/4" (5.7 cm) Factory Bronze
4.2 (59 metric) 1/2" NPT 2 1/4" (5.7 cm) I0KSatin Chrome Bright Chrome
(80 metric) 1/2" NPT 2 1/4 (5.7 cm) 'vVhite Polyester+
7.8 (III metric) 1/2" NPT 2 1/4' (5.7 cm) Black Polyester+
8.1 (I 16 metric) 3/4' NPT 2 7/16' (6.2 cm) **Lead Coated
NOTE: METRIC CONVERSIONS ARE APPROXIMATE. * HORIZONTAL SIDEWALL IS 2 9116".
FINISHES AVAILABLE ON SPECIAL ORDER.
+ AVAILABLE AS UL AND C-UL LISTED CORROSION
APPROVALS - RESISTANT WHEN SPECIFIED ON ORDER.
STYLE MODEL K 135°F 155°F 175°F 200°F 286°F U.L.U.L.F.M. CANADIAN N.Y.C.- D.O.S.
FACTOR 57°C 68°C 79°C 93°C 141°C MEA I0I-92-E
GL2815 2.8 X X X X X X X --- X
GL42I5 4.2 X X X X X X X --- X
UPRIGHT GL5615 /56 X X X X X X X X x
GL8IIS 7.8* X X X X X X X -- X
GL8118 8.1 X X X X X X X -- X
GL2801 2.8 X X X X X X X --- X
GL4201 4.2 x X X X X X X --- X
PENDENT GL560I 5.6 X X X X X X X X x
GL8I0I 7.8* X X X X X X X --- X
GL8106 8.1 X X X X X X X --- x
VERTICAL t GL5632 5.6 X X X X X X X
SIDEWALL GL8133 8.1 X X X X X X X
GL2826 2.8 X X X X X X X --- X
HORIZONTAL
SIDEWALL § GL4226 4.2 X X X X X X X --- X
GL5626 5.6 X X X X X X X X X
CONVENTIONAL GL5624 5.6 X X X X X ---
(OLD STYLE) GL8 125 8.1 X X X X X --- --- --- --
S HORIZONTAL SIDEWALL UL AND C-UL LISTED FOR DEFLECTOR 4" TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6".
t VERTICAL SIDEWALL SPRINKLER UL AND C.UL LISTED FOR LIGHT HAZARD ONLY.
PENDENT VERTICAL SIDEWALL UL AND C.UL LISTED FOR 6' MIN. SPACING.
UPRIGHT VERTICAL SIDEWALL UL AND C.UL LISTED FOR 9' MIN. SPACING.
*1/2" NPT.
ORDERING INFORMATION + FM APPROVED FOR 1357 AND I 55F ONLY.
SPECIFY
Quantity Model Number Style
Orifice Thread Sizes Temperature
Finishes desired
Quantity - Wrenches - P/N 325390 (1/2");
P/N 312366 (LO.)
L OB E® 'U, FIRE SPRINKLER
CORPORATION
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
517-846-4583 FAX 517-846-9231
1-800-248-0278 www.globesprinkIer.com
NOVEMBER 2000 PRINTED U.S.A. BULLETIN GL5615
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufac-
tured products found to be defective in material or workman-
ship for a period of one year from date of shipment.
For specific details of our warranty please refer to Price
List Terms and Conditions of Sale (Our Price List).