HomeMy WebLinkAbout5909 SEA OTTER PL; ; FPC2017-0147; PermitPERMIT REPORT
k-cityof
C arlsbad
Print Date: 10/24/2024 Permit No: FPC2017-0147
Job Address: 5909 SEA OTTER P1, CARLSBAD, CA 92010-6674 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel #: 2090820900 Track #: Applied: 05/31/2017
Valuation: $1,591,432.67 Lot #: Issued: 06/20/2017
Occupancy Group: Project #: Finaled Close Out: 04/08/2021
#of Dwelling Units: Plan #:
Bedrooms: Construction Type: Final Inspection:
Bathrooms: Orig. Plan Check #: INSPECTOR: Stowe, Daniel
Plan Check #: Wong, Cindy
Fieri, Dominic
Project Title:
Description: SYNTERACT -SPRINKLER TI >100 (215 HEADS)
FPContractor:
HCI SYSTEMS INC
4585 MURPHY CANYON RD
SAN DIEGO, CA 92123-4318
(909) 628-7773
FEE AMOUNT
FIRE NFPA 13 or 13R System > 100 heads $634.00
FIRE Reinspection (per inspection) $187.00
Total Fees: $821.00 Total Payments To Date:
--
$821.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 442-339-2665 1 Inspections: 442-339-2660 1 www.carlsbadca.gov
Ontario. San Diego Irvine Northern California
~CCIOHCX Telephone: (877) 331-2084 • Fax: (909) 628-7774
Systems Inc. State Contractors License C-7, C-10, C-I6 #905493
4/14/2017
MATERIALS SUBMITTAL PACKAGE
Wet Automatic Fire Sprinkler T.I. Modifications
Synteract Tenant Improvement Project
5909 Sea Otter Place
Carlsbad, CA 92010
FPC20I7-0147
5909 SEA OTTER PL
Munn (CFLib
FIRE SPRINKLER CORPORATION
QUICK RESPONSE
A U TOMA TI C SPRINKLERS
GL SERIES
UPRIGHT ° PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE)
DESCRIPTION AND OPERATION
The Globe Quick Response GL Series Sprinklers are a
low profile yet durable design which utilizes a 3mm frangible glass
ampule as the thermosensitive element. This provides sprinkler
operation approximately six times faster than ordinary sprinklers.
While the Quick Response Sprinkler provides an aesthetically
pleasing appearance, it can be installed wherever standard spray
sprinklers are specified when allowed by the applicable stan-
dards. It offers the additional feature of greatly increased safe-
ty to life and is available in various styles, orifices, temperature
ratings and finishes to meet many varying design requirements.
Quick Response Sprinklers should be used advisedly and under
the direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuat-
ing assembly is a hermetically sealed frangible glass ampule that
contains a precisely measured amount of fluid. When heat is ab-
sorbed, the liquid within the bulb expands increasing the internal
pressure. At the prescribed temperature the internal pressure
within the ampule exceeds the strength of the glass causing the
glass to shatter. This results in water discharge which is distrib-
uted in an approved pattern depending upon the deflector style
used.
TECHNICAL DATA
See reverse side for Approvals and Specifications.
Q CK RESPONSE
f UPRIGHT) CONVENTIONAL UI' v CKRESPONSE
PENDENT VERTICAL
- SIDEWALL
go
- rdLLUIy LbLU HyLlrostatically LU UU pikaff D1S)
Maximum low temperature glass bulb rating is -67°F (-55°C) QUICK RESPONSE
Frame - bronze Deflector - brass • Screw - brass HORIZONTAL LPC/CE
Lodgement Wire - stainless steel Bulb seat - copper SIDEWALL HORIZONTAL
Spring - nickel alloy • Seal - teflon SIDEWALL
Bulb - glass with alcohol based solution, 3mm size
oSPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
CLASSIFICATION AVAILABLE SPRINKLER BULB COLOR I N.F.P.A. MAXIMUM
IFMPERATURES CEILING TEMPERATURE
ORDINARY'-' (J35'F/155'F .- 57'C168°C
-
1OF rc "t
INTERMEDIATE 7'I/2OOF 79C193'C YELLOW/GREEN
HIGH 286F 141'C BLUE
-
225F 107'C
NOV 2016 GFS-100a (FomierlyA-20)
Temperature Ratings - 1350F (57°C)r155°F(68°C),
175°F (79°C), 200°F (930C), 286°F (141 °C) Th
Water Working Rating - 175 psi (12 Bars)
QUICK RESPONSE
A UTOMA TIC SPRINKLERS
GL SERIES
UPRIGHT PENDENT VERTICAL SIDEWALL
HORIZONTAL SIDEWALL CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL "K" FACTOR THREAD SIZE LENGTH' FINISHES
2.8 (40 metric) 1/2"NPT (15mm) 2 1/4" (5.7cm)
4.2 (60 metric) 1/2"NPT (15mm) 2 1/4" (5.7cm) Factory Bronze
(56 (80metnc) 1/2NPT(15rnm) 21/4 (57cm) i. -
Chrome
Whit ter2
8.0 (115 mefric) 1/2"NPT (15mm) 2 1/4" (5.7cm) Black Polyester23
8.0 (115 metric) I 314"NPT (20mm) 2 7/16" (6.2cm)
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
'HORIZONTAL SIDEWALL IS 2 9/16".
2FINISHES AVAILABLE ON SPECIAL ORDER.
'AVAILABLE AS cULus LISTED COROSION RESISTANT WHEN SPECIFIED ON ORDER.
APPROVALS
TEMPERATURE
STYLE SIN
MODEL
K
FACTOR HAZARD' cULus FM LPC CE NYC-DOB
MEAIOI-92-E 135°F 155°F 175°F 200°F 286°F
(57°C) (68°C) (79°C) (93°C) (141°c)
GL2815 2.8 LH X X X X X X - - -- X
GL4215
GL5815..
4.2
c56'.<
LH
tHJOH"
X
X
X X
X
X
X
X
X
X
X
-
X
-
X
-
X
X
X
GL8115'- 8.0* LHIOH X X X X X X - - - X
GL8118 8.0 LH/OH X X X X X X X X X X
GL2801 2.8 LH X X X X X X - - - X
, GL4201 4.2 LH X X X X X X - - - X
¶PENDENT GL5601 C5.6'"' [H/OH X f Xi-" X X X X X X X X
GLBIOI 8.0* LH/OH X x X X X X X - - X
GL8106 8.0 LH/OH X X X X X X X X X X
VERTICAL GL5632 5.6 LH X X X X X X X - - -
SIDEWALLt GL8133 8.0 LH X X X X X X -- - - -
GL2826 2.8 LH X X X X X X -- - - X
HORIZONTAL GL4226 4.2 LH X X X X X X - - - X
SIDEWALL GL5626 5.6 LH/OH X X X X X X X - - X
GL5627a 5.6 LH/OH X X X X X - - X X -
GL8127 8.0 LH/OH X X X X X X -- -- - -
CONVENTIONAL GL5624 5.6 LH/OH X X X X X - - X X -
(OLD STYLE) GL8125 8.0 LH/OH X X X I X I X - - X X -
SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA1 3 AND ANY OTHER RELATED DOCUMENTS.
§HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4° 1012° BELOW THE CEILING, FM APPROVED 470 6° BELOW THE CEILING.
DINSTALL IN ACCORDANCE TO BS5308 AND ANY OTHER RELATED DOCUMENTS.
tPENDENT VERTICAL SIDEWALL cULus LISTED FOR 6' MIN. SPACING.
tUPRIGHT VERTICAL SIDEWALL cULus LISTED FOR 9' MIN. SPACING.
OH: ORDINARY HAZARD
4r, LH: LIGHT HAZARD --
'j F2° NPT
ORDERING INFORMATION GLOBE@ PRODUCT WARRANTY SPECIFY Globe agrees to repair or replace any of its own manufactured
Quantity Model Number 'Style Orifice products found to be defective in material or workmanship for a
Thread Size 'Temperature • Finishes desired period of one year from date of shipment.
Quantity - Wrenches - PIN 325390 (1/2°); For specific details of our warranty please refer to Price List
P/N 312366 (L.O.) Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.globesprinkler.com
SIRE SPRINKLER CORPORATION
NOV 2016 PRINTED U.S.A. GFS-1 00a (Formerly A-20)
Dimensions
Rod Max. Rec. Load Lbs.
Size For Service Temp
650°F.
- 730.1
1/2 1350
5/8 2160
3/4 3230
7/8 4480
- - - Component of State of Fig. 98 - Rod Stiffener. caJomiaosHPDApproved L - - - - - - - -- -. Seismic Restraints System S er w/Break-oft Bolt Head Ii
Size Range - Secures 3/8" thru 7/8" hanger rod
Material - Carbon Steel
Function - Secureschannei to hanger rod for vertical seismic bracing.
ApPrivais - InclUded in our Seismic Restraints Catalog approved
by the State of California Office of Statewide Health Planning and
Development (OSHPD). For additional load, spacing and placement
information relating to OSHPD projects. please refer to the TOLCO
Seismic Restraint Systems Guidelines
Finish - Electro Galvanized
Note - Available in HDG finish or Stainless Steel materials.
Order By - Figure number
Fil All Thread Rod Cut
Size-AdIffige—ecures3/8thru7/8"rodin
1" increments -
Material - Carbon Steel
Maximum Temperature - 750°F
Finish - Plain
Note - Available in Electro-Galvanized and
HDG finish or Stainless Steel materials.
Order By - Figure number, rod diameter, rod
length and finish
Fig. 100 - All Thread Rod Full Lnnth
Size Range - Secures 3/8" thru 1½" rod in
10' lengths
Material - Carbon Steel
Maximum Temperature - 750°F
Finish - Plain
Note - Available in Electro-Galvanized and
HDG finish or Stainless Steel materials.
Order By - Figure number, rod diameter
and finish
Dimensions • Weights
Max Rec. Load Lbs.
Rod For Service Temps Approx.
Size 650°F WtJIOO
1/4 240 12
3/8 730 29
1/2 1350 53
5/8 2160 84
3/4 3230 123 7/8 4480 169
1 5900 222
11/4 9500 360
1½ 13800 510
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
lAflMW F.M. mm
TacoF,sI
TOLOOK.99AU
CF:ig. 75 - Swivel =Aft6chmeni
Size Range -- 3/8" Rod Attachment "
Material — Carbon Steel
Function - There are three recommended applications for
this product: May be used as a Branch Line Restraint for
structural attachment to anchor bolt, beam clamp, etc. May
be used in a pitched or sloped roof application, to meet
requirements of NFPA 13 (2010) 9.1.2.6. May be used as an
upper attachment with short hanger rod to omit seismic
bracing (per UBC97).
Approvals - Underwriters' Laboratories Listed In the USA
(UL) and Canada (cUL) to support up to 411 pipe. Meets
requirements of Uniform Building Code (UBC) 1997 Table 0,
Section 3.B.
Finish — Electro-Galvanized
Order By — Figure number
PATENT PENDING
C®uS USTEO
a £
T,c0AG13ktS1EL ' CELMPLATE
75 ticn
-1Oc0FGI5tt
IW.EADROD
/ tcconsssuror ==
May be used as a structural attachment component of a
branch line restraint
May be used as an upper aachment with shod hanger rod to omit
seismic bracing (per (107).
BKIWIIP
—.-
1C0FSa
ATTLCfEN1
TOZIM 99 at
ThPADR0]
Maybe used with a pitched roof applicalion, to meet requirements
of NFPA 13 (2002) Sec 9.12.5.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA. CA 92879 • PH: 951.737.5598 • FAX: 951.737.0330
CUSTOMER SERVICE • 980.786.5266
a......
5ze
58 hreaded Side Beam Bracket
V-11 a e — 3/8" rod, pipe sizes 1/2" thru 4"
Material - Carbon Steel
Function — Practical and economical bracket used to support
piping from woodocloncrete or steel beams.
Features - Unique design allows rod to be easily threaded into
bracket. Offset design permits unlimited rod adjustment. Center
mounting hole will accept 3/8"d 1/2" fastener bolts. Per NFPA
13: 1/2" thru 2" pipe requires 3/8" fastener, 21/2" thru 4" pipe
requires 1/2" fastener.*
Approvals - Underwriters' Laboratories Listed in the USA (UL)
and Canada (cUL), and Factory Mutual Engineering approved thru
4" pipe.
*Note — Additionally UL has listed the Fig. 58 with fasteners as
shown in table below.
Finish — Pre-Galvanized
Order By — Figure number
UL Listed Fastener Table
C® Its LISTED
Pipe Size Qty. Fastener Type Material
2 2 #16 x 2 Drive Screws Wood
2 1 3/8 Lag Bolt Wood
21A - 4 1 1/2 Lag Bolt Wood
31A 2 1/4x1½ Lag Bolt Wood
4 2 1/4 x 2 Lag Bolts* Wood
4 2 1/4 x 1 tek screws 14 gauge
4 2 114 x 1 tek screws 16 gauge
* No pre-drilling required
Dimensions • Weights
Pipe Rod Max. Rec. Approx.
Size Size A B C Load Lbs.* Wt./100
1/2 thru 4 3/8 23/4 1½ 1½ 300 14
2- 114 x 2 Lag Bolts
(No Pre-drilling) Up
104 inch Pipe
Per NFPA
- 1 - LagBolt '
'Up To 4 inch Pipe.T\
2-#16x2
Drive Screws
1/2 Thru 2 inch Pipe
* With safety factor of 5. 2#14 x 1
j--"Tek Type Screws
Into Mm. 16Ga. Steel
Up To 4 inch Pipe
Boll & Hex Nut
Lip To4 inch —
Pipe _V-1
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA. CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.766.5268
Steel Pipe
Z at
Schedule 40 & 80
Pipe Sched. Wall Wt. Per Water Weight Pipe Sched. Wall Wt. Per Water Weight
Size No. O.D. Thickness Foot per FtJLbs Size No. O.D. Thickness Foot per Ft. Lbs.
3/8 40 .675 .091 .567 .083 40 5.563 .258 14.620 8.660
80 .126 .738 .061 80 .375 20.780 7.870
1/2 40 .840 .109 .850 .132 6 40 6.625 .280 18.970 12.510
80 .147 1.087 .101 80 .432 28.570 11.290
314 40 1.050 .113 1.130 .230 8 40 8.625 .322 28.550 21.600
80 .154 1.473 .186 80 .500 43.390 19.800
i, .40v 4.315 1.678" 10 40 10.750 .365 40.480 34.100
-. 80 .179 2.171 .311 80 .593 64.400 31.100
1¼ 4° 1.660 .104 2.272 .647 12 40 12.750 .406 53.600 48.500
80 .191 2.996 .555 80 .687 88.60 44.000
1½ 40 1.900 .145 2.717 .882 14 40 14.000 .437 63.00 58.500 80 .200 3.631 .765 80 .750 107.000 51.200
2 40 2.375 .154 3.652 1.452 16 4° 16.000 .500 83.000 76.500 80 .218 5.022 1.279 80 .843 137.000 69.700
21k 40 2.875 .203 5.790 2.072 18 40 18 .000 .563 105.000 97.200
80 .276 7.660 1.834 80 .937 171.000 88.500
40 3.500 .216 7.570 3.200 20 40 20.000 .593 123.000 120.400 80 .300 10.250 2.860 80 1.031 209.000 109.400
3½ 4° 4.000 :226 9.110 4.280 24 40 24 .687 171.000 174.200
80 318 12.510 3.850 80 1.218 297.000 158.200
4 4° 4.500 :237 10.790 5.510 30 20 30.000 .500 158.000 286.000
80 337 14.980 4.980 36 API 36.000 .500 190.000 417.000
ype Type K
tbe . Wall Wt. Per Water Weight Tube O.D. Wall Wt. Pe ter Weight Size Thblng D. Thickness Foot per Ft/Lbs Size Thblng O.D. ThIckness t per Ft. Lbs.
1/4 3/8 .375 030 .126 .034 1/4 3/8 .375 . .145 .032
3/8 1/3 .500 .0 .198 .062 3/8 1/2 .50 .049 .269 .055
1/2 5/8 .625 .040 . .100 1/2 5/8 . 25 .049 .344 .094
5/8 I1 .
1¼ 13A 1.375 .055 .884 .5 1% 1.375 .065 1.040 .527 1½ 1% 1.625 .060 1.140 . 67 1½ 1.625 .072 1.360 .743
2 21/s 2.125 .070 1. 1.341 2 21A .125 .083 2.050 1.310 2½ 2% 2.625 .080 .480 2.064 2½ 2% 2VM, .095 2.920 2.000
3 3½ 3.125 0 3.330 2.949 3 31A 3.125 . 4.000 2.960 3½ 3% 3. .100 4.290 3.989 3½ 35A 3.625 .120%",_5.
120 3.900
4 41 .125 .110 5.380 5.188 4 41A 4.125 .134 6. 5.060
5 5.125 .125 7.610 8.081 5 5% 5.125 .160 9.670 000
6¼ 6.125 .140 10.200 11.616 6 6¼ 6.125 .192 13.870 11.
OFRCEJMANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA. CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330 CUSTOMER SERVICE • 800.786.5266
Fig. 200 - Trimline" Adjustable Band Hanger
e - 1/2° thru 8" pipe
Material - Carbon Steel, Mu. Galvanized to G90
specifications
Function - For fire sprinkler and other general piping
purposes. Knurled swivel nut design permits hanger
adjustment after installation.
Features -
(1/20 thru 2°) Flared edges ease installation for
all pipe types and protect CPVC plastic pipe from
abrasion. Captured design keeps adjusting nut
from separating with hanger. Hanger is easily
installed around pipe.
(21ho thru 8°) Spring tension on nut holds it
securely in hanger before installation. Adjusting
nut is easily removed.
Approvals - Underwriters' Laboratories listed (1/2"
thru 8°) in the USA (UL) and Canada (cUL) for steel
and CPVC plastic pipe and Factory Mutual Engineering
Approved (3/4" thru 8"). Conforms to Federal
Specifications WW-H-171 E, Type 10 and Manufacturers
Standardization Society SP-58, Type 10.
Maximum Temperature - 650°F
Finish - Mil. Galvanized. For Stainless Steel materi-
als, order TOLCO® Fig. 200WON.
Order By - Figure number and pipe size
Note - For removable nut feature, order Fig. 200 S
C®US LISTED
- 2 1/2° THRU 8" PIPE 1THRU2"PIPE
Dimensions • Weights
Pipe Rod Size Max. Rec. Approx.
Size Inch Metric A B Load Lbs. WtJ100
1/2 3/8 8mm or 10mm 31A 2% 400 11 3/4 3/8 8mm or 10mm 31&., 2½ 400 11 1 318 8mm or 10mm'3% 25W' 400 12 '
11/4 3/8 8mm or 10mm 3% 27A 400 13
1½ 3/8 8mm or 10mm 37A 27A 400 14
2 3/8 8mm or 10mm 41h 3 400 15
21h 3/8 10mm 5% 41A 600 27 3 3/8 10mm 57A 4 600 29 31h 3/8 10mm 7% 51/4 600 34
4 3/8 10mm 7% 5 1000 35 5 1/2 12mm 91A 61/4 1250 66 6 1/2 12mm 10½ 63/4 1250 73
8 1/2 12mm 131A 83/4 1250 136
OFHCE)MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA. CA 92879 • PH: 951.737.5599 • FAX: 951.7370330
CUSTOMER SERVICE • 800.786.5266
..'.-..,#..,-.,
Index -4pipe Hangers ajd Straps
- - .
Fig. 1
Standard Clovis Hanger
MSS SP-58, 1pe 1
WW-H-171E, Type 1
Page 5
Fig. 1CBS
Cross Bolt Spacer
Page 8
P 0
Fig. 24
Hanger for
CPVC Plastic Pipe,
Double Fastener Strap
Type Side Mount
Page 19
Fig. IF
Standard Clovis Hanger
with Felt Lining
Page 7
Flg.2
Adjustable Band Hanger
MSs.SP-58, Type 10
1WW-H-171E, Type .10
Page 8"
Trimline Band Hanger
with Reducer Rod Size
MSS SP-58, Type 10
WW-H-171E, Type 10
Page 8
Fig. 200
Trimline Band Hanger
MSS SP-58, 1ipe 10
WW-H-171E,Type 10
Page 43
N
Fig. 28
Standoff Hanger and
Restrainer for CPVC
Plastic Pipe
Page 21
Fig. 1PVC
PVC Coated
Clovis Hanger
MSS SP-58, Type 1
WW-H-171 E, Type 1
Page 7
Fig. 3
J-Hanger for
Pipe or Conduit
MSS SP-58, Type 5
Page 11
Fig. 22
Hanger for CPVC
Plastic Pipe
Single Fastener Type
Page 17
Fig. 28M
CPVC Hanger and
Restrainer for CPVC
Plastic Pipe
Page 22
Fig. 2F
Adjustable Band Hanger
with Felt Lining
MSS SP-58, Type 10
WW-H-171E, Type 10
Page 9
Fig. 3F
J-Hanger with Felt Lining
MSS SP-58, Type 5
Page 11
Fig. 23
Hanger for CPVC
Plastic Pipe, Double
Fastefler Strap Type.
Page 18
Fig. 29
CPVC Double Offset
Page 23
Fig. 2FWON
Adjustable Band
Hanger
w/o Swivel Nut
with Felt Lining
MSS SP-58, Type 10
WW-H-1 71 E, Type 10
Page 10
Fig. 3PVC
J-Hanger
with PVC Coating
MSS SP-58, Type 5
Page 11
V
Fig. 120
U-Hanger
Page 38
Fig. 2WON
Adjustable Band Hanger
w/o Swivel Nut
MSS SP-58, Type 7
WW-H-171 E, Type 7
Page 10
Fig. 200WON
Trimilne Band Hanger
w/o Swivel Nut
MSS SP-58, Type 7
WW-H-171E, Type 7
Page 45
Fig. 200H
Heavy Duty Band
Hanger (for Trapeze)
MSS SP-58, Type 10
WW-H-171 E, Type 10
Page 44
Fig. 120HWA (B)
Retrofit Wrap Around
0-Hanger Clamp
MSS SP-58, Type 4
WW-H-171E, Type 4
Page 40
NOTE: For more information on TOLCO products, please see TOLCO® Pipe Hangers and Support Systems Catalog.
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA. CA 92879 • PH: 951.737.5599 • fAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
.1.,.
CFig. 25 Restrainer
Size Range - One size fits 3/4" thru 211 pipe.
Material - Pre-Galvanized Steel
Function - Designed to be used in conjunction with TOLCO® Band Hangers to
restrict the upward movement of piping as it occurs during sprinkler head
activation or earthquake type activity. The surge restrainer is easily and efficient-
ly installed by snapping into a locking position on the band hanger. This product
is intended to satisfy the requirements as indicated in the National Fire Protection
Association NFPA 13, 2010 edition, 9.2.3.4.4.1 and 9.2.3.4.4.4 Can be used to
restrain either steel pipe or CPVC plastic Pipe.
Approvals - Underwriters' Laboratories Listed pAll when used with TOLCO
band hangers Fig. 2, 2NFPA and 200, in the USA (UL) and
Canada (cUL).
Finish - Pre-Galvanized
Order By - Figure number and TOLCO band hanger, size from 3/41
thru 2".
Patent #5,344,108
C®US LISTED
OFFICEIMANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.731.5599 • FAX 951.737.0330
CUSTOMER SERVICE • 800.786.5266
Mfltfl fltSI •flnT
cft ftJ@G E
FM Approved and Fully Listed Sprinkler Pipe SCHEDULE 10 SPECIFICATIONS Wheatiand's Schedule 10 and Schedule 40
steel fire sprinkler pipe is FM Approved and UL NOMINAL NOMINAL
C-UL and FM Listed. S NOM 00 NON ID WALL WEIGHT UL PIEC
Approvals and Specifications In. mm In. mm In. mm ros./ft. kg/rn CRR Lift
Both products meet or exceed 1¼ 1.660 422 1.442 36.6 .109 2.77 1.81 2.69 .3 61
the following standards: 1½ 1.900 48 1.682 42.7 109 2.77 2.09 . 5.8 61
ASTM A135, Type E, Grade A (Schedule 10)
ASTM A795, Type E,-Grade A (Schedule
2 2.375 60.3 2.1 54.8 .109 2.77 3.93 4.7 37
2½ 2.875 73.0 2.635 6 . .120 3.53 5.26 3.5 30 NFPA 13
3 3.500 88.9 3.260 82.8 .1 - 3.05 4.34 6.46 2.6 19
Manufacturing Protocols
Schedule 10 and Schedule are subjected 4 4.500 114.3 4.260 10 320 . 5.62 8.37 1.6 19
to the toughest slbletèstig protocols to 5 5.563 141.3 529 134.5 .134 3.40 . 1158 15 13 ensure the highest quality and long-lasting
performance. 6 6.625 168.3 6.357 161.5 .134 3.40 9.30 1.0 10
Finishes and Coatings 8 8.625 219.1 8249 209.5 .188 4.78 16.96 25.26 1 7
All Wheatland black steel fire sprinkler pipe Ckgia using Standard Ut. CIA formula, Ut. F. Protection Dbectopy, Cat.go,1' vizy.
17, lisa ratio value used to m.asure toe ability of a pipe to withstand corrosion. up to 6 receives a proprietary mill coating to d,d Schedule 40 steel pip* is used as the benchmark (value of 1.0). ensure a clean, corrosion-resistant surface that
outperforms and outlasts standard lacquer
coatings. This coating allows the pipe to be cc!DULET0PECIFICATiONS easily painted, without special preparation.
Schedule 10 and Schedule 40 èan be ordered in NOMINAL NOMINAL ç black, or with hot-dip galvanizing, to meet NIPS NOM 00 NON ID WALL WEIGHT UL PIECES
FM/UL requirements for dry systems that meet
the zinc coating specifications of ASTM A795 hi/9 CRR- Lift
or A53. All Wheatland galvanized material is i 33.4 _1.049- 26.6... -..133___ 3.38 _250-, .70
also UL Listed. 1½ 1.660 42.2 1.380 35.1 .140 3.56 2.27 3.39 1.00 51
Product Marking 1½ 1.900 48.3 1.610 40.9 .145 3.68 2.72 4.05 1.00 44
Each length of Wheatland fire sprinkler 2 2.375 60.3 2.067 52.5 .154 3.91 3.86 5.45 100 30 pipe is continuously stenciled to show
the manufacturer, type of pipe, grade, size • calculated using Standard Ut. CAR f0mu1a.. UL Fira Protection Directory, Categoiy VIZ)
and length. Barcoding is acceptable as a The CAR Is ratio value used to m.asu,e toe ability of a pipe to withstand corrosiom
supplementary identification method. Threaded Schedule 40 5t..i pipe Is used as the benchmark (value 011.0).
@ C @ APPSOVCD
1
PROJECT: CONTRACTOR: DATE:
ENGINEER: SPECIFICATION REFERENCE: SYSTEM TYPE:
LOCATIONS: COMMENTS:
o BLACK 0 HOT-DIP GALVANIZED
700 South Dock .treet intcc wheal land.corn
- S ror. PA 16i4l Tube P800 25717'2 Fc½: us'.. Tttrr:
F 72.1.346 72( 0 A DIVISION OF ZEKELMAN 140/IS TRIES
ñi3s9 V
Tee Reducing,
..• -
Size A B C 0 E F Unit Weight Black
NPS ON NPS ON NPS ON In mm in mm in mm In mm in mm in mm lbs k
1/2 15 1/2 15
1/4
3/
3/4
1
8
10
20
25
1'/16
11/16
1/16
1
17
17
22
25
11/16
11/16
13/lo
1
17
17
22
25
13/a
3/4
11/16
WI
22
19
17
22
We
V/s
11/4
1/16
29
29
32
37
1'/8 29
1'/s 29
11/4 32
V/to 37
11/a
1'/8
'/16
V/a
29
29
22
35
0.57 0.26
0.57 0.26
0.68 0.31
1.00 0.45
1/2 15 /2
3/4
15
20
11/16
1/16
17
22
"/is
'/16
17
22
's/is
11he
22
22
1 /16
16/io
22
24
1½ 29
11/4 32
11/4
1 /16
32
24
0.64 0.29
0.75 0.34
3/4 20
3/4 20
1/4
3/
/2
1
8
10
15
25
/l6
11/16
11/16
14
17
17
24
/i
"he
11/16
1 15/16
14
17
17
24
7/
15/16
Wis
1 /16
22
24
22
22
11/16
13/16
'Iis
11/is
17
22
22
37
11/18 17
22
I3/ 22
11/i6 37
13/16
11/4
11/4
1/8
22
32
32
35
0.62 0.28
0.75 0.34
0.76 0.34
0.99 0.45 1/4 8 1 25 1 5/te 24 /16 24 15/16 24 11/3 38 11/4 32 11/2 38 1.08 0.49
' '/2 15
-
1/2
3/4
1
15
20
25
V/16
1/io
1/i6
17.
24
I3f
15/16
_/4j9"/is
22
24
'/16
'/io
24
24
24
11/4 32
1 3/j 735
1h/z38
13/16 22
1'/4----32-
1/s 35 -
1/8
--17/16
35
37
38
0.90 0.41
0.91 0.41
1:08-0.49 -
25
3/4 20
1/2
3/4
1
15
20
25
11/16
1/16
1 h6
17
22
24
1/is
13/16
15/16
17
22
24
l5/
15/16
'/16
24
24
24 1
11/4
1/6
11/2
32
35
38
13/16 22
'/16 24
17/is 37
j3/
V/i6
11/2
35
37
38
0.89 0.40
1.00 0.45
1.13 0.51
1 25
1/4
1/2
3/4
1'/4
11/2
2
8
15
20
32
40
50
1'/IG
11/16
11/i6
11/8
11/4
17/16
17
17
22
29
32
37
11/15
'/I8
'/16
We
11/4
17/16
17
17
22
29
32
37
lh/e
/i 6
15/16
5/5
1
1
29
24
24
24
25
25
11/a
11/4
1 /6
111/16
113/16
2
29
32
35
43
47
50
11/4 32
11/4 32
1 /8 35
111/16 43
1'/16 47
2 50
1/8
1/e
1 /i6
11/16
1/4
15A41
35
35
37
40
44 1
1.01 0.46
1.01 0.46
1.11 0.50
1.49 0.68
1.84 0.83
2.70 1.22
[CäSt. WonTheadEdFittings
1ass 125 (Standard) 1
IGURE 358'v,"'Size Tee A Unit Weight
Black
•
dIII .
-
2
- -
A 1 f
C
1
NPS ON In mm In mm lbs k9 1/4 8 1/2 13 13/16 22 0.22 0.10
Ie 10 /8 16 1 25 0.35 0.16
/2 15 11/16 17 1/8 29 0.56 0.25
--1/16- 0.84
1 V 25 1 /16 -' 24 1½ '-' 38 1.25 -' 0.57
1 /4 32 11/8 29 1/4 44 2.03 0.92
1'/2 40 1/16 33 115/16 49 2.70 1.22
2 50 1/16 40 21/4 57 4.23 1.92 21/2 65 113/16 47 Phs 68 6.67 3.02 3 80 2/16 56 31/8 79 10.00 4.54 31/2 90 Pis 62 The 87 13.29 6.03 4 100 211/16 68 33/4 95 16.33 7.41 5 125 3/is 84 41/2 114 27.33 12.39 6 150 3/8 98 5½ 130 40.85 18.53
8 200 5/l6 132 69/i6 167 79.00 35.83
LI
Note: See page 35 for pressure-temperature rafings. Continued on next page.
nr
iir-
§[--C'A~Slt IR Ji! III
Ctl-as-s-
Iireadèd Fittjngsj
125 (Standafd) ]
Concentric
TReducer
LB1
Size
__________________
A
__________________ __________________
Unit Weight
Black NPS DN NPS ON in mm in mm lbs kg 3/4 20 /2 15 5/ 16 1/,6 40 0.40 0.18
5 -
\1/ (Hex) 15
(Hex) 20
"/ii
7/16
17-
11 1 V2
1"/ie
38
0.54
0.63 0.29
11/4 32
'/2
3/4
1
15
20
25
/16
1
14
25
24
1/e
25's
21/8
41
54
54
0.84 0.38
0.90 0.41
1.07 0.49
11h 40
'/2
3/4
1
1'/4
15
20
25
32
1/2
1/2
1/2
1
13
13
13
25
1Ie
1/4
21/4
1%41
41
44
57
1.00 0.45
1.20 0.54
1.50 0.68
1.45 0.66
2 50
1/2
3/4
1
1'/4
11/2
15
20
25
32
40
5/
3/4
3/4
13/
Is
16
19
19
22
22
2
2
2
21/8
2/,s
51
51
51
54
56
2.00 0.91
1.90 0.86
1.83 0.83
1,78 0.81
1.98 0.90
21/2 65 11/2
2
40
50
3/4
1
19
25
2
2/16
51
65
3.10 1.41
2.98 1.35
3 80
3/4
2
21/2
20
50
65
15/1
11/16
15/is
24
27
24
21I2
2/4
2'Ii6
64
70
73
4.31 1.95
3.96 1.80
4.40 2.00
4 100
2
21/2
3
50
65
80
1/16
1/,6
V/16
30
30
27
215/16
31/a
31/8
75
79
79
6.50 2.95
7.78 3.53
7.01 3.18
5 125 4 100 1'/,6 27 35/1 84 10.48 4.75
6 150 4
5
100
125
11/8
11/8
29
29
37/16
3/16
87
90
13.83 6.27
15.53 7.04
8 200 6 150 11/4 32 3/a 98 29.10 13.20
* Dimension does not conform toASME standard.
Note: See page 35 for pressure-temperature ratings.
MM
: •806 PF-1214
FIGURE 388
Square Head Plugs,
Solid
Size Unit Weight
Black Galv.
NPS ON lbs kg lbs kg
1..
1/2 15 0.10 0.05 0.10 0.05
3/4 20 0.17 0.08 0.17 0.08
1 25 0.32 0.15 0.32 0.15
11/4 32 0.53 0.24 0.53 0.24
11/2 40 0.76 0.34 0.76 0.34
2 50 1.23 0.56 1.23 0.56
21/2 65 2.00 0.91 2.00 0.91
3 80 3.18 1.44 1 3.18 1.44
31/2 90 4.38 1.99 - -
FIGURE 380 Unit Weight
Bar Plugs, Size Black
Solid NPS ON lbs kg
4 100 5.68 2.58
5 125 9.60 4.35
6 150 14.78 6.70
FIGURE 381
Cap Size Unit Weight
Black Galv.
NPS ON lbs kg lbs kg
21/2 65 2.55 1.16 - -
3 80 4.10 1.86 - -
4 100 6.40 2.90 - -
5 125 10.70 4.85 - -
6 150 14.20 6.44 14.20 6.44
1
8 200 27.23 12.35 27.23 12.35
CAST IRoN
L 1
(Lcait Iron TheàddFiftings
L t Class 125..(Standard) J
FIGURE 381,'
Square Head Plugs, 1 Cored
Size
_________
Unit Weight
Black Galv.
NPS ON lbs kg lbs kg
Zinc Plated
3/4* 20 0.13 0.06 0.13 0.06
1"25 0.2511 025'fi1
2 50 0.82 0.37 0.82 0.37
21Iz 65 1.32 0.60 1.32 0.60
3 80 1.87 0.85 1.87 0.85
3'/2 90 2.50 1.13 1 2.50 1.13
4 100 4.00 1.81 1 4.00 1.81
FIGURE 389
Bar Plugs,
Cored
Size Unit Weight
Black Galv.
NPS ON lbs kg lbs kg
•
4. . -. r
4 100 3.82 1.73 3.82 1.73
5 125 6.50 2.95 6.50 2.95
6 150 9.94 4.51 9.94 4.51
8 200 20.26 9.19 20.26 9.19
FIGURE 390
Countersunk Plugs Size Unit Weight
Black Galv.
See page 31(Malleable Iron)
for other available sizes.
NPS ON lbs kg lbs kg
1 25 0.20 0.09 0.20 0.09
11/4 32 0.32 0.15 0.32 0.15
11/2 40 0.47 0.21 0.47 0.21
2 50 0.84 0.38 0.84 0.38
2'Ia 65 1.40 0.63 - -
3 80 2.25 1.02 - -
3'/2 90 3.02 1.37 - -
1 4 100 3.76 1.71 -. -
According to specifications, hex bushings and cored plugs should be used with 150* malleable iron and 125# cast iron. Solid plugs and face bushings are recommended for use with 250# and 300* fittings.
Note: See page 35 for pressure-temperature ratings.
PF-111R
-- 3A1NVIL
CCast Lion ThIëadid FittingsI
cc1ss 125.(Standard)
FIGURE 366
Screwed Hex Coupling
. Size Across Fiats
A B C Unit Weight
Black !: •cLi''
NPS ON in mm in mm In mm lbs kg
02 0.7
FIGURE 487
Flanged Union Gasket Type Size Diam. of
Flanges
No. of
Bolts
Unit Weight
Black Galv.
Assembled vvith gaskets NPS ON In mm - lbs lbs kg
1/2 15 215/16 75 3 1.75 0.79 1.75 0.79
3/4 20 3 76 3 2.00 0.91 2.00 0.91
1 25 31/4 83 3 225 1.02 2.25 1.02
11/4 32 4/16 106 4 4.75 2.15 4.75 2.15
11/2 40 43/i 111 4 5.00 2.27 5.00 2.27
2 50 5 127 4 6.50 2.95 6.50 2.95
2V2 65 55/s 143 4 8.50 3.85 8.50 3.85
3 80 6/s 162 4 11.00 4.99 11.00 4.99
31/2 90 6/8 175 4 12.75 5.78 - -
4 100 711/16 195 5 18.00 8.16 18.00 8.16
5 125 815/16 227 5 22.00 9.98 - -
6 150 101I4 260 6 30.00 13.61 30.00 13.61
8 200 1215/16 329 8 51.00 23.13 51.00 23.13
Note: See page 35 for pressure-temperature ratings.
45J
I
asf Iron Threaded Fittings
dass 125 (Standard)-- J
r FIGURE 351
1900 Elbow l Size A B Unit Weight
Black
k-A-Il
A
..
NPS ON in mm in mm lbs kg
1/4 8 1/2 13 13/16 22 0.16 0.07
10 s/16 14 15/16 24 0.25 0.11
1/2 15 11/16 17 11/8 29 0.40 0.18
3/4 20 13/is 22 115/16 33 0.60 0.27
1- W V/2 38 - 0.92 0.42
1 '14 32 11/8 29 l/4 44 1.44 0.65
1'I2 40 15/1 33 115/16 49 1.95 0.88
2 50 11/1e 40 21/4 57 3.13 1.42
2'/2 65 l'/is 47 2U/1e 68 4.94 2.24
3 80 2/ie 56 31/s 79 7.21 3.27
31/2 90 2/,6 62 3/16 87 9.67 4.39
4 100 211/,6 68 3l3/16 98 12.17 5.52
5 125 3I1e 84 41/2 114 21.46 9.73
6 150 37/i 98 51/s 130 31.33 14.21
8 200 53/16 132 6/i6 167 64.56 29.28
FIGURE 371
90° Elbow,
Flange & Screw __
Size A B Unit Weight
Black
NPS ON In mm In mm lbs kg
1-----7:iTIJj..
2½ 65 1'Vis 47 21Yi6 68 10.22 4.63
I 3 80 2Vis 56 31/o 79 13.25 6.01
4 100 2"/is 68 3% 98 21.56 9.78
6 150 3% 98 51h 130 40.50 18.37
tNomiaI Pipe Sizes of 4" (tOO DiV and larger have two holes tapped for stud or tap boils.
Note: See page 35 for pressure-temperature ratings.
W anv iiiiii &Oxaovl~ WI 4J
CARLSBAD FIRE DEPARTMENT
Fire Prevention Division
1635 Faraday Avenue - Carlsbad, CA 92008
760.602.4665
WATER AVAILABILITY FORM
SECTION A: TO BE COMPLETED BY CUSTOMER
PROJECT NAME: 5909 Sea Otter Place SR#:
(Assigned upon plan submittal)
PROJECT ADDRESS: 5909 Sea Otter Place, Carlsbad, CA 92008 CITY: Carlsbad
PHONE: (909) 628.7773 (Marlon Coronado, HCI Systems) FAX NUMBER: (909) 628.7774
Largest Building (ft.2): Sprinkled? YES Construction Type:
SECTION B: TO BE COMPLETED BY LOCAL WATER COMPANY. CUSTOMER TO PROVIDE RESULTS TO CFD.
Water Purveyor: City of Carlsbad
Location of test (reference map required): 5909 Sea Otter Place (H20762)
TEST INFORMATION IS VALID FOR 6 MONTHS FROM DATE PERFORMED
Flow Test Results
Static pressure: 124 PSI Hydrant Number (if applicable):H20762
Elevation of test: 413 Feet Date/Time of Test':
Pitot Tube Reading: PSI Corresponding Flow: GPM
Total Flow: 5,125 GPM Residual Pressure94 PSI
At peak demand, this water system is capable of providing a fire flow discharge @ 20 psi in excess of 8,000 GPM, but
exceeds maximum velocities of 15 fps. The maximum flow available at 15 fps is 5,125 gpm.
1Test to be performed as close as possible to the time the most conservative flows and pressures are expected.
Note: If the water availability information was obtained in a manner other than a flow test (i.e. computer
modeling), fill out the information above as applicable and check here: x
Name: Jennifer R. Mael, P.E. Eng. Lic. No. (if applicable):C69606
Signature:__________________________________________
7
Title/Org:P -
Ct Manager Date: 05/08/2017
CPS
00 10*
H20762
Project Site
S
j0
CPS
S
8'
A 4
5909 Sea Otter Place - Fire Flow Analysis
Prepared By: Jennifer R. Mael, P.E. - MCS