HomeMy WebLinkAbout889 PALOMAR AIRPORT RD; ; FS982936; Permit12/27/24.12:53 PM FS982936 Permit Data
City of Carlsbad
Fixed Systems Permit
Permit No: F5982936
889 PALOMAR
Job Address:
AIRPORT RD
Permit Type: FIXSYS
Parcel No: 2110500100
Lot #: 0
Reference No.:
PC #:
Status: ISSUED
Applied 2/24/1999
Approved:
Issued:
Inspector:
Project Title: ISLANDS RESTAURANT
Applicant: Owner:
WINTER RAY TR
1745 ROCKY RD
FULLERTON CA
Fees ($) Add1 Fees ($) Total ($) Balance ($)
90 0 90 0
about:blarik 1/1
City of Carlsbad . 98213
Fire Department Bureau of Prevention
Plan Review: Requirements Category: Hood & Duct Systems r-S2
Date of Report:Tuesday, March 2, 1999 Reviewed by:
Contact Name Westech Fire Systems
2 /2- 4 ( 9
Address 6682 Kimdale Rd
City, State San Gabriel CA 91775
Bldg. Dept. No. CB982936 Planning No. SDP97-24
Job Name Islands Restaurant
Job Address 889 Palomar Airport Ste. or Bldg. No. Rd
Approved - The item you have submitted for review has been approved. The approval is
based on plans; information and/or specifications provided in your submittal;
therefore any changes to these items after this date, including field modifica-
tions, must be reviewed by this office to insure continued conformance with
applicable codes. Please review carefully all comments attached, as failure
to comply with instructions in this report can result in suspension of permit to
construct or install improvements.
O Disapproved - Please see the attached report of deficiencies. Please make corrections to
plans or specifications necessary to indicate compliance with applicable
codes and standards. Submit corrected plans and/or specifications to this
office for review.
For Fire Department Use Only
Review 1st 2nd 3rd
Other Agency ID
CFD Job# 98213 File#__________
2560 Orion Way 0 Carlsbad, California 92008 0 (619) 931-2121
r_j W_ 2 2-~~
WESTECH FIRE SYSTEMS PR OJECT
6682 KIMDALE ROAD
SAN GABRIEL, CA. 91775 ISLAND'S RESTAURANT
626-287-4251 FAX 626-287-0989 889 PALOMAR AIRPORT RD.
LICENSE NO. 698719 CARLSBAD, CA. 92008
CONTACT: BOB TRUDELL
SYSTEM TYPE: ANSUL R-102 9.0 GALLON (STANDARD UL 300 LISTED)
HOOD SIZE HOOD #1 24'3" DUCT SIZE 2 @ 12" X 24"
HOOD #2 4' 0" DUCT SIZE: 12" X 12"
FLO\V TOTAL
NOL/l F S QUANTITY PART NO. TI NO. POINTS POINTS
DUCT 419336 1W
DUCT 3 419337 2W 2 6
419335
BRAISING PAN 419339 230 2
RANGE - 419340 - 24 - 2 -
SALAMANDER 5692 I 2N 1 2
F RY FR 5 419339 230 2 10
GRIDDLE 419341 260 2 2
RANGE 419333 IF 1
FRYER 419338 3N 3
GRIDDLE 4 419335 IN 1 4
TOTAL )LOW POINTS USER 27
TOTAL FLOW POINTS AVAJLABLE 33
INSTALLATION NQTES:
INSTALLATION SHALL CONFORM WITH NFPA 96, 17, 17A AND AUTHORITY HAVING
JURISDICTION.
ALL PIPE AND FITTINGS WILL BE 3/8" BLACK IRON SCHEDULE 40.
FUEL SHUT OFF:
GAS AND OR ELECTRIC FUEL SUPPLY MUST SHUT OFF WHEN FIRE SYSTEM IS ACTIVATED,
ALARM SYSTM:
EXISTING FIRE ALARM MUST BE INTERCONNECTED TO ANSIJL FIRE SYSTEM.
TESTING SYSTEM:
A FIELD TEST SHALL BE PERFORMED WITH AUTHORITY HAVING JURISDICTION, UTILIZING
A STANDARD BALLOON TEST.