lProducts
FiTè &tqco
Technical Services: Tel: (800) 3817-9312 / Fax: (800) 791-5500
Series TYB - 2.8, 56, and 80 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Standard Response, Standard Coverage
1
General
Description
The Series TV-B, 2.8, 5.6, and 8.0
K-factor, Upright and Pendent Sprin-
klers described in This data sheet are
standard response - standard cover-
age, decorative 5 mm glass bulb type
spray sprinklers designed for use in
light, ordinary, or extra hazard, com-
mercial occupancies such as banks,
hotels, shopping malls, factories, refin-
eries, chemical plaits, etc.
The recessed version of the Series
TV-B Pendent Sprinkler, where appli-
cable, is intended for use in areas with
a finished ceiling. It uses a two-piece
Style 10(1/2 inch NPT) or Style 40(3(4
inch NPT) Recessed Escutcheon. The
Recessed Escutcheon provides 1/2
inch (12,7 mm) o recessed adjust-
ment or up to 3/4 inch (19,1 mm) of
total adjustment from the flush pen-
dent position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the fixed pipe
drops to the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilzed to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed thd
standard corrosion tests of the appli-
cable approval agencies, the testing is
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause hie sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 8
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level version of the
Series TV-B Pendent Sprinkler can be
obtained by utilizing the Series TV-B
Pendent Sprinkler in combination with
the Model S2 Shield.
WARNINGS
The Series TY-B Sprinklers described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
Impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
JULY, 2004 TFPI5I
TY1151 - Upright 2.8K, 1/2NPT
1Y1251 - Pendent 2.8K, 1/2'NPT
TV3151 - Upright 5.6K, 112'NPT
TY3251 - Pendent 5.6K, 1/2'NPT
TY4151 - Upright 8.0K, 314"NPT
TY4251 - Pendent 8.0K, 3/4'NPT
TY4851 - Upright 8.0K, 1/2'NPT
1Y4951 - Pendent 8.0K, 1/2'NPT
ESCUTCHEON
PLATE SEATING
SURFACE
2-1/4
(57,2 mm)
1-9/16"
(39,7 mm)
1/20 **
NPT
7/16'
11,1 mm)
IOMINAL
MAKE-IN
2-3/16°
(55,6 mm)
6*
WRENC
FLATS
1/2° NPT**
Page 2 of 8 TFPI5I
NOMINAL SSU
MAKE-IN DEFLECTOR
1l!i%mm)
: L ,Li_I
DEFLECTOR CROSS
PENDENT UPRIGHT SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
STANDARD RESPONSE SERIES TV-B UPRIGHT (TY1 151) AND PENDENT (TV1251) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16" (11,1 mm)
PLATE SEATING ** NOMINAL
SURFACE 1/2,,
MAKE-IN NPT
23t16. \ A
(55,6 mm) f
(38,1 mm)
SSP DEFLECTOR* 1---- 2-7/8° (73,0 mm) DIA,
SSU *
DEFLECTOR
STYLE 10
RECESSED
ESCUTCHEON
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3- Sealing 4 - Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
STANDARD RESPONSE SERIES TV-B UPRIGHT (TY3151) AND PENDENT(TY3251) SPRINKLERS
5.6 K-FACTOR, 112 INCH NPT
.-.-.. SSP*
DEFLECTOR CROSS
UPRIGHT SECTION
WRENCI-
FLATS
TFPI5I Page 3 of 8
ESCUTCHEON 1/2' (12,7 mm) STYLE 40
PLATE SEATING ** NOMINAL RECESSED
SURFACE MAKE-IN ESCUTCHEON SSU
NPT DEFLECTOR
i 4~~ /
112' 1
2-5/16' (12,7 mm)
NOMINAL I (58,7 mm)
(39,7 mm)
Hi
1-9/16'
MAKE-IN 2-1/4'
r 2
WRENC
(57,2 mm) 3
FLATS
SSP DEFLECTOR 2-7/8"(73,0 mm) DIA. -1 3/4' NPT ** I *
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Ejection orifice seat on frame. Screw Spring **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
STANDARD RESPONSE SERIES TY-B UPRIGHT (TY4 151) AND PENDENT (TY4251) SPRINKLERS
8. K-FACTOR, 3/4 INCH NPT
ESCUTCHEON
PLATE SEATING
SURFACE
_F_ ~
2-1/4
(57,2 mm)
1-9/16"
(39,7 mm)
1 - Frame 3 - Sealing
2 - Button Assembly
7/16' (11,1 mm)
1/2" ** NOMINAL
MAKE-IN NPT
6 - Deflector * Temperature rating is indicated on deflector or adjacent to
orifice seat on frame.
**Pipe thread connections per ISO 7/1 can be provided on
special request.
SSU *
DEFLECTOR
PENDENT
4 - Bulb
5 - Compression
Screw
FIGURE 4
STANDARD RESPONSE SERIES TY-B UPRIGHT (TY4851) AND PENDENT (TY4951) SPRINKLERS
8.0 K-FACTOR, 112 INCH NPT
Page 4 of 8 TFPI5I
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
CHROME
PLATED
I WHITE...
POLYESTER
LEAD I
COATED
WAX I
COATED
WAX OVER
LEAD COATED
2.8
1/2°
NPT
PENDENT
(TY1251)
and
UPRIGHT
(TY115I)
135°F/57°C Orange
1,2,3 N/A
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
286°F/1 41 °C Blue
360°F/1 82°C Mauve 1,2
5.6
1/2°
NPT
PENDENT
(TY3251)
and
UPRIGHT
(TV3151)
135°F/57°C Orange
1,2,3,4,5,6,7 1,2,3,5 1,2,3,5 1,2,3,5
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
2867F/141°C Blue) 1*,2**, 5°° 1", 2°°, 3* 5*
360°F/1 82°C Mau N/A
RECESSED
PENDENT
(TY3251)*
Figure 4
135°F/57°C Orange
1,2, 3,4, 5
I I I
I 1,2,4,5
I
Green
N/A
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C
8.0 3/40
NPT
PENDENT
(TY4251)
and
UPRIGHT
(TY4151)
135°F/57°C Orange
1,2,3,4, 5,6,7
1,2,5 1,2,3,5 1,2,5
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
286°F/141°C Blue 3'*, 5 1°°, 2°°,
360°F/1 82°C Mauve N/A
RECESSED
PENDENT
(TY4251)°
Figure 5
135°F/57°C Orange
1, 2, 3,4, 5 N/A
155°F/68°C Red
1750F/79°C Yellow
200°F/93°C Green
8.0
1/2'
NPT
PENDENT
(TY4951)
and
UPRIGHT
(TY4851)
135°F/57°C Orange
1, 2, 3,5 N/A
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
1
286°F/141°C Blue
360-F/1 82°C Mauve
NOTES:
Listed by Underwriters Laboratories, Inc. (UL).
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL).
Approved by Factory Mutual Research Corporation (FM).
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k103).
Approved by the City of New York under MEA 354-01 -E.
VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/05).
Where Polyester Coated, Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be UL and C-UL Listed, the
sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated, Wax Coated, and Wax over Lead Coated
Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. 150°F/66°C Maximum Ceiling Temperature.
Frame and deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
TFPISI Page 5 of 8
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
2-7/8 DIA.
(73,0 mm) 3/4"(19,1 mm)
1/4 (6,4mm) 2-1/4' DIA.
(57,2 mm) MOUNTING
I Ar
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END 'B" USED FOR
3/4" NPT MODELS)
FIGURE 7
W- TYPE 6 SPRINKLER
WRENCH
MOUNTING
SURFACE
CLOSURE SEES
(3,2 mm)
1-1/4' (31,8 mm)
314' (19,1 mm)
FIGURE 5
SERIES TV-B RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8" DIA.
5/8±1/4" (73,0 mm) 3/4"(19,1 mm)
(15,9±6,4 mm) 2-1/4° DIA. I 1/4" (6,4 mm)
(57,2 mm) FACE OF MOUNTING
SPRINKLER PLATE
FITTING
1/8
3,2 mm) It
//
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16" (33,3 mm)
TV-B 13/16" (20,6 mm)
FIGURE 6
SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 314 INCH NPT
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 8
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Page 6 of 8 TFPI5I
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, VdS, and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 2.8 GPM/ps11/2 (40,3 LPM/barll2)
K = 5.6 GPM/psi112 (80,6 LPM/bar1/2)
K = 8.0 GPM/psi112 (115,2 LPMIbar1I2)
Temperature Ratings
Refer to Table A
Finishes
Sprinkler: Reessed Escutcheon: White
Coated, Chrome Plated, or Brass
Plated
Physical Characteristics
Frame .............Bronze
Button .........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflont
Bulb ...............Glass
Compression Screw .....Bronze
Deflector ...........Copper
Bushing (K=2.8) .......Bronze
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Series TV-B Pendent and Upright
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules rec-
ognized by the applicable Listing or
Approval agency (e.g., UL Listing is
based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM's Loss Prevention
Data Sheets). Only the Style 10 or 40
Recessed Escutcheon, as applicable,
is to be used for recessed pendent
installations.
Installation
The Series TY-B Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/57°C to 3/32
inch (2,4 mm) for the 360°F/1820C
temperature ratings.
A leak tight 1/2 inch NPTsprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TV-B Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 7),
except that an 8 or 10 inch adjustable
Crescent wrench is to be used for wax
coated sprinklers. With reference to
Figures 1, 2, 3, and 4 the W-Type 7
Sprinkler Wrench or the adjustable
Crescent wrench, as applicable is to
be applied to the wrench flats.
When installing wax coated sprinklers
with the adjustable Crescent wrench,
additional care needs to be exercised
to prevent damage to the wax coating
on the sprinkler wrench flats or frame
arms and, consequently, exposure of
bare metal to the corrosive environ-
ment. The jaws of the wrench should
be opened sufficiently wide to pass
over the wrench flats without damag-
ing the wax coating. Before wrench
tightening the sprinkler, the jaws of the
wrench are to be adjusted to just con-
tact the sprinkler wrench flats. After
wrench tightening the sprinkler, loosen
the wrench jaws before removing the
wrench.
After installation, the sprinkler wrench
flats and frame arms must be in-
spected and the wax coating re-
touched (repaired) whenever the coat-
ing has been damaged and bare metal
is exposed. The wax coating on the
wrench flats can be retouched by gen-
tly applying a heated 1/8 inch diameter
steel rod to the areas of wax that have
been damaged, to smooth it back over
areas where bare metal is exposed.
NOTES
Only retouching of the wax coating ap-
plied to the wrench flats and frame
arms is permitted, and the retouching
is to be performed only at the time of
the initial sprinkler installation.
The steel rod should be heated only to
the point at which it can begin to melt
the wax, and appropriate precautions
need to be taken, when handling the
heated rod, in order to prevent the
installer from being burned.
If attempts to retouch the wax coating
with complete coverage are unsuc-
cessful, additional wax can be ordered
in the form of a wax stick (the end of
which is color coded). Only the correct
color coded wax is to be used, and
retouching of wrench flats and frame
arms is only permitted at the time of
initial sprinkler installation. With the
steel rod heated as previously de-
scribed, touch the rod to the area re-
quiring additional wax with the rod an-
gled downward, and then touch the
wax stick to the rod approximately
one-half inch away from the area re-
quiring retouching. The wax will melt
and run down onto the sprinkler.
The Series TV-B Recessed Pendent
Sprinklers must be installed in ac-
cordance with the following instruc-
tions.
Step A. After installing the Style 10 or
40 Mounting Plate, as applicable, over
the sprinkler threads and with pipe
thread sealant applied to the pipe
threads, hand tighten the sprinkler into
the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 8). With reference to Figure 3 or
4, the W-Type 7 Recessed Sprinkler
Wrench is to be applied to the sprinkler
wrench flats.
Step C. After the ceiling has been in-
TFPI5I Page 7 of 8
stalled or the finish coat has been ap-
plied, slide on the Style 10 or 40 Clo-
sure over the Series TV-B Sprinkler
and push the Closure over the Mount-
ing Plate until its flange comes in con-
tact with the ceiling.
Care and
Maintenance
The Series TV-B Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY I
MADEJ1LLJEU OF ANY AND ALL
IMPLIED. INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
POSE.
Page 8 of 8 TFPI5I
P/N 57 - XXX - X - XXX
I
MODEL/SIN
1
7
3
9
7
6
8
I
SPRINKLER I TEMPERATUF
RATING
135 135°F/57°C
155 155°F/68°C
175 175°F179°C
200 200°F193°C
286 286°F/141°C
360 360°F1182°C
-
530 2.8K UPRIGHT (112°NPT) TY1151 NATURAL BRASS
531 2.8K PENDENT(1/2°NPT) TY1251 * WHITE POLYESTER
570 5.6K UPRIGHT (1/2°NPT) TY3151 WHITE (RAL9010)*
571 5.6K PENDENT (1/2NPT) 1Y3251 CHROME PLATED
590 8.0K UPRIGHT (3/4NPT) TY4151 LEAD COATED
591 8.0K PENDENT (3/4NPT) 1Y4251 WAX COATED
286°F/141°C MAX. -
560 8.OK UPRIGHT (1/2°NPT) TY4851
1 WAX OVER LEAD
286°F/141°C MAX. 561 8.0K PENDENT (1/2°NPT) TY4951
*
TABLE B
Eastern Hemisphere sales only.
PART NUMBER SELECTION
SERIES TV-B PENDENT AND UPRIGHT SPRINKLERS
Ordering
Procedure
When placing an order, indicate the full
product name. Refer to the Price List
for complete listing of Part Numbers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Stand-
ard Response, (specify K-factor),
(specify temperature rating), Series
TV-B (specify Pendent or Upright)
Sprinkler with (specify type of finish or
coating), P/N (specify from Table B).
Recessed Escutcheon:
Specify: Style (specify) Recessed Es-
cutcheon with (specify finish), P/N
(specify).
1/2° (15 mm)
Style 10
P Plated .........PIN 56-701-9-010
1/2' (IS mm)
Style 10
White Color -
Coated ...............PIN 56-701-4-010
1/2' (15 mm)
Style 10
White RAL9010' .......P/N 56-701-3-010
1/2' (15 mm)
Style 10
Brass Plated...........P/N 56.701-2-010
3/4° (20 mm)
Style 40
Chrome Plated .........PIN 56-700-9-010
3/4' (20 mm)
Style 40
White Color
Coated ...............P/N 56-700-4-010
3/4° (20 mm)
Style 40
White RAL9010° .......PIN 56-700.3-010
3/4' (20 mm)
Style 40
Brass Plated...........P/N 56-700-2-010
* Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
Wax Sticks:
(for retouching wrench damaged
wax coating)
Specify: (Specify color) color coded
Wax Stick for retouching (Specify tem-
perature rating) temperature rated Se-
ries TV-B Sprinklers, P/N (specify).
Black for 135°F ............P/N 56-065-1-135
Red for 155°F .............P/N 56-065-1-155
Yellow for 175°F .........PIN 56-065-1-175
Blue for 200°F and
286°F .................P/N 56-065-1-286
NOTES
Each wax stick is suitable for retouch-
ing up to twenty-five sprinklers.
The wax used for 286°F sprinklers is
the same as for 200°F sprinklers, and,
therefore, the 2860Fsprinkleris limited
to the same maximum ceiling tempera-
ture as the 200°F sprinkler (i.e.,
150°F).