HomeMy WebLinkAbout2647 MARMOL CT; ; AS100015; Permit1/2/25, 7:43 AM AS100015 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: ASI000I5
Job Address: 2647 MARMOL CT Status: ISSUED
Permit Type: SPRINK Applied 2/3/2010
Parcel No: 2154910200 Approved: 2/3/2010
Lot #: 0
Reference No.: Issued: 2/3/2010
PC #: Inspector:
Project Title: PADILLA RESIDENCE TWO RESIDENTIAL FIRE SPRINKLER
INSPECTIONS @ $65/EA
Applicant:
ALLWAYS FIRE PROTECTION
1451 KENT AV.
ESCONDIDO, CA
760-294-5461
Owner:
PADILLA JOSEPH A
2114 CRYSTAL COVE WAY
SAN MARCOS CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
L 130 0 130 0
about:blank 1/1
- FILE COPY
Aliways Fire Protection, Inc.
1451 Kent Avenue APP Escondido, California 92027 AS U8MjTTED
HYDRAULIC CALCULATIONS CA
ME T
FOR
Two Sprinklers Flowing
Flat Ceiling
Padilla Residence
2647 Marmol Court
Carlsbad, California
FILE NUMBER: Padilla Residence2.sdf
DATE: JAN 28, 2010
-DESIGN DATA-
Total Square Footage of Dwelling: 10,531 square feet
Maximum Sprinkler Spacing 12' x 14' max.
Area Calculated: Cabana Room
Minimum Flow at Each Sprinkler: 15 gpm
NUMBER OF SPRINKLERS CALCULATED: 2 sprinklers
FLOW REQUIRED: 35.6 gpm
PRESSURE REQUIRED AT SOURCE: 51.5 psi
PRESSURE AVAILABLE AT SOURCE: 90.0 psi
SPRINKLER ORIFICE SIZE: 7/16"
NOTE: Pipe numbers with "+" indicated length of equivalent tees on run
included into pipe length, instead of fitting length.
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 50110279
HRS SYSTEMS, INC.
ATLANTA, GA
These plans have Ien reviewed foi apparent compliance
with the oirient appi icahie codes and standards in force
in the juit,dicnon. The owner or contractor may Liii lice
11111,RWA-11 in support of an application for a building
peottit with Oie espress understanding that this review
it no was rcheyes the owner or contrac or or their
pri)lesstohtal engineer or architect for sole responsihi lttv
for full compliance with said codes and standards.
ttciiting the building code or forany responsihifty for
ik ociencies. errors. omissions or negligence in these
ilaits whether or not noted in this review.
Date: Reviewer:
RECOMMEND APPROVAL
0 RECOMMEND APPROVAL. AS NOTED
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 1/28/2010 C:\HASS78\FILES\PADILLA RESIDENCE2.SDF
JOB TITLE: Padilla Residence - Cabana Room
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. 0 PRESS. 0 DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
SOURCE 90.0 89.9 100.0 90.0 35.6 51.5
Required pressure is 38.5 psi (43%) less than available pressure.
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 35.6 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 30.6 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 321.0 - - - - 21.3
2 321.0 - - - - 21.3
3 299.0 K= 4.90 10.2 15.6
4 299.0 K= 4.90 9.4 15.0
5 299.0 - - - - 22.7
6 299.0 - - - - 21.8
A 310.0 - - - - 26.8
B 310.0 - - - - 24.4
C 310.0 - - - - 25.3
D 310.0 - - - - 26.5
E 321.0 - - - - 20.6
F 321.0 - - - - 21.3
G 321.0 - - - - 21.6
H 321.0 - - - - 21.3
I 299.0 - - - - 25.0
J 299.0 - - - - 22.7
TOR 310.0 - - - - 31.6 - - -
BOR 300.0 HOSE STREAM 37.0 5.0
U 297.0 - - - - 39.7
M2 310.0 - - - - 34.7
Ml 310.0 - - - - 42.5
SOURCE 310.0 SOURCE 51.5 35.6
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 1/28/2010 C:\HASS78\FILES\PADILLA RESIDENCE2 .SDF
JOB TITLE: Padilla Residence - Cabana Room
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 0.0 1.101 PL 1.00 FE' 0.0
1 321.0 0.0 21.3 0.0 0.0 150 FTG ET FE 0.0
H 321.0 0.0 21.3 0.0 0.000 TL 13.00 PV
Pipe: 2 0.0 1.101 PL 1.00 PF 0.0
2 321.0 0.0 21.3 0.0 0.0 150 FTG ET FE 0.0
H 321.0 0.0 21.3 0.0 0.000 TL 13.00 PV
Pipe: 3 0.0 1.101 PL 35.00 PF 0.0
H 321.0 0.0 21.3 0.0 0.0 150 FTG 3T2R FE 0.0
F 321.0 0.0 21.3 0.0 0.000 TL 52.00 PV
Pipe: 4 -5.9 1.101 FL 26.00 PF 0.2
F 321.0 0.0 21.3 0.0 2.0 150 FTG ER FE 0.0
G 321.0 0.0 21.6 0.0 0.007 TL 34.00 PV
Pipe: 5+ 5.9 1.101 FL 86.00 PF 0.1
F 321.0 0.0 21.3 0.0 2.0 150 FTG 2E PE 0.0
H 321.0 0.0 20.6 0.0 0.007 TL 100.00 PV
Pipe: 6 5.9 1.101 PL 11.00 PF 0.1
H 321.0 0.0 20.6 0.0 2.0 150 FTG H PE 4.8
C 310.0 0.0 25.3 0.0 0.007 TL 18.00 PV
Pipe: 7 5.9 1.101 FL 72.00 FE' 0.9
C 310.0 0.0 25.3 0.0 2.0 150 FTG 6E6R FE 0.0
B 310.0 0.0 24.4 0.0 0.007 TL 120.00 PV
Pipe: 8 -24.7 1.101 FL 18.00 PF 2.4
B 310.0 0.0 24.4 0.0 8.3 150 FTG TR FE 0.0
A 310.0 0.0 26.8 0.0 0.101 TL 24.00 PV
Pipe: 9 -5.9 1.101 FL 14.00 PF 0.2
G 321.0 0.0 21.6 0.0 2.0 150 FTG ET PH 4.8
D 310.0 0.0 26.5 0.0 0.007 TL 26.00 PV
Pipe: 10 -5.9 1.101 FL 37.00 FE' 0.3
D 310.0 0.0 26.5 0.0 2.0 150 FTG SR FE 0.0
A 310.0 0.0 26.8 0.0 0.007 TL 42.00 PV
Pipe: 11 -30.6 1.400 FL 64.00 FE' 4.1
A 310.0 0.0 26.8 0.0 6.4 150 FTG 4E6R PE 0.0
TOR 310.0 0.0 31.6 0.0 0.046 TL 102.00 PV
Pipe: 12 -30.6 1.400 FL 10.00 FE' 1.1
TOR 310.0 0.0 31.6 0.0 6.4 150 FTG 2RC FE 4.3
BOR 300.0 H.S. 37.0 5.0 0.046 TL 23.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 1/28/2010 C:\HASS78\FILES\PADILLA RESIDENCE2.SDP
JOB TITLE: Padilla Residence - Cabana Room
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (PT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 13 -35.6 1.265 FL 5.00 PP 1.5
8CR 300.0 H.S. 37.0 5.0 9.1 150 FTG TG PE 1.3
U 297.0 0.0 39.7 0.0 0.101 TL 14.50 PV
Pipe: 14 -35.6 2.000 PL 60.00 PP 0.6
U 297.0 0.0 39.7 0.0 3.6 150 FTG ---- PE -5.6
M2 310.0 0.0 34.7 0.0 0.011 TL 60.00 PV
Pipe: 15 FIXED PRESSURE LOSS DEVICE
Ml 310.0 0.0 42.5 0.0 7.8 psi, 35.6 gpm
M2 310.0 0.0 34.7 0.0
Pipe: 16 35.6 0.995 PL 20.00 PF 8.9
SOURCE 310.0 SRCE 51.5 (N/A) 14.7 150 FTG TG PE 0.0
Ml 310.0 0.0 42.5 0.0 0.324 TL 27.50 PV
Pipe: 17 -15.0 1.101 FL 12.00 PP 0.8
4 299.0 4.9 9.4 15.0 5.1 150 FTG ER PE 0.0
3 299.0 4.9 10.2 15.6 0.040 TL 20.00 PV
Pipe: 18 -30.6 1.101 FL 58.00 PF 11.7
3 299.0 4.9 10.2 15.6 10.3 150 FTG 2E6R FE 0.0
6 299.0 0.0 21.8 0.0 0.150 TL 78.00 PV
Pipe: 19 -30.6 1.101 FL 1.00 PF 0.9
6 299.0 0.0 21.8 0.0 10.3 150 FTG T FE 0.0
J 299.0 0.0 22.7 0.0 0.150 TL 6.00 PV
Pipe: 20 0.0 1.101 FL 19.00 PF 0.0
5 299.0 0.0 22.7 0.0 0.0 150 FTG ET FE 0.0
J 299.0 0.0 22.7 0.0 0.000 TL 31.00 PV
Pipe: 21 -30.6 1.101 FL 10.00 PP 2.2
J 299.0 0.0 22.7 0.0 10.3 150 FTG T FE 0.0
I 299.0 0.0 25.0 0.0 0.150 TL 15.00 PV
Pipe: 22 -30.6 1.101 FL 16.00 PF 4.2
I 299.0 0.0 25.0 0.0 10.3 150 FTG ET FE -4.8
B 310.0 0.0 24.4 0.0 0.150 TL 28.00 PV
NOTES (HASS):
Calculations were performed by the HASS 8.0 computer program
under license no. 50110279 granted by
URS Systems, inc.
208 South Public Square
Petersburg, TN 37144
The system has been calculated to provide an average
imbalance at each node of 0.001 gpm and a maximum
imbalance at any node of 0.030 gpm.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 1/28/2010 C:\HASS78\FILES\PADILLA RESIDENCE2 .SDF JOB TITLE: Padilla Residence - Cabana Room
Total pressure at each node is used in balancing the system.
Maximum water velocity is 14.7 ft/sec at pipe 16.
PIPE FITTINGS TABLE
Pipe Table Name: STANDARD.PIP
PAGE: * MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Eli Tee LngEl1 ChkViv BfyVlv GatVlv AlmChk DPVlv NPTee 2.067 5.00 10.00 3.00 11.00 6.00 1.00 10.00 10.00 10.00
PAGE: K MATERIAL: CT-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet (in) E T F R C S G V K Eli Tee 45-Eli TeeRun Coupig SwgChk GatViv AngVlv CockVi 0.995 2.00 6.00 1.50 1.50 0.50 7.50 0.00 14.00 5.00
PAGE: L MATERIAL: CT-L HWC: 150
Diameter Equivalent Fitting Lengths in Feet (in) E T L R C S G Eli Tee 45-Eli TeeRun Coupig SwgChk GatVlv 1.265 4.50 9.00 1.50 3.00 0.50 5.50 0.00
PAGE: Z MATERIAL: CPVC-C HWC: 150
Diameter Equivalent Fitting Lengths in Feet (in) E T L R B G C D Eli Tee 45-Eli TeeRun Btrfly Gate Check 1.101 700 5.00 1.50 1.00 0.00 1.50 7.50 0.00 1.400 8.00 6.00 2.00 1.00 0.00 1.50 11.00 0.00
100. 0
1
G 80.0 A
U
G
E
60.0
E
S 2
S
U
B. 40.0 E
p
S
20.0
—14.
WATER SUPPLY ANALYSIS
-
200 300 400 500 600 700 8uu Juu
FLOW (GPM)
Aliways Fire Protection, Inc.
1451 Kent Avenue
Escondido, California 92027
APP V DAss HYDRAULIC CALCULATIONS
FOR
PARMNT
Two Sprinklers Flowing
Flat Ceiling
Padilla Residence
2647 Marmol Court
Carlsbad, California
FILE NUMBER: Padilla Residence.sdf
DATE: JAN 28, 2010
-DESIGN DATA-
Total Square Footage of Dwelling: 10,531 square feet
Maximum Sprinkler Spacing
Area Calculated:
Minimum Flow at Each Sprinkler:
NUMBER OF SPRINKLERS CALCULATED:
FLOW REQUIRED:
PRESSURE REQUIRED AT SOURCE:
PRESSURE AVAILABLE AT SOURCE:
SPRINKLER ORIFICE SIZE:
20' x 20' max.
Cabana Room
20 gpm
2 sprinklers
45.0 gpm
79.8 psi
90.0 psi
7/16"
NOTE: Pipe numbers with "+" indicated length of equivalent tees on run
included into pipe length, instead of fitting length.
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE * 50110279
HRS SYSTEMS, INC.
ATLANTA,
Date: 2//6/ia Reviewer:
RECOMMEND APPROVAL
10 RECOMMEND APPROVAL. AS NOTED
These plans have heen reviewed tot apPacl coniphancc
with the cullefli applicable codes and standards in trcc
in the urindiction. The ownes 01 contractor nay uO tie
las ci cci in .iippott or all application lot it building
mu j1h the e spiecs undco.taitduig. diat this review
it it,, iay relics en the owner or contractor or their
pcotessiicnal engineer or itrchiieclfor sole responsibility
lid till cicillpliaICC with said codes and standards.
hucli.Iuiug the building code or to, any responsihitty for
delicleitcies. errors. outlisslons or negligence it, ibese
pfans whether or not noted in this review.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 1/28/2010 C:\HASS78\FILES\PADILLA RESIDENCE.SDF
JOB TITLE: Padilla Residence - Wardrobe
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. 8 PRESS. 8 DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
SOURCE 90.0 89.9 100.0 90.0 45.0 79.8
Required pressure is 10.1 psi (11%) less than available pressure.
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 45.0 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 40.0 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 321.0 K= 4.90 16.7 20.0
2 321.0 K= 4.90 16.7 20.0
3 299.0 - - - - 49.3 - - -
4 299.0 - - - - 49.3 - - -
5 299.0 - - - - 49.3 - - -
6 299.0 - - - - 49.3 - - -
A 310.0 - - - - 45.5 - - -
B 310.0 - - - - 44.6
C 310.0 - - - - 39.8 - - -
D 310.0 - - - - 41.2 - - -
E 321.0 - - - - 34.3 - - -
F 321.0 - - - - 30.3 - - -
G 321.0 - - - - 33.8
H 321.0 - - - - 17.5 - - -
I 299.0 - - - - 49.3 - - -
J 299.0 - - - - 49.3 - - -
TOR 310.0 - - - - 53.3 - - -
BOR 300.0 HOSE STREAM 59.4 5.0
U 297.0 - - - - 62.9
M2 310.0 - - - - 58.3
Ml 310.0 - - - - 66.1
SOURCE 310.0 SOURCE 79.8 45.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 1/28/2010 C:\HASS78\FILES\PADILLA RESIDENCE.SDF
JOB TITLE: Padilla Residence - Wardrobe
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 -20.0 1.101 PL 1.00 PF 0.9
1 321.0 4.9 16.7 20.0 6.7 150 FTG ST PS 0.0
H 321.0 0.0 17.5 0.0 0.068 TL 13.00 PV
Pipe: 2 -20.0 1.101 PL 1.00 PF 0.9
2 321.0 4.9 16.7 20.0 6.7 150 FTG ET PE 0.0
H 321.0 0.0 17.5 0.0 0.068 TL 13.00 PV
Pipe: 3 -40.0 1.101 PL 35.00 PF 12.8
H 321.0 0.0 17.5 0.0 13.5 150 FTG 3T2R PE 0.0
F 321.0 0.0 30.3 0.0 0.245 TL 52.00 PV
Pipe: 4 -25.0 1.101 PL 26.00 PF 3.5
F 321.0 0.0 30.3 0.0 8.4 150 FTG ER PE 0.0
G 321.0 0.0 33.8 0.0 0.103 TL 34.00 PV
Pipe: 5+ -15.0 1.101 PL 86.00 PF 4.0
F 321.0 0.0 30.3 0.0 5.1 150 FTG 2E PE 0.0
S 321.0 0.0 34.3 0.0 0.040 TL 100.00 PV
Pipe: 6 15.0 1.101 PL 11.00 PF 0.7
E 321.0 0.0 34.3 0.0 5.1 150 FTG E PS 4.8
C 310.0 0.0 39.8 0.0 0.040 TL 18.00 PV
Pipe: 7 -15.0 1.101 PL 72.00 PF 4.8
C 310.0 0.0 39.8 0.0 5.1 150 FTG 6E6R PS 0.0
B 310.0 0.0 44.6 0.0 0.040 TL 120.00 PV
Pipe: 8 -15.0 1.101 PL 18.00 PF 1.0
B 310.0 0.0 44.6 0.0 5.1 150 FTG TR PS 0.0
A 310.0 0.0 45.5 0.0 0.040 TL 24.00 PV
Pipe: 9 -25.0 1.101 PL 14.00 PF 2.7
G 321.0 0.0 33.8 0.0 8.4 150 FTG ST PS 4.8
D 310.0 0.0 41.2 0.0 0.103 TL 26.00 PV
Pipe: 10 -25.0 1.101 PL 37.00 PF 4.3
D 310.0 0.0 41.2 0.0 8.4 150 FTG 5R PS 0.0
A 310.0 0.0 45.5 0.0 0.103 TL 42.00 PV
Pipe: 11 -40.0 1.400 PL 64.00 PF 7.8
A 310.0 0.0 45.5 0.0 8.3 150 FTG 456R PE 0.0
TOR 310.0 0.0 53.3 0.0 0.076 TL 102.00 PV
Pipe: 12 -40.0 1.400 PL 10.00 PF 1.8
TOR 310.0 0.0 53.3 0.0 8.3 150 FTG 2RC PE 4.3
BOR 300.0 H.S. 59.4 5.0 0.076 TL 23.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 1/28/2010 C:\HASS78\FILES\PADILLA RESIDENCE.SDF
JOB TITLE: Padilla Residence - Wardrobe
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 13 -45.0 1.265 PL 5.00 PF 2.2
BOR 300.0 H.S. 59.4 5.0 11.5 150 FTG TG PE 1.3
U 297.0 0.0 62.9 0.0 0.155 TL 14.50 PV
Pipe: 14 -45.0 2.000 PL 60.00 PF 1.0
U 297.0 0.0 62.9 0.0 4.6 150 FTG ---- PE -5.6
M2 310.0 0.0 58.3 0.0 0.017 TL 60.00 PV
Pipe: 15 FIXED PRESSURE LOSS DEVICE
Ml 310.0 0.0 66.1 0.0 7.8 psi, 45.0 gpm
M2 310.0 0.0 58.3 0.0
Pipe: 16 45.0 0.995 PL 20.00 PF 13.7
SOURCE 310.0 SRCE 79.8 (N/A) 18.6 150 FTG TG PE 0.0
Ml 310.0 0.0 66.1 0.0 0.499 TL 27.50 PV
Pipe: 17 0.0 1.101 PL 12.00 PF 0.0
4 299.0 0.0 49.3 0.0 0.0 150 FTG ER PE 0.0
3 299.0 0.0 49.3 0.0 0.000 TL 20.00 PV
Pipe: 18 0.0 1.101 PL 58.00 PF 0.0
3 299.0 0.0 49.3 0.0 0.0 150 FTG 2E6R PE 0.0
6 299.0 0.0 49.3 0.0 0.000 TL 78.00 PV
Pipe: 19 0.0 1.101 PL 1.00 PF 0.0
6 299.0 0.0 49.3 0.0 0.0 150 FTG T PE 0.0
J 299.0 0.0 49.3 0.0 0.000 TL 6.00 PV
Pipe: 20 0.0 1.101 PL 19.00 PF 0.0
5 299.0 0.0 49.3 0.0 0.0 150 FTG ET PE 0.0
J 299.0 0.0 49.3 0.0 0.000 TL 31.00 PV
Pipe: 21 0.0 1.101 PL 10.00 PF 0.0
J 299.0 0.0 49.3 0.0 0.0 150 FTG T PE 0.0
I 299.0 0.0 49.3 0.0 0.000 TL 15.00 PV
Pipe: 22 0.0 1.101 PL 16.00 PF 0.0
I 299.0 0.0 49.3 0.0 0.0 150 FTG ET PE -4.8
B 310.0 0.0 44.6 0.0 0.000 TL 28.00 PV
NOTES (HASS):
Calculations were performed by the HASS 8.0 computer program
under license no. 50110279 granted by
HRS Systems, Inc.
208 South Public Square
Petersburg, TN 37144
The system has been calculated to provide an average
imbalance at each node of 0.001 gpm and a maximum
imbalance at any node of 0.008 gpm.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 1/28/2010 C:\HASS78\FILES\PADILLA RESIDENCE.SDF
JOB TITLE: Padilla Residence - Wardrobe
Total pressure at each node is used in balancing the system.
Maximum water velocity is 18.6 ft/sec at pipe 16.
PIPE FITTINGS TABLE
Pipe Table Name: STANDARD.PIP
PAGE: * MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Eli Tee LngEll ChkVlv BfyVlv GatVlv AimChk DPVlv NPTee
2.067 5.00 10.00 3.00 11.00 6.00 1.00 10.00 10.00 10.00
PAGE: K MATERIAL: CT-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T F R C S G V K
Ell Tee 45-Eli TeeRun Couplg SwgChk GatVlv AngVlv CockVi
0.995 2.00 6.00 1.50 1.50 0.50 7.50 0.00 14.00 5.00
PAGE: L MATERIAL: CT-L HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L R C S G
Eli Tee 45-Ell TeeRun Coupig SwgChk GatVlv
1.265 4.50 9.00 1.50 3.00 0.50 5.50 0.00
PAGE: Z MATERIAL: CPVC-C HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L R B G C D
Eli Tee 45-Eli TeeRun Btrfly Gate Check
1.101 7.00 5.00 1.50 1.00 0.00 1.50 7.50 0.00
1.400 8.00 6.00 2.00 1.00 0.00 1.50 11.00 0.00
WATER SUPPLY ANALYSIS
200 300 400 500 600 700 800 900 1000
FLOW (GPM)
100 .0
1
G 80.02 A
U
G
E
60.0 R
E
S
S
U
R 40.0 E
p
S
20.0
0.0
—14.7
tqC17 Fire Suppression
& Building Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series RFII - 56 K-factor
"Royal Flush II" Concealed Pendent Sprinklers
Quick Response, Extended Coverage
General
Description
The Tyco® Series RFII, 5.6 K-factor,
Extended Coverage, Light Hazard
(ECLH) "Royal Flush" Concealed Pen-
dent Sprinklers are decorative, 3 mm
bulb-type sprinklers featuring a flat
cover plate designed to conceal the
sprinkler. These sprinklers are opti-
mal for architecturally sensitive areas
such as hotel lobbies, office buildings,
churches, and restaurants.
The Series RFll sprinklers are intended
for use in automatic sprinkler systems
designed in accordance with standard
installation rules (for example, NFPA
13). The fast-response thermal sensi-
tivity rating of the Series RFll (TY3532)
provides for a quick response, extend-
ed coverage (QREC) rating up to a
20 ft. x 20 ft. coverage area.
Each sprinkler includes a Cover Plate!
Retainer Assembly and a Sprinkler!
Support Cup Assembly. The separable,
two-piece assembly design provides
the following benefits:
Allows installation of the sprinklers
and pressure testing of the fire pro-
tection system prior to installation
of a suspended ceiling or applica-
tion of the finish coating to a fixed
ceiling.
Permits the removal of suspended
ceiling panels for access to building
service equipment without having
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
Page 1 of 4
to first shut down the fire protection
system and remove sprinklers.
Provides for 1/2 inch (12,7 mm) of
vertical adjustment to allow a mea-
sure of flexibility in determining the
length of fixed piping to cut for the
sprinkler drops.
The Series RFll Sprinklers are shipped
with a Disposable Protective Cap. The
Protective Cap is temporarily removed
during installation and replaced to help
protect the sprinkler during ceiling in-
stallation or finish. The tip of the Pro-
tective Cap can be used to mark the
center of the ceiling hole into plaster
board or ceiling tiles by gently push-
ing the ceiling product against the Pro-
tective Cap. When ceiling installation
is complete, the Protective Cap is re-
moved and the Cover Plate/Retainer
Assembly is installed.
NOTICE
The Series RFll Concealed Pendent
Sprinklers described herein must be
installed and maintained in compli-
ance with this document and with the
applicable standards of the National
Fire Protection Association, in addi-
tion to the standards of any authori-
ties having jurisdiction. Failure to do
so may impair the performance of
these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condi-
tion. The installing contractor or sprin-
kler manufacturer should be contact-
ed with any questions.
Sprinkler
Identification
Number (SIN)
TY3532
JULY 2009
Technical
Data
Approvals
UL and C-UL Listed
NYC Approved under MEA 353-01-E
(The listings apply only to the service
conditions indicated in the Design Cri-
teria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K= 5.6 GPM/psP'2 (80,6 LPM/bar112)
Temperature Rating
155°F!68°C Sprinkler with
139°F/59°C Plate
200°F/93°C Sprinkler with
1650F/74"C Plate
Adjustment
1/2 inch (12,7 mm)
Finishes
See the Ordering Procedure section.
Physical Characteristics
Frame ...................Bronze
Support Cup... Chrome Plated Steel
Guide Pins .........Stainless Steel
Deflector.................Bronze
Compression Screw.........Brass
Blub ......................Glass
Cap.............Bronze or Copper
Sealing Assembly................
Beryllium Nickel w/Teflont
Cover Plate................Brass
Retainer ..................Brass
Ejection Spring......Stainless Steel
DuPont Registered Trademark
TFP26O
1/2' NPT SEALING
ASSEMBLY
FRAME
CAP
SUPPORT
CUP WITH BULB
ROLL FORMED
THREADS
- COMPRESSION
SCREW
GUIDE
PINS (2)
DEFLECTOR
DEFLECTOR POSITION)
SPRINKLER/SUPPORT CUP
I
ASSEMBLY
THREAD INTO AINER
SUPPORT CUP THREAD
UNTIL MOUNTING DPLES
SURFACE IS
FLUSH WITH
CEILING
LEJECTION
RING
SOLDER COVER
TABS (3) COVER PLATE/RETAINER PLATE ASSEMBLY
FIGURE 1
SERIES RFII CONCEALED SPRINKLER
RESPONSE SPACING MINIMUM
RATING FLOW/PRESSURE
QUICK 16'x16' 26.0 GPM/21.6 PSI (4,9 m x 4,9 m) (98,4 LPM / 1,49 BAR)
QUICK 18'x 18' 33.0 GPM / 34.7 PSI
(5,5 m x 5,5 m) (124,9 LPM / 2,39 BAR)
QUICK 20' x 20' 40.0 GPM / 51 PSI
(6,1 mx 6,1 m) (151,4 LPM / 3,52 BAR)
TABLE A
SERIES RFII (TY3532)
1550F/680C AND 200°F/930C CONCEALED SPRINKLER
HYDRAULIC DESIGN CRITERIA
TFP26O
Page 2 of 4
Design
Criteria
The Tyco® Series RFII Concealed
Pendent Sprinklers (TY3532) are
UL and C-UL Listed for use in light
hazard occupancies, using the design
criteria in Table A, in addition to the
requirements specified in the current
NFPA 13 for extended coverage
pendent sprinklers.
The Series RFII Concealed Pendent
Sprinklers are only listed and approved
with the Series RFII Concealed Cover
Plates with a factory-applied finish.
NOTICE
Do not use the Series RFII in
applications where the air pressure
above the ceiling is greater than
that below. Down drafts through the
Sprinkler/Support Cup Assembly
can delay sprinkler operation in a fire
situation.
Operation
When exposed to heat from a fire, the
Cover Plate, normally soldered to the
Retainer at three points, falls away to
expose the Sprinkler/Support Cup
Assembly.
The Deflector—supported by the
Guide Pins—then drops down to its
operational position.
The glass Bulb contains a fluid that ex-
pands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, activating the sprinkler and
allowing water to flow.
Installation
The Tyco® Series RFII must be installed
in accordance with the following
instructions.
NOTICE
Do not install any bulb-type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bub-
ble should be present. The diameter
of the air bubble is approximately 1/16
inch (1,6 mm) for the 155°F/68°C and
3/32 inch (2,4 mm) for the 200°F/93°C
temperature ratings.
Obtain a 1/2 inch NPT sprinkler joint
by applying a minimum to maximum
torque of 7 to 14 ft.lbs. (9,5 to 19,0
Nm). Higher levels of torque can dis-
tort the sprinkler Inlet with consequent
leakage or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in the Sprin-
kler by under- or over-tightening
the Sprinkler/Support Cup Assembly.
Re-adjust the position of the sprinkler
fitting to suit.
Step 1. Install the sprinkler only in the
pendent position with the centerline
of the sprinkler perpendicular to the
mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant ap-
plied to the pipe threads, hand-tighten
the sprinkler into the sprinkler fitting.
TFP26O
Page 3 of 4
Step 4. Wrench-tighten the sprinkler
using only the RFII Sprinkler Wrench
shown in Figure 3. Apply the RFII
Sprinkler Wrench to the Sprinkler as
shown in the figure.
Step 5. Replace the Protective Cap
by pushing it upwards until it bottoms
out against the Support Cup. (Refer to
Figure 4.)
The Protective Cap helps prevent dam-
age to the Deflector and Frame Arms
when installing or finishing the ceiling.
You can also use it to locate the center
of the clearance hole by gently push-
ing the ceiling material up against the
center point of the Protective Cap.
L'(.)ttiI
As long as the Protective Cap remains
in place, the system is considered
"Out of Service"
Step 6. After the ceiling has been com-
pleted with the 2-1/2 inch (63,5 mm)
diameter clearance hole and in prepa-
ration for installing the Cover Plate/Re-
tainer Assembly, remove and discard
the Protective Cap.
Verify that the Deflector moves up and
down freely. If the Sprinkler is dam-
aged and the Deflector does not move
up and down freely, replace the entire
Sprinkler. Do not attempt to modify or
repair a damaged sprinkler.
Step 7. Screw on the Cover Plate/Re-
tainer Assembly until its flange makes
contact with the ceiling. Do not con-
tinue to screw on the Cover Plate/Re-
tainer Assembly so that it lifts a ceiling
panel out of its normal position. If you
cannot engage the Cover Plate/Re-
tainer Assembly with the Support Cup
or you cannot engage the Cover Plate/
Retainer Assembly sufficiently to con-
tact the ceiling, you must reposition
the Sprinkler Fitting.
TFP26O
Page 4 of 4
Care and
Maintenance
The Tycow Series RFII must be
maintained and serviced in accordance
with the following instructions.
NOTICE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, obtain permission to shut
down the affected fire protection sys-
tem from the proper authorities and
notify all personnel who may be affect-
ed by this action.
Absence of the Cover Plate/Retainer
Assembly can delay sprinkler opera-
tion in a fire situation.
When properly installed, there is a
nominal 3/32 inch (2,4 mm) air gap be-
tween the lip of the Cover Plate and
the ceiling, as shown in Figure 2. This
air gap is necessary for proper oper-
ation of the sprinkler. If the ceiling re-
quires repainting after sprinkler instal-
lation, ensure that the new paint does
not seal off any of the air gap.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Replace sprinklers that are leaking or
exhibiting visible signs of corrosion.
Never repaint, plate, coat, or otherwise
alter automatic sprinklers after they
leave the factory. Never repaint fac-
tory-painted Cover Plates. If neces-
sary, replace them with factory-paint-
ed units. Non-factory applied paint can
adversely delay or prevent sprinkler
operation in the event of a fire.
Replace modified or over-heated
sprinklers.
Exercise care to avoid damage to
the sprinklers before, during, and
after installation. Replace sprinklers
damaged by dropping, striking, wrench
twisting, wrench slipping, or the like.
Also, replace any sprinkler that has
a cracked bulb or that has lost liquid
from its bulb. Refer to the Installation
Section.
If you must remove a sprinkler, do not
reinstall it or a replacement without
reinstalling the Cover Plate/Retainer
Assembly. If a Cover Plate/Retainer
Assembly becomes dislodged during
service, replace it immediately.
Responsibility lies with the owner for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection
Association (for example, NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. Contact
the installing contractor or sprinkler
manufacturer regarding any questions.
Automatic sprinkler systems should
be inspected, tested, and maintained
by a qualified Inspection Service in
accordance with local requirements
and/or national code.
Limited
Warranty
Products manufactured by Tyco Fire
Suppression & Building Products
(TFSBP) are warranted solely to the
original Buyer for ten (10) years against
defects in material and workmanship
when paid for and properly installed
and maintained under normal use and
service. This warranty will expire ten
(10) years from date of shipment by
TFSBP. No warranty is given for prod-
ucts or components manufactured by
companies not affiliated by ownership
with TFSBP or for products and com-
ponents which have been subject to
misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by TFSBP to be defective
shall be either repaired or replaced, at
TFSBP's sole option. TFSBP neither
assumes, nor authorizes any person
to assume for it, any other obligation
in connection with the sale of prod-
ucts or parts of products. TFSBP shall
not be responsible for sprinkler system
design errors or inaccurate or incom-
plete information supplied by Buyer or
Buyer's representatives.
In no event shall TFSBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFSBP
was informed about the possibility of
such damages, and in no event shall
TFSBP's liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, ex-
press or implied, including warranties
of merchantability and fitness for a
particular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name.
Sprinkler/Support Cup Assembly
Specify: TY3532, (temperature rating,
listed below) Series RFII Concealed
Pendent Sprinkler, P/N (specify).
155°F/68°C 200°FI93C
TY3532 51-794-1-155 51-794-1-200
Separately Ordered Cover Plate!
Retainer Assembly
Specify: (temperature rating, listed
below) Series RFII Concealed Cover
Plate with (finish), P/N (specify).
139F/59°C(a) 165FI740C (b)
Brass..........56-792-1-135 56-792-1-165
Chrome........56-792-9-135 56-792-9-165
Signal White
(RAL 9003) 56-792-4-135 56-792-4-165
Grey White
(RAL 9002) 56-792-0-135 56-792-0-165
Pure White (c)
(RAL 9010) 56-792-3-135 56-792-3-165
Custom ........56-792-X-135 56-792-X-165
For use with 155°F/68°C sprinklers.
For use with 200F/93°C Sprinklers.
Eastern Hemisphere sales only.
Sprinkler Wrench
Specify: RFII Sprinkler Wrench,
P/N 56-000-1-075.
@2008-2009 TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446