HomeMy WebLinkAbout3115 MELROSE DR; ; AS070162; Permit12/27/24,10:06 AM AS070162 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address: 3115 MELROSE DR
Permit Type: SPRINK
Parcel No: 2218801300
Lot #: 0
Permit No: AS070162
Status: ISSUED
Applied 6/14/2007
Approved: 6/14/2007
Reference No.: Issued: 6/14/2007
PC #: Inspector:
Project Title: PROGRESSIVE CLAIMS OFFICE THREE FIRE SPRINKLER
INSPEXTIONS @ $62/EA
Applicant:
ADVANCE FIRE PROTECTION
1451 W. LAMBERT RD
LA HABRA, CA
714-526-2231'
OWner:
OPUS WEST CORP
4350 LA JOLLA VILLAGE DR #110
SAN DIEGO CA
Fees Add'l Fees_($) Total ($) Balance($)
186 0 186 0
about:blank 1/1
9 TTJ t I, ~Iq I
- - Fire Protection by Computer Design
Advance Fire Protection Co.
1451 W. Lambert Road
La Habra, CA 90631
562-691-0918
Job Name : PROGRESSIVE - CLAIMS OFFICE
Building : LOT 25
Location : 3115 MELROSE DR-CARLSBAD, CA.
System ST FLOOR
Contract : 07-0335
Data File : 07-0335.WXF
APPRQVED AS S
7111~ Te
TTED
__
74u ,
- CAD FIRE PA 9NT
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Advance Fire Protection Co. Page 1
PROGRESSIVE - CLAIMS OFFICE Date 6-6-07
Hydraulic Design Information Sheet
- Name - PROGRESSIVE - CLAIM OFFICE Date - 6-6-07
Location - 3115 MELROSE DR.-CARLSBAD, CA.
Building - LOT 25 System No. - 2ST FLOOR
Contractor - ADVANCE FIRE PROTECTION Contract No. - 07-0335
Calculated By - CHARLIE T. Drawing No. - 1 OF 1.
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height - 91 -.0
Occupancy - OFFICES
S (X) NFPA 13 (X) Lt. Haz. Ord.Haz.Gp. ( ) 1 ( ) 2 ( ) 3 ( ) Ex.Haz.
Y ( ) NFPA 231 ( ) NFPA 231C ( ) Figure Curve
S Other
T Specific Ruling Made By Date
E
N Area of Sprinkler Operation - 1500 System Type Sprinkler/Nozzle
Density - 0.1 (X) Wet Make TYCO
D Area Per Sprinkler - 324 ( ) Dry Model EC-11
E Elevation at Highest Outlet - 9 ( ) Deluge Size i" ORIFICE
S Hose Allowance - Inside - 100 GPM ( ) Preaction K-Factor 11.2
I Rack Sprinkler Allowance - N/A ( ) Other Temp.Rat.155°F
G Hose Allowance - Outside - N/A
N
Note
Calculation Flow Required - 401.57 Press Required - 56.084 At BOR
Summary C-Factor Used: 120 Overhead 150 Underground
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - 1-18-06 Cap. -
T Time of Test - 9:18 AM Rated Cap.- 500 Elev.-
E Static Press - 135 8 Press - 75
R Residual Press - 126 Elev. - 2 Well
Flow - 2632 Proof Flow
S Elevation - 0
U
P Location - EXISTING CITY WATER MAIN IN LIONSHEAD AVE.
P
L Source of Information - WATER FLOW TEST WITH MARK SODERGERG-CARLSBAD FIRE INS
Y
Commodity
Storage Ht.
Storage Method:
Single Row
Double Row
Mult. Row
Class
Area
Solid Piled %
Conven. Pallet
Slave Pallet
Location
Aisle W.
Palletized % Rack
Auto. Storage ( ) Encap.
Solid Shelf ( ) Non
Open Shelf
Flue Spacing Clearance:Storage to Ceiling
Longitudinal Transverse
Horizontal Barriers Provided:
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
C
0
N
N
SR
TA
O C
R K
A
G
E
AMINA IIIIIIIIIIIIF WIN E
FIRE PROTECTION CD., INCA
1451 WEST LAMBERT ROAD
LA HABRA, CALIFORNIA 90831-6599
(562) 691-0918 (714) 526-2231
FAX$ (562) 691-5482
STATE LICENSE
259936
January 23, 2006
City Of Carlsbad
1635 Faraday Avenue
Carlsbad, CA 92008
Attn: Mark Soderberg
Re: Fire hydrant flow test results performed at
3190 Lionshead Avenue, Carlsbad, CA
Dear Mark,
The results of the Fire Flow test performed at the above address are as follows:
Static Water Pressure: 150 psi
Residual Water Pressure 140 psi
Observed Water Flow: 2632 gpm
Pitot Reading: 75 psi
Outlet Size: 2% inch x 2 outlets flowing simultaneously
Flow At 20 psi: 10529 gpm (Calculated)
Date: 1-18-06
Time: 9:18 am
As you may know, daily usage can fluctuate and may change results.
Feel free to contact me with questions or concerns regarding this test.
Sincerely,
Advance Fire Protecti Co., Inc.
Brian Callahan
VP of Engineering
Water Supply Curve (C)
Advance Fire Protection Co. Page 2
PROGRESSIVE - CLAIMS OFFICE Date 6-6-07
City Water Supply: Demand:
Cl - Static Pressure : 135 Dl - Elevation : 5.124
C2 - Residual Pressure: 126 D2 - System Flow : 301.567
C2 - Residual Flow : 2632 D2 - System Pressure : 65.403
Hose(Adj City)
Hose ( Demand) : 100
D3 - System Demand : 401.567
Safety Margin : 69.319
150
-0+—' 140 -
130 - ______ - -_ C ? ____________ ______________ _________________
p120
R 110
E10°
S90
80
U70 0
) D60
E5°
40
30
20
10
I I I I I I I
300 600 900 1200 1500 1800 2100 2400 2700
-
FLOW (NA1.85):
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
Advance Fire Protection Co. Page 3 PROGRESSIVE - CLAIMS OFFICE Date 6-6-07
Fitting Legend
Abbrev. Name ½ % 1 1% 1% 2 2%. 3 31/2 4 5 6 8 10 1214 16 16 20 24
B Generic Butterfly Valve 0 0 0 0 3 5.5 7 10 0 12 9 10 12 19 21 0 0 0 0 0 E 90 Standard Elbow 2 2 2 3 4 5 6 7 B 10 12 14 18 22 27 35 40 45 50 61 F 45 Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28 G Generic Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 L Long Turn Elbow 1 1 2 2 2 3 4 5 5 6 8 9 13 16 18 24 27 30 34 40 S Generic Swing Check Vlv 4 5 5 7 9 11 14 2 0 22 27 32 45 55 65 76 87 98 109 130 T 90 Flow ThruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units
Length Units
Flow Units
Pressure Units
Inches
Feet
US Gallons per Minute
Pounds per Square Inch
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure I Flow Summary - STANDARD
Advance Fire Protection Co. Page 4
PROGRESSIVE - CLAIMS OFFICE Date 6-6-07
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Rea
- TYP 9.0 11.2 12.8 na 40.07 0.1 400 12.8
1 11.83 41.37 na
2 11.83 K= K @ ARM 28.75 na 44.92
3 11.83 K = K @ ARM 28.7 na 44.89
5 11.83 41.48 na
6 11.83 K= K@ ARM 23.17 na 40.33
7 11.83 K= K@ ARM 22.87 na 40.07
8 11.83 K= K@ ARM 23.43 na 40.56
10 11.83 42.0 na
11 11.83 K= K@ ARM 29.36 na 45.4
12 11.83 K= K@ ARM 29.34 na 45.39
14 11.83 44.15 na
15 11.83 42.44 na
18 11.83 44.01 na
20 11.83 43.98 na
22 11.83 43.98 na
4 11.83 36.94 na
9 11.83 37.14 na
13 11.83 38.29 na
16 11.83 40.31 na
17 11.83 41.14 na
19 11.83 42.21 na
21 11.83 42.28 na
24 11.83 44.27 na
TOR 11.83 47.0 na
BOR 0.0 56.09 na 100.0
UG 0.0 56.15 na
CITY 0.0 65.4 na
The maximum velocity is 14.88 and it occurs in the pipe between nodes TYP and ARM
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
Advance Fire Protection Co. Page 5 PROGRESSIVE - CLAIMS OFFICE Date 6-6-07
Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. .1c.,or Ftng's Pe Pv Notes Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
TYP 40.07 1.049 1E 2.0 12.000 12.800 K Factor = 11.20 to 120 2T 10.0 12.000 -1.226 ARM 40.07 0.4707 0.0 24.000 11.296 Vel = 14.88
0.0
40.07 22.870 K Factor = 8.38
1 -49.73 1.442 1 7.432 77.250 41.366
to 120 0.0 7.432 0.0 2 -49.73 -0.1490 - 0.0 84.682 -12.621 Vel = 9.77
2 44.92 1.442 0.0 21.250 28.745 K Factor @ node ARM to 120 0.0 0.0 0.0 3-4.81 -0.0020 0.0 21.250 -0.042 Vel=0.94
3 44.89 1.442 2L 4.955 70.000 28.703 K Factor @ node ARM to 120 11 7.432 12.387 0.0 4 40.08 0.1000 0.0 82.387 8.238 Vel = 7.87
0.0
40.08 36.941 KFactor=6.59
5 -60.80 1.442 1 7.432 77.250 41.476
to 120 0.0 7.432 0.0
6 -60.8 -0.2161 0.0 84.682 -18.303 Vel= 11.94
6 40.33 1.442 0.0 10.500 23.173 K Factor @ node ARM to 120 0.0 0.0 0.0 7 -20.47 -0.0289 0.0 10.500 -0.303 Vel = 4.02
7 40.07 1.442 0.0 21.000 22.870 K Factor @ node ARM to 120 0.0 0.0 0.0 819.60.0266 0.0 21.000 0.559 Vel =3.85
8 40.56 1.442 1 7.432 57.250 23.429 K Factor @ node ARM to 120 0.0 7.432 0.0 960.160.2119 -0.0 64.682 13.709 Vel =11.82
0.0
60.16 37.138 K Factor = 9.87
10 - -49.76 1.442 1 7.432 77.250 41.997
to 120 0.0 7.432 0.0 ii -49.76 -0.1492 0.0 84.682 -12.636 VeI= 9.78
11 45.40 1.442 0.0 10.500 29.361 K Factor @ node ARM to 120 0.0 0.0 0.0 12 -4.36-0.0016 0.0 _10.500 -0.017 Vel =0.86
12 45.39 1.442 iT 7.432 78.250 29.344 K Factor @ node ARM to 120 0.0 7.432 0.0
13 41.03 0.1044 0.0 85.682 8.944 Vel =8;06
0.0
41.03 38.288 K Factor= 6.63
14 -27.20 1.682 2T 19.799 54.500 44.154 to 120 0.0 19.799 0.0 15 -27.2-0.0231 0.0 74.299 -1.713 Vel =3.93
15 12.12 1.442 1L 2.477 120.000 42.441
to 120 iT 7.432 9.909 0.0
16 -15.08 -0.0164 0.0 129.909 -2.128 Vel = 2.96
0.0
-15.08 40.313 K Factor= -2.38
15 -12.12 1.442 IT 7.432 112.000 42.441
to 120 0.0 7.432 0.0 17 -12.12-0.0109 0.0 119.432 -1.306 Vel=2.38
0.0
-12.12 41.135 KFactor= -1.89
18 -91.82 3.26 21 40.319 166.500 44.011
to 120 0.0 40.319 0.0
19 -91.82 -0.0087 0.0 206.819 -1.805 VeI= 3.53
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
Advance Fire Protection Co. Page 6 PROGRESSIVE - CLAIMS OFFICE Date 6-6-07
Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. I.C1.or Ftngs Pe Pv Notes Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
0.0
-91.82 42.206 - K Factor = -14.13
20 -11.17 1.442 2T 14.864 166.500 43.984 to 120 0.0 14.864 0.0 21 -11.17 -0.0094 0.0 181.364 -1.706 Vel= 2.19
0.0
-11.17 42.278 KFactor= -1.72
22 -11.08 1.442 2T 14.864 166.500 43.977 to 120 0.0 14.864 0.0
23 -11.08-0.0093 0.0 181.364 -1.680 Vel = 2.18
0.0
-11.08 42.297 K Factor -1.70
4 40.08 2.157 0.0 14.000 36.941 to 120 0.0 0.0 0.0 9 40.08 0.0141 0.0 14.000 0.197 Vel = 3.52
9 60.16 2.157 0.0 15.000 37.138 to 120 0.0 0.0 0.0 13 100.24 0.0767 0.0 15.000 1.150 - Vel = 8.80 - 13 41.03 2.157 0.0 14.000 38.288 to 120 0.0 0.0 0.0 16 141.27 0.1446 0.0 14.000 2.025 Vel = 12.40
16 -15.08 2.157 0.0 7.000 40.313 to 120 0.0 0.0 0.0
17 126.19 0.1174 0.0 7.000 0.822 Vel = 11.08
17 -12.12 2.157 0.0 11.000 41.135 to 120 0.0 0.0 0.0
19 114.07 0.0974 0.0 11.000 1.071 Vel _10.02
19 -91.82 2.157 0.0 15.000 42.206 to 120 0.0 0.0 0.0 21 22.250.0048 0.0 15.000 0.072 Vel _1.95
21 -11.17 2.157 0.0 15.000 42.278 to 120 0.0 0.0 0.0 23 11.080.0013 0.0 15.000 0.019 Vel _0.97
0.0
-11.08
- 42.297 K Factor = 1.70
1 49.73 2.635 0.0 14.000 41.366 to 120 0.0 0.0 0.0 5 49.73 0.0079 0.0 14.000 0.110 Vel = 2.93
5 60.81 2.635 0.0 15.000 41.476
to 120 0.0 0.0 0.0 10 110.54 0.0347 0.0 15.000 0.521 Vel = 6.50
10 49.76 2.635 IT 16.474 16.500 41.997
to 120 0.0 16.474 0.0 24 160.3 0.0689 0.0 - 32.974 2.273 Vel = 9.43
0.0
160.30 44.270 K Factor= 24.09
22 11.08 2.635 0.0 15.000 43.977
to 120 0.0 0.0 0.0
20 11.08 0.0005 0.0 15.000 0.007 Vel= 0.65
20 11.17 2.635 0.0 15.000 43.984 to 120 0.0 0.0 0.0 18 22.25 0.0018 0.0 15.000 0.027 Vel= 1.31
18 91.82 3.26 0.0 11.000 44.011
to 120 0.0 0.0 0.0 14 114.07 0.0130 0.0 11.000 0.143 VeI= 4.38
14 27.20 3.26 0.0 6.000 44.154 to 120 0.0 0.0 0.0
24 141.27 0.0193 0.0 6.000 0.116 Vel = 5.43
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
Advance Fire Protection Co. Page 7 PROGRESSIVE - CLAIMS OFFICE Date 6-6-07
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. 'C' or Ftng's Pe Pv Notes Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
24 160.30 3.26 IL 6.72 28.000 44.270
to 120 0.0 6.720 0.0
TOR 301.57 0.0787 0.0 34.720 2.734 Vel = 11.59
TOR 0.0 3.26 is 2.688 10.000 47.004
to 120 iF 4.032 40.319 5.124
BOR 301.57 0.0787 lB 13.44 50.319 3.961 Vel = 11.59
iT 20.159
BOR 100.00 8.249 2L 40.614 15.000 56.089 Qa = 100 to 140 0.0 40.614 0.0
UG 401.57 0.0011 0.0 55.614 0.061 Vel = 2.41
UG 0.0 8.385 6L 149.906 60.000 56.150
to 150 iT 67.266 224.858 9.000 * Fixed loss = 9 CITY 401.57 0.0009 1G 7.687 284.858 0.253 Vel _=_2.33
0.0
401.57 - -- 65.403 K Factor = 49.65
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
tqco /Fire & Building
/ Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series TY-FRB - 28,42,56, and 80 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The Series TY-FRB, 2.8, 4.2, 5.6, and
8.0 K-factor, Upright and Pendent
Sprinklers described in this data sheet
are quick response - standard cover-
age, decorative 3 mm glass bulb type
spray sprinklers designed for use in
light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20(1/2 inch NPT) or Style 30 (3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the fixed pipe
drops to the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fall
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 8
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TY-FRB Pendent Sprinklers are
detailed in Technical Data Sheet
TFP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain
-ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY1131 - Upright 2.81K, 1/2NPT
TY1231 - Pendent 2.81K, 1/2NPT
TY2131 - Upright 4.2K, 1/2NPT
TY2231 - Pendent 4.2K, 1/2NPT
TY3131 - Upright 5.61K, 1/2NPT
JULY, 2004
TY3231 - Pendent 5.61K, 1/2NPT
TY4131 - Upright 8.01K, 3/4'NPT
TY4231 - Pendent 8.01K, 3/4'NPT
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 2.8 GPM/p5i112 (40,3 LPM/barl'2)
K = 4.2 GPM/psi1/2 (60,5 LPM/barl/2)
K = 5.6 GPM/psi112 (80,6 LPM/bar1/2)
K = 8.0 GPM/psi1/2 (115,2 LPM/barl'2)
Temperature Ratings
Refer to Table A and B
TFPI7I
.4—
Page 2 of 8
ESCUTCHEON 7/16 (11,1 mm)
PLATE SEATING ** NOMINAL
SURFACE 1/2,
MAKE-IN NPT
(5m)
1-9/16
(39,7 mm)
'J11V'
TFPI7I
STYLE 100r20
RECESSED
ESCUTCHEON
LccrLtL, I UN
6
7/16"
(11,1mm) I
NOMINAL I
MAKE-IN
2-3/16"I
_5
WRENCH (55,6 mm)
FLATS
1/2" NPT** SSP DEFLECTOR * h— 2-7/8' (73,0 mm) DIA.
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3- Sealing 4 - Bulb 6 - Deflector Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7- Bushing orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1I3I) AND PENDENT (TY1231) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16(11,1 mm) STYLE 10or20
PLATE SEATING 1/2" ** NOMINAL RECESSED ssu SURFACE NPT MAKE-IN ESCUTCHEON DEFLECTOR
7/16"
2-3/16° 1,1 mm)
VFLATS
OMINAL(55,6 mm)
(38,1mm) 2-3/
MAKE-IN
1-1/2"
C (55,6mm)
SSP DEFLECTOR* 2-7/8 (73,0 mm) DIA. --I 1/2' NPT ** I
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3- Sealing 4- Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K-FACTOR, 1/2 INCH NPT
Finishes Bulb ..............Glass
Sprinkler: Refer to Table A and B Compression Screw .....Bronze Operation
Recessed Escutcheon: White Coated, Deflector .......Copper/Bronze
Chrome Plated, or Brass Plated Bushing (K=2.8) .......Bronze The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the Physical Characteristics fluid expands sufficiently to shatter the Frame .............Bronze glass Bulb, allowing the sprinkler to Button .........Brass/Copper activate and water to flow. Sealing Assembly ..........
Beryllium Nickel w/Teflonf
TFPI71 Page 3 of 8
ESCUTCHEON
PLATE SEATING
SURFACE
2-3/16' 6
mm)
55,6 mm)
1-
(38,
7/16 (11,1 mm)
1/2 ** NOMINAL
MAKE-IN NPT
STYLE 10 or 20
RECESSED SSU* ESCUTCHEON DEFLECTOR /
7/16 /
L
(11,1 mm) 1
MAKE-IN
N
tJ CH
MAK
2-3/16'
WREN
NOMINAL I
(55,6 mm)
FLATS
1/2' NPT** SSP DEFLECTOR* H-- 2-7/8" (73,0 mm) DIA.
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4- Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2(12,7mm) STYLE 30 or 40 PLATE SEATING 3/4fl ** NOMINAL RECESSED SSU* SURFACE MAKE-IN ESCUTCHEON NPT DEFLECTOR
T__ — 1/2"
6*
2-5/16" (12,7 mm) (58,7 mm) NOMINAL
L ?2:
(39,7 mm) IEIN 2-1
1-9/16
FLATS
(57,2 mm) WRENCH
SSP DEFLECTOR* 2-7/8 (73,0 mm) DIA. 3/4 NPT **
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3- Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Installation
The Series TY-FRB Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
Page 4 of 8
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED
I WHITE***
IPOLYESTER
2.8
1/2
PENDENT
(TY1231)
and
UPRIGHT
(TY1131)
135°F157°C Orange
1,2,3,5
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
286°F/141C Blue
NPT RECESSED
PENDENT
(TY1231)*
Figure 5
135°F/57°C Orange
1,2, 5
155°FI68C Red
175°F/79°C Yellow
200°FI93C Green
RECESSED
PENDENT
(TY1231)**
Figure 6
135°F/57C Orange
155F/68°C He
175°F/79°C Yellow
200°F/93°C Green
4.2
1/2"
NPT
PENDENT
(TY2231)
and
UPRIGHT
(TY2131)
135°F/57°C Orange
1,2
155°F168°C Red
175°F179°C Yellow
200°F/93°C Green
286'F/1 41'C Blue
RECESSED
PENDENT
(TY2231)*
Figure 7
135°F/57°C Orange
155°F/68°C Red
175F/79°C Yellow
200°F193°C Green
RECESSED
PENDENT
(TY2231)**
Figure 8 1
135°F/57°C Orange
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C I Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response
Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354-01 -E.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2' NPT) or Style 40 (3/4' NPT) 3/4' Total Adjustment
Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2' NPT) or Style 30 (3/4" NPT) 1/2' Total Adjustment
Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
held horizontally, a small air bubble A leak tight 1/2 inch NPT sprinkler joint
should be present. The diameter of the should be obtained with a torque of 7
air bubble is approximately 1/16 inch to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
(1,6 mm) for the 135°F/57°C to 3/32 mum of 21 ft. lbs. (28,5 Nm) of torque
inch (2,4 mm) for the 2861F/1411C may be used to install sprinklers with
temperature ratings. 112 NPT connections. A leak tight 314
TFPI7I
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 13).
With reference to Figures 1, 2, 3, and
4, the W-Type 6 Sprinkler Wrench is-to
be applied to the sprinkler wrench
flats.
The Series TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Reoessed Sprinkler Wrench (Ref.
Figure 14). With reference to Figure 1,
2, 3, and 4, the W-Type 7 Recessed
Sprinkler Wrench is to be applied to
the sprinkler wrench flats.
Step C. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 10, 20, 30, or
40 Closure over the Series TY-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
TFPI7I Page 5 of 8
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL I CHROME I WHITE*** LEAD
LIQUID BRASS J PLATED 1POLYESTER COATED
135F/57°C Orange
PENDENT
(TY3231)
and
1,2, 3, 4, 5, 6,7 1,2,3,5
155°F/68°C Red
175°F/79°C Yellow
UPRIGHT 200°F/93°C Green
5.6 (TY3131)
286°F/141°C Blue 1/2"
NPT 135°F/57°C Orange
RECESSED
PENDENT
(TY3231)* 1,2, 4,5 N/A
155°F/68°C Red
175°F/79°C Yellow
Figure 9 200°F/93"C Green
135°F/57 C Orange
RECESSED
PENDENT
(TY3231)** 1,2,3,4,5 1,2,4,5 N/A
155°F/68°C Red
175°F/79°C Yellow
Figure 10 200°F/93°C Green
135°F/57°C Orange
PENDENT
(1Y4231)
and
UPRIGHT 1, 2,3,4,5,6,7
1,2,5
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
8.0 (TY4131)
286°F/141°C Blue 3/4,,
NPT 135°F/57°C Green
RECESSED
PENDENT
(TY4231)* 1,2,4,5 N/A
155°F/68°C Orange
175°F/79°C Red
Figure 11 200°F/93°C Yellow
135°F/57°C Orange
RECESSED
PENDENT
(TY4231)** 1, 2, 3,4, 5 N/A
155F/68°C Red
175°F/79°C Yellow
Figure 12 1 200°F/93°C I Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4' NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2' NPT) or Style 30 (3/4" NPT) 1/2' Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
Page 6 of 8
2-7/8 DIA. -
5/8±1/4' (73,0 mm) 3/4' (19,1 mm)
(15,9±6,4 mm) - 2-1/4" DIA. 1/4" (6,4 mm)
SPRINKLER PLATE I FACE OF ._57,2 mm) MOUNTING
1/8'
FITTING
3,2 mm)
2
_____ ___ _______
4i /
___ ______ / MOUNTING /
1-5/16'
SURFACE///
(33,3 mm) I CLOSURE SERIES
.TY-FRB 13/16"(20,6 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
- 2-7/8" DIA.
5/8±1/4' (73,0 mm) I 3/4'(19,1 mm)
(15,9±6,4 mm) 2-1/4' DIA. 1/4' (6,4 mm) I
FACE OF mm) MOUNTING
SPRINKLER PLATE
FITTING I
MOUNTING
SURFACE
SERIES 1-1/4' (31,8 mm) CLOSURE TY-FRB 3/4" (19,1 mm)
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
TFPI7I
2-7/8" DIA.
1/2±1/8' (73,0 mm) 1/2'(12,7mm)
E (12,7±3,2 mm) - 21/4" DIA. 1/4' (6,4 mm)
I I FACE OF L_57,2 mm) MOUNTING
SPRINKLER PLATE I FITTING
1 -7
8
SURFACE
i
(32 mm)
I \
MOUNTIN
CLOSURE SERIES 1-5/16' (33,3 mm)
TY-FRB 1-1/16" (27,0 mm)
FIGURE 6
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
- 2-7/8" DIA.
(73,0 mm) 1/2±1/8' I 1/2'(12,7mm)
E (12,7±3,2 mm) 2-1/4" DIA. I 1/4' (6,4 mm) I
FACE OF 57,2 MM MOUNTING
PLATE I SPRINKLER
FITTING
1/8'
mm)
\ MOUNTING
SURFACE
SERIES 1-1/4(31,8mm) CLOSURE TYFRB 1" (25,4 mm)
FIGURE 8
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
Care and
Maintenance
The Series TY-FRB Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who maybe affected
by this action must be notified.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
TFPI7I
- 2-7/8 DIA.
5/8±1/4
(73,0 mm) 3/4" (19,1 mm)
(159±6,4 mm) 2-1/4 DIA. 1/4 (6,4 mm)
FACE OF
SPRINKLER
57,2 mm) MOUNTING
PLATE FITTING
1/8'
(3,2 mm)
MOUNTING
SURFACE
CLOSURE SERIES 1-1/4" (31,8 mm)
TY-FRB 3/4' (19,1 mm)
FIGURE 9
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8" DIA. -
5/8±1/4' (73,0 mm) 3/4" (19,1 mm)
(15,9±6,4 mm) 2-1/4" DIA. 1/4'(6,4 mm)
FACE OF
4R 1
(57,2 mm) MOUNTING I
PLATE SPRINKLE
FITTING
1/8"
(3,2 mm)
MOUNTIN
CLOSURE SERIES 1-5/16 (333 mm)
SURFACE
TY-FRB 13/16" (20,6 mm)
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
Page 7 of 8
- 2-7/8 DIA.
(73,0 mm) 1/2±1/8" 1/2" (12,7 mm)
r (1 2,7±3,2 mm) 2-1/4' DIA. 1/4' (6,4 mm) I
SPRINKLER PLATE I j FITTING
MOUNTING
(32 mj
FACE_OF 572 mm) MOUNTING
SURFACE
SERIES 1-1/4" (31,8 CLOSURE TYFRB 1"(25,4 mm)
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
- 2-7/8" DIA. -
1/2±1/8" (73,0 mm) 1/2" (12,7 mm)
(12,7±3,2 mm) 2-1/4' DIA. 1/4"(6,4 mm)
FACE OF (57,2 mm)
/ I
E
MOUNTING
SPRINKLER P
FITTING
(2rrn,
T-7-- -
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16" (33,3 mm)
TY-FRB 1-1/16" (27,0 mm)
FIGURE 12
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
tion and the long term integrity of the
corrosion resistant Coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END 'B" USED FOR
3/4' NPT MODELS)
FIGURE 13
W-TYPE 6 SPRINKLER
WRENCH
local requirements and/or national
codes.
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 14
W- TYPE 7 RECESSED
SPRINKLER WRENCH
Page 8 of 8 TFPI7I
P/N 57 - XXX - X - XXX
I L
MODEL/SIN
330 2.8K UPRIGHT (1/2NPT) TY1131
331 2.8K PENDENT (1/2NPT) 1Y1231
340 4.2K UPRIGHT (1/2NPT) TY2131
341 4.2K PENDENT (1/2NPT) TY2231
370 5.6K UPRIGHT (1/2NPT) 1Y3131
371 5.6K PENDENT (1/2NPT) 1Y3231
390 8.0K UPRIGHT (3/4NPT) TY4131
391 8.0K PENDENT (3/4NPT) TY4231
I I I SPRINKLER
1 NATURAL BRASS
4 WHITE POLYESTER
3 WHITE (RAL9010)*
9 CHROME PLATED
7 LEAD COATED
I
135
155
175
200
286
TEMPERATURE
RATING
___________
135*F/57*C
155°F/68°C
175°F/79°C
200°F/93°C
286*F/141*C
* Eastern Hemisphere sales only.
TABLE C
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEEDAN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
Ordering
Procedure
staratii local distributor for avail-
abftly.indicate the
full product
name. Refer to
the Price List for
complete listing
of Part Numbers.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table C).
Recessed Escutcheon:
Specify: Style (specify) Recessed Es-
cutcheon with (specify finish), P/N
(specify).
1/2 (15 mm)
Style 10
Chrome Plated ............P/N 56-701-9-010
White Coated .............P/N 56-701-4-010 White RAL9010*P/N 56-701-3-010 Brass Plated ..............P/N 56-701-2-010
1/2 (15 mm)
Style 20
Chrome Plated ............P/N 56-705-9-010 White Coated .............P/N 56-705-4-010 White RAL90I0*P/N 56-705-3-010 Brass Plated ..............P/N 56-705-2-010
3/4 (20 mm)
Style 30
Chrome Plated ............P/N 56-705-9-011 White Coated .............P/N 56-705-4-011 White RAL9010*P/N 56-705-3-011
Brass Plated ..............P/N 56-705-2-011
3/4" (20 mm)
Style 40
Chrome Plated ............P/N 56-700-9-010 While Coated .............P/N 56-700-4-010
White RAL9010" ...........P/N 56-700-3-010 Brass Plated ..............P/N 56-700-2-010
* Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446